Lecture 10 Unbalanced Fault Analysis Dr Mostafa Elshahed Cairo University Single Line-to-Ground (SLG) Faults Unbalanced faults unbalance the network, but only at the fault location. This causes a coupling of the sequence networks. How the sequence networks are coupled depends upon the fault type. We’ll derive these relationships for several common faults. With a SLG fault only one phase has non-zero fault current -- we’ll assume it is phase A. 1 1 SLG Faults, cont’d f Ia f Ib f I c ? 0 0 Then since I 0f 1 ? 1 1 1 1 f 2 0 I f 1 0 I f I f I f I a 3 3 1 2 0 I f 2 SLG Faults, cont’d f Va f Va f Vb f Vc f Z f Ia 0 V f 1 1 1 2 V f 1 1 2 V f This means f Va 0 Vf Vf Vf The only way these two constraints can be satisified is by coupling the sequence networks in series 3 2 SLG Faults, cont’d With the sequence networks in series we can solve for the fault currents (assume Zf=0) If 1.050 0 j1.964 I f I f j (0.1389 0.1456 0.25 3Z f ) I A Is f Ia j 5.8 (of course, f Ib f Ic 0) 4 Line-to-Line (LL) Faults The second most common fault is line-to-line, which occurs when two of the conductors come in contact with each other. With out loss of generality we'll assume phases b and c. Current f Relationships: I a Voltage Relationships: 0, f Ib f Ic , 0 If 0 Vbg Vcg 5 3 LL Faults, cont'd Using the current relationships we get 0 I f 1 0 1 1 1 2 f I f 1 I b 3 1 2 I f I f b 0 If 0 If 1 f 2 Ib 3 Hence If If 1 f 2 Ib 3 I f 6 LL Faults, con'td Using the voltage relationships we get V f0 1 1 V f 1 3 1 V f Hence 1 f Vf Vag 3 1 f V f Vag 3 To satisfy If 1 2 f 1 Vag 2 f Vbg Vcgf f Vbg f Vbg 2 2 I f & Vf Vf Vf Vf the positive and negative sequence networks must be connected in parallel 7 4 LL Faults, cont'd Solving the network for the currents we get If 1.050 3.691 90 j 0.1389 j 0.1456 f Ia f Ib f I c 1 1 1 0 0 2 3.691 90 6.39 1 1 2 3.69190 6.39 8 LL Faults, cont'd Solving the network for the voltages we get Vf 1.050 j 0.1389 3.691 90 0.5370 Vf j 0.1452 3.69190 0.5370 Vaf f Vb f Vc 1 0 1.074 1 1 2 0.537 0.537 1 1 2 0.537 0.537 9 5 Double Line-to-Ground Faults With a double line-to-ground (DLG) fault two line conductors come in contact both with each other and ground. We'll assume these are phases b and c. f Ia f Vbg 0 f Vcg f Z f ( Ib f Ic ) 10 DLG Faults, cont'd From the current relationships we get f Ia f Ib f I c 0 I f 1 1 1 2 I f 1 2 1 I f Since f Ia 0 0 If If If 0 Note, because of the path to ground the zero sequence current is no longer zero. 11 6 DLG Faults, cont'd From the voltage relationships we get f V ag 0 V f 1 1 1 1 2 f V f 1 Vbg 3 2 1 f V f Vbg Since f Vbg Then f Vbg f Vcg 0 Vf Vf ( 2 Vf )V f 2 2 But since 1 0 f Vbg 0 Vf 1 Vf 12 DLG Faults, cont'd f Vbg 0 Vf Vf f Z f ( Ib f Ic ) Also, since f Ib f Ic 0 If 2 I f 0 If I f I f 2 I f 2 Adding these together (with -1) f Vbg 0 Vf Vf 0 Z f (2 I f 0 3Z f I f If If ) with 0 If I f If 13 7 DLG Faults, cont'd The three sequence networks are joined as follows Assuming Zf=0, then V 1.050 If 0 Z Z // ( Z 3Z f ) j 0.1389 j 0.092 4.547 0 14 DLG Faults, cont'd Vf 1.05 4.547 90 j 0.1389 0.4184 If 0.4184 / j 0.1456 j 2.874 0 If I f If j 4.547 j 2.874 j1.673 Converting to phase: f Ib f Ic 1.04 j 6.82 1.04 j 6.82 15 8 Example 9.3 Determine pu and actual value of the current and line voltage at generator bus, when a SLG fault occurs at bus 2. 16 Fault Impedance (3-ph Fault) 17 9 Fault Impedance (SLG Fault) 18 Fault Impedance (LL Fault) (LL Fault) (DLG Fault) 19 10 Fault Variables Fault Current (If ) Voltage at faulted bus (Vf = If Zf) Voltage of healthy buses Currents flow on transmission lines Generators currents You must calculate the phase values. 20 Fault Summary 3-ph: Positive sequence only SLG: Sequence networks are connected in series, parallel to three times the fault impedance LL: Positive and negative sequence networks are connected in parallel; zero sequence network is not included since there is no path to ground DLG: Positive, negative and zero sequence networks are connected in parallel, with the zero sequence network including three times the fault impedance 21 11