Product Manual: RTS151

advertisement
I56-0469-015
INSTALLATION AND MAINTENANCE INSTRUCTIONS
RTS151
Remote Test Station
SPECIFICATIONS
Dimensions:
Weight:
Power Requirements
Alarm LED:
Coil Current:
Test Switch:
Reset Switch:
Alarm Response Time:
Temperature:
Humidity:
Listing:
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
4.8˝ H × 2.90˝ W × 1.4˝ D
.16 lbs.
2.8 – 32 VDC, 10 mA max.
95 mA max.
10 VA @ 32 VDC
10 VA @ 32 VDC
40 sec. max.
–10°C to 60°C (14°F to 140°F)
95% RH Non-condensing Max
UL, FM, CE
FIGURE 1. RTS151 REMOTE TEST STATION:
NOTE: RTS151 replaces RTS451.
NOTICE: This manual shall be left with the owner/user of this equipment.
NOTE: A test coil is required only for use with D2/DNR/DH400/DH500 models. For D2 models order part #DCoil. For the DH400/500 models order part
is #Coil.
GENERAL INFORMATION
System Sensor’s RTS151 is an automatic fire detector accessory designed to
test a remotely located detector. Consult detector installation instructions for
additional information.
The National Fire Protection Association has published codes, standards, and
recommended practices for the installation and use of the above product. It is
recommended that the installer be familiar with these requirements, with local
codes, and any special requirements of the local authority having jurisdiction.
H0196-01
RTS151 CONTENTS
1 RTS151 remote test station
FIGURE 2. WIRING DIAGRAM FOR RTS151 TO D4120 4-WIRE DUCT
SMOKE DETECTOR:
1 screw pack (2 mounting screws)
D4120
RTS151
1 M02-04 test magnet
WIRING OF RTS151
Consult the appropriate detector installation instructions for the applicable
wiring diagram. The RTS151 mounts to a single gang box (2 1/2” minimum
depth), or directly to the wall or ceiling.
19
FIELD
INSTALLED
JUMPER
See Figure 8 for wiring diagram of RTS151 with Duct Smoke Detectors.
2
20 AUX OUT –
4
(RED LED) 1
ALARM 5
In Canadian applications, the RTS151 is intended to be located in the same
room as the smoke detector and within 60 feet of the unit.
AUX OUT +
3
OPERATION
Test Function
15 ALARM
11 R TEST
2
R RESET
Place and hold the painted side of the magnet to the test location RTS151.
H0582-20
Alarm Indication
FIGURE 3. WIRING DIAGRAM FOR RTS151 TO DNR 2-WIRE DUCT
SMOKE DETECTOR WITH REMOTE TEST CAPABLE HEAD:
With the magnet in place some time will elapse (40 sec. maximum) depending on the detector type, before the alarm indicating LED will light.
TEST COIL +
Reset Function
1
Gently insert a /8˝ maximum diameter tool into the hole until it stops and
LED turns off. The RTS151 is capable of resetting only certain System Sensor
models of detectors. Refer to detector installation instructions for additional
information.
TEST COIL –
COMM +
RTS451/RTS451KEY
RTS151/RTS151KEY
1
OUT (CONV ONLY) +
COMM –
RA/RTS –
2
3
RA +
4
RTS +
5
JUMPER
H0633-00
1
I56-0469-015
06-10
FIGURE 4. WIRING DIAGRAM FOR RTS151 TO D2-2WIRE DUCT SMOKE DETECTOR:
4
MAGNET
TEST
SWITCH
+ TEST COIL
– TEST COIL
(–)
5
(+)
+ IN
2
(–)
ALARM
LED (RED)
+ OUT
(+)
1
24 VDC
AUX POWER
SUPPLIED
BY USER
(100mA
SUPPLY)
24 VDC
AUX POWER
SUPPLIED
BY USER
(100mA
SUPPLY)
– TEST COIL
5
+ IN
2
24 VAC (+10%, –15%)
FULL WAVE RECTIFIED,
UNFILTERED POWER
MAY BE USED
–
+ TEST COIL
4
MAGNET
TEST
SWITCH
24 VAC (+10%, –15%)
FULL WAVE RECTIFIED,
UNFILTERED POWER
MAY BE USED
+ OUT
(–)
–
ALARM
LED (RED)
1
(+)
– RA
– RA
RTS151
(OPTIONAL) REMOTE
TEST STATION
RTS151
(OPTIONAL) REMOTE
TEST STATION
+ RA
+ RTS
D2
METHOD #1 - AUX POWER LOCATED
AT DUCT DETECTOR
+ RA
+ RTS
METHOD #2 - AUX POWER LOCATED
AT TEST STATION
D2
NOTE: THE USE OF THE RTS151 REQUIRES THE INSTALLATION OF
AN ACCESSORY COIL, DCOIL, SOLD SEPARATELY.
FIGURE 5. WIRING DIAGRAM FOR RTS151 TO DH100ACDC 4-WIRE
DUCT SMOKE DETECTOR:
DH100ACDC
Alarm Signal +
Aux. Power –
Reset
DH100
20
RTS151
Test +
1
5
Test / Reset –
2
4
Reset +
3
3
RA +
4
1
RA –
5
2
V Out +
6
6 No Connection
(Red LED) Alarm
1
2
2
3
Field
Installed
Jumper
Test
FIGURE 6. WIRING DIAGRAM FOR RTS151 TO DH100 2-WIRE DUCT
SMOKE DETECTOR:
RTS151
15
Reset
4
Test
5
11
H0612-11
Test
Alarm
LED
Reset
H0198-04
H0197-01
FIGURE 8. WIRING DIAGRAM FOR RTS151 TO BEAM1224/BEAM1224S
SMOKE DETECTOR:
FIGURE 7. WIRING DIAGRAM FOR RTS151 TO DH400ACDC DUCT
SMOKE DETECTOR:
RTS151
DH400ACDC
5
BEAM1224/BEAM1224S
1
ALARM SIGNAL (+)
6
R
E
D
2
AUX POWER (–)
REMOTE ALARM OUT 1
AUX (–) 2
T2-2
RESET INPUT 3
T2-4
REMOTE TROUBLE OUTPUT 4
T3-3
TEST INPUT 5
T2-3
4
3
RESET (–)
4
TEST (–)
FIELD
INSTALLED
JUMPER
3
RTS151
T2-1
RESET
OPTIONAL YELLOW LED
1 (RED LED) ALARM
2
RESET
3
4
TEST
5
5 TEST
H0149-02
H0586-03
THREE-YEAR LIMITED WARRANTY
System Sensor warrants its enclosed product to be free from defects in materials and
workmanship under normal use and service for a period of three years from date of
manufacture. System Sensor makes no other express warranty for the enclosed product.
No agent, representative, dealer, or employee of the Company has the authority to increase or alter the obligations or limitations of this Warranty. The Company’s obligation
of this Warranty shall be limited to the replacement of any part of the product which is
found to be defective in materials or workmanship under normal use and service during
the three year period commencing with the date of manufacture. After phoning System
Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization number,
send defective units postage prepaid to: Honeywell, 12220 Rojas Drive, Suite 700, El Paso
TX 79936, USA. Please include a note describing the malfunction and suspected cause
of failure. The Company shall not be obligated to replace units which are found to be
defective because of damage, unreasonable use, modifications, or alterations occurring
after the date of manufacture. In no case shall the Company be liable for any consequential or incidental damages for breach of this or any other Warranty, expressed or implied
whatsoever, even if the loss or damage is caused by the Company’s negligence or fault.
Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This Warranty gives you
specific legal rights, and you may also have other rights which vary from state to state.
2
I56-0469-015
©2016 System Sensor. 06-10
Download