Datamate Base 3.2

advertisement
Technical Specification Sheet
Document Number 149-803
Rev. 5, June, 2007
Datamate Base 3.2
Description
•
Remote field panel communication via modem
from a desktop or Laptop
•
Runs on the most common hardware platforms:
desktop and laptop computers as well as Pocket
PCs
•
Online User Guide
•
Terminal Emulation to communicate locally with
field panel and FLN devices
•
Software password protection
®
Datamate Base for the APOGEE Automation System
is a software package that provides controller
database backup and restore capabilities for APOGEE
and pre-APOGEE networks. Database transfers and
terminal emulation can be accomplished locally or
remotely over telephone lines using a modem from a
desktop or laptop. The Datamate Base software
package allows building operators to communicate
with any APOGEE or pre-APOGEE Automation Level
Network (ALN) or Floor Level Network (FLN) device
using a single easy-to-use software package. A
Database backed up with Datamate Base can be
stored on any media and kept for permanent storage.
Features
Backup and Restore
Datamate Base allows building operators to perform
field panel backup and restore functions with any field
panel on the ALN and their connected FLN devices.
Users can select one field panel or multiple field
panels to transfer databases.
•
Complete backup and restore support for
APOGEE and pre-APOGEE field panels
•
Support for Firmware 2.8.1, 2.8 and earlier, Power
Open Processors and Ethernet field panels
•
System-wide Compatibility with all APOGEE and
pre-APOGEE BLN and FLN devices
•
Auto-connect without knowing configuration
information
•
System profile view of the ALN, FLN, and system
controllers makes communication and database
transfer operations easy
Terminal Emulation
•
Automatically builds a system profile of the
connected field panel and its associated FLN
devices or the entire parent ALN
A computing device running Datamate Base in
terminal mode can function as an operator terminal.
•
Wireless Sensor Commissioning Tool (WSCT)
built into Datamate Base allows a wireless TEC
transceiver to bind and synchronize a wireless
Room Temperature Sensor
Document No. 149-803P25
System Profile
Auto-build System Profile while plugged into a field
panel to get a better view of the network. While the tool
is plugged into an ALN device, you can auto-detect
and build a System Profile that includes FLNs, and
FLN devices just for the ALN device or for the entire
ALN associated with that device.
Page 1 of 2
While in terminal mode and connected to a field panel
MMI communication port, an operator can perform the
following functions online via the operator interface:
•
Display point information
•
Command point values
•
Edit lines of PPCL code in control programs
•
Create, modify, and delete system points
•
Create and modify operational schedules
•
Display system reports
•
Create Panel Trend Definitions
•
Modify BLN User Accounts
•
View Trend Data
Pocket PC
Requirements
Pocket PCs must meet specific
hardware requirements. Ask
your local Siemens Building
Technologies office for the latest
list of compatible platforms.
Windows Mobile 5.0 or
Windows Pocket PC 2003
operating systems
Serial COM Port to
communicate with the device,
either natively or via an add-on
device such as a Compact
Flash (CF) serial IO card
Microsoft ActiveSync® version
4.0 or later on the personal
computer
FLN Devices
Optional 4 MB Flash Card
In addition to communicating with field panels,
Datamate Base allows users to interface locally with
Unitary Controllers, TECs, ATECs, Laboratory
controllers and Wireless Room Temperature Sensors.
This eliminates the need to install separate software
programs to communicate with non-field panel
devices.
Specifications
Computer
Operating System
Environment
Microsoft® Windows® XP
Professional or Windows
2000 Professional
Workstation operating system
Minimum
Computer
Hardware
Requirements*
Personal computer that can
run Microsoft Windows XP
Professional or Microsoft
Windows2000 Professional
MMI Cable
9-pin female to RJ-11 cable –
order separately (540-143)
Ordering Information
Description
Part Number
Datamate Base 3.2 includes
software, single user license,
electronic user manual
545-496-3P2
Communication cable: PC 9-pin
female to field panel RJ-12
540-143
Optional modem for remote
communications
*Additional RAM and available disk space are
recommended for systems with a large database
(points, program, trend, schedules, etc.) Contact your
local Siemens representative for further sizing
recommendations.
Modem
Information in this document is based on specifications believed correct at the time of publication. The right is reserved to make changes as design
improvements are introduced. APOGEE is a registered trademark of Siemens Building Technologies, Inc. Other product or company names mentioned
herein may be the trademarks of their respective owners. © 2007 Siemens Building Technologies, Inc.
Siemens Building Technologies, Inc.
1000 Deerfield Parkway
Buffalo Grove, IL 60089-4513
Your feedback is important to us. If you have comments
about this document, please send them to
sbt_technical.editor.us.sbt@siemens.com.
Document No. 149-803
Country of Origin: US
Page 2 of 2