OTC-245-X CLICK-FIT® Composite Outdoor Termination PRODUCT DESCRIPTION The Termination is designed to connect an extruded high voltage cable to outdoor apparatus or overhead lines. BASIC COMPONENTS 1) INSULATOR Outdoor cable termination for very heavy polluted condition Composite type insulator with glass fiber reinforced epoxy resin tube and silicon rubber sheds, shed color light grey Top and bottom flanges bonded to the composite insulator Corona shield integrated in top flange Solid rod top connector 2) CABLE END Pre-moulded and factory-tested stress cone Base plate Copper casing provided with M12 earth connections. Support insulators (epoxy resin), with stainless steel studs Un-pressurized synthetic oil as an insulating medium 1 2 RANGE OF APPLICATION Maximum system voltage Aluminum round solid conductor Aluminum round stranded or Milliken conductor Copper round stranded or Milliken conductor : : : : Maximum cable insulation diameter (prepared) : 117 mm[1] CREEPAGE DISTANCE Minimum guaranteed flashover distance Minimum guaranteed creepage distance Pollution level IEC-60815, excl. K=1.1 : 2365 mm : 8235 mm : IV (Very Heavy ≥31mm/kV) 245 400 400 400 kV - 1600 mm² - 2500 mm² - 2500 mm² ADDITIONAL OPTIONS Arcing horns Aerial lugs Integration of optical fiber exit in the copper casing Integration of PD sensor RECOMMENDATIONS FOR AERIAL LUGS Aerial lugs are not included in the accessory kit. Depending on the conductor material of the cable, the advised aerial lugs are specified below. In all cases contact grease must be used between the top connector of the outdoor termination and the aerial lug. ALUMINIUM CONDUCTOR Top connector: aluminum aluminum lug transition lug (Al - Cu) possible alternative: tinned copper (bronze) lug [1] COPPER CONDUCTOR Top connector: tinned copper copper (bronze) lug transition lug (Cu - Al) possible alternative: aluminum lug deviating cable specifications possible on request Prysmian Netherlands B.V. 1 of 3 March 2014 OTC-245-X CLICK-FIT® Composite Outdoor Termination ELECTRICAL INFORMATION Rated voltage 24 hours AC 1 minute AC Lightning impulse withstand voltage (+10 / -10) Support insulator withstands voltages AC voltage DC voltage Impulse discharge voltage (+10 / -10) Electrical routine test AC voltage withstand test Partial discharge test : 380 kV : 460 kV : 1050 kV : 20 kV for 1min : 20 kV for 1min : 60 kV : 318 kV for 30 min : Free of discharges at 220 kV Current capacity Nominal operating current Short circuit current (1sec.) : Limited by cable specification : 60 kA [2] ALL TYPE TESTS ACCORDING TO REQUIREMENTS National and International standards : IEC-62067 IEEE Std.48 MECHANICAL DATA Maximum allowed inclination with vertical Approximate weight Maximum allowed force on top connector : 30° : 465 kg : 5000 N (horizontal) INSTALLATION Condition Installation Installation temperature Ambient operating temperature : : : : [2] Protected against rain and dust By certified/trained jointers only min 0 °C / max 40 °C min -60 ºC / max +50 ºC depending on conductor size Prysmian Netherlands B.V. 2 of 3 March 2014 OTC-245-X CLICK-FIT® Composite Outdoor Termination TYPICAL DRAWING Conductor Cross section [mm2] 400 Al 500 - 1200 Al >1200 - 2500 Al 400 Cu 500 - 800 Cu 1000 - 1200 Cu >1200 - 2500 Cu L [mm] 3040 3095 3015 2990 3045 3045 3015 D [mm] 40 40 60 40 40 60 60 Note: for the US “D” will be 1,5 inch instead of 40mm and 2 inch instead of 60mm for the UK market: Length of the areal lug will be 130mm instead of 100mm Length L = Ltable + 30mm Prysmian Netherlands B.V. 3 of 3 March 2014