iC60L circuit breakers (curve B, C, K, Z) IEC/EN 60947-2 IEC/EN 60898-1 up to 40 A DB122858 DB123525 DB116619 Protection Circuit protection b iC60L circuit breakers are multi-standard circuit breakers which combine the following functions: v circuit protection against short-circuit currents, v circuit protection against overload currents, v suitable for industrial isolation according to IEC/EN 60947-2, standard. v fault tripping indication by a red mechanical indicator in circuit breaker front face. PB104452-40 PB104442-40 &RXQWU\DSSURYDOSLFWRJUDPV Alternating current (AC) 50/60 Hz Breaking capacity (Icu) according to IEC/EN 60947-2 Voltage (Ue) Ph/Ph (2P, 3P, 4P) 12 to 133 V Service breaking capacity (Ics) 220 to 240 V 380 to 415 V 440 V 12 to 60 V 100 kA 100 to 133 V 100 kA 220 to 240 V 100 kA 70 kA 70 kA 50 kA 25 kA 20 kA 50 % of Icu (1) 32 / 40 A 70 kA 36 kA 20 kA 15 kA 50 % of Icu 50 / 63 A 70 kA 30 kA 15 kA 10 kA 50 % of Icu Ph/N (1P) Rating 0.5 to 4 A (In) 6 to 25 A 100 % of Icu Breaking capacity (Icn) according to IEC/EN 60898-1 Voltage (Ue) Ph/Ph 400 V Ph/N 230 V Rating 0.5 to 40 A 15000 A (In) Direct current (DC) Breaking capacity (Icu) according to IEC/EN 60947-2 Voltage (Ue) Between +/- 12 to 60 V y 72 V y 125 V y 180 V y 250 V Number of poles 1P 2P 3P 4P 20 kA 20 kA 20 kA Rating (In) 1 to 63 A 25 kA Catalogue numbers 20 kA Service breaking capacity (Ics) 100 % of Icu iC60L circuit breaker 2P E45094 1P E45092 Type 1 2 Auxiliaries Vigi iC60 Rating (In) 1 3 2 4 Remote tripping and indication, module CA907000 and CA907002 Remote tripping and indication, module CA907000 and CA907002 Vigi iC60 add-on residual current device, module CA902005 Vigi iC60 add-on residual current device, module CA902005 Quality label Curve Curve (2) 0.5 A 1A 1.6 A 2A 3A 4A 6A 10 A 16 A 20 A 25 A 32 A 40 A 50 A 63 A Width in 9-mm modules Accessories B C K Z B C K Z A9F93170 A9F93101 A9F93102 A9F93103 A9F93104 A9F93106 A9F93110 A9F93116 A9F93120 A9F93125 A9F93132 A9F93140 A9F93150 A9F93163 2 A9F94170 A9F94101 A9F94102 A9F94103 A9F94104 A9F94106 A9F94110 A9F94116 A9F94120 A9F94125 A9F94132 A9F94140 A9F94150 A9F94163 A9F95170 A9F95101 A9F95172 A9F95102 A9F95103 A9F95104 A9F95106 A9F95110 A9F95116 A9F95120 A9F95125 A9F95132 A9F95140 A9F95150(3) A9F95163(3) A9F92170 A9F92101 A9F92172 A9F92102 A9F92103 A9F92104 A9F92106 A9F92110 A9F92116 A9F92120 A9F92125 A9F92132 A9F92140 A9F92150 A9F92163 A9F93270 A9F93201 A9F93202 A9F93203 A9F93204 A9F93206 A9F93210 A9F93216 A9F93220 A9F93225 A9F93232 A9F93240 A9F93250 A9F93263 4 A9F94270 A9F94201 A9F94202 A9F94203 A9F94204 A9F94206 A9F94210 A9F94216 A9F94220 A9F94225 A9F94232 A9F94240 A9F94250 A9F94263 A9F95270 A9F95201 A9F95272 A9F95202 A9F95203 A9F95204 A9F95206 A9F95210 A9F95216 A9F95220 A9F95225 A9F95232 A9F95240 A9F95250 A9F95263 A9F92270 A9F92201 A9F92272 A9F92202 A9F92203 A9F92204 A9F92206 A9F92210 A9F92216 A9F92220 A9F92225 A9F92232 A9F92240 A9F92250 A9F92263 Module CA907000 and CA907001 Module CA907000 and CA907001 RI,FXIRUUDWLQJVWR$XQGHU8HWR9$&3K3KDQG8HWR9$&3K1 ,QIRUPDWLRQWREHSURYLGHGE\WKHFRXQWU\ :LWKRXWDSSURYDO 56 Version : 3.4 21/01/2013 CA901004E Protection Circuit protection PB104436-40 iC60L circuit breakers (curve B, C, K, Z) (cont.) b Insulated terminals IP20 Visi-trip window b Fault tripping is indicated by a red mechanical indicator on the front face b Large circuit labelling area Positive contact indication b Suitable for industrial isolation according to IEC/EN 60947-2 standard. b The presence of the green strip guarantees physical opening of the contacts and allows operations to be performed on the downstream circuit in complete safety b Double clip for dismounting with comb busbar in place b Increased product service life thanks to: v overvoltage resistance by high level of industrial performances conception (pollution degree, rated impulse withstand voltage and insulation voltage), v high performance limitation (see limitation curves), v fast closing independent of the speed of actuation of the toggle. b Remote indication, open/closed/tripped, by optional auxiliary contacts. b Top or bottom electrical feeding. 4P 1 3 5 2 4 6 E45097 E45095 3P 1 3 5 7 2 4 6 8 Remote tripping and indication, module CA907000 and CA907002 Remote tripping and indication, module CA907000 and CA907002 Vigi iC60 add-on residual current device, module CA902005 Vigi iC60 add-on residual current device, module CA902005 Curve Curve B C K Z B C K Z A9F93370 A9F93301 A9F93302 A9F93303 A9F93304 A9F93306 A9F93310 A9F93316 A9F93320 A9F93325 A9F93332 A9F93340 A9F93350 A9F93363 4 A9F94370 A9F94301 A9F94302 A9F94303 A9F94304 A9F94306 A9F94310 A9F94316 A9F94320 A9F94325 A9F94332 A9F94340 A9F94350 A9F94363 A9F95370 A9F95301 A9F95372 A9F95302 A9F95303 A9F95304 A9F95306 A9F95310 A9F95316 A9F95320 A9F95325 A9F95332 A9F95340 A9F95350 A9F95363 A9F92370 A9F92301 A9F92372 A9F92302 A9F92303 A9F92304 A9F92306 A9F92310 A9F92316 A9F92320 A9F92325 A9F92332 A9F92340 A9F92350 A9F92363 A9F93470 A9F93401 A9F93402 A9F93403 A9F93404 A9F93406 A9F93410 A9F93416 A9F93420 A9F93425 A9F93432 A9F93440 A9F93450 A9F93463 6 A9F94470 A9F94401 A9F94402 A9F94403 A9F94404 A9F94406 A9F94410 A9F94416 A9F94420 A9F94425 A9F94432 A9F94440 A9F94450 A9F94463 A9F95470 A9F95401 A9F95472 A9F95402 A9F95403 A9F95404 A9F95406 A9F95410 A9F95416 A9F95420 A9F95425 A9F95432 A9F95440 A9F95450 A9F95463 A9F92470 A9F92401 A9F92472 A9F92402 A9F92403 A9F92404 A9F92406 A9F92410 A9F92416 A9F92420 A9F92425 A9F92432 A9F92440 A9F92450 A9F92463 Module CA907000 and CA907001 CA901004E Module CA907000 and CA907001 Version : 3.4 21/01/2013 57 Protection Circuit protection iC60L circuit breakers (curve B, C, K, Z) (cont.) Without accessory With accessories Rating 14 mm 6.5 mm Tightening Copper cables torque Rigid Flexible 50 mm² Screw-on Al connection terminal for ring terminal 0.5 to 25 A 32 to 63 A 2 N.m 3.5 N.m 1 to 25 mm2 1 to 35 mm2 DB118789 DB122935 DB122945 PZ2 DB122946 or ferrule 1 to 16 mm2 1 to 25 mm2 50 mm2 Multi-cables terminal Rigid cables Flexible cables 3 x 16 mm2 3 x 10 mm2 DB118787 DB123060 Connection Ø 5 mm DB123310 Technical data Main characteristics According to IEC/EN 60947-2 500 V AC Pollution degree 3 Rated impulse withstand voltage (Uimp) 6 kV Thermal tripping Reference temperature 50 °C Temperature derating See module CA908007 Magnetic tripping B curve 4 In ± 20 % C curve 8 In ± 20 % K curve 12 In ± 20 % DB123312 &OLSRQ',1UDLOPP Insulation voltage (Ui) Z curve 3 In ± 20 % Utilization category A According to IEC/EN 60898-1 ,QGLIIHUHQWSRVLWLRQRILQVWDOODWLRQ Limitation class 3 Rated making and breaking capacity of an individual pole (Icn1) Icn1 = Icn DB123314 Additional characteristics IP20 Breaking capacity under 1 pole with IT 380-415 V isolated neutral system (case of double fault) Degree of protection (IEC 60529) IP40 Endurance (O-C) 40 A 4 kA 50/63 A 3 kA Device only IP20 Device in modular enclosure Electrical IP40 Insulation classe II 10,000 cycles Mechanical Circuit-breaker Type IV Operating temperature -35°C to +70°C Storage temperature -40°C to +85°C Tropicalization (IEC 60068-1) Treatment 2 (relative humidity 95 % to 55°C) Dimensions (mm) iC60L 1P 125 2P 250 3P 375 4P 500 DB123586 Weight (g) 20,000 cycles Overvoltage category (IEC 60364) 4P 78.5 72 3P 69.5 54 50 2P 1P 36 5.5 18 4.4 45 94 85 64 4.6 58 Version : 3.4 21/01/2013 CA901004E