EAPL Model A1D1 FRONT VIEW INSTRUCTION MANUAL FUNCTION A1D1 (CSA) is an ON Delay Timer. On Power application preset timing starts and at the end of the timing 2C/O relay contacts changes over and remain in this state till the power is interrupted. A1D1 (CSA) ON DELAY TIMER www.eaplindia.com DIMENSIONS NOTE: ALL DIMENSION ARE IN MM Terminal Details A1, A2 : Source Voltage 15, 16, 18 : C1, NC1, NO1 25, 26, 28 : C2, NC2, NO2 Contact Rating 5Amps @ 250V AC/ 28V DC Resistive Load CONNECTIONS SIDE VIEW 1. 2. 3. 4. 5. Terminal block Slide switches for range selection Relay status LED Time Tuning Pot Range viewing window DOC NO: OD RA AN 09000 0 REV NO.: 00 Dtd: 26/06/2013 Page 1 of 2 Special instruction for CE marked product : 1) Ensure specified operating voltage is applied to the product as per Product Specification. 2) Ensure connected LOAD does not exceed the specified contact rating of the product. (Refer Product Specification). 3) Use 2.5mm2 wire with Fork type Terminal Ends (Insulated with metal re-inforcement) to connect Load terminals (15-16,18 & 25-26,28) and source terminals (A1 & A2). 4) Wrong use and application of wires not only shorten their lives but may also cause a serious accident. 5) To prevent Fire and Electric Shock use UL and/or CSA approved wires. 6) After connecting the Source and Load connections place protective cover on terminal block and ensure perfect locking such that, protective cover shall not fall due to vibrations. PROGRAMMING INSTRUCTION : Select the range with the help of 2 Once the product life is slide switches on the side panel. The over, you may send selected range can be seen in the back the unit to EAPL windows on the front panel. for disposition. Set the required time by gently rotating the Front pot with suitable screw driver. Apply rated voltage across source TROUBLE ANALYSIS terminals. The time starts immediately and RED Unit not working. LED glows and Relay changes over. Check power supply (Rated supply should be After the set time the LED stops glowing and relay contact changes applied). from NC to NO. Relay remains in same state, till CONTACT power is interrupted. 7) Ensure Live Parts are not accessible after placing the protective cover. 8) Mount the product on DINRAIL and ensure the Spacing of 10mm minimum between product to product. 9) During time setting and range selection ensure power is removed for both source and load terminals. 10) Do not open the product at any instance since no user serviceable parts inside. HINTS ON CORRECT USAGE Use proper gauge wires for connections. Ensure all terminals are tightly screwed. Source Voltage should not exceed specified limits. DISPOSITION CAUTION Electronic Automation Pvt. Ltd #20, KHB Industrial area Newtown Yelahanka Bangalore -106 Do not change the time range & set time while the timer is in Ph:+91-80-28567561/2 operation. ,/42802345 Switch off the power while changing the time range and set Email : info@eaplindiamail.com time. www.eaplindia.com Application of voltage other than the specified one will permanently damage the timer. Do not forcibly rotate the pot. It will damage the timer. DOC NO: OD RA AN 09000 0 Dtd : 26/06/2013 Page 2 of 2 SIGN & DATE PREPARED: K.Priyadarshini 25/06/2013 CHECKED: B.S.Sridevi 26/06/2013 APPROVED: Kalavathi Shanbhag 26/06/2013 DOC NO: OD RA AN 09000 0 Dtd : 26/06/2013