SIMATIC Process Control System PCS 7 Advanced Process Library (V8.0 SP2) Forming the group status for interlock information Forming the group status for interlock information Forming the group status for interlock information A group status for interlock information is required for: • Interlock state for: ― Interlocked ― Not interlocked ― Deactivated Group status for the interlock state All the effective interlock states are combined and displayed in the block icon. The interlock states are displayed with the following prioritization: 1. Function interlocked, shown in the block icon with a closed padlock 2. Function not interlocked, shown in the block icon as an open padlock 3. Function disabled, shown in the block icon as a crossed-out, closed padlock Overview: Display for the interlock status in faceplate In the case that the function Separate evaluation for excluded and simulated interlock signals is not enabled (Feature bit =0), the bypass signals in the structures Permission, Protection, and Interlock are not evaluated. Interlocks are shown in the faceplate as follows: Parameter: Parameter: Value: Status: Button Icon Icon BypProt Perm_En or Permission or Permission or Prot_En or Protection or Protection or Intl_En Intlock Intlock x x X 16#FF - - - x 0 x x - - - 0 1 1 16#00 Visible 0 1 1 16#28 Visible This document constitutes a free excerpt compiled by the user himself/herself from the documentation provided by Siemens for this product. Siemens disclaims all liability for the completeness of this document. It shall only be used for the user's own internal purposes. It shall not be passed on to third parties. The complete documentation can be found at: /dokumentation/default.aspx?DocVersionId=55656085131&Language=en-US&TopicId=54850745995 10/1/2016 SIMATIC Process Control System PCS 7 Advanced Process Library (V8.0 SP2) Forming the group status for interlock information Parameter: Parameter: Value: Status: Button Icon Icon BypProt Perm_En or Permission or Permission or Prot_En or Protection or Protection or Intl_En Intlock Intlock 0 1 0 16#60 Visible 0 1 1 16#60 Visible 0 1 0 ≠ 16#FF Visible Status based on priority 0 1 1 ≠ (16#FF, 16#60, 16#00, 16#28) Visible Status based on priority 1 (for local 1 mode and simulation only) x ≠ 16#FF Visible Status based on priority Comments on table: • X: The value is irrelevant for the display of the icon. Note If values are forced in the block, this is indicated in the block icon by a crossed-out, closed padlock. In the case that the function Separate evaluation for excluded and simulated interlock signals (Feature bit =1), the bypass signals in the structures Permission, Protection, and Interlock are evaluated. The bypass signals can be read from the upstream interlock block at the output Bypass. Excluded interlock signals are shown in the faceplate as follows: Parameter: Status: Bypass: Button Icon Perm_En or Permission or Permission or Prot_En or Protection or Protection or Intl_En Intlock Intlock x 16#FF x - - 0 x x - - 1 ≠ 16#FF 0 Visible 1) 1 ≠ 16#FF 1 Visible 1) This document constitutes a free excerpt compiled by the user himself/herself from the documentation provided by Siemens for this product. Siemens disclaims all liability for the completeness of this document. It shall only be used for the user's own internal purposes. It shall not be passed on to third parties. The complete documentation can be found at: /dokumentation/default.aspx?DocVersionId=55656085131&Language=en-US&TopicId=54850745995 10/1/2016 SIMATIC Process Control System PCS 7 Advanced Process Library (V8.0 SP2) Forming the group status for interlock information Comments on table: • • See also X: The value is irrelevant for the display of the icon. 1): Icon corresponding to the status of the interlock signal (for 16#80 no icon) → Separate evaluation for excluded and simulated interlock signals This document constitutes a free excerpt compiled by the user himself/herself from the documentation provided by Siemens for this product. Siemens disclaims all liability for the completeness of this document. It shall only be used for the user's own internal purposes. It shall not be passed on to third parties. The complete documentation can be found at: /dokumentation/default.aspx?DocVersionId=55656085131&Language=en-US&TopicId=54850745995 10/1/2016