ACS-CRM CONTROL AND MONITORING MODULES FOR USE WITH THE RAYCHEM ACS-30 SYSTEM INSTALLATION INSTRUCTIONS DESCRIPTION A The ACS-CRM provides ground-fault and line current sensing, alarming, switching and RTD inputs for five heat-tracing circuits when used with the ACS-UIT2. The ACS-CRM is used to control Electromechanical Relays (EMRs) when installed in the ACS-PCM2-5 power control panel. TOOLS REQUIRED • Wire cutters • RJ11 stripping/crimping tool • RJ11 connectors • #36 drill bit • Screwdriver small blade - standard • #6-32 tap B ADDITIONAL MATERIALS REQUIRED • Power supply - 12 Vdc @ 400 mA • RJ11 4 conductor cable KIT CONTENTS ItemQty Description APPROVALS/CERTIFICATIONS Hazardous Locations Class I, Div. 2, Groups A,B,C,D Ex nC IIC T5 Class I, Zone 2, AEx nC IIC T5 General Supply Voltage Internal power consumption Ambient operating temperature Ambient storage temperature Environment Max. altitude Humidity A 1 ACS-CRM (card rack module with connectors) B 1 NGC-30-CTM (current transformer module) Line Current Sensors 12 Vdc ± 10% < 5 W per ACS-CRM –40ºF to 140ºF (–40ºC to 60ºC) –40ºF to 167ºF (–40ºC to 75ºC) PD2, CAT III 2000 m 0 – 90% non-condensing Max current Accuracy 60 A ± 2% of reading Ground Fault Sensor Range Accuracy 10 – 200 mA ± 4% of range at 30 A line current Outputs CRM output relays Alarm Relay Electromagnetic Compatibility Form A 3-Amp @ 277 Vac max 50/60 Hz Form C 3-Amp @ 277 Vac max 50/60 Hz Immunity Heavy Industrial Emission Industrial Environment Communication to ACS-UIT 100-ohm platinum RTD, 3-wire, α = 0.00385 ohms/ohm/ºC Can be extended with a 3-conductor shielded cable of 20 ohm maximum per conductor Up to five wired directly to each ACS-CRM Connection Terminals Temperature Sensors Type Quantity Current Sensors Mounting Quantity per NGC-30-CTM Din Rail – 35 mm Five for ground-current measurement Five for line current measurement Type Cable Length Quantity 2 wire RS-485 One shielded twisted pair 4000 ft. (1200 M) maximum Up to 52* ACS-CRM may be connected to one ACS-UIT Power supply/Pilot Relay/ 18 – 12 AWG (0.8 – 3.3 mm2) RTD/Comm Port (RS485) * May require an RS-485 repeater if communication length is greater than 4000 ft. WARNING: This component is an electrical device that must be installed correctly to ensure proper operation and to prevent shock or fire. Read these important warnings and carefully follow all of the installation instructions. THERMAL BUILDING SOLUTIONS • Component approvals and performance are based on the use of Pentair Thermal Management-specified parts only. Do not use substitute parts. • Keep components dry before and during installation. EN-RaychemACSCRM-IM-H58283 03/15 • Leave these instructions with the end user for reference and future use. For technical support, call Pentair Thermal Management at (800) 545-6258. 1/8 Cleaning Instructions Optional Card Rack Installation Instructions If dust accumulates on the ACS-CRM circuit board use compressed air to remove the dust. Turn off all power to the ACS-30 panel. Carefully disconnect all cables from a single ACS-CRM card, making sure to label cables so that they can be reconnected after board cleaning. Wear an anti-static wrist strap connected to ground in order to avoid component damage. Remove the CRM circuit card from the card cage and place on a clean lint-free surface. Use dry compressed air from a can for cleaning circuit boards. (Avoid factory compressed air since it may contain enough moisture or oil to cause permanent damage.) Use short quick blasts to remove dust build-up as necessary. After cleaning, replace the CRM in the same card cage position and reconnect all cables. Remove only one card at a time for cleaning to avoid any problems during re-installation. Mounting of Card Rack Use the mounting template shown in the NGC-30-CRM Installation Instructions (H57723) to mount the rack on a panel backplane. There are four holes (0.188 in. diameter) to secure it to the mounting surface using #8 screws. Once the card rack is installed, a earth bonding wire (green 18 AWG min.) terminated with a #10 Ring terminal must be connected to the card rack using the ground screw provided. Note: The card rack must be installed on a noncombustible surface. 10.97" (279 mm) 7.20" (183 mm) 11.15" (283 mm) Mounting the ACS-CRM Directly to the Panel's Back Pan The ACS-CRM is intended to be installed on the backpan of the ACS-PCM2-5 power control panel. Grounding screw Note: Screw is located on the outside of the enclosure Use the attached template (see page 7) to locate the 6 mounting holes on the panel’s back pan. Using a #36 drill bit, drill the six holes and using a #6-32 tap, tape the 6 holes. Install a #6 nylon standoff (1 in. long) between the panel’s back pan and CRM board and secure with the #6-32 screw (1 1/4 in. long). ACS-CRM Installation Instructions ACS-CRM MSB LSB TB 1 TB 2 TB 3 TB 4 TB 5 TB 13 TB 14 TB 15 TB 16 TB 17 1 2 3 TB 19 THERMAL BUILDING SOLUTIONS Tx Relay 5 Relay 3 Alarm output Relay outputs (5x) LEDs (9x) Fuse 12 Vdc Inputs (2x) End of Line (EOL) jumper RS-485 Communications Line & ground-fault sensor inputs (5x) RTD Inputs Address Switches Rx Relay 1 Relay 4 Power TB 6 Alarm TB 7 Relay 2 TB 12 LED functions 7.00 in. (178 mm) EN-RaychemACSCRM-IM-H58283 03/15 10.75 in. (273 mm) 2/8 1 2 1 Common Alarm The common alarm terminal block (TB12) provides a form C dry contact, rated at 277 Vac max (3A). 2 When the Raychem ACS-PCM2-5 panel is powered on, the common alarm relay coil is energized and pin 2 is connected to pin 1 (common). This is the "No Alarm" condition for the CRM board. Note: Power supply must be sized correctly based on the number of ACS-CRM modules. RS-485 Communications The RS-485 connector (TB6) is a dual three pin connector. Either connector allows for RS-485 input signals (pin #1 (shield), pin #2 (+), pin #3 (–)) and bussing of RS485 signal to other ACSCRM modules. End of Line (EOL) Jumper If this device (ACS-CRM) is the last device in the RS-485 network, the J1 jumper needs to be moved from terminals 2 & 3 to terminals 1 & 2. If the alarm occurs, or the CRM board loses power, the relay coil is de-energized and pin 1 (common) is disconnected from pin 2 and connected to pin 3 to indicate an alarm condition exits. 1 2 3 Normal position 1 2 3 1 2 3 End of Line position 1 2 3 RTD Inputs – ­ Ordinary Area 3 wire RTDs with shield may be connected to RTD Ch1 thru Ch 5 (TB1 - TB5). The two common wires (usually red, red) are connected to terminals 2 & 3, the source (usually white) to terminal 1 and the braid to terminal 1 2 3 4 4 (earth ground). per each ACS-CRM board Note: RTD's are not required if monitoring current/ground-faults only or if RTD's are connected via RMM2s. Address Switches (SW1 & SW2) Each ACS-CRM must have a unique communication address selected. The valid address switch range when using the ACSUIT is 1-99. SW1 is the ones digit (0–9) and SW2 is the tens digit (0 or 9). RTD RTD RTD RTD Relay "No Alarm" Note: When adding an ACS-CRM to the sysCondition tem, you must first cycle power on the CRM board and then perform a network update at the ACS-UIT. Ground-Fault/Line Current Sensors Connections from ACS-CRM to NGC-30-CTM. Using an RJ11 connector/cable assembly, connect one end to an RJ11 input (TB13TB17) and the other end to the appropriate NGC-30-CTM RJ11 connector. Typical connection (1 of 5) RTD connected directly to CRM board RTD 1 2 3 COM Closed Open Power Supply The power supply connector (TB19) is a dual two pin connector. Either connector allows for power in (pin #1 (+), pin #2 (–) and bussing of power to other ACS-CRM modules). 1 2 3 4 Shield 1 2 3 4 Shield 1 2 3 4 Shield 1 2 3 4 Shield 1 2 3 4 Shield RTD1 RTD2 RTD3 RTD4 CRM PCB Ground-Fault/Line Current Cable Assembly Notes: A complete cable may be ordered as part number: 20578010XXX where XXX = Length (L) in inches. RTD5 Chassis Ground (L) THERMAL BUILDING SOLUTIONS EN-RaychemACSCRM-IM-H58283 03/15 3/8 Mounting of NGC-30-CTM Each NGC-30-CTM mounts on a DIN 35 rail. It should be located between the terminal block and contactor in the ACS-PCM2-5 power control panel. DIN rail mounting foot DIN rail mounting foot DIN rail NGC-30-CTM Installation Instructions NGC-30-CTM Line & ground-fault sensor outputs (5x) Line current sensor (5x) Ground-fault current sensor (5x) DIN rail mounting foot (X2) Typical GF / LC wiring through transformers Ground-fault transformer Phase / Neu. Line current transformer Phase 3.5 in (89.9 mm) 9.75 in (248 mm) top of DIN rail DIN rail THERMAL BUILDING SOLUTIONS EN-RaychemACSCRM-IM-H58283 03/15 4/8 System Layout ACS-CRM ACS-PCM2-5 120 - 277 Vac in ACS -UIT2 Touch Screen 12 Vdc Power Supply RTDs ACS-CRM Alarm relay output AC voltage up to 277Vac + – 12 Vdc Distribution panel board with standard ci rcuit breakers To contactor coils (see detail) NGC-30-CTM C Ø1 Ø2 Ø3 N Relay drivers 1 2 3 4 5 3 C 8 C 10 C 12 C 6 C Pilot relays Contactor located on coils circuit board THERMAL BUILDING SOLUTIONS C To heater's power junction box 1 C C C EN-RaychemACSCRM-IM-H58283 03/15 5/8 General Installation Instructions 1. The Raychem ACS-30 components must be installed: • In compliance with all local electrical and safety codes • In an enclosure suitable for the application environment. 2.The Raychem ACS-30 components must be protected by external overcurrent and disconnect devices. This may be a circuit breaker or a combination of disconnect switch and fuses. The disconnect device: • Must disconnect all ungrounded, current-carrying conductors • Should be located in close proximity to the equipment • Be within easy reach of the operator • Be marked as the disconnecting device for the equipment 3. Supply wiring insulation must be rated for the highest voltage and temperature to be encountered in the application. Conductors must be sized for the application and be protected by an external overcurrent device. 4. Some wiring configurations will use more than one power source and all must be de-energized prior to performing any maintenance on a controller circuit. 5. Protection provided by this equipment may be impaired if the device is used outside of its ratings or for applications other than is intended. 6. Always be sure that the intended location is classified as an area for which the product is approved. 7. The Raychem ACS-30 components have no user serviceable parts. Contact your Pentair Thermal Management Representative for service and a Return Authorization if required. Conducted and Radiated Emissions - Statement Of Compliance This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: – Reorient or relocate the receiving antenna. – Increase the separation between the equipment and receiver. – Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. – Consult the dealer or an experienced radio/TV technician for help. This Class A digital apparatus complies with Canadian ICES-003. Cet appareil numérique de la Classe A conforme à la norme NMB003 du Canada. ACS-30 Installation Test Procedures Once assembled into a panel, the Raychem ACS-PCM2-5 components must be tested as a system to ensure that the ground fault detection circuitry is functional. The following tests must be conducted by qualified personnel familiar with the equipment and its operation, test procedures, and electrical code requirements. Make as many copies of this checklist as required to document successful tests for each circuit in the panel. Abbreviations: GF = Ground Fault CT = Current Transformer ACS-CRM Board: Tested By: Date: Circuit #1 Circuit #2 Circuit #3 Circuit #4 Circuit #5 Inspect the wiring to ensure that all load conductors pass through the GF CT. Verify that no ground (PE) conductors pass through the GF CT. Ensure that conductors on the load side of the GF CT are not grounded. Simulate a GF on the load side of the GF CT large enough to cause the ACSCRM or ACS-CRMS to trip its output off. This should occur within approx. 1 second of applying the test GF current. Completed forms should be retained with the panel and available for inspection by the local Electrical Inspection Authority. THERMAL BUILDING SOLUTIONS EN-RaychemACSCRM-IM-H58283 03/15 6/8 0.17 in. 10.53 in. 5.35 in. 7.0 in. ACS-CRM Mounting holes 6x ø 0.15 in. 6.83 in.w EN-RaychemACSCRM-IM-H58283 03/15 THERMAL MANAGEMENT BUILDING SOLUTIONS SOLUTIONS 7/8 WWW.PENTAIRTHERMAL.COM NORTH AMERICA EUROPE, MIDDLE EAST, AFRICA ASIA PACIFIC LATIN AMERICA Tel:+1.800.545.6258 Fax:+1.800.527.5703 Tel:+1.650.216.1526 Fax:+1.650.474.7711 thermal.info@pentair.com Tel:+32.16.213.511 Fax:+32.16.213.603 thermal.info@pentair.com Tel:+86.21.2412.1688 Fax:+86.21.5426.2937 cn.thermal.info@pentair.com Tel.:+1.713.868.4800 Fax:+1.713.868.2333 thermal.info@pentair.com Pentair is owned by Pentair or its global affiliates. All other trademarks are the property of their respective owners. Pentair reserves the right to change specifications without prior notice. © 2013-2015 Pentair. THERMAL BUILDING SOLUTIONS EN-RaychemACSCRM-IM-H58283 03/15 8/8