TSI BravO HC 2.5kVA / 230Vac The TSI Bravo HC inverter system is specially designed to cater to air conditioning unit, typically in telecom shelters, or motor loads. The TSI Bravo HC is a single phase Inverter with two operational modes called Online mode (DC to AC) and EPC mode (AC to AC), providing conditioned power with very high efficiency. System Description The TSI Bravo HC is a 48VDC/230VAC inverter built in 19” reggudized sub-rack as per telecom standard Its massive power density provides up to 5KVA in a 2U package, or up to 10 kVA in two racks (4U). The use of the TSI technology* allows the systems to operate at up to 96% efficiency and to have a seamless transfer between the primary and secondary sources. The TSI Bravo HC is able to provide 330% overload for a period of 900ms The Inverter has dual (AC & DC) inputs, and has a Static Transfer Switch Function built-in. Terminal Blocks for ACin, ACout & DCin located in Front. Rack mounting option with additional fixing bracket and back end support for 19” Rack Wall mountable without additional kits. The TSI Bravo HC system is CE marked according to IEC/EN 60950:1, IEC/EN62040 and also complies with EMC Class A. * for more information about the TSI Technology, please visit http://www.cet-power.com/en/tsi or scan this TSI Bravo HC – Datasheet – v1.0 www.cet-power.com TSI BravO HC 2.5kVA / 230Vac GENERAL DC INPUT SPECIFICATIONS EMC (immunity) EN 61000-4-3,6 Nominal voltage (DC) 48 V EMC (emission) EN 55022 (Class A) Voltage range (DC) 40 - 60 V Safety EN 60950-1 EN 62040-1,2 Nominal current (at 40Vdc) n x 56 A Cooling Forced Maximum input current (for 15 second) n x 84 A Isolation Doubled Voltage ripple MTBF 240000 hrs Input voltage boundaries user selectable Efficiency (Typical) Enhanced Power Conversion 96% On Line91% < 2mV AC INPUT SPECIFICATIONS Nominal voltage (AC) True Redundant Systems Compliant 3 disconnection levels on ACout and DCin power ports 4 disconnection levels on ACin port Voltage range (AC) 150 – 265 V Brownout150 to 185 V 1784 W @150V RoHSCompliant Conformity rangeAdjustable Connection I/O Terminal block Protected against inversion of polarity Power Factor>99% Frequency range (selectable) Self adaptive to wide operating conditions and comprehensive table of troubleshooting codes Synchronization range 47 – 53 Hz 57 – 63 Hz Dielectric strength DC/AC 4300Vdc AC OUTPUT POWER Nominal Output power n x 2500 VA Output power (resistive load) n x 2000 W Short time overload capacity 150% 15 second 300% 900msec Permanent overload capacity 110% Admissible load power factor Full power rating from 0 inductive to 0 capacitive Internal temperature management and switch off TSI Bravo HC – Datasheet – v1.0 www.cet-power.com 230 V 50 - 60 Hz TSI BravO HC 2.5kVA / 230Vac AC OUTPUT SPECIFICATIONS SIGNALING & SUPERVISION Nominal voltage (AC) (*) 230 V DisplaySynoptic LED Voltage range (AC) 200 – 240 V Alarms output Dry contacts on shelf Voltage accuracy 2% Supervision Use optional devices Frequency 50 - 60 Hz Frequency accuracy 0.03 % Total harmonic distortion (resistive load) <1.5 % Width19inch Load impact recovery time 0.4 ms Depth510mm Turn on delay 40 s Height Nominal current Protected against reverse current n x 10.9 A Weight Crest factor at nominal power 3.1 In Short circuit clear up capacity 10 x In for 20msec Available while Mains is available at AC input port With magnitude control and management Short circuit current after clear up capacity 2.1 In Short circuit current after 15 sec WEIGHT & DIMENSIONS Module (Max 4) 4.5Kg Shelf W/O Modules 7.0Kg Material (casing) 1.5 In TRANSFER PERFORMANCES Maximum voltage interruption 0s Total transient voltage duration (max) 0s ENVIRONMENT Altitude above sea without derating Derating slope upper than 1500m 0,8% by 100m Ambient temperature- 20 to 50 °C Storage temperature- 40 to 70 °C Relative humidity 2U & 4U <1500 m 95% , non condensing TSI Bravo HC – Datasheet – v1.0 www.cet-power.com Coated steel TSI BravO HC 2.5kVA / 230Vac TSI Bravo HC – Datasheet – v1.0 www.cet-power.com TSI BravO HC 2.5kVA / 230Vac How to order Each inverter module provides 2500VA/2000W running power and 330% short term overload for a period of 900ms (start up) followed by a 150% overload for 14 seconds. Max two (2) inverters per shelf & Max two (2) shelves per system Product Code description: Product Code Model Name Description Nom. Output Power Startup (900ms) Overload (15s) S32H73E0102S TSI Bravo HC 2500VA 1 shelf + 1 Module - no T2S - Alarm Contact 2.5kVA / 2kW 8.25kVA / 6.6kW 3.75kVA / 3kW S32H73E0202S TSI Bravo HC 5000VA 1 shelf + 2 Module - no T2S - Alarm Contact 5kVA / 4kW 16.5kVA / 13.2kW 7.5kVA / 6kW S32H73E0304S TSI Bravo HC 7500VA 1 shelf + 3 Module - no T2S - Alarm Contact 7.5kVA / 6kW 24.75kVA / 19.8kW 11.25kVA / 9kW S32H73E0404S TSI Bravo HC 10000VA 1 shelf + 4 Module - no T2S - Alarm Contact 10kVA / 8kW 33kVA / 26.4kW 15kVa / 12kW S32G73E0102S TSI Bravo HC 2500VA 1 shelf + 1 Module + 1 T2S 2.5kVA / 2kW 8.25kVA / 6.6kW 3.75kVA / 3kW S32G73E0202S TSI Bravo HC 5000VA 1 shelf + 1 Module + 1 T2S 5kVA / 4kW 16.5kVA / 13.2kW 7.5kVA / 6kW S32G73E0304S TSI Bravo HC 7500VA 1 shelf + 1 Module + 1 T2S 7.5kVA / 6kW 24.75kVA / 19.8kW 11.25kVA / 9kW S32G73E0404S TSI Bravo HC 10000VA 1 shelf + 1 Module + 1 T2S 10kVA / 8kW 33kVA / 26.4kW 15kVa / 12kW Warranty options: change the position 7 “E” to “F” for 3 years warranty “G” for 4 years warranty “H” for 5 years warranty To have “Soft-Start” inrush on DC (not CE marked!) change the ending “S” to “C” TSI Bravo HC – Datasheet – v1.0 www.cet-power.com