Combination Starters and Distribution Units

advertisement
SFIM-7002B-0608
Section D, June, 2008
Combination Starters and Distribution
Units
Several different kinds of combination starters and
distribution units can be put into a MCC. Typical combination starters and units are listed below with their
standard abbreviations:
Figure 1 - 6” High Density Unit
Figure 2 - Standard Unit
FVNR
DFVNR
FVC
FVR
2S1W
2S2W
PW
RVAT
YDC
YDO
FCB
DFCB
FDS
DFDS
XFMR
PNLBD
RVSS
VFD
HFVNR
Full Voltage Non Reversing ...............................................................................
Dual Full Voltage Non-Reversing .......................................................................
Full Voltage Contactor ......................................................................................
Full Voltage Reversing ......................................................................................
Two Speed One Winding ..................................................................................
Two Speed Two Winding ..................................................................................
Part Winding ....................................................................................................
Reduced Voltage Auto-Transformer ..................................................................
Reducing Voltage Wye Delta Closed Transition .................................................
Reducing Voltage Wye Delta Open Transition ...................................................
Feeder Circuit Breaker .....................................................................................
Dual Feeder Circuit Breaker .............................................................................
FeederDisconnect Switch ................................................................................
Dual Feeder Disconnect Switch .......................................................................
Transformer (lighting) ......................................................................................
Panel Board .....................................................................................................
Reduced Voltage Soft Start ..............................................................................
Variable Frequency Drive .................................................................................
High Density Full Voltage Non-Reversing ..........................................................
Siemens Energy & Automation, Inc.
D2-D5
D6-D7
D8-D9
D10-D11
D12-D13
D14-D15
D16-D17
D18-D19
D20-D21
D22-D23
D24
D24
D24
D24
D25
D26
D26
D26
D26
D1
SFIM-7002B-0608
Section D, June, 2008
Combination Starter Ratings and
Dimensions
• Electrical starter seal-in contact for 3-wire control:
Size 0 - 1, NO only. Sizes 2 - 4, SPST.
Size 5 - 6, SPDT.
FVNR - Full Voltage Non-Reversing Unit With
Fusible Switch or Circuit Breaker
• Control circuit terminals:
Type A - Connect to component terminal.
Type Bd, Bt, C - Unit stationary terminal blocks.
Standard Features
• Plug-in unit, Sizes 0 - 5.
• Circuit Breaker Sizes 0 - 5.
• Fusible Switch Sizes 0 - 4.
Molded case switch, Sizes 5 and 6.
Fuse clips for Class R fuses.
• Load power terminals:
Type A, Bd.
- Connect to starter terminals.
Type Bt, C.
- Sizes 0 - 3, stationary blocks.
Sizes 4 - 6, connect to starter terminals.
• Starters: Innova/Plus, Sizes 0 - 4
• Bimetallic Ambient Compensated Overload
Typical Schematic
D2
Siemens Energy & Automation, Inc.
SFIM-7002B-0608
Section D, June, 2008
Available Features - Standard Unit Size
• Surge Suppressor.
• Control power transformer with fused secondary
and Surge suppressor. Dual fused primary.
• ETM.
• Solid state overloads.
• Handle Interlocks operate with handle.
• Pull-apart control terminals.
• Extra starter auxillary contacts in addition to NO seal-in
contact.
• Pull-apart load terminals, Sizes 0 - 2. seal-in contact.
• Class J Fuse Clips.
• Thermal magnetic circuit breaker.
• Refer to tables below for maximum size control power
transformers, relays, and timer addition.
• 4 pilot devices mounted on unit device panel.
• Communicating devices (ASi, SIMICODE-PRO)
• Control relay.
Auxiliary Contacts
Starter
Extra Contacts
Size
Per Starter
0-1
4
2-4
3
5-6
3
Type
SPST NO or NC
SPST NO or NC
SPDT NO & NC
FVNR with ITE MCP Type Breaker: Disconnect Ratings and Space Requirements
Maximum Horsepower
200V
230V
460-575V
3
3
5
7 1/2
7 1/2
10
10
15
25
25
20
50
25
20
50
40
50
100
75
100
200
150
200
400
Starter
Size
0
1
2
3
3
4
5
6
MCP
Frame
Size
125
125
125
125
125
125/250
400
600
Unit
Height
12
12
12
18
24**
24
36
48
Unit
Space
Factor
1
1
1
1 1/2
2
2
3
4
Standard
Control
Transformer
VA
50
50
50
150
150
150
50
150
Maximum
Control
Transformer
VA
150
150
150
250
250
250
150
250
Relay
1*
1*
1*
1*
2
2
1
2
Timer
1*
1*
1*
1*
1
1
1
FVNR with Fusible Switch (Refer to Pg E4): Disconnect Ratings and Space Requirements
Maximum Horsepower
200V
230V
460-575V
3
3
5
7 1/2
7 1/2
10
10
15
25
25
30
50
40
50
100
75
100
200
150
200
400
*
**
1
2
3
Starter
Size
0
1
2
3
4
5
6
Maximum
Fuse
Switch
Clip
Unit
Size
Size
Height
30
30
12
30
30
12
60
60
12
100
100
24
200
200
42
400
600
721
600
600
722
Unit
Space
Factor
1
1
1
2
3 1/2
6
6
Standard
Control
Transformer
VA
50
50
50
150
150
503
150
Maximum
Control
Transformer
VA
150
150
150
250
250
1503
250
Relay Timer
1*
1*
1*
1*
1*
1*
1*
1*
2
1
2
2
1
1
Either/or but not both
Oversized for additional equipment
Fixed mounted unit
Fixed mounted unit - space behind not available
Starter supplied with interposing relay(s)
200, 230V applications
Siemens Energy & Automation, Inc.
D3
SFIM-7002B-0608
Section D, June, 2008
Combination Starter Ratings and
Dimensions
FVNR-High Density Full Voltage NonReversing Unit With Circuit Breaker
Standard Features
• Plug-in unit, Sizes 0 - 1.
• Circuit Breakers Sizes 0 - 1.
• Starters: Innova/Plus, Sizes 0 - 1, ESP100 Overload
• Electrical starter seal-in contact for 3-wire control:
Size 0 - 1, NO only.
• Control circuit terminals: Unit stationary terminal blocks.
Typical Schematic
D4
Siemens Energy & Automation, Inc.
SFIM-7002B-0608
Section D, June, 2008
Available Features - Standard Unit Size
• Control power transformer with fused secondary
and dual fused primary.
• Thermal magnetic circuit breaker.
• 2 pilot devices mounted on unit device panel.
• Surge suppressor.
• Internal Circuit Breaker Interlock.
• Extra starter auxiliary contacts in addition to NO seal-in
contact.
• Clips.
• Refer to tables below for maximum size control power
transformer, relays, and timer addition.
• Communicating devices (ASi, SIMOCODE-DP), (AS-i or
SIMOCODE not available on high density units with control
power transformer.
Auxiliary Contacts
Starter
Size
0-1
Extra Contacts
Per Starter
2
Type
SPSTNO orNC
FVNR with MCP Type Breaker: Disconnect Ratings and Space Requirements
Maximum Horsepower
200V 230V 460-575V
3
3
5
7 1/2
7 1/2
10
Siemens Energy & Automation, Inc.
Starter
Size
0
1
Frame
Size
125
125
MCP
Unit
Height
6
6
Unit
Space
Factor
1/2
1/2
Standard
Control
Transformer
VA
50
50
Maximum
Control
Transformer
VA
Relay
50
0
50
0
Timer
0
0
D5
SFIM-7002B-0608
Section D, June, 2008
Combination Starter Ratings and Dimensions
Dual FVNR-Full Voltage Non-Reversing Unit With Fusible Switch or Circuit Breaker
Standard Features
• Plug-in unit
• Size 0 and 1
• MCP or thermal magnetic circuit breaker
• Innova/Plus Starters - Bimetallic OL Relay
• Control circuit terminals:
Type A - Connect to component terminal.
Type Bd, Bt, C - Unit stationary terminal blocks
• Load power terminals:
Type A, Bd, Bt, C
• Electrical starter seal-in contact for 3-wire control:
Size 0 - 1, NO only.
Qualifications
• Extra capacity control power transformer not available.
• Current limiter attachment not available.
• No room for relays or timers.
• Maximum of four pilot devices per dual unit.
• Maximum of 12 control and 3 power terminal points per
starter
• Circuit breaker type disconnect only. Fusible disconnect
not available.
TYPICAL SCHEMATIC
D6
Siemens Energy & Automation, Inc.
SFIM-7002B-0608
Section D, June, 2008
Available Features - Standard Unit Size
• Ambient Compensated Bimetal Overloads.
• Standard capacity control power transformer with
fused primary and secondary.
• Solid state overload.
• Pull-apart control terminals.
• Pull-apart load terminals.
• Thermal magnetic circuit breaker. Barrier between
starters.
• Surge suppressors. Handle interlocks operate with handle.
• Extra starter auxiliary contacts in addition to NO seal-in
contact.
• Communicating devices (ASi, SIMOCODE-PRO)
Auxiliary Contacts
Starter
Size
0-1
Extra Contacts
Per Starter
4
Type
SPST NO or NC
Dual FVNR with MCP Type Breaker: Disconnect Ratings and Space Requirements
Maximum Horsepower
200V
230V
460-575V
3
3
5
1/2
7 1/2
10
Siemens Energy & Automation, Inc.
Starter
Size
0
1
MCP
Frame
Size
125
125
Unit
Height
18
18
Unit
Space
Factor
1 1/2
1 1/2
Standard
Control
Transformer
VA
50
50
Maximum
Control
Transformer
VA
50
50
Relay Timer
-
D7
SFIM-7002B-0608
Section D, June, 2008
Combination Contactor Ratings and Dimensions With Fusible Switch or Circuit Breaker
Standard Features
• Thermal magnetic circuit breaker.
• Plug-in unit, Sizes 0 - 5.
• Fusible Switch Sizes 0 - 4. Molded case switch,
Sizes 5 and 6. Fuse clips for Class R fuses.
• Contactor: Innova/Plus, Sizes 0 - 4
• Electrical starter seal-in contact for 3-wire control:
Size 0 - 1, NO only. Size 2 - 4, SPST. Size 5 - 6,
SPDT.
• Control circuit terminals:
Type A - Connect to component terminals.
Type Bd, Bt, C - Unit stationary terminal blocks.
• Load power terminals:
Type A, Bd
- Connect to starter terminals.
Type Bt, C
- Sizes 0 - 3, stationary blocks.
- Sizes 4 - 6, connect to starter terminals.
TYPICAL SCHEMATIC
D8
Siemens Energy & Automation, Inc.
SFIM-7002B-0608
Section D, June, 2008
Available Features - Standard Unit Size
• Control power transformer with fused secondary,
and dual fused primary.
• Pull-apart control terminals.
• Pull-apart load terminals, Sizes 0 - 2.
• 4 pilot devices mounted on unit device panel.
• Control relay.
• Surge suppressor.
• ETM
• Handle interlocks operate with handle.
• Extra starter auxillary contacts in addition to NO seal-in
contact.
• Class J fuse clips.
• Refer to tables for maximum size control power transformer, relays, and timer addition.
• Communicating devices (ASi, SIMOCODE-PRO)
Auxiliary Contacts
Starter
Size
0-1
2-4
5-6
Extra
Per Starter
4
3
3
Contacts
Type
SPST NO or NC
SPST NO or NC
SPDT NO & NC
Full Voltage Contactor with Circuit Breaker Disconnect Ratings and Space Requirements
Maximum KW
Resistance Heating Leads
200V
230V
460V
575V
6.92
8.0
15.9
19.9
10.4
11.9
23.9
29.8
24.2
27.8
55.7
69.6
43.3
50.0
99.4
124
43.3
50.0
99.4
124
67.5
77.6
155
194
121
139
278
348
162
210
415
515
Circuit
Breaker
Contactor Frame
Size
Size
0
125
1
125
2
125
3
125
3
125
4
125/250
5
400
6
600
Unit
Height
12
12
12
18
24**
24
36
482
Unit
Space
Factor
1
1
1
1 1/2
2
2
3
4
Standard
Maximum
Control
Control
Transformer Transformer
VA
VA
Relay
50
150
1*
50
150
1*
50
150
1*
150
250
1*
150
250
2
150
250
2
1503
1
503
150
250
2
Timer
1*
1*
1*
1*
1
1
1
Full Voltage Contactor with Fusible Switch (refer to Pg E4): Disconnect Ratings
and Space Requirements
Maximum Horsepower
200V 230V 460V 575V
6.92
8.0
15.9 19.9
10.4 11.9
23.9 29.8
24.2 27.8
55.7 69.6
31.1 35.8
71.6 89.5
43.3 50.0
99.4 124
67.5 77.6
155
194
121
139
278
348
162
210
415
515
*
**
1
2
3
Contactor
Size
0
1
2
3
3
4
5
6
Maximum
Fuse
Switch
Clip
Unit
Size
Size Height
30
30
12
30
60
12
60
60
12
100
100
24
100
100
24
200
200
42
400
600
721
600
600
722
Unit
Space
Factor
1
1
1
2
2
3
5
6
Standard
Control
Transformer
VA
50
50
50
50
150
150
503
150
Maximum
Control
Transformer
VA
Relay Timer
150
1*
1*
150
1*
1*
150
1*
1*
250
1*
1*
250
1*
1*
250
2
1
1503
2
2
250
1
1
Either/or but not both
Oversized for additional equipment
Fixed mounted unit
Fixed mounted unit - Space behind not available
Starter supplied with interposing relay(s)
200, 230V applications
Siemens Energy & Automation, Inc.
D9
SFIM-7002B-0608
Section D, June, 2008
Combination Starter Ratings and Dimensions
FVR-Full Voltage Reversing Unit With Fusible Switch or Circuit Breaker
Standard Features
• Plug-in unit, Sizes 0 - 4 with HMCP, Sizes 0 - 3 with
fusible switch.
• Circuit Breakers Sizes 0 - 5.
• Fusible switches, Sizes 0 - 4. Molded case switches
Sizes 5 - 6. Fuse clips for Class R fuses.
• Electrical starter seal-in contact for 3-wire control:
Size 0 - 1, NO only. Size 2 - 4, SPST. Size 5 - 6,
SPDT. NC reversing electrical interlock per contactor.
• Mechanical interlock on contactors.
• Bimetallic Ambient Compensated Overload
• Starter: Innova/Plus, Sizes 0 - 1 with vertical mechanical
interlock. Innova/Plus, Sizes 2 - 4 with horizontal
mechanical interlock. Bimetallic OL
• Control circuit terminals:
Type A-Connect to component terminal.
Type Bd, Bt, C-Unit stationary terminal blocks.
• Load power terminals:
Type A, Bd-Connect to starter terminals.
Type Bt, C-Sizes 0 - 3, stationary blocks.
Sizes 4 - 6, connect to starter terminals.
Typical Schematic
D10
Siemens Energy & Automation, Inc.
SFIM-7002B-0608
Section D, June, 2008
Available Features-Standard Unit Size
• Control power transformer with fused secondary
and dual fused primary.
• Solid state overload.
• Pull-apart control terminals.
• Pull-apart load terminals, Sizes 0 - 2.
• Thermal magnetic circuit breakers.
• 4-pilot devices mounted on unit device panel.
• Control relay (2).
•
•
•
•
Surge suppressors.
ETM.
Handle interlocks operate with handle.
Extra starter auxiliary contacts in addition to NO maintaining seal-in contact and NC electrical interlock.
• Class J fuse clips.
• Refer to tables below for maximum size control power
tranformer, relays, and timer additions.
• Communicating devices (ASi, SIMOCODE-PRO)
Auxiliary Contacts
Starter
Extra Contacts
Size
Per Starter
0-1
3
2-4
2
5-6
2
Type
SPST NO or NC
SPST NO or NC
SPDT NO & NC
FVR with MCP Type Breaker: Disconnect Ratings and Space Requirements
MCP
Starter Frame
Unit
Size
Size
Height
0
125
18
1
125
18
2
125
24
3
125
30
4
125/250
36
5
400
721
6
600
722
Maximum Horsepower
200V 230V 460-575V
3
3
5
7 1/2
7 1/2
10
10
15
25
25
30
50
40
50
100
75
100
200
150
200
400
Unit
Space
Factor
1 1/2
1 1/2
2
2 1/2
3
6
6
Standard
Control
Transformer
VA
50
50
50
150
150
503
150
Maximum
Control
Transformer
VA
150
150
250
250
250
2503
250
Relay
1*
1*
2
2
2
3
2
Timer
1*
1*
1
1
1
1
1
FVR with Fusible Switch (Refer to Pg E4): Disconnect Ratings and Space Requirements
Maximum Horsepower
200V 230V 460-575V
3
3
5
7 1/2 7 1/2
10
10
15
25
25
30
50
40
50
100
75
100
200
Starter
Size
0
1
2
3
4
5
Maximum
Fuse
Unit
Switch
Clip
Unit
Space
Size
Size
Height Factor
30
30
18
1 1/2
30
60
18
1 1/2
60
60
24
2
100
100
36
3
4 1/2
200
200
541
400
600
30x721
6
Standard
Control
Transformer
VA
50
50
50
150
150
503
Maximum
Control
Transformer
VA
150
150
150
250
250
1503
Relay
2*
2*
2
2
2
2
Timer
1*
1*
1
1
1
2
* Either/or but not both a
• Fixed mounted unit
• Fixed mounted unit-space behind not available
• Starter supplied with interposing relay(s)
200-230V applications
Siemens Energy & Automation, Inc.
D11
SFIM-7002B-0608
Section D, June, 2008
Combination Starter Ratings and Dimensions
2S1W - Two Speed - One Winding Reconnectable Consequent Pole Unit
with Fusible Switch or Circuit Breaker
Standard Features
• Plug-in unit, Sizes 0 - 4 with MCP, Sizes 0 - 3 with
fusible switch.
• Circuit Breaker, Sizes 0 - 5.
• Fusible switch Sizes 0 - 4. Molded case switch size
5. Fuse clips for Class R fuses.
• Electrical starter interlocks-interlock supplied as
required for selective control and to electrically
interlock starters. seal-in contact. Size 0 - 1, NO
only. Sizes 2 - 4, SPST. Size 5 SPDT.
• Mechanically interlocked starters. Innova/Plus,
Sizes 0 - 4.
• Bimetallic Ambient Compensated Overload
• 5-pole starter and 3-pole starter horizontally interlocked.
Size 2 vertical reversing starter and separate starter. Size
3 - 4 horizontal reversing starter and separate starter.
• Control circuit terminals:
Type A-Connect to component terminal.
Type Bd, Bt, C-Unit stationary terminal blocks.
• Load power terminals:
Type A, Bd-Connect to starter terminals.
Type Bt, C-Sizes 0 - 3, stationary blocks.
Size 4 and larger, connect to starter terminals.
Typical Schematic
D12
Siemens Energy & Automation, Inc.
SFIM-7002B-0608
Section D, June, 2008
Available Features-Standard Unit Size
• Solid state overload.
• Control power transformer with fused secondary
and dual fused primary.
• Pull-apart control terminals.
• Pull-apart load terminals Size 0 - 2.
• Thermal magnetic circuit breakers.
• 4-pilot devices mounted on unit device panel.
• Handle interlock operates with handle.
• Extra starter auxiliary contacts vary per size of
starter. Relays will be supplied if number of available contacts is exceeded.
• Compelling control starts on low speed only. Push “Stop”
before transferring from higher to lower speed.
• ETM.
• Progressive control. Automatic starting on low speed and
automatic transfer to fast; stops before transferring from
fast to slow.
• Automatic deceleration.
• Class J fuse clips.
• Refer to tables below for maximum size control power
transformer, relays, and timer additions.
• Control relay (1).
• Surge suppressors.
• Communicating devices (ASi, SIMOCODE-PRO)
Auxiliary Contacts
Extra Contact
Starter
Constant or Variable Torque
Size
High/Low
0-1
0/2
2-4
4/2
5
4/2
Extra Contact
Constant Horsepower
High/Low
2/0
2/4
2/4
Type
SPSTNO orNC
SPSTNO orNC
SPDT NO & NC
2S1W with MCP Type Breaker: Disconnect Ratings and Space Requirements
Standard
Maximum
Constant or Variable
Constant
MCP
Unit
Control
Control
Torque
Horsepower
Starter Frame Unit
Space Transformer Transformer
200V 230V 460-575V 200V 230V 460-575V Size
Size Height Factor
VA
VA
Relay Timer
3
3
5
2
2
3
0
125
24
2
50
250
2
1
7 1/2 7 1/2
10
5
5
7 1/2
1
125
24
2
50
250
2
1
10
15
25
7 1/2
10
20
2
125
24
2
150
250
1
1
25
30
50
20
25
40
3
125
36
3
150
250
2
2503
2
1
40
50
100
30
40
75
4
125/250 48
4
503
75
100
200
60
75
150
5
400
30x721
6
503
2503
2
2
2S1W with Standard Fusible Switch (Refer to Pg E4): Disconnect Ratings
and Space Requirements
Maximum
Standard
Maximum
Constant orVariable
Constant
Fuse
Unit
Control
Control
Torque
Horsepower
Starter Switch Clip Unit
Space Transformer Transformer
200V 230V 460-575V 200V 230V 460-575V Size
Size Size Height Factor
VA
VA Relay Timer
3
3
5
2
2
3
0
30
30
24
2
50
150
2
1
7 1/2 7 1/2
10
5
5
7 1/2
1
30
60
24
2
50
150
2
1
10
15
25
7 1/2 10
20
2
60
60
24
2
150
250
1
1
25
30
50
20
25
40
3
100
100
48
4
150
250
2
1
6
503
2503 4
1
40
50
100
30
40
75
4
200
200
721
75
100
200
60
75
150
5
400
600 30x721
5
503
2503 2
1
1 Fixed mounted unit
3 Starter supplied with interposing relay(s)
200 & 230V applications
Siemens Energy & Automation, Inc.
D13
SFIM-7002B-0608
Section D, June, 2008
Combination Starter Ratings and Dimensions
2S2W - Two Speed - Two Winding Unit With Fusible Switch or Circuit Breaker
Standard Features
• Plug-in unit, Sizes 0 - 4 with circuit breakers, Sizes
0 - 3 with fusible switch.
• Circuit Breaker, Sizes 0 - 5.
• Fusible switch Sizes 0 - 4. Molded case switches,
Sizes 5. Fuse clips for Class R fuses.
• Electrical starter interlocks - supplied as required
for selective control and to electrically interlock
starters.
Seal-in contact:
Sizes 0 - 1, NO only.
Sizes 2 - 4, SPST.
Size 5, SPDT.
• Bimetallic Ambient Compensated Overload
• Mechanical interlock on starters.
Starters: Innova/Plus, Sizes 0 - 4.
Sizes 0 - 4: Innova/Plus consisting of 2 starters horizontally interlocked.
Sizes 5: 2 starters with vertical mechanical interlock.
• Control circuit terminals:
Type A - Connect to component terminal.
Type Bd, Bt, C - Unit stationary - terminal blocks.
• Load power terminals:
Type A, Bd - Connect to starter terminals.
Type Bt, C - Sizes 0 - 3, stationary blocks.
Size 4 and larger, connect to starter terminals.
Typical Schematic
D14
Siemens Energy & Automation, Inc.
SFIM-7002B-0608
Section D, June, 2008
Available Features - Standard Unit Size
• Solid state overload.
• Control power transformer with fused secondary,
and dual fused primary.
• Pull-apart control terminals.
• Pull-apart load terminals. Sizes 0 - 2.
• Thermal magnetic circuit breakers.
• 4 pilot devices mounted on unit device panel.
• Handle interlock operates with handle.
• Extra starter auxiliary contacts vary per size of
starter. Relays will be supplied if number of available auxiliary contacts are exceeded.
• Compelling control starts on low speed only. Push “Stop”
before transferring from high to low speed.
• Progressive control. Automatic starting on low speed and
automatic transfer to fast. Stops before transferring from
fast to slow.
• Automatic deceleration.
• Class J fuse clips.
• Refer to tables below for maximum size control power
transformer, relays, and timer additions.
• Control relay (1).
• Surge suppressors.
• ETM.
• Communicating devices (ASi, SIMOCODE-PRO)
Auxiliary Contacts
Starter
Extra Contacts
Size
Hi/Low
0-1
3/3
2-4
2/2
5
2/2
Type
SPST NO or NC
SPST NO or NC
SPDT NO & NC
2S2W with MCP Type Breaker: Disconnect Ratings and Space Requirements
Constant or Variable
Torque
200V 230V 460-575V
3
3
5
7 1/2 7 1/2
10
10
15
25
25
30
50
40
50
100
75 100
200
Constant Horsepower
200V 230V 460-575V
2
2
3
5
5
7 1/2
7 1/2 10
20
20
25
40
30
40
75
60
75
150
Standard
Maximum
MCP
Unit
Control
Control
Starter Frame Unit
Space Transformer Transformer
Size
Size Height Factor
VA
VA
Relay Timer
0
125
24
2
50
250
2
1
1
125
24
2
50
250
2
1
2
125
24
2
50
250
2
1
3
125
30
2 1/2
150
250
2
1
2503
2
1
4
125/250
36
3
503
5
400
30x721
6
503
2503
2
1
2S2W with Standard Fusible Switch (Refer to Pg E4): Disconnect Ratings
and Space Requirements
Maximum
Constant or Variable
Fuse
Torque
Constant Horsepower Starter Switch Clip Unit
200V 230V 460-575V 200V 230V 460-575V Size
Size Size Height
3
3
5
2
2
3
0
30
30
24
7 1/2 7 1/2
10
5
5
7 1/2
1
30
60
24
10
15
25
7 1/2
10
20
2
60
60
24
25
30
50
20
25
40
3
100
100
36
40
50
100
30
40
75
4
200
200
541
75
100
200
60
75
150
5
400
600 30x721
Unit
Space
Factor
2
2
2
3
4 1/2
6
Standard Maximum
Control Control
Transf. Transf.
VA
VA
Relay
50
150
2
50
150
2
50
150
2
150
250
2
503
2503
1
503
2503
2
55BA
1
1
1
1
1
2
1 Fixed mounted unit
3 Starter supplied with interposing relay(s)
200 & 230V applications
Siemens Energy & Automation, Inc.
D15
SFIM-7002B-0608
Section D, June, 2008
Combination Starter Ratings And Dimensions
PW - Full Voltage Part Winding Unit with Fusible Switch or Circuit Breaker
Standard Features
• Plug-in units.
• Sizes 0 - 4, circuit breaker. Sizes 0 - 4, fusible
switch.
• Thermal magnetic breaker, Sizes 0 - 5.
• Fusible switches.
Sizes 0 - 3. Molded case switches, Sizes 4 5.Molded case switch,
Size 4, on 230V.Fuse clips for Class R fuses.
• Starters: Innova/Plus: 0 - 4.
• Bimetallic Ambient Compensated Overload
• Electrical starter interlocks-NO interlock supplied on 1M
for 3 wire control.
Sizes 1, NO only.
Sizes 2 - 4, SPST.
Sizes 5, SPDT.
• Control circuit terminals:
Type A - Connect to component terminal.
Type Bd, Bt, C - Unit stationary terminal blocks.
• Load power terminals:
Type A, Bd - Connect to starter terminals.
Type Bt, C - Sizes 0 - 3, stationary blocks.
Sizes 4 - 5 connect to starter.
Typical Schematic
D16
Siemens Energy & Automation, Inc.
SFIM-7002B-0608
Section D, June, 2008
Available Features-Standard Unit Size
• Control power transformer-Fused secondary and
dual fused primary.
• Pull-apart control terminals.
• Solid state overload.
• Pull-apart load terminals, Sizes 0 - 2.
• 4 pilot devices mounted on unit device panel.
• Handle interlock operates with handle.
• Control relay.
• Surge suppressors.
• Extra starter auxiliary contacts in addition to NO seal-in
contact.
• Class J fuse clips.
• Refer to tables below for maximum size control power
transformer, relays, and timer additions.
• Communicating devices (ASi, SIMOCODE-PRO)
Auxiliary Contacts
Starter
Extra Contacts
Size
Per Starter
0-1
3
2-4
2
5
3
Type
SPST NO or NC
SPST NO or NC
SPST NO or NC
PW with Circuit Breaker: Disconnect Ratings and Space Requirements
Maximum Horsepower
200V 230V 460-575V
10
10
15
20
25
40
40
50
75
40
50
75
75
75
150
150 150
350
Starter
Size
1
2
3
3
4
5
Circuit
Breaker
Frame
Size
125
125
125
250
400
600
Unit
Height
24
24
30
36
36
721
Unit
Space
Factor
2
2
2 1/2
3
3
6
Standard
Control
Transformer
VA
150
150
150
150
503
503
Maximum
Control
Transformer
VA
250
250
250
250
1503
2503
Relay
2
2
2
2
2
2
Timer
55BA
1
1
1
1
1
1
PW with Standard Fusible Switch (Refer to Pg E4): Disconnect Ratings and Space Requirements
Maximum Horsepower
200V 230V 460-575V
10
10
15
20
25
40
40
50
75
75
75
150
150
150
350
Starter
Size
1
2
3
4
5
Maximum
Fuse
Switch
Clip
Unit
Size
Size
Height
60
60
24
100
100
30
200
200
48
400
400
721
600
600
30x721
Unit
Space
Factor
2
2 1/2
4
6
6
Standard
Control
Transformer
VA
150
150
150
503
503
Maximum
Control
Transformer
VA
Relay
250
2
250
2
250
2
2503
1
2503
2
Timer
55BA
1
1
1
1
2
1 Fixed mounted unit
3 Starter supplied with interposing relay(s)
200 & 230V applications
Siemens Energy & Automation, Inc.
D17
SFIM-7002B-0608
Section D, June, 2008
Combination Starter Ratings and Dimensions
RVAT - Reduced Voltage Auto-Transformer Unit with Fusible Switch or Circuit Breaker
Standard Features
• Fixed mounted units, Sizes 2 - 6.
• Fusible switch Sizes 0 - 4.
• Molded case switches, Sizes 5 - 6. Fuse clips sized
for time delay fuses. Class R.
• Starter: Innova/Plus, Sizes 2 - 4. Starter (R) and contactor (1S) with mechanical interlock. 3 pole contactor (2S).
• Bimetallic Ambient Compensated Overloads.
• Auto Transformer
NEMA medium duty 3 coil: 50%, 65%, 80% taps.
Class F insulation (minimum). Mounted across bottom of structure.
• Electrical starter interlocks-NO on (2S); (R) for 3 wire control.
Sizes 2 - 4, SPST.
Sizes 5 - 6, SPDT.
• Control circuit terminals:
Type A - Connect to component terminal.
Type Bd, Bt, C - Unit stationary terminal blocks.
• Load power terminals.
Type A, Bd - connect to starter terminals.
Type Bt, C - Sizes 0 - 3, stationary blocks.
Sizes 4 - 6, connect to starter terminals.
Typical Schematic
D18
Siemens Energy & Automation, Inc.
SFIM-7002B-0608
Section D, June, 2008
Available Features-Standard Unit Size
• Control power transformer-fused secondary and
dual fused primary.
• Pull-apart control terminal.
• Pull-apart load terminals, Sizes 0 - 2.
• Solid state overload.
• Thermal-magnetic circuit breakers.
•
•
•
•
Extra starter auxiliary contacts, 2S or R (relay used).
Surge suppressors.
Class J fuse clips.
Refer to tables below for maximum size control power
transformer, relays, and timer additions.
• Communicating devices (ASi, SIMOCODE-PRO)
RVAT with MCP Type Breaker: Disconnect Ratings and Space Requirements
Maximum Horsepower
Starter
200V 230V 460-575V
Size
10
15
25
2
25
30
50
3
40
50
100
4
75
100
200
5
150
200
400
6
400
6
MCP
Frame
Size
125
125
125/250
400
600
800
Unit
Height
421
421
481
30X722
30X722
30X722
Unit
Space
Factor
3 1/2
3 1/2
4
6
6
6
Standard
Control
Transformer
VA
150
150
503
503
503
503
Maximum
Control
Transformer
VA
250
250
2503
2503
2503
2503
Relay
2
1
2
1
2
2
Timer
1
1
1
2
2
RVAT with Standard Fusible Switch (Refer to Pg E4): Disconnect Ratings
and Space Requirements
Maximum Horsepower
200V 230V 460-575V
10
15
25
25
30
50
40
50
100
75
100
200
150
200
350
400
1
2
3
4
Starter
Size
2
3
4
5
6
6
Maximum
Fuse
Switch
Clip
Unit
Size
Size Height
60
60
421
100
100
481
200
200
601
400
600
30x722
600
600
30x722
800
800
50x7224
Unit
Space
Factor
3 1/2
4
6
6
6
6
Standard
Control
Transformer
VA
150
150
503
503
503
503
Maximum
Control
Transformer
VA
Relay
250
2
250
2
2503
2503
1
2503
2
2503
-
Timer
1
1
1
-
Fixed mounted unit
Fixed mounted unit - space behind not available
Starter supplied with interposing relay(s)
Requires 20” deep structure
200 & 230V applications
Siemens Energy & Automation, Inc.
D19
SFIM-7002B-0608
Section D, June, 2008
Combination Starter Ratings And Dimensions
YDC - Reduced Voltage Wye Delta Closed Transition
Standard Features
• Plug-in units.
• Sizes 0 - 6, circuit breaker. Sizes 0 - 5, fusible
switch.
• Fusible switches.
Sizes 0 - 3. Molded case switches, Sizes 4 - 5.
• Starters: Innova/Plus: 0 - 4.
• Bimetallic Ambient Compensated Overloads
• Control circuit terminals:
Type A-Connect to component terminal.
Type Bd, Bt, C-Unit stationary terminal blocks.
• Electrical starter interlocks-NO interlock
For 3 wire control.
Sizes 2 - 4, SPST.
Sizes 5 - 6, SPDT.
• Load power terminals:
Type A, Bd - Connect to starter terminals.
Type Bt, C - Sizes 0 - 3, stationary blocks.
Sizes 4 - 6 connect to starter.
TYPICAL SCHEMATIC
D20
Siemens Energy & Automation, Inc.
SFIM-7002B-0608
Section D, June, 2008
Available Features-Standard Unit Size
• Control power transformer-Fused secondary and
dual fused primary.
• Pull-apart control terminals.
• Solid state overload.
• Phase Failure Relay
• Pull-apart load terminals, SIzes 0 - 2.
• 4 pilot devices mounted on unit device panel.
•
•
•
•
Handle interlock operates with handle.
Control relay.
Surge suppressors.
Extra starter auxiliary contacts in addition to NO seal-in
contact.
• Class J fuse clips.
• Refer to tables below for maximum size control power
transformer, relays, and timer additions.
Auxiliary Contacts
Starter
Extra Contacts
Size
Per Starter
2-4
3
5-6
3
Type
SPST NO or NC
SPST NO or NC
YDC with Circuit Breaker: Disconnect Ratings and Space Requirements
Maximum Horsepower
200V 230V 460-575V
20
25
40
40
50
75
40
50
75
60
75
150
150
150
300
300
350
700
300
350
700
Starter
Size
2
3
3
4
5
6
6
Circuit
Breaker
Frame
Size
125
125
125
250
600
600
800
Unit
Height
42
42
48
48
30x721
40x721
40x721
Unit
Space
Factor
3 1/2
3 1/2
4
4
6
6
6
Standard
Control
Transformer
VA
150
150
150
503
503
503
503
Maximum
Control
Transformer
VA
250
250
250
1503
2503
2503
2503
Relay
2
2
2
2
4
2
2
Timer
2
2
1
1
2
1
1
YDC with Standard Fusible Switch (Refer to Pg E4): Disconnect Ratings and Space Requirements
Maximum Horsepower
200V 230V 460-575V
20
25
40
40
50
75
60
75
150
150
150
300
Starter
Size
2
3
4
5
Maximum
Fuse
Switch
Clip
Unit
Size
Size Height
100
100
48
200
200
60
400
400
721
600
600
30x721
Unit
Space
Factor
4
5
6
6
Standard
Maximum
Control
Control
Transformer Transformer
VA
VA
Relay
150
250
2
150
250
2
503
2503
2
503
2503
4
Timer
2
1
1
2
1 Fixed mounted unit
2 Starter supplied with interposing relay(s)
Siemens Energy & Automation, Inc.
D21
SFIM-7002B-0608
Section D, June, 2008
Combination Starter Ratings And Dimensions
YDO - Reduced Voltage Wye Delta Open Transition
Standard Features
• Sizes 0 - 6, circuit breaker. Sizes 0 - 5, fusible
switch.
• Fusible switches.
Sizes 0 - 3. Molded case switches, Sizes 4 - 5.
• Starters: Innova/Plus: 0 - 4.
• Bimetal Ambient Compensated Overloads
• Control circuit terminals:
Type A-Connect to component terminal.
Type Bd, Bt, C-Unit stationary terminal blocks.
• Electrical starter interlocks-NO interlock
For 3 wire control.
Sizes 2 - 4, SPST.
Sizes 5 - 6, SPDT.
• Load power terminals:
Type A, Bd - Connect to starter terminals.
Type Bt, C - Sizes 0 - 3, stationary blocks.
Sizes 4 - 6 connect to starter.
TYPICAL SCHEMATIC
D22
Siemens Energy & Automation, Inc.
SFIM-7002B-0608
Section D, June, 2008
Available Features-Standard Unit Size
• Control power transformer-fused secondary and
dual fused primary.
• Pull-apart control terminals.
• Solid state overload.
• Phase Failure Relay
• Pull-apart load terminals, SIzes 0 - 2.
• 4 pilot devices mounted on unit device panel.
• Handle interlock operates with handle.
• Control relay
• Surge suppressors.
• Extra starter auxiliary contacts in addition to NO seal-in
contact.
• Class J fuse clips.
• Refer to tables below for maximum size control power
transformer, relays, and timer additions.
Auxiliary Contacts
Starter
Extra Contacts
Size
Per Starter
Type
2-4
3
SPSTNO orNC
5-6
3
SPSTNO orNC
YDO with Circuit Breaker: Disconnect Ratings and Space Requirements
Maximum Horsepower
200V 230V 460-575V
20
25
40
40
50
75
60
75
150
150
150
300
300
350
700
300
350
700
Starter
Size
2
3
4
5
6
6
Circuit
Breaker
Frame
Size
125
125
250
600
600
800
Unit
Height
30
30
36
30x721
40x721
40x721
Unit
Space
Factor
2 1/2
2 1/2
3
6
6
6
Standard
Control
Transformer
VA
150
150
503
503
503
503
Maximum
Control
Transformer
VA
250
250
1503
2503
2503
2503
Relay
3
3
2
4
2
2
Timer
1
1
1
2
1
1
YDO with Standard Fusible Switch (Refer to Pg E4): Disconnect Ratings and Space Requirements
Maximum Horsepower
200V 230V 460-575V
20
25
40
40
50
75
Starter
Size
2
3
Maximum
Fuse
Switch
Clip
Unit
Size
Size
Height
100
100
36
200
200
48
Unit
Space
Factor
3
4
Standard
Maximum
Control
Control
Transformer Transformer
VA
VA
Relay
150
250
2
150
250
2
Timer
1
1
60
75
150
4
400
400
721
6
503
2503
2
1
150
150
300
5
600
600
30x721
6
503
2503
4
2
1 Fixed mounted unit
3 Starter supplied with interposing relay(s)
Siemens Energy & Automation, Inc.
D23
SFIM-7002B-0608
Section D, June, 2008
FeederTap Fusible Switches
Fusible feeder switches, 30A through 200A, are mounted in
plug-in units. Switches above 200A are fixed mounted and
consist of molded-case switches and separate fuse blocks.
Dual-mounted fusible switches are available, 30A and 60A,
with clips of same rating. Fuse clips are Class RK dimensions
for 30-600A.
FeederTap Circuit Breakers
These breakers are thermal magnetic type and feed
lighting or power circuits. 125A and 250A frame
breakers are mounted in plug-in units. Higher rated
breakers are fixed mounted. (See chart on page G6
for short circuit ratings and type of circuit breakers
available.)
Dual mounted 125A frame breakers may be mounted
in a 12” plug-in unit with a common door.
Circuit breakers
Fusible disconnect switch
FeederTap Circuit Breakers and Fusible Switches: Disconnect Ratings and Space Requirements
Unit
Height
-
Switch
Rating
(A.)
30
60
100
200
Fuse
Clip
Size
Amps
30
60
100
200
1 Sw.
122
122
18
30
2 SW.
122
122
-
-
400
400
4213
-
-
600
600
4213
-
Frame
Size
125
Max.
Trip
Amps
125
1CB
12
2CB
12
250
250
18
400
400
2413
600
600
2413
Unit
Height
1 Fixed mounted unit.
2 Requires load terminal blocks.
3 Stab opening at top of unit not available in rear.
D24
Siemens Energy & Automation, Inc.
SFIM-7002B-0608
Section D, June, 2008
Distribution Units
A Motor Control Center is principally intended to
house multiple combination starters for the control of
electrical motors. It is often convenient to include a
limited number of power distribution units.
Transformer Protection - Lighting and Master
Control
Primary protection is required, per NEC sizes as follows: (lp = transformer primary currents.)
125% lp for lp greater than 9A.
167% lp for lp less than 9A.
300% lp for lp less than 2A.
In addition to primary protection, secondary protection must be supplied if the transformer secondary is
3 or 4 wire (dual voltage). Secondary protection is
not required if the transformer is 2 wire (single voltage secondary).
Description of Standard Transformers
Single Phase Transformers
1KVA thru 2KVA
240/480V Primary
120V Secondary
50/60 Hz
3KVA and larger sizes are mounted in bottom of section. 20KVA or larger sizes require 20” deep sections.
Single Phase Transformer
480/240V - 120/240V Secondary 60 Hz
Transformer
Unit
Height *
12
12
18
18
18
24
Primary
Size Trip
240V
20
30
40
50
70
125
Note:
No vertical bus behind or below.
5.0KVA and larger.
20KVA or larger requires 20” deep structures.
* Does not include 6” bottom wireway space.
Siemens Energy & Automation, Inc.
3KVA thru 5KVA
240/480V Primary
240/120V Secondary
50/60 Hz
7 1/2, 10, 15, 25, 30KVA
240/480V Primary with (2) 2 1/2%
FCAN and (4) 2 1/2% FCBM Taps
240/120V Secondary, 60 Hz
220C insulation, 150C rise
Three Phase Transformer
6 to 15 KVA
480V Primary with (2) 5% FCBN taps
208/120V “Y” - connected Secondary
25-45 KVA
480V Primary with (2) 2 1/2% FCAN and (40) 2 1/2%
FCBN taps
208/120V “Y” - connected Secondary
220C insulation, 150C rise
Transformer Ratings and Space Requirements
Single Phase Transformers:
1KVA and 2KVA sizes with 120V secondary can be
mountedin a single 12” plug-in unit with a primary
circuit breaker or fusible disconnect.
KVA
Rating
3.0
5.0
7.5
10
15
25
These units consist of the following:
• Transformers
• Feeder tap circuit breakers
• Feeder tap fusible disconnects
• Lighting panels
3 Phase Transformers:
All three phase transformers require 20” deep sections, must
be mounted in the bottom, and will not have vertical bus in
that compartment. Refer to page B22 for conduit entry.
All 3KVA and larger single phase and all three phase transformers are mounted approximately 5 inches above the
structure base channel sills.
Three Phase Transformer
480V Primary - 208/120V Secondary 60 Hz
Breaker
Amps
480V
15
15
20
30
40
60
KVA
Rating
9
15
25
30
45
Unit
Height *
12
18
18
18
24
Primary Breaker
Size Trip Amps
480V
15
25
30
45
70
Note:
All three phase transformers require 20” deep structures and
20” wide doors.
D25
SFIM-7002B-0608
Section D, June, 2008
Panel Board
Panel Boards
Full size bolt-on breakers - 1, 2, and 3 pole - 15 to
100A.
1 phase 3 wire - 120/240 volt
or
3 phase 4 wire - 120/208 volt
3 phase 4 wire - 380/220 volt
3 phase 4 wire - 480/277 volt
Aluminum bus - 100 and 225A depending on number
of circuits.
Main lug only - 100 and 225A
Main circuit breaker - 100 and 225A - 12 to 42 circuits.
Disconnect Ratings and Space Requirements:
Circuit Breaker Panel Boards
Main
Bus
Number
Breaker
Rating
Circuits
Type
(Amps)
(Amps)
18
1Ø-3W
100
30
1Ø-3W
225
42
1Ø-3W
225
18
3Ø-4W
100
30
3Ø-4W
225
42
3Ø-4W
225
18
1Ø-3W
100
100
30
1Ø-3W
225
225
42
1Ø-3W
225
225
18
3Ø-4W
100
100
30
3Ø-4W
225
225
42
3Ø-4W
225
225
Unit
Height
(Inches)
30
36
42
30
36
42
30
36
36
30
36
42
10,000A 240V short circuit rating. UL listed.
D26