SFIM-7002B-0608 Section D, June, 2008 Combination Starters and Distribution Units Several different kinds of combination starters and distribution units can be put into a MCC. Typical combination starters and units are listed below with their standard abbreviations: Figure 1 - 6” High Density Unit Figure 2 - Standard Unit FVNR DFVNR FVC FVR 2S1W 2S2W PW RVAT YDC YDO FCB DFCB FDS DFDS XFMR PNLBD RVSS VFD HFVNR Full Voltage Non Reversing ............................................................................... Dual Full Voltage Non-Reversing ....................................................................... Full Voltage Contactor ...................................................................................... Full Voltage Reversing ...................................................................................... Two Speed One Winding .................................................................................. Two Speed Two Winding .................................................................................. Part Winding .................................................................................................... Reduced Voltage Auto-Transformer .................................................................. Reducing Voltage Wye Delta Closed Transition ................................................. Reducing Voltage Wye Delta Open Transition ................................................... Feeder Circuit Breaker ..................................................................................... Dual Feeder Circuit Breaker ............................................................................. FeederDisconnect Switch ................................................................................ Dual Feeder Disconnect Switch ....................................................................... Transformer (lighting) ...................................................................................... Panel Board ..................................................................................................... Reduced Voltage Soft Start .............................................................................. Variable Frequency Drive ................................................................................. High Density Full Voltage Non-Reversing .......................................................... Siemens Energy & Automation, Inc. D2-D5 D6-D7 D8-D9 D10-D11 D12-D13 D14-D15 D16-D17 D18-D19 D20-D21 D22-D23 D24 D24 D24 D24 D25 D26 D26 D26 D26 D1 SFIM-7002B-0608 Section D, June, 2008 Combination Starter Ratings and Dimensions • Electrical starter seal-in contact for 3-wire control: Size 0 - 1, NO only. Sizes 2 - 4, SPST. Size 5 - 6, SPDT. FVNR - Full Voltage Non-Reversing Unit With Fusible Switch or Circuit Breaker • Control circuit terminals: Type A - Connect to component terminal. Type Bd, Bt, C - Unit stationary terminal blocks. Standard Features • Plug-in unit, Sizes 0 - 5. • Circuit Breaker Sizes 0 - 5. • Fusible Switch Sizes 0 - 4. Molded case switch, Sizes 5 and 6. Fuse clips for Class R fuses. • Load power terminals: Type A, Bd. - Connect to starter terminals. Type Bt, C. - Sizes 0 - 3, stationary blocks. Sizes 4 - 6, connect to starter terminals. • Starters: Innova/Plus, Sizes 0 - 4 • Bimetallic Ambient Compensated Overload Typical Schematic D2 Siemens Energy & Automation, Inc. SFIM-7002B-0608 Section D, June, 2008 Available Features - Standard Unit Size • Surge Suppressor. • Control power transformer with fused secondary and Surge suppressor. Dual fused primary. • ETM. • Solid state overloads. • Handle Interlocks operate with handle. • Pull-apart control terminals. • Extra starter auxillary contacts in addition to NO seal-in contact. • Pull-apart load terminals, Sizes 0 - 2. seal-in contact. • Class J Fuse Clips. • Thermal magnetic circuit breaker. • Refer to tables below for maximum size control power transformers, relays, and timer addition. • 4 pilot devices mounted on unit device panel. • Communicating devices (ASi, SIMICODE-PRO) • Control relay. Auxiliary Contacts Starter Extra Contacts Size Per Starter 0-1 4 2-4 3 5-6 3 Type SPST NO or NC SPST NO or NC SPDT NO & NC FVNR with ITE MCP Type Breaker: Disconnect Ratings and Space Requirements Maximum Horsepower 200V 230V 460-575V 3 3 5 7 1/2 7 1/2 10 10 15 25 25 20 50 25 20 50 40 50 100 75 100 200 150 200 400 Starter Size 0 1 2 3 3 4 5 6 MCP Frame Size 125 125 125 125 125 125/250 400 600 Unit Height 12 12 12 18 24** 24 36 48 Unit Space Factor 1 1 1 1 1/2 2 2 3 4 Standard Control Transformer VA 50 50 50 150 150 150 50 150 Maximum Control Transformer VA 150 150 150 250 250 250 150 250 Relay 1* 1* 1* 1* 2 2 1 2 Timer 1* 1* 1* 1* 1 1 1 FVNR with Fusible Switch (Refer to Pg E4): Disconnect Ratings and Space Requirements Maximum Horsepower 200V 230V 460-575V 3 3 5 7 1/2 7 1/2 10 10 15 25 25 30 50 40 50 100 75 100 200 150 200 400 * ** 1 2 3 Starter Size 0 1 2 3 4 5 6 Maximum Fuse Switch Clip Unit Size Size Height 30 30 12 30 30 12 60 60 12 100 100 24 200 200 42 400 600 721 600 600 722 Unit Space Factor 1 1 1 2 3 1/2 6 6 Standard Control Transformer VA 50 50 50 150 150 503 150 Maximum Control Transformer VA 150 150 150 250 250 1503 250 Relay Timer 1* 1* 1* 1* 1* 1* 1* 1* 2 1 2 2 1 1 Either/or but not both Oversized for additional equipment Fixed mounted unit Fixed mounted unit - space behind not available Starter supplied with interposing relay(s) 200, 230V applications Siemens Energy & Automation, Inc. D3 SFIM-7002B-0608 Section D, June, 2008 Combination Starter Ratings and Dimensions FVNR-High Density Full Voltage NonReversing Unit With Circuit Breaker Standard Features • Plug-in unit, Sizes 0 - 1. • Circuit Breakers Sizes 0 - 1. • Starters: Innova/Plus, Sizes 0 - 1, ESP100 Overload • Electrical starter seal-in contact for 3-wire control: Size 0 - 1, NO only. • Control circuit terminals: Unit stationary terminal blocks. Typical Schematic D4 Siemens Energy & Automation, Inc. SFIM-7002B-0608 Section D, June, 2008 Available Features - Standard Unit Size • Control power transformer with fused secondary and dual fused primary. • Thermal magnetic circuit breaker. • 2 pilot devices mounted on unit device panel. • Surge suppressor. • Internal Circuit Breaker Interlock. • Extra starter auxiliary contacts in addition to NO seal-in contact. • Clips. • Refer to tables below for maximum size control power transformer, relays, and timer addition. • Communicating devices (ASi, SIMOCODE-DP), (AS-i or SIMOCODE not available on high density units with control power transformer. Auxiliary Contacts Starter Size 0-1 Extra Contacts Per Starter 2 Type SPSTNO orNC FVNR with MCP Type Breaker: Disconnect Ratings and Space Requirements Maximum Horsepower 200V 230V 460-575V 3 3 5 7 1/2 7 1/2 10 Siemens Energy & Automation, Inc. Starter Size 0 1 Frame Size 125 125 MCP Unit Height 6 6 Unit Space Factor 1/2 1/2 Standard Control Transformer VA 50 50 Maximum Control Transformer VA Relay 50 0 50 0 Timer 0 0 D5 SFIM-7002B-0608 Section D, June, 2008 Combination Starter Ratings and Dimensions Dual FVNR-Full Voltage Non-Reversing Unit With Fusible Switch or Circuit Breaker Standard Features • Plug-in unit • Size 0 and 1 • MCP or thermal magnetic circuit breaker • Innova/Plus Starters - Bimetallic OL Relay • Control circuit terminals: Type A - Connect to component terminal. Type Bd, Bt, C - Unit stationary terminal blocks • Load power terminals: Type A, Bd, Bt, C • Electrical starter seal-in contact for 3-wire control: Size 0 - 1, NO only. Qualifications • Extra capacity control power transformer not available. • Current limiter attachment not available. • No room for relays or timers. • Maximum of four pilot devices per dual unit. • Maximum of 12 control and 3 power terminal points per starter • Circuit breaker type disconnect only. Fusible disconnect not available. TYPICAL SCHEMATIC D6 Siemens Energy & Automation, Inc. SFIM-7002B-0608 Section D, June, 2008 Available Features - Standard Unit Size • Ambient Compensated Bimetal Overloads. • Standard capacity control power transformer with fused primary and secondary. • Solid state overload. • Pull-apart control terminals. • Pull-apart load terminals. • Thermal magnetic circuit breaker. Barrier between starters. • Surge suppressors. Handle interlocks operate with handle. • Extra starter auxiliary contacts in addition to NO seal-in contact. • Communicating devices (ASi, SIMOCODE-PRO) Auxiliary Contacts Starter Size 0-1 Extra Contacts Per Starter 4 Type SPST NO or NC Dual FVNR with MCP Type Breaker: Disconnect Ratings and Space Requirements Maximum Horsepower 200V 230V 460-575V 3 3 5 1/2 7 1/2 10 Siemens Energy & Automation, Inc. Starter Size 0 1 MCP Frame Size 125 125 Unit Height 18 18 Unit Space Factor 1 1/2 1 1/2 Standard Control Transformer VA 50 50 Maximum Control Transformer VA 50 50 Relay Timer - D7 SFIM-7002B-0608 Section D, June, 2008 Combination Contactor Ratings and Dimensions With Fusible Switch or Circuit Breaker Standard Features • Thermal magnetic circuit breaker. • Plug-in unit, Sizes 0 - 5. • Fusible Switch Sizes 0 - 4. Molded case switch, Sizes 5 and 6. Fuse clips for Class R fuses. • Contactor: Innova/Plus, Sizes 0 - 4 • Electrical starter seal-in contact for 3-wire control: Size 0 - 1, NO only. Size 2 - 4, SPST. Size 5 - 6, SPDT. • Control circuit terminals: Type A - Connect to component terminals. Type Bd, Bt, C - Unit stationary terminal blocks. • Load power terminals: Type A, Bd - Connect to starter terminals. Type Bt, C - Sizes 0 - 3, stationary blocks. - Sizes 4 - 6, connect to starter terminals. TYPICAL SCHEMATIC D8 Siemens Energy & Automation, Inc. SFIM-7002B-0608 Section D, June, 2008 Available Features - Standard Unit Size • Control power transformer with fused secondary, and dual fused primary. • Pull-apart control terminals. • Pull-apart load terminals, Sizes 0 - 2. • 4 pilot devices mounted on unit device panel. • Control relay. • Surge suppressor. • ETM • Handle interlocks operate with handle. • Extra starter auxillary contacts in addition to NO seal-in contact. • Class J fuse clips. • Refer to tables for maximum size control power transformer, relays, and timer addition. • Communicating devices (ASi, SIMOCODE-PRO) Auxiliary Contacts Starter Size 0-1 2-4 5-6 Extra Per Starter 4 3 3 Contacts Type SPST NO or NC SPST NO or NC SPDT NO & NC Full Voltage Contactor with Circuit Breaker Disconnect Ratings and Space Requirements Maximum KW Resistance Heating Leads 200V 230V 460V 575V 6.92 8.0 15.9 19.9 10.4 11.9 23.9 29.8 24.2 27.8 55.7 69.6 43.3 50.0 99.4 124 43.3 50.0 99.4 124 67.5 77.6 155 194 121 139 278 348 162 210 415 515 Circuit Breaker Contactor Frame Size Size 0 125 1 125 2 125 3 125 3 125 4 125/250 5 400 6 600 Unit Height 12 12 12 18 24** 24 36 482 Unit Space Factor 1 1 1 1 1/2 2 2 3 4 Standard Maximum Control Control Transformer Transformer VA VA Relay 50 150 1* 50 150 1* 50 150 1* 150 250 1* 150 250 2 150 250 2 1503 1 503 150 250 2 Timer 1* 1* 1* 1* 1 1 1 Full Voltage Contactor with Fusible Switch (refer to Pg E4): Disconnect Ratings and Space Requirements Maximum Horsepower 200V 230V 460V 575V 6.92 8.0 15.9 19.9 10.4 11.9 23.9 29.8 24.2 27.8 55.7 69.6 31.1 35.8 71.6 89.5 43.3 50.0 99.4 124 67.5 77.6 155 194 121 139 278 348 162 210 415 515 * ** 1 2 3 Contactor Size 0 1 2 3 3 4 5 6 Maximum Fuse Switch Clip Unit Size Size Height 30 30 12 30 60 12 60 60 12 100 100 24 100 100 24 200 200 42 400 600 721 600 600 722 Unit Space Factor 1 1 1 2 2 3 5 6 Standard Control Transformer VA 50 50 50 50 150 150 503 150 Maximum Control Transformer VA Relay Timer 150 1* 1* 150 1* 1* 150 1* 1* 250 1* 1* 250 1* 1* 250 2 1 1503 2 2 250 1 1 Either/or but not both Oversized for additional equipment Fixed mounted unit Fixed mounted unit - Space behind not available Starter supplied with interposing relay(s) 200, 230V applications Siemens Energy & Automation, Inc. D9 SFIM-7002B-0608 Section D, June, 2008 Combination Starter Ratings and Dimensions FVR-Full Voltage Reversing Unit With Fusible Switch or Circuit Breaker Standard Features • Plug-in unit, Sizes 0 - 4 with HMCP, Sizes 0 - 3 with fusible switch. • Circuit Breakers Sizes 0 - 5. • Fusible switches, Sizes 0 - 4. Molded case switches Sizes 5 - 6. Fuse clips for Class R fuses. • Electrical starter seal-in contact for 3-wire control: Size 0 - 1, NO only. Size 2 - 4, SPST. Size 5 - 6, SPDT. NC reversing electrical interlock per contactor. • Mechanical interlock on contactors. • Bimetallic Ambient Compensated Overload • Starter: Innova/Plus, Sizes 0 - 1 with vertical mechanical interlock. Innova/Plus, Sizes 2 - 4 with horizontal mechanical interlock. Bimetallic OL • Control circuit terminals: Type A-Connect to component terminal. Type Bd, Bt, C-Unit stationary terminal blocks. • Load power terminals: Type A, Bd-Connect to starter terminals. Type Bt, C-Sizes 0 - 3, stationary blocks. Sizes 4 - 6, connect to starter terminals. Typical Schematic D10 Siemens Energy & Automation, Inc. SFIM-7002B-0608 Section D, June, 2008 Available Features-Standard Unit Size • Control power transformer with fused secondary and dual fused primary. • Solid state overload. • Pull-apart control terminals. • Pull-apart load terminals, Sizes 0 - 2. • Thermal magnetic circuit breakers. • 4-pilot devices mounted on unit device panel. • Control relay (2). • • • • Surge suppressors. ETM. Handle interlocks operate with handle. Extra starter auxiliary contacts in addition to NO maintaining seal-in contact and NC electrical interlock. • Class J fuse clips. • Refer to tables below for maximum size control power tranformer, relays, and timer additions. • Communicating devices (ASi, SIMOCODE-PRO) Auxiliary Contacts Starter Extra Contacts Size Per Starter 0-1 3 2-4 2 5-6 2 Type SPST NO or NC SPST NO or NC SPDT NO & NC FVR with MCP Type Breaker: Disconnect Ratings and Space Requirements MCP Starter Frame Unit Size Size Height 0 125 18 1 125 18 2 125 24 3 125 30 4 125/250 36 5 400 721 6 600 722 Maximum Horsepower 200V 230V 460-575V 3 3 5 7 1/2 7 1/2 10 10 15 25 25 30 50 40 50 100 75 100 200 150 200 400 Unit Space Factor 1 1/2 1 1/2 2 2 1/2 3 6 6 Standard Control Transformer VA 50 50 50 150 150 503 150 Maximum Control Transformer VA 150 150 250 250 250 2503 250 Relay 1* 1* 2 2 2 3 2 Timer 1* 1* 1 1 1 1 1 FVR with Fusible Switch (Refer to Pg E4): Disconnect Ratings and Space Requirements Maximum Horsepower 200V 230V 460-575V 3 3 5 7 1/2 7 1/2 10 10 15 25 25 30 50 40 50 100 75 100 200 Starter Size 0 1 2 3 4 5 Maximum Fuse Unit Switch Clip Unit Space Size Size Height Factor 30 30 18 1 1/2 30 60 18 1 1/2 60 60 24 2 100 100 36 3 4 1/2 200 200 541 400 600 30x721 6 Standard Control Transformer VA 50 50 50 150 150 503 Maximum Control Transformer VA 150 150 150 250 250 1503 Relay 2* 2* 2 2 2 2 Timer 1* 1* 1 1 1 2 * Either/or but not both a • Fixed mounted unit • Fixed mounted unit-space behind not available • Starter supplied with interposing relay(s) 200-230V applications Siemens Energy & Automation, Inc. D11 SFIM-7002B-0608 Section D, June, 2008 Combination Starter Ratings and Dimensions 2S1W - Two Speed - One Winding Reconnectable Consequent Pole Unit with Fusible Switch or Circuit Breaker Standard Features • Plug-in unit, Sizes 0 - 4 with MCP, Sizes 0 - 3 with fusible switch. • Circuit Breaker, Sizes 0 - 5. • Fusible switch Sizes 0 - 4. Molded case switch size 5. Fuse clips for Class R fuses. • Electrical starter interlocks-interlock supplied as required for selective control and to electrically interlock starters. seal-in contact. Size 0 - 1, NO only. Sizes 2 - 4, SPST. Size 5 SPDT. • Mechanically interlocked starters. Innova/Plus, Sizes 0 - 4. • Bimetallic Ambient Compensated Overload • 5-pole starter and 3-pole starter horizontally interlocked. Size 2 vertical reversing starter and separate starter. Size 3 - 4 horizontal reversing starter and separate starter. • Control circuit terminals: Type A-Connect to component terminal. Type Bd, Bt, C-Unit stationary terminal blocks. • Load power terminals: Type A, Bd-Connect to starter terminals. Type Bt, C-Sizes 0 - 3, stationary blocks. Size 4 and larger, connect to starter terminals. Typical Schematic D12 Siemens Energy & Automation, Inc. SFIM-7002B-0608 Section D, June, 2008 Available Features-Standard Unit Size • Solid state overload. • Control power transformer with fused secondary and dual fused primary. • Pull-apart control terminals. • Pull-apart load terminals Size 0 - 2. • Thermal magnetic circuit breakers. • 4-pilot devices mounted on unit device panel. • Handle interlock operates with handle. • Extra starter auxiliary contacts vary per size of starter. Relays will be supplied if number of available contacts is exceeded. • Compelling control starts on low speed only. Push “Stop” before transferring from higher to lower speed. • ETM. • Progressive control. Automatic starting on low speed and automatic transfer to fast; stops before transferring from fast to slow. • Automatic deceleration. • Class J fuse clips. • Refer to tables below for maximum size control power transformer, relays, and timer additions. • Control relay (1). • Surge suppressors. • Communicating devices (ASi, SIMOCODE-PRO) Auxiliary Contacts Extra Contact Starter Constant or Variable Torque Size High/Low 0-1 0/2 2-4 4/2 5 4/2 Extra Contact Constant Horsepower High/Low 2/0 2/4 2/4 Type SPSTNO orNC SPSTNO orNC SPDT NO & NC 2S1W with MCP Type Breaker: Disconnect Ratings and Space Requirements Standard Maximum Constant or Variable Constant MCP Unit Control Control Torque Horsepower Starter Frame Unit Space Transformer Transformer 200V 230V 460-575V 200V 230V 460-575V Size Size Height Factor VA VA Relay Timer 3 3 5 2 2 3 0 125 24 2 50 250 2 1 7 1/2 7 1/2 10 5 5 7 1/2 1 125 24 2 50 250 2 1 10 15 25 7 1/2 10 20 2 125 24 2 150 250 1 1 25 30 50 20 25 40 3 125 36 3 150 250 2 2503 2 1 40 50 100 30 40 75 4 125/250 48 4 503 75 100 200 60 75 150 5 400 30x721 6 503 2503 2 2 2S1W with Standard Fusible Switch (Refer to Pg E4): Disconnect Ratings and Space Requirements Maximum Standard Maximum Constant orVariable Constant Fuse Unit Control Control Torque Horsepower Starter Switch Clip Unit Space Transformer Transformer 200V 230V 460-575V 200V 230V 460-575V Size Size Size Height Factor VA VA Relay Timer 3 3 5 2 2 3 0 30 30 24 2 50 150 2 1 7 1/2 7 1/2 10 5 5 7 1/2 1 30 60 24 2 50 150 2 1 10 15 25 7 1/2 10 20 2 60 60 24 2 150 250 1 1 25 30 50 20 25 40 3 100 100 48 4 150 250 2 1 6 503 2503 4 1 40 50 100 30 40 75 4 200 200 721 75 100 200 60 75 150 5 400 600 30x721 5 503 2503 2 1 1 Fixed mounted unit 3 Starter supplied with interposing relay(s) 200 & 230V applications Siemens Energy & Automation, Inc. D13 SFIM-7002B-0608 Section D, June, 2008 Combination Starter Ratings and Dimensions 2S2W - Two Speed - Two Winding Unit With Fusible Switch or Circuit Breaker Standard Features • Plug-in unit, Sizes 0 - 4 with circuit breakers, Sizes 0 - 3 with fusible switch. • Circuit Breaker, Sizes 0 - 5. • Fusible switch Sizes 0 - 4. Molded case switches, Sizes 5. Fuse clips for Class R fuses. • Electrical starter interlocks - supplied as required for selective control and to electrically interlock starters. Seal-in contact: Sizes 0 - 1, NO only. Sizes 2 - 4, SPST. Size 5, SPDT. • Bimetallic Ambient Compensated Overload • Mechanical interlock on starters. Starters: Innova/Plus, Sizes 0 - 4. Sizes 0 - 4: Innova/Plus consisting of 2 starters horizontally interlocked. Sizes 5: 2 starters with vertical mechanical interlock. • Control circuit terminals: Type A - Connect to component terminal. Type Bd, Bt, C - Unit stationary - terminal blocks. • Load power terminals: Type A, Bd - Connect to starter terminals. Type Bt, C - Sizes 0 - 3, stationary blocks. Size 4 and larger, connect to starter terminals. Typical Schematic D14 Siemens Energy & Automation, Inc. SFIM-7002B-0608 Section D, June, 2008 Available Features - Standard Unit Size • Solid state overload. • Control power transformer with fused secondary, and dual fused primary. • Pull-apart control terminals. • Pull-apart load terminals. Sizes 0 - 2. • Thermal magnetic circuit breakers. • 4 pilot devices mounted on unit device panel. • Handle interlock operates with handle. • Extra starter auxiliary contacts vary per size of starter. Relays will be supplied if number of available auxiliary contacts are exceeded. • Compelling control starts on low speed only. Push “Stop” before transferring from high to low speed. • Progressive control. Automatic starting on low speed and automatic transfer to fast. Stops before transferring from fast to slow. • Automatic deceleration. • Class J fuse clips. • Refer to tables below for maximum size control power transformer, relays, and timer additions. • Control relay (1). • Surge suppressors. • ETM. • Communicating devices (ASi, SIMOCODE-PRO) Auxiliary Contacts Starter Extra Contacts Size Hi/Low 0-1 3/3 2-4 2/2 5 2/2 Type SPST NO or NC SPST NO or NC SPDT NO & NC 2S2W with MCP Type Breaker: Disconnect Ratings and Space Requirements Constant or Variable Torque 200V 230V 460-575V 3 3 5 7 1/2 7 1/2 10 10 15 25 25 30 50 40 50 100 75 100 200 Constant Horsepower 200V 230V 460-575V 2 2 3 5 5 7 1/2 7 1/2 10 20 20 25 40 30 40 75 60 75 150 Standard Maximum MCP Unit Control Control Starter Frame Unit Space Transformer Transformer Size Size Height Factor VA VA Relay Timer 0 125 24 2 50 250 2 1 1 125 24 2 50 250 2 1 2 125 24 2 50 250 2 1 3 125 30 2 1/2 150 250 2 1 2503 2 1 4 125/250 36 3 503 5 400 30x721 6 503 2503 2 1 2S2W with Standard Fusible Switch (Refer to Pg E4): Disconnect Ratings and Space Requirements Maximum Constant or Variable Fuse Torque Constant Horsepower Starter Switch Clip Unit 200V 230V 460-575V 200V 230V 460-575V Size Size Size Height 3 3 5 2 2 3 0 30 30 24 7 1/2 7 1/2 10 5 5 7 1/2 1 30 60 24 10 15 25 7 1/2 10 20 2 60 60 24 25 30 50 20 25 40 3 100 100 36 40 50 100 30 40 75 4 200 200 541 75 100 200 60 75 150 5 400 600 30x721 Unit Space Factor 2 2 2 3 4 1/2 6 Standard Maximum Control Control Transf. Transf. VA VA Relay 50 150 2 50 150 2 50 150 2 150 250 2 503 2503 1 503 2503 2 55BA 1 1 1 1 1 2 1 Fixed mounted unit 3 Starter supplied with interposing relay(s) 200 & 230V applications Siemens Energy & Automation, Inc. D15 SFIM-7002B-0608 Section D, June, 2008 Combination Starter Ratings And Dimensions PW - Full Voltage Part Winding Unit with Fusible Switch or Circuit Breaker Standard Features • Plug-in units. • Sizes 0 - 4, circuit breaker. Sizes 0 - 4, fusible switch. • Thermal magnetic breaker, Sizes 0 - 5. • Fusible switches. Sizes 0 - 3. Molded case switches, Sizes 4 5.Molded case switch, Size 4, on 230V.Fuse clips for Class R fuses. • Starters: Innova/Plus: 0 - 4. • Bimetallic Ambient Compensated Overload • Electrical starter interlocks-NO interlock supplied on 1M for 3 wire control. Sizes 1, NO only. Sizes 2 - 4, SPST. Sizes 5, SPDT. • Control circuit terminals: Type A - Connect to component terminal. Type Bd, Bt, C - Unit stationary terminal blocks. • Load power terminals: Type A, Bd - Connect to starter terminals. Type Bt, C - Sizes 0 - 3, stationary blocks. Sizes 4 - 5 connect to starter. Typical Schematic D16 Siemens Energy & Automation, Inc. SFIM-7002B-0608 Section D, June, 2008 Available Features-Standard Unit Size • Control power transformer-Fused secondary and dual fused primary. • Pull-apart control terminals. • Solid state overload. • Pull-apart load terminals, Sizes 0 - 2. • 4 pilot devices mounted on unit device panel. • Handle interlock operates with handle. • Control relay. • Surge suppressors. • Extra starter auxiliary contacts in addition to NO seal-in contact. • Class J fuse clips. • Refer to tables below for maximum size control power transformer, relays, and timer additions. • Communicating devices (ASi, SIMOCODE-PRO) Auxiliary Contacts Starter Extra Contacts Size Per Starter 0-1 3 2-4 2 5 3 Type SPST NO or NC SPST NO or NC SPST NO or NC PW with Circuit Breaker: Disconnect Ratings and Space Requirements Maximum Horsepower 200V 230V 460-575V 10 10 15 20 25 40 40 50 75 40 50 75 75 75 150 150 150 350 Starter Size 1 2 3 3 4 5 Circuit Breaker Frame Size 125 125 125 250 400 600 Unit Height 24 24 30 36 36 721 Unit Space Factor 2 2 2 1/2 3 3 6 Standard Control Transformer VA 150 150 150 150 503 503 Maximum Control Transformer VA 250 250 250 250 1503 2503 Relay 2 2 2 2 2 2 Timer 55BA 1 1 1 1 1 1 PW with Standard Fusible Switch (Refer to Pg E4): Disconnect Ratings and Space Requirements Maximum Horsepower 200V 230V 460-575V 10 10 15 20 25 40 40 50 75 75 75 150 150 150 350 Starter Size 1 2 3 4 5 Maximum Fuse Switch Clip Unit Size Size Height 60 60 24 100 100 30 200 200 48 400 400 721 600 600 30x721 Unit Space Factor 2 2 1/2 4 6 6 Standard Control Transformer VA 150 150 150 503 503 Maximum Control Transformer VA Relay 250 2 250 2 250 2 2503 1 2503 2 Timer 55BA 1 1 1 1 2 1 Fixed mounted unit 3 Starter supplied with interposing relay(s) 200 & 230V applications Siemens Energy & Automation, Inc. D17 SFIM-7002B-0608 Section D, June, 2008 Combination Starter Ratings and Dimensions RVAT - Reduced Voltage Auto-Transformer Unit with Fusible Switch or Circuit Breaker Standard Features • Fixed mounted units, Sizes 2 - 6. • Fusible switch Sizes 0 - 4. • Molded case switches, Sizes 5 - 6. Fuse clips sized for time delay fuses. Class R. • Starter: Innova/Plus, Sizes 2 - 4. Starter (R) and contactor (1S) with mechanical interlock. 3 pole contactor (2S). • Bimetallic Ambient Compensated Overloads. • Auto Transformer NEMA medium duty 3 coil: 50%, 65%, 80% taps. Class F insulation (minimum). Mounted across bottom of structure. • Electrical starter interlocks-NO on (2S); (R) for 3 wire control. Sizes 2 - 4, SPST. Sizes 5 - 6, SPDT. • Control circuit terminals: Type A - Connect to component terminal. Type Bd, Bt, C - Unit stationary terminal blocks. • Load power terminals. Type A, Bd - connect to starter terminals. Type Bt, C - Sizes 0 - 3, stationary blocks. Sizes 4 - 6, connect to starter terminals. Typical Schematic D18 Siemens Energy & Automation, Inc. SFIM-7002B-0608 Section D, June, 2008 Available Features-Standard Unit Size • Control power transformer-fused secondary and dual fused primary. • Pull-apart control terminal. • Pull-apart load terminals, Sizes 0 - 2. • Solid state overload. • Thermal-magnetic circuit breakers. • • • • Extra starter auxiliary contacts, 2S or R (relay used). Surge suppressors. Class J fuse clips. Refer to tables below for maximum size control power transformer, relays, and timer additions. • Communicating devices (ASi, SIMOCODE-PRO) RVAT with MCP Type Breaker: Disconnect Ratings and Space Requirements Maximum Horsepower Starter 200V 230V 460-575V Size 10 15 25 2 25 30 50 3 40 50 100 4 75 100 200 5 150 200 400 6 400 6 MCP Frame Size 125 125 125/250 400 600 800 Unit Height 421 421 481 30X722 30X722 30X722 Unit Space Factor 3 1/2 3 1/2 4 6 6 6 Standard Control Transformer VA 150 150 503 503 503 503 Maximum Control Transformer VA 250 250 2503 2503 2503 2503 Relay 2 1 2 1 2 2 Timer 1 1 1 2 2 RVAT with Standard Fusible Switch (Refer to Pg E4): Disconnect Ratings and Space Requirements Maximum Horsepower 200V 230V 460-575V 10 15 25 25 30 50 40 50 100 75 100 200 150 200 350 400 1 2 3 4 Starter Size 2 3 4 5 6 6 Maximum Fuse Switch Clip Unit Size Size Height 60 60 421 100 100 481 200 200 601 400 600 30x722 600 600 30x722 800 800 50x7224 Unit Space Factor 3 1/2 4 6 6 6 6 Standard Control Transformer VA 150 150 503 503 503 503 Maximum Control Transformer VA Relay 250 2 250 2 2503 2503 1 2503 2 2503 - Timer 1 1 1 - Fixed mounted unit Fixed mounted unit - space behind not available Starter supplied with interposing relay(s) Requires 20” deep structure 200 & 230V applications Siemens Energy & Automation, Inc. D19 SFIM-7002B-0608 Section D, June, 2008 Combination Starter Ratings And Dimensions YDC - Reduced Voltage Wye Delta Closed Transition Standard Features • Plug-in units. • Sizes 0 - 6, circuit breaker. Sizes 0 - 5, fusible switch. • Fusible switches. Sizes 0 - 3. Molded case switches, Sizes 4 - 5. • Starters: Innova/Plus: 0 - 4. • Bimetallic Ambient Compensated Overloads • Control circuit terminals: Type A-Connect to component terminal. Type Bd, Bt, C-Unit stationary terminal blocks. • Electrical starter interlocks-NO interlock For 3 wire control. Sizes 2 - 4, SPST. Sizes 5 - 6, SPDT. • Load power terminals: Type A, Bd - Connect to starter terminals. Type Bt, C - Sizes 0 - 3, stationary blocks. Sizes 4 - 6 connect to starter. TYPICAL SCHEMATIC D20 Siemens Energy & Automation, Inc. SFIM-7002B-0608 Section D, June, 2008 Available Features-Standard Unit Size • Control power transformer-Fused secondary and dual fused primary. • Pull-apart control terminals. • Solid state overload. • Phase Failure Relay • Pull-apart load terminals, SIzes 0 - 2. • 4 pilot devices mounted on unit device panel. • • • • Handle interlock operates with handle. Control relay. Surge suppressors. Extra starter auxiliary contacts in addition to NO seal-in contact. • Class J fuse clips. • Refer to tables below for maximum size control power transformer, relays, and timer additions. Auxiliary Contacts Starter Extra Contacts Size Per Starter 2-4 3 5-6 3 Type SPST NO or NC SPST NO or NC YDC with Circuit Breaker: Disconnect Ratings and Space Requirements Maximum Horsepower 200V 230V 460-575V 20 25 40 40 50 75 40 50 75 60 75 150 150 150 300 300 350 700 300 350 700 Starter Size 2 3 3 4 5 6 6 Circuit Breaker Frame Size 125 125 125 250 600 600 800 Unit Height 42 42 48 48 30x721 40x721 40x721 Unit Space Factor 3 1/2 3 1/2 4 4 6 6 6 Standard Control Transformer VA 150 150 150 503 503 503 503 Maximum Control Transformer VA 250 250 250 1503 2503 2503 2503 Relay 2 2 2 2 4 2 2 Timer 2 2 1 1 2 1 1 YDC with Standard Fusible Switch (Refer to Pg E4): Disconnect Ratings and Space Requirements Maximum Horsepower 200V 230V 460-575V 20 25 40 40 50 75 60 75 150 150 150 300 Starter Size 2 3 4 5 Maximum Fuse Switch Clip Unit Size Size Height 100 100 48 200 200 60 400 400 721 600 600 30x721 Unit Space Factor 4 5 6 6 Standard Maximum Control Control Transformer Transformer VA VA Relay 150 250 2 150 250 2 503 2503 2 503 2503 4 Timer 2 1 1 2 1 Fixed mounted unit 2 Starter supplied with interposing relay(s) Siemens Energy & Automation, Inc. D21 SFIM-7002B-0608 Section D, June, 2008 Combination Starter Ratings And Dimensions YDO - Reduced Voltage Wye Delta Open Transition Standard Features • Sizes 0 - 6, circuit breaker. Sizes 0 - 5, fusible switch. • Fusible switches. Sizes 0 - 3. Molded case switches, Sizes 4 - 5. • Starters: Innova/Plus: 0 - 4. • Bimetal Ambient Compensated Overloads • Control circuit terminals: Type A-Connect to component terminal. Type Bd, Bt, C-Unit stationary terminal blocks. • Electrical starter interlocks-NO interlock For 3 wire control. Sizes 2 - 4, SPST. Sizes 5 - 6, SPDT. • Load power terminals: Type A, Bd - Connect to starter terminals. Type Bt, C - Sizes 0 - 3, stationary blocks. Sizes 4 - 6 connect to starter. TYPICAL SCHEMATIC D22 Siemens Energy & Automation, Inc. SFIM-7002B-0608 Section D, June, 2008 Available Features-Standard Unit Size • Control power transformer-fused secondary and dual fused primary. • Pull-apart control terminals. • Solid state overload. • Phase Failure Relay • Pull-apart load terminals, SIzes 0 - 2. • 4 pilot devices mounted on unit device panel. • Handle interlock operates with handle. • Control relay • Surge suppressors. • Extra starter auxiliary contacts in addition to NO seal-in contact. • Class J fuse clips. • Refer to tables below for maximum size control power transformer, relays, and timer additions. Auxiliary Contacts Starter Extra Contacts Size Per Starter Type 2-4 3 SPSTNO orNC 5-6 3 SPSTNO orNC YDO with Circuit Breaker: Disconnect Ratings and Space Requirements Maximum Horsepower 200V 230V 460-575V 20 25 40 40 50 75 60 75 150 150 150 300 300 350 700 300 350 700 Starter Size 2 3 4 5 6 6 Circuit Breaker Frame Size 125 125 250 600 600 800 Unit Height 30 30 36 30x721 40x721 40x721 Unit Space Factor 2 1/2 2 1/2 3 6 6 6 Standard Control Transformer VA 150 150 503 503 503 503 Maximum Control Transformer VA 250 250 1503 2503 2503 2503 Relay 3 3 2 4 2 2 Timer 1 1 1 2 1 1 YDO with Standard Fusible Switch (Refer to Pg E4): Disconnect Ratings and Space Requirements Maximum Horsepower 200V 230V 460-575V 20 25 40 40 50 75 Starter Size 2 3 Maximum Fuse Switch Clip Unit Size Size Height 100 100 36 200 200 48 Unit Space Factor 3 4 Standard Maximum Control Control Transformer Transformer VA VA Relay 150 250 2 150 250 2 Timer 1 1 60 75 150 4 400 400 721 6 503 2503 2 1 150 150 300 5 600 600 30x721 6 503 2503 4 2 1 Fixed mounted unit 3 Starter supplied with interposing relay(s) Siemens Energy & Automation, Inc. D23 SFIM-7002B-0608 Section D, June, 2008 FeederTap Fusible Switches Fusible feeder switches, 30A through 200A, are mounted in plug-in units. Switches above 200A are fixed mounted and consist of molded-case switches and separate fuse blocks. Dual-mounted fusible switches are available, 30A and 60A, with clips of same rating. Fuse clips are Class RK dimensions for 30-600A. FeederTap Circuit Breakers These breakers are thermal magnetic type and feed lighting or power circuits. 125A and 250A frame breakers are mounted in plug-in units. Higher rated breakers are fixed mounted. (See chart on page G6 for short circuit ratings and type of circuit breakers available.) Dual mounted 125A frame breakers may be mounted in a 12” plug-in unit with a common door. Circuit breakers Fusible disconnect switch FeederTap Circuit Breakers and Fusible Switches: Disconnect Ratings and Space Requirements Unit Height - Switch Rating (A.) 30 60 100 200 Fuse Clip Size Amps 30 60 100 200 1 Sw. 122 122 18 30 2 SW. 122 122 - - 400 400 4213 - - 600 600 4213 - Frame Size 125 Max. Trip Amps 125 1CB 12 2CB 12 250 250 18 400 400 2413 600 600 2413 Unit Height 1 Fixed mounted unit. 2 Requires load terminal blocks. 3 Stab opening at top of unit not available in rear. D24 Siemens Energy & Automation, Inc. SFIM-7002B-0608 Section D, June, 2008 Distribution Units A Motor Control Center is principally intended to house multiple combination starters for the control of electrical motors. It is often convenient to include a limited number of power distribution units. Transformer Protection - Lighting and Master Control Primary protection is required, per NEC sizes as follows: (lp = transformer primary currents.) 125% lp for lp greater than 9A. 167% lp for lp less than 9A. 300% lp for lp less than 2A. In addition to primary protection, secondary protection must be supplied if the transformer secondary is 3 or 4 wire (dual voltage). Secondary protection is not required if the transformer is 2 wire (single voltage secondary). Description of Standard Transformers Single Phase Transformers 1KVA thru 2KVA 240/480V Primary 120V Secondary 50/60 Hz 3KVA and larger sizes are mounted in bottom of section. 20KVA or larger sizes require 20” deep sections. Single Phase Transformer 480/240V - 120/240V Secondary 60 Hz Transformer Unit Height * 12 12 18 18 18 24 Primary Size Trip 240V 20 30 40 50 70 125 Note: No vertical bus behind or below. 5.0KVA and larger. 20KVA or larger requires 20” deep structures. * Does not include 6” bottom wireway space. Siemens Energy & Automation, Inc. 3KVA thru 5KVA 240/480V Primary 240/120V Secondary 50/60 Hz 7 1/2, 10, 15, 25, 30KVA 240/480V Primary with (2) 2 1/2% FCAN and (4) 2 1/2% FCBM Taps 240/120V Secondary, 60 Hz 220C insulation, 150C rise Three Phase Transformer 6 to 15 KVA 480V Primary with (2) 5% FCBN taps 208/120V “Y” - connected Secondary 25-45 KVA 480V Primary with (2) 2 1/2% FCAN and (40) 2 1/2% FCBN taps 208/120V “Y” - connected Secondary 220C insulation, 150C rise Transformer Ratings and Space Requirements Single Phase Transformers: 1KVA and 2KVA sizes with 120V secondary can be mountedin a single 12” plug-in unit with a primary circuit breaker or fusible disconnect. KVA Rating 3.0 5.0 7.5 10 15 25 These units consist of the following: • Transformers • Feeder tap circuit breakers • Feeder tap fusible disconnects • Lighting panels 3 Phase Transformers: All three phase transformers require 20” deep sections, must be mounted in the bottom, and will not have vertical bus in that compartment. Refer to page B22 for conduit entry. All 3KVA and larger single phase and all three phase transformers are mounted approximately 5 inches above the structure base channel sills. Three Phase Transformer 480V Primary - 208/120V Secondary 60 Hz Breaker Amps 480V 15 15 20 30 40 60 KVA Rating 9 15 25 30 45 Unit Height * 12 18 18 18 24 Primary Breaker Size Trip Amps 480V 15 25 30 45 70 Note: All three phase transformers require 20” deep structures and 20” wide doors. D25 SFIM-7002B-0608 Section D, June, 2008 Panel Board Panel Boards Full size bolt-on breakers - 1, 2, and 3 pole - 15 to 100A. 1 phase 3 wire - 120/240 volt or 3 phase 4 wire - 120/208 volt 3 phase 4 wire - 380/220 volt 3 phase 4 wire - 480/277 volt Aluminum bus - 100 and 225A depending on number of circuits. Main lug only - 100 and 225A Main circuit breaker - 100 and 225A - 12 to 42 circuits. Disconnect Ratings and Space Requirements: Circuit Breaker Panel Boards Main Bus Number Breaker Rating Circuits Type (Amps) (Amps) 18 1Ø-3W 100 30 1Ø-3W 225 42 1Ø-3W 225 18 3Ø-4W 100 30 3Ø-4W 225 42 3Ø-4W 225 18 1Ø-3W 100 100 30 1Ø-3W 225 225 42 1Ø-3W 225 225 18 3Ø-4W 100 100 30 3Ø-4W 225 225 42 3Ø-4W 225 225 Unit Height (Inches) 30 36 42 30 36 42 30 36 36 30 36 42 10,000A 240V short circuit rating. UL listed. D26 Siemens Energy & Automation, Inc.