Dimensional Details

advertisement
Dimensional Details
Fleet Wall Hung Boilers
Boiler General Dimensions and Clearance
150
540
540
150
Gland holes
21mm dia. x 2
Electric - 490
D
45
B
35
20
900 min.
clearance
C (Flue dia.)
560 crs
134
Return - 120
Safety valve - 195
Plan View
Flow - 270
Condense - 345
Gas - 470
View on Underside
134
Note… Terminals can be
cut to length (from elbow
connection end) to suit the
application.
300 min.
15
50
40
540
440
410
50
B
When shortening terminals
or terminal extensions, the
outer section only should be
cut first. This will allow access
to the inner section, which,
for a correct fit into the next
concentric pipe fitting, must
be cut so that it is 10 cm
longer than the outer section.
8 holes 12 dia.
930
Wall mounting
plate
Plate centreline
notched
Boiler outline
shown hatched
Wall Mounting
Arrangment
540
A
Front View
Side Flue Exit
Side View
Rear Flue Exit
All dimensions in mm
Dimensions (mm)
Reference
Model
F40W
F50W
F60W
F70W
F85W
F100W
F125W
F150W
Casing depth
A
470
570
Flue depth
B
380
480
Flue diameter
C
80/125
100/150
Electrical connections
D
350
450
9
Dimensional Details
Fleet Wall Hung Boiler Pipe Kits & Flue Headers
Low Loss Headers
Single Boiler Arrangement
A.A.V.
180
Nom.
Secondary
return
190
Nom.
380 Nom.
Primary
flow
Primary
return
560 Nom
Secondary
flow
665 Nom.
30
540
300 Min
147
150
760 Nom.
165 O/D
Pocket for temperature
sensors x 2
507
A.A.V.
Internal transfer pipe
1500 Nom.
1405 Nom.
560 Nom.
370 Nom.
180
Nom.
380 Nom.
190
Nom.
560
Secondary
returns
Primary
flow
Primary
return
950 Nom. .
Pocket for temperature
sensors x 2
Rp ½” Socket
(flow & return)
1330 Nom.
Secondary
flows
1140 Nom.
1740 Min
165 O/D
507
All dimensions in mm
All dimensions in mm
Two Boiler Arrangement
E
85
419
560 crs
H
550 max
600 Min
1530
300
F
G (Nominal)
Horizontal plane
Header axis
1830 Nom.
1740 Nom.
1740
.
.
Header at 3° fall to
horizontal.
(29 mm drop between
adjacent boiler terminal
connections).
Flow
Rp ½” Socket
(flow & return)
1120
128
225
190 Nom.
22mm SRV relief pipe
(option)
380 Nom.
Condense
Return
(option)
524 Nom.
Gas
All dimensions in mm
10
Dimensional Details
Fleet Wall Hung Boiler Pipe Kits & Flue Headers
Pipe Kit and Low Loss
Header Connection Sizes
Three Boiler Arrangement
DN65 – PN16
Return
2090
DN65 – PN16
Gas
Condense
85
R2"
Horizontal plane
40 mm
Header axis
Dimensions (mm)
560 crs
F
G
H
F40W to
F100W
470
233
368
150
F125W to
F150W
570
304
319
200
.
E
Sensor
Spool
Kit
550 max
29
G (nominal)
Header at 3° fall to
horizontal.
(29 mm drop between
adjacent boiler terminal
connections).
Boiler Flue Dimensions
Models
H
419
300
1740 Nom.
Flow
600 Min.
All Models
Sensor Pocket ½" BSP
Rp ½” Socket
(flow & return)
DN65
1680
120
All dimensions in mm
2650
300
300
85
Horizontal plane
419
29
560 crs
H
550 max
600 Min.
Four Boiler Arrangement
G (nominal)
Header axis
Header at 3° fall to
horizontal.
(29 mm drop between
adjacent boiler terminal
connections).
1740
.
B23 open flue header vertical
terminal with air inlet filter
and 90° ellbow.
Note...On two, three and four boiler
arrangements, standard length vertical
terminals are supplied for each boiler.
These must be cut to length to maintain
the recommended 3° fall in the
main horizontal header, falling away
from the main flue riser.
The first terminal (for the boiler nearest
to the main flue riser) does not need
to be cut, but each terminal thereafter
should be cut 29mm shorter than the
previous terminal to achieve the
recommended 3° fall.
Rp ½” Socket
(flow & return)
2240
All dimensions in mm
11