Piscataway, NJ – EWR1

advertisement
Piscataway, NJ Data Center/EWR1
Tier III+ Data Centers / Carrier Neutral / SSAE16 Certified
Innovate. Create. Accelerate.
Email:sales@netdc.com
Toll Free: 1.888.931.3444
International:
1.310.426.6700
LO C ATION :
Piscataway, NJ Data Center
EWR1 - 101 Possumtown Road
AB O UT US :
Net Data Centers provides mission critical cloud
and internet services from enterprise-grade, world
class data centers. Our continuous investment in
next-generation security, advanced power and cooling
technologies, cloud and network offerings provide
comprehensive solutions to meet your technology
requirements with complete confidence.
Leading social networks, enterprises, finance, content
companies, and communications service providers rely
on Net Data Centers for uninterruptable operations and
support of core, mission critical business processes
and applications.
DATA CENTER SP ECI FIC ATION S :
Building Area: 360,000 square feet
Security: Staffed 24/7; keycard access and dual authentication with biometric readers; ballistic glass enclosed
security check-in, front window areas and loading dock;
security fence surrounds entire land area/building with
guard house; CCTV 24/7 camera surveillance of interior
and exterior of the facility
Flooring: Raised floor area is 176,200 square feet; 42”
under raised floor plenums; raised floor to ceiling height
is 15-22 feet
HVAC: 16 centrifugal chillers with 1,080 ton capacity
each; two 500,000 gallon above ground chilled water
storage tanks, N+2 redundancy
Fire Suppression: Conventional smoke detector and laser
based incipient smoke detection systems and double
interlocked pre-action sprinkler system
ON - N ET BAN DWI DTH FI BER P ROVI DERS :
AboveNet
AT&T
Cablevision
Cogent
Cross River Fiber
Fibertech
Intellifiber
Level 3
Lightower
Lightpath
NetDC
OCG
Sidera
Spread Networks
Sunesys
Universal eBusiness
Verizon Business
Verizon Telecom
Power: 36.4 MW of critical power; 32 Rotary
power systems with 1,300 kW of critical output each
(N+2 redundancy); 32 diesel-powered emergency
generators with 2,250 kW capacity (N+2 redundancy);
dual input 300 kVA PDU - 600 volt primary
Loading Dock: Four (4) secured loading bays
Carrier Neutral: Yes. Cross-connect to the building
meet-me-room to diverse carriers on premise.
Local Access to Internet Exchanges in NY/NJ Metro.
Standards & Controls: Tier IV, LEED building standard.
SAS 70 Type II Certified
POWER
Up to 22kW
per Cabinet
P ER FOR MANCE
100%
Availability
VALUE
Affordable
Solution