Most Widely Accepted and Trusted 0 ICC‐ES Legacy Report ER‐2541 Y C T A R G O E P L E R ICC‐ES | (800) 423‐6587 | (562) 699‐0543 | www.icc‐es.org 000 Reissued 03/2016 This report is subject to renewal 03/2017. DIVISION: 09—FINISHES SECTION: 09260—GYPSUM BOARD ASSEMBLIES REPORT HOLDER: GEORGIA‐PACIFIC GYPSUM SHAFTWALL SYSTEMS GEORGIA‐PACIFIC GYPSUM LLC 2861 MILLER ROAD DECATUR, GEORGIA 30035 EVALUATION SUBJECT: 620 SERIES SHAFTWALL SYSTEMS Look for the trusted marks of Conformity! “2014 Recipient of Prestigious Western States Seismic Policy Council (WSSPC) Award in Excellence” ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed as an endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as to any finding or other matter in this report, or as to any product covered by the report. Copyright © 2016 ICC Evaluation Service, LLC. All rights reserved. A Subsidiary of ICC-ES Legacy Report ER-2541 Reissued March 2016 Y C T A R G O E P L E R www.icc-es.org | (800) 423-6587 | (562) 699-0543 A Subsidiary of the International Code Council ® Legacy report on the 1994 Uniform Building Code™ and the 1994 ICBO Uniform Mechanical Code™ DIVISION: 09—FINISHES Section: 09260—Gypsum Board Assemblies studs are then fitted over the long edges of the panel. This sequence is continuous with additional panels and studs installed similarly. GEORGIA-PACIFIC GYPSUM SHAFTWALL SYSTEMS 2.2 620 Two-hour Shaftwall: GEORGIA-PACIFIC GYPSUM LLC 2861 MILLER ROAD DECATUR, GEORGIA 30035 The basic construction is as described above under Section 2.1 and Figure 1. A base layer of 1/2-inch ® ToughRock Fireguard C gypsum wallboard is installed with vertical joints over studs and attached to minimum No. 25 gage studs with 1-inch No. 6 Type S screws spaced 24 inches on center. The face layer of the wallboard is installed with all joints offset 24 inches from the base layer and attached with 15/8-inch No. 6 Type S screws spaced 8 inches on center. Both layers are installed horizontally. As an alternative, one layer of the two wallboard layers may be installed vertically. Type S-12 screws are used to attach gypsum wallboard to No. 20 gage steel framing. Joints on the face layer are taped and covered with joint compound. Screwheads are also covered with joint compound. 1.0 SUBJECT 620 Series Shaftwall Systems. 2.0 DESCRIPTION 2.1 General: The 620 Series Shaftwall Systems consist of 1-inch ToughRock® Fireguard (Type X) Shaftliner supported by 1 2 /2-, 4- or 6-inch “C-T” galvanized steel studs complying with ASTM A 653 Grade 33, 0.022 inch (No. 25 gage) or 0.035 inch (No. 20 gage) in thickness. Studs are faced on one or both sides with single or multiple layers of 1/2-inch ® Fireguard C or 5/8-inch ToughRock® ToughRock Fireguard (Type X) gypsum wallboard to form a nonbearing partition. The 1/2-inch and 5/8-inch wallboards comply with ASTM C 36. The basic construction is entirely built from one side starting with a J-runner channel attached to ceiling and floor with approved fasteners spaced at 24 inches on center, maximum. The J-runner is galvanized steel with 21/4-inch and 1-inch legs and depth the same as the stud depth. See Figure 6. The metal thickness of the J-runner is the same as the C-T stud unless noted in tables. Minimum 0.035 (No. 20 gage) J-runner track is required for 10 and 15 psf loads. Minimum 21/2-inch-deep 0.022-inch metal thickness (No. 25 gage) galvanized steel or 0.036-inch metal thickness (No. 20 gage) galvanized steel C-T studs are spaced a maximum of 24 inches on center. See Figure 7. Mechanical fastening of the studs to the runner is not required. ToughRock® Fireguard (Type X) Shaftliner panels 1-inch-thick by 24-inches-wide, by length 1 inch shorter than ceiling height are inserted in the J-runners on the shaft side of the wall. Each panel is fastened to the Jrunner with three 15/8-inch Type S screws. First and last panels are fastened to the long leg of vertical J-runner with 15/8-inch screws spaced a maximum of 24 inches on center. Horizontal manufactured cut joints in the panel need not be back blocked, but should be staggered minimum 24 inches between adjoining panels. The C-T 2.3 620 Two-hour Shaftwall (Air Shaft): Where the 620 Shaftwall is used as a medium pressure duct system in accordance with Section 601.1 of the 1994 ICBO Uniform Mechanical Code, the construction is identical with Section 2.1 and 2.2 above, except studs are a minimum No. 20 gage. The joints and all perimeter connections are additionally caulked with a nonhardening caulking compound, and the face layer of 1/2-inch ® TouchRock Fireguard C gypsum wallboard prime coated with an oil or emulsion paint or primer. The air shafts are recognized for a maximum vacuum of 4 inches of water and a maximum pressure of 2 inches of water. Refer to Table 3 for allowable heights. Inside and outside corners are constructed as shown in Figure 2. 2.4 621 Two-hour Shaftwall (Stairwells): The basic construction is as described under Section 2.1 and Figure 3. A face layer of 1/2-inch TouchRock® Fireguard C gypsum board is applied to each side of minimum No. 25 gage studs and fastened with 1-inch No. 6 Type S screws and spaced 8 inches on center. Gypsum wallboard is installed horizontally. As an alternative, gypsum wallboard on one face may be installed vertically. Type S-12 screws attach the gypsum wallboard to No. 20 gage steel framing. Joints are staggered 24 inches on opposite sides of the wall and are taped and covered with two coats of joint compound. Screwheads are also covered with joint compound. ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed as an endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICC Evaluation Service, Inc., express or implied, as to any finding or other matter in this report, or as to any product covered by the report. Copyright © 2016 ICC Evaluation Service, LLC. All rights reserved. Page 1 of 5 ER-2541 | Most Widely Accepted and Trusted Page 2 of 5 2.5 622 One-hour Shaftwall: Basic construction is as described under Section 2.1 and Figure 4. A face layer of 5/8-inch TouchRock® Fireguard (Type X) gypsum wallboard is applied vertically to the room side of inches on center in the field of the board. Type S-12 screws are used to attach gypsum board to No. 20 gage steel framing. The joints are taped and covered with two coats of joint compound along with all screwheads. As an alternate finishing procedure to the 620 and 621 shaftwalls, veneer plaster baseboard of the same type and thickness of core may be substituted for the outer layer of gypsum wallboard. The veneer base is to receive a 1 minimum of /16-inch veneer plaster. Where veneer plaster finish is used, allowable height criteria shall be for brittle finish requirements with minimum deflection of height divided by 240. Y C T A R G O E P L E R 2.6 One- or Two-hour Corridor Ceiling and Stair Soffits: The following systems provide fire-resistive protection for the underside of stairs and at corridor ceilings in accordance with Section 1005.7 of the Uniform Building Code: The basic construction is similar to that described in Section 2.1. J-runners are attached to all intersecting vertical and horizontal framing members outlining the opening. Fasteners are spaced a maximum of 24 inches on center and require a working load of 200 pounds in shear or pullout. C-T studs are spaced 24 inches on center ® and 1-inch TouchRock Fireguard (Type X) Shaftliner is inserted in the top flange. 1 /2-inch For two-hour protection, two layers of ® ToughRock Fireguard C gypsum board are applied and finished as described for the 620 two-hour shaftwall in Section 2.2. 5 For one-hour protection, a single layer of /8-inch ® ToughRock Fireguard (Type X) gypsum board is applied and finished as described for the 622 one-hour shaft wall in Section 2.5. 2.7 627 Two-hour Horizontal Horizontal Duct Protection: Membrane and The J-runner and C-T studs are installed as described in Section 2.6, except one 1/2-inch No. 6 Type S panhead framing screw attaches the ends of each stud to the 1-inch leg of the J-runner. The 1-inch Fireguard Shaftliner panels are installed as described in Section 2.1, except panels are full length and 15/8-inch-long No. 6 Type S screws spaced at 12 inches on center are used to attach the panels to the 21/4-inch-long leg of the J-runner. A base layer of 1/2-inch Fireguard C gypsum wallboard is attached parallel to studs on the room side with 1-inch No. 6 Type S screws spaced 24 inches on center. A second layer of the same type of wallboard is placed over the base layer parallel to the 5 studs and attached with 1 /8-inch No. 6 Type S screws spaced 12 inches on center. Edge joints are offset 24 inches from the base layer. A face layer of 1/2-inch Fireguard C gypsum wallboard is applied perpendicular to studs and attached with 2-inch-long No. 6 Type S screws 12 inches on center. Screws are 1 inch and 6 inches from edge joints and then 12 inches on center between. Screws must penetrate all three layers of gypsum wallboard and into stud flanges. Butt joints should occur between framing members offset 24 inches from each other. Butt joints are secured to the previous layer of gypsum wallboard with 11/2-inch No. 8 Type G screws spaced 8 inches on center and 3 inches in from each side of a butt joint. Treatment of gypsum board joints and fasteners is not necessary. See Figure 5. 2.8 Alternate Construction: For the 620 and 621 two-hour shaftwall systems, a base 5 ® layer and a face layer of /8-inch ToughRock Fireguard (Type X) may be used in lieu of each base and face layer of 1/2-inch ToughRock® Fireguard C. 2.9 Identification: Each piece of 1/2-inch ToughRock® Fireguard C is imprinted on the face of the board along one edge with “1/2 Type X-C.” Each piece of 5/8-inch Type X ToughRock® Fireguard is imprinted on the face of the board along one 5 edge with “ /8 Type X.” Each piece of 1-inch Type X Fireguard Shaftliner is identified as “Type X” along one edge. Each stud and J-runner is identified with the name, Georgia-Pacific, the ICC-ES evaluation report number (ER-2541) and the minimum base-metal thickness stamped at 24 inches on center. 3.0 EVIDENCE SUBMITTED Test reports on UBC Standard 7-1, lateral load, and calculations, and quality control data in compliance with the Acceptance Criteria for Steel Studs, Joists and Tracks, dated January 1994. 4.0 FINDINGS That the Georgia-Pacific Gypsum LLC 620 Series Shaftwall Systems described in this report comply with the 1994 Uniform Building Code™ and 1994 ICBO Uniform Mechanical Code™ for one- and two-hour fireresistive noncombustible nonload-bearing partitions, subject to the following conditions: 4.1 Construction conforms to this report and the manufacturer’s instructions. 4.2 Maximum unsupported heights for the 620 and 621 partitions comply with Table 1. 4.3 Maximum unsupported heights partition comply with Table 2. for the 622 4.4 Maximum unsupported heights for the 620 air shaft partition comply with Table 3. The air shaft has a maximum vacuum pressure of 4 inches of water and a maximum positive pressure of 2 inches of water. 4.5 The maximum horizontal spans for the 620, 622 and 627 partitions used horizontally comply with Table 4. 4.6 The assembly described in Section 2.7 may be used to protect two-hour horizontal ducts (horizontal duct shafts) or where a two-hour horizontal membrane is required and is not part of a floor-ceiling or roof-ceiling assembly. This system is designed to support its own weight only and should not be used where there is an attic or loft above, or any probability of storage. 4.7 Uncoated minimum steel thickness of stud members as delivered to the jobsite shall not be less than 95 percent of the minimum design thickness. 4.8 Studs are manufactured at 4817 East Sheila Street, Los Angeles, California. ER-2541 | Most Widely Accepted and Trusted Page 3 of 5 1 2 TABLE 1—ALLOWABLE HEIGHTS —620 AND 621 SHAFTWALLS (Nos. 25 and 20 Gage Studs) STUD DEPTH (inches) MINIMUM DESIGN THICKNESS (inches) STUD GAGE 1 0.022 25 2 /2 STUD SPACING (inches) DEFLECTION SPAN RATIO 24 LOAD (psf) 3 15 3 5 7.5 10 120 180 240 360 17' - 3" 15' - 0" 13' - 8" 11' - 11" 13' - 3" 13' - 2" 11' - 11" 10' - 5" 13' - 8" 11' - 11" 10' - 10" 9' - 6" 11' - 11" 10' - 5" 9' - 6" 8' - 3" 18' - 6" 16' - 1" 14' - 8" 12' - 10" 16' - 1" 14' - 1" 12' - 10" 11' - 2" 14' - 8" 12' - 10" 11' - 8" 10' - 2" 12' - 10" 11' - 2" 10' - 2" 8' - 11" Y C T A R G O E P L E R 1 2 /2 0.035 20 24 120 180 240 360 4 0.022 25 24 120 180 240 360 19' - 11" 17' - 11" 16' - 3" 14' - 11" 13' - 3" 13' - 3" 13' - 3" 12' - 5" 16' - 3" 14' - 2" 12' - 11" 11' - 3" 11' - 10" 11' - 10" 11' - 3" 9' - 10" 23' - 10" 20' - 10" 18' - 11" 16' - 6" 20' - 10" 18' - 2" 16' - 6" 14' - 4" 18' - 11" 16' - 6" 15' - 0" 13' - 2" 16' - 6" 14' - 5" 13' - 2" 11' - 6" 4 0.035 20 24 120 180 240 360 6 0.022 25 24 120 180 240 360 19' - 11" 19' - 11" 19' - 11" 19' - 7" 13' - 3" 13' - 3" 13' - 3" 13' - 3" 14' - 8" 14' - 8" 14' - 8" 14' - 8" 9' - 10" 9' - 10" 9' - 10" 9' - 10" 6 0.035 20 24 120 180 240 360 28' - 0" 27' - 1" 24' - 7" 21' - 6" 27' - 1" 23' - 8" 21' - 6" 18' - 9" 24' - 7" 21' - 6" 19' - 6" 17' - 1" 18' - 8" 18' - 8" 17' - 1" 14' - 11" 1 The tabulated partition heights are based on the steel studs acting as a composite section with the wallboard to conform to the load and deflection criteria specified in Section 1610.2 of the code. Maximum practical stud length is 28 feet. 3 Minimum 0.035-inch (No. 20 gage) J-runner track is required. 2 1 TABLE 2—ALLOWABLE HEIGHTS —622 SHAFTWALLS (Nos. 25 and 20 Gage Studs) STUD DEPTH (inches) STUD GAGE STUD SPACING (inches) DEFLECTION SPAN RATIO LOAD (psf) 2 15 2 5 7.5 10 14' - 6" 12' - 8" 11' - 6" 10' - 0" 12' - 8" 11' - 1" 10' - 0" 8' - 9" 11' - 6" 10' - 0" 9' - 1" 8' - 0" 10' - 0" 8' - 9" 8' - 0" 7' - 0" 1 2 /2 0.022 25 24 120 180 240 360 1 0.035 20 24 120 180 240 360 15' - 6" 13' - 7" 12' - 4" 10' - 9" 13' - 7" 11' - 10" 10' - 9" 9' - 5" 12' - 4" 10' - 9" 9' - 9" 8' - 6" 10' - 9" 9' - 5" 8' - 6" 7' - 6" 18' - 7" 16' - 3" 14' - 9" 12' - 10" 13' - 3" 13' - 3" 12' - 10" 11' - 3" 14' - 9" 12' - 10" 11' - 8" 10' - 3" 12' - 10" 11' - 3" 10' - 3" 8' - 11" 2 /2 4 0.022 25 24 120 180 240 360 4 0.035 20 24 120 180 240 360 20' - 1" 17' - 6" 15'- 11" 13' - 11" 17' - 6" 15' - 4" 13'- 11" 12' - 2" 15' - 11" 13' - 11" 12' - 8" 11' - 1" 13' - 11" 12' - 2" 11' - 1" 9' - 8" 6 0.022 25 24 120 180 240 360 19' - 11" 19' - 11" 18' - 10" 16'- 6" 13' - 3" 13' - 3" 13' - 3" 13' - 3" 18' - 10" 16' - 6" 15' - 0" 13' - 1" 16' - 6" 14' - 5" 13' - 1" 11' - 5" 24 120 180 240 360 26' - 1" 22' - 9" 20' - 8" 18' - 1" 22' - 9" 19' - 11" 18' - 1" 15' - 9" 20' - 8" 18' - 1" 16' - 5" 14' - 4" 18' - 1" 15' - 9" 14' - 4" 12' - 6" 6 1 MINIMUM DESIGN THICKNESS (inches) 0.035 20 The tabulated partition heights are based on the steel studs acting as a composite section with the wallboard to conform to the load and deflection criteria specified in Section 1610.2 of the code. Minimum 0.035-inch (No. 20 gage) J-runner track is required. 2 ER-2541 | Most Widely Accepted and Trusted Page 4 of 5 TABLE 3—ALLOWABLE HEIGHTS—620 AIR SHAFTWALL STUD DEPTH (inches) MINIMUM DESIGN THICKNESS (inches) STUD GAGE STUD SPACING (inches) ALLOWABLE HEIGHT 2 /2 1 0.035 20 24 10' - 11" 4 0.035 20 24 14' - 1" 6 0.035 20 24 17' - 4" 1 Y C T A R G O E P L E R 1 Stud heights are based upon either a transverse load of 20 pounds per square foot at a deflection of 1.14 inches or the maximum allowable end reaction, whichever governs, as a composite section with the gypsum wallboard. 1 TABLE 4—HORIZONTAL SPANS FOR 620, 622 AND 627 C-T SHAFTWALL STUDS STUD DEPTH (inches) STUD GAGE 1 25 20 25 20 25 20 2 /2 1 2 /2 4 4 6 6 1 CORRIDOR CEILINGS AND STAIR SOFFITS 2 HORIZONTAL MEMBRANE AND 3,4 DUCT PROTECTION 622 One-hour Fire-resistive Rating 620 Two-hour Fire-resistive Rating 627 Two-hour Fire-resistive Rating 8' - 0" 8' - 6" 10' - 3" 11' - 1" 13' - 1" 14' - 4" 9' - 6" 10' - 2" 11' - 3" 13' - 2" 14' - 8" 17' - 1" 8' - 3" 8' - 11" 9' - 10" 11' - 6" 9' - 10" 14' - 11" Systems are designed to support their own dead weight only and should not be used where there is access to an attic or loft above or any probability of storage. 2 1 Load of 10 pounds per square foot and deflection limitation of /360. 3 1 Load of 15 pounds per square foot and deflection limitation of /360. 4 Ducts should be designed as a separate system. FIGURE 1 FIGURE 2 FIGURE 5 FIGURE 3 FIGURE 4 ER-2541 | Most Widely Accepted and Trusted Page 5 of 5 Y C T A R G O E P L E R FIGURE 6 FIGURE 7