NAPS-2000, Waterloo, ON, October 2000 Stability Improvement Using TCSC in Radial Power Systems Alberto Del Rossoy Claudio A. Ca~nizares Victor Quintana University of Waterloo Department of Electrical & Computer Engineering Waterloo, ON, Canada N2L 3G1 c.canizares@ece.uwaterloo.ca Abstract|This paper examines the use of Thyristor Controlled Series Capacitors (TCSC) for stability improvement of power systems. An appropriate TCSC model for angle stability studies is used to design a simple controller based primarily on the dynamic response of the system. An analysis of dierent locally measurable controller input signals is conducted by means of linear systems techniques, for both pre-fault and postfault system congurations, as well as time domain simulations involving large disturbances; limitations of control laws based upon linearized system models are then discussed for this particular problem. A simplied model of the Argentinean high voltage interconnected system is used to illustrate the concepts presented in the paper. Keywords: Stability limits, radial power systems, transient stability, FACTS, TCSC, controller design. I. Introduction In radial power systems, large amounts of power are transmitted from low cost power stations (hydro, gas) to major load centers over long transmission lines. Power systems with these features are commonly found in geographically broad countries with low population density, such as Argentina and other South American countries. In these systems, stability problems are a major issue due to the fact that system disturbances on the interconnecting lines easily lead to loss of synchronism or sustained oscillations [1]. Radial type systems are also rather susceptible of voltage stability problems, especially in a liberalized electricity market environment on which systems are being operated under increasingly stressed conditions. Dynamic security assessment, i.e., the evaluation of the power system ability to withstand a set of severe disturbances, surviving the transient perturbation to recover acceptable steady-state conditions [2], is an essential task for secure operation of power systems. To ensure that a system remains dynamically secure, preventive and/or corrective remedial actions must be designed. Preventive actions are applied in the pre-contingency system, i.e., prior to any disturbance, so that after any \credible" contingency, the system remains stable. Examples of these types of actions include restrictions on interface ows, generation active power re-dispatch and voltage rescheduling. Typically, reduction of interface power ow limits, i.e., reducing the available transfer capability (ATC) of the system, is the most common preventive action taken by operators, thus forcing expensive energy to be produced near load centers and hence increasing operation costs for the whole system. The ATC calculation basically consists on determining the stability limits of a system for a given load pattern by nding the maximum power that can be transferred across an interface such that, if credible contingencies actually occur, the system will not lose stability [3]. Corrective y Visiting Scholar from the Universidad Nacional de San Juan, Instituto de Energa Electrica, Argentina. Victor Do~na Universidad Nacional de San Juan Instituto de Energa Electrica Argentina remedial actions, on the other hand, are major actions taken immediately after a disturbance, such as tripping, load rejection, break resistors, fast-valving, capacitor bank or reactor switching, etc. More recently, Flexible AC Transmission System (FACTS) controllers are giving grid planners and operators a greater exibility regarding the type of preventive and corrective actions that can be taken on a power system [4]. The use of FACTS Controlled Series Compensators, particularly Thyristor Controlled Series Capacitors (TCSC), for stability enhancement has been widely studied and reported in various papers and technical reports (e.g., [1]). In radial power systems, the installation of Controlled Series Compensators in the main transmission corridors might result in a cost eective measure to increase stability limits. Hence, the aim of this paper is to analyze the design a proper TCSC controller based on small-signal and transient stability analysis so that transfer capability limits can be increased. Dierent control techniques have been applied to TCSC control design, so that power system oscillations can be damped to improve system dynamic response. In [5], modal sensitivities and residue methods are used to determine the TCSC location, feedback signals and control design; the proposed method is applied to a 3-area, 6machines test systems for illustration purposes. Authors in [6] propose an output feedback damping controller for a TCSC in meshed multi-machine power systems; a 9-bus, 3-machine system is used to demonstrate the proposed approach. In [7, 8, 9], dierent control laws for damping power system oscillations are derived based on transient energy function methods. In all of these papers, simplied models of the TCSC and small test systems are used to test the performance of the proposed control strategies. In the present paper, a linear dynamic compensator is proposed for damping control using a more accurate model of the TCSC as proposed in [10, 11]. Since transient stability improvement is of major concern here, tuning of the control parameters is carried out mainly via simulation of severe fault conditions. Furthermore, studies are conducted in a realistic 89-bus, 72-machine radial system model of the Argentinean power grid. The paper is structured as follows: Section II describes the TCSC model suitable for time domain simulations and stability analysis used in this paper. The design of the TCSC controller for stability improvement and the proper selection of the feedback signals are discussed in Section III. In Section IV, the test system model of the Argentinean power grid used for simulations is described; a brief description of the analysis tools used in this work is also presented in this section. The performance of the TCSC and the proposed controller design for stability enhancement are discussed in Section V, analyzing the increase in stability limits when the TCSC controller is used in the proposed model. Finally, Section VI summarizes the main contributions of this paper and suggests directions for fu- ture research. X’m II. TCSC model A typical TCSC module consists of a xed series capacitor (FC) in parallel with a thyristor controlled reactor (TCR). The TCR is formed by a reactor in series with a bi-directional thyristor valve that is red with an angle ranging between 90 and 180 with respect to the capacitor voltage [12]. The model to be adopted for any device in power systems analysis must be in accordance with the type of study involved and the tools used for simulation. Since this work is concerned with the application of the TCSC for stability improvement, the TCSC model used must rely in the assumptions that are typically adopted for transient stability analysis, i.e., voltages and currents are sinusoidal, balanced, and operate near fundamental frequency. In [10, 11], an appropriate TCSC model suitable for voltage and angle stability applications and power ows studies is discussed. In that model, the equivalent impedance Xe of the controller at fundamental frequency is represented as a function of the ring angle , based on the assumption of a sinusoidal steady-state total current. Thus, k 2 ( + sin ) Xe = ;Xc 1 ; x 2 (kx ; 1) 2 2 + 4kx cos2 (=22) (kx tan kx2 ; tan 2 ) (1) (kx ; 1) where = 2( ; ); kx = prx = Xc =XL ; Xc is the capacitor nominal reactance; and XL is the inductor reactance. The device can be continuously controlled in the capacitive or inductive regions by controlling the ring angle ; this mode of operation is known as Vernier control mode. It can be observed that there is a value of = r that causes steady-state resonance, i.e., Xe = 1 in (1); this value of r depends on the ratio rx. As the TCSC is connected in series with a transmission line, the resonant point must be avoided to prevent damage in the controller components as well as line current interruptions. Furthermore, operation close to the resonant point and on the inductive region should be avoided, as there is substantial harmonic content in the controller line current under these operating conditions [10]. Hence, the limits of the ring angle for a TCSC operating in the capacitive region may be dened as min 180, where min > r to prevent parallel resonance. In this paper, only operation on the capacitive region is considered, which is a realistic operating condition for the TCSC, given the undesirable current harmonics produced in the inductive region; furthermore, model (1) fails to represent the controller when operating in this region. Since the relationship between angle and the equivalent fundamental frequency impedance Xe is a uniquevalued function, the TCSC can be modeled, for simulation purposes, as a variable capacitive reactance within the operating region dened by the limits imposed by the ring angle , i.e., Xemin Xe Xemax , where Xemin = Xe (min) and Xemax = Xe (180 ) = Xc . The general block diagram of the TCSC model used for stability studies is shown in the Fig. 1. In this gure, Xm is the stability or damping control modulation reactance value, as determined by the control blocks. This signal is then put through a rst order lag that represents the ring p max Xe0 Input Signal 1 Xm CONTROLLER X’m + + Xe 1 + sT X’m min Fig. 1. TCSC model for stability studies. Limiter Input Signal Kc (sTw ) 1 + sTw 1 + sT1 1 + sT2 1 + sT3 1 + sT4 Xm Fig. 2. Transfer function for the TCSC controller. control and natural response of the device; a typical value for the TCSC lag time constant is 15 ms [13]. Xe0 is the desired steady-state reactance of the TCSC. The values of the limits Xm0 max and Xm0 min are obtained from the Xe limits, e.g., Xm0 min = Xemin ; Xe0 . Observe that for each value of the output variable Xe , there is a corresponding value of the angle , as for (1). III. Controller design Considering a radial type interconnected power system with a TCSC installed in a tie-line forming an interconnection corridor, when the system is subjected to a severe disturbance, the controller must provide maximum compensation level for the immediate post-fault period, to increase synchronizing torque in order to improve rstswing stability, as well as provide proper modulation to damp the subsequent power oscillation. In [12], a two loop controller is proposed for stability enhancement. The rst control loop is used for synchronization, yielding a maximum compensation level during a predened acting time; the control is then transferred to the damping loop, which is in charge of damping the remaining oscillations. In this paper, a simple linear controller is proposed for stability enhancement. It is shown below that, with a proper selection of control parameters and controller input signals for this linear controller, it is possible to accomplish the aforementioned control requirements. The general structure of the proposed controller is laid out in Fig. 2. It consists of a washout lter, a dynamic compensator and a limiter. The washout lter is mainly provided to avoid the controller respond to the dc oset of the input signal. The dynamic compensator consists of two or more lead-lag blocks to provide the necessary phase-lead characteristics. Two fundamental elements in the controller design process, i.e., the input signal and parameter tuning, are discussed below. A. Input Signals The selection of the appropriate input signal is an important issue in the design of an eective and robust controller. The following are some of the main characteristics of a proper input signal: The input signal should preferably be locally measur- able. This is desirable to avoid additional costs associated with communication and mainly to improve reliability. The oscillations modes to be damped should be \observable" in the input signal. Mode observability can be used to select the most eective signal to damp out the critical modes under consideration. The selected input signal must yield correct control action when a severe fault occurs in the system. It is shown in [7] that when active power is used as input signal of a pure derivative controller, the control signal may cause negative damping eects in the presence of disturbances involving large changes in generator power angles. Line active power, line reactive power, line current magnitude and bus voltage magnitude are all good candidates to be considered in the selection of input signals for the TCSC, when the aim of the controller design is stability improvement. If line current magnitude is used as an input signal, in the event of severe network faults, the signal should be kept at its initial value during the fault-on period and then returned to the actual measurements after fault clearance; this way, the controller receives a step input in the immediate post-fault period, reacting by yielding the high compensation level necessary to reduce rst-swing oscillation amplitude. Yacyreta Bracho Resistencia Rincón Noreste Argentino (NEA) Recreo Noroeste Argentino (NOA) Malvinas Litoral Romang Almafuerte Embalse Salto Grande R. Oeste C. Elía V. Lía Zárate Centro San Nicolás G. Mendoza Cuyo Corridor Comahue−Gran Buenos Aires Gran Buenos Aires (GBA) Matheu Rodriguez Ezeiza Abasto Pergamino Comahue Buenos Aires Henderson Puelches Cerrito Costa Olavarría Bahía Blanca Chocón 500 kV 220 kV Choele Choel B. Parameter Tuning A number of alternative techniques may be used for selection of control parameters. Some of the most popular ones based on linear systems theory are phase and gain margin technique, pole placement techniques based on root locus rules, eigenvalue placement using residues, and optimal selection of control parameters using eigenvalues sensitivities. However, in real power systems, the TCSC damping eect and its control parameters can be highly nonlinear functions [14]. Such characteristics make dicult the use of linear techniques for parameter tuning, especially those that require eigenvalues sensitivity calculation. Furthermore, when the performance of the controller under severe disturbances is of major concern, analysis based on system linearizations or small signal approximations are usually not valid. Therefore, an initial design may be carried out using any of the aforementioned linear techniques, and then adjust the control parameters using time domain simulations that incorporate all system nonlinearities and limit settings. Fig. 3. Argentinean Interconnected System or SADI (500kV). generation is composed mainly by hydro power plants and, to a less extent, by thermal generation units using low-cost natural gas. The main load centers are located in the Gran Buenos Aires (GBA) and Centro (CEN) areas. Two transmission corridors of about 1100 km transmit power from NEA and COM to GBA. In the simplied network used in this work, only 500 kV buses and some of the 220 kV buses are represented. The test systems consist of 89 nodes, 133 branches, including transformers, and 72 equivalent machines. Transient model are used for generators, including exciters, voltage regulators, power systems stabilizers and governors; \classical" machine models are used for some of the generators. Loads are represented as constant PQ loads. Figure 3 depicts a sketch of the Argentinean high IV. Test System and Analysis Tools voltage interconnection system (SADI); notice the radial In this paper, simulations have been carried out in a nature of the grid. simplied network model of the Argentinean high voltage (500 kV) interconnected system (SADI). The main charThe Power System Toolbox (PST) was used here for all acteristics of this system are as follows: simulations, eigenvalue calculations and mode observability analyses [15]. This package is a MATLAB based power Extensive and unmeshed HV transmission system. system analysis toolbox that was initially developed at RPI perform power system analysis using user-dened mod Principal low cost generation areas far from the major to els. It has several graphical tools, namely, a voltage staload centers. bility tool, a transient stability tool, and a small signal The power transfer capability of interface tie-lines is stability tool. The models for TCSC and other controllers and devices are included into the toolbox by means of userbasically dened by stability limits. dened \modules". The original code provided with the The principal generation areas are the Comahue (COM) program was modied to be able to implement dierent and Noroeste Argentino (NEA) areas. In these areas, the input signals for the TCSC controller. V. Simulations and Results The main objective of this study is to analyze the effectiveness of TCSC controllers to improve system stability and thus increase power transfer capability limits. The transmission corridor Comahue-Gran Buenos Aires is studied here. This corridor is mainly composed of two lines, i.e., Line-A, which is a double line going through Cerrito Costa-Puelches-Henderson-Ezeiza, and Line-B, which goes through Chocon-Choele ChoelBahia Blanca-Olavarria-Abasto. In the real system, both tie-lines are series compensated with xed capacitor banks at a compensation level of about 45%. The limits on the maximumactive power that the corridor is able to transmit are basically imposed by stability problems in the system. For the purposes of this work, a TCSC is rst assumed to be installed at the mid-point of Line-A. The characteristics of the TCSC are as follows: The capacitor fundamental frequency reactance (50 Hz) is Xc = ;39 . The value of the ratio rx = Xc =XL = 10, which yields a resonant point at r = 151:50. The adopted ring angle limits are max = 180 and min = 155 ; the limits of the TCSC net reactance corresponding to these limits are then Xemax = ;39 , and Xemin = ;96:4 . The TCSC steady-state reactance (set point) adopted for simulations is Xe0 = ;58 , which corresponds to a compensation level of 44%, and an 0 = 158:6. Simulations were conducted for dierent operation conditions corresponding to dierent power levels transmitted through the corridor for various power generation dispatch settings. The total load of the system is Pl = 11404 MW, Ql = 4800 MVAR, which was kept unchanged for all study cases. In the base case, the total generated power is Pg = 11820 MW, Qg = 4170 MVAR, and the active power owing on Line-A is PA = 1742 MW, and on Line-B is PB = 822 MW. Two severe contingencies are considered, i.e., 1. Fault-1: A three-phase short circuit on Line-A near the bus Cerrito Costa, followed by a tripping of the faulted circuit. 2. Fault-2: A three-phase short circuit on Line-B near the bus Chocon, followed by a tripping of the line. All stability limit calculations are based on the analysis of these two contingencies. A. Input Signals The active power and the current magnitude through the line where the TCSC is located are considered here as possible input signals. As discussed in Section II, an appropriate feedback signal should have signicant observability of the critical modes to be damped out. Hence, mode observability analyses were carried out for these two signals considering dierent operating conditions [2, 6], i.e., for the pre-fault network and for the two post-contingency operating states corresponding to Fault-1 and Fault-2. Table I shows the results of the open loop eigenvalue and mode observability analysis corresponding to an operation state in which the power generated in area Comahue is increased with respect to the base case, so that Line out | | | Line-A Line-A Line-A Line-B Line-B Line-B TABLE I Eigenvalues and mode observability Mode Damping Freq. I P. ratio Hz. Obs. Obs. Int.-area 0.070 0.606 0.824 0.855 Int.-area 0.046 0.711 0.861 0.877 Int.-area 0.051 0.860 0.724 0.716 Int.-area 0.011 0.480 0.823 0.298 Int.-area 0.080 0.680 0.809 0.279 Local 0.050 0.820 0.749 0.227 Int.-area 0.009 0.501 1.457 0.601 Int.-area 0.081 0.680 1.362 0.547 Local 0.046 0.825 1.236 0.429 TABLE II Parameters of the TCSC controller kc Tw T1 T2 T3 T4 1.1 5 1.1 0.05 0.08 0.5 power ow over the corridor is augmented. The active power ow in Line-A and Line-B for this condition are PA = 1948 MW and PB = 907 MW, respectively. The system presents three poorly damped electromechanical modes. Modes shapes analysis shows that these modes are inter-area modes in the pre-contingency system. It is observed that, in the pre-fault state, observability of the three modes from active power (P) and current magnitude (I) are signicant and their values are close to each other. However, in the post-fault system conguration, the observability of the modes in the current magnitude is considerably greater than in the active power. Therefore, one would expect that the performance of the TCSC controller when using line current as the input signal would be better than when the active power is used, especially in the stressed system when critical transmission lines are tripped o as a consequence of a fault. B. Parameter Settings The controller parameters are given in Table II. The adjustment of their values has been carried out via multiple time domain simulations with the aim of improving the transient response of the system for dierent operating and fault conditions. C. Simulations 1. Case I: The operating condition considered in this case corresponds to the base case. Fault-2 is applied at t = 0:1 s, and cleared after 100 ms. Figure 4 shows the oscillations of the active power ow of the line where the TCSC is installed, i.e., Line-A, for three dierent system conditions, namely, for the system without TCSC, and for the system with TCSC with current and active power as input control signals. The simulation results show that the system without TCSC is rst swing stable for this fault, but post-contingency oscillations are not well damped. The TCSC signicantly reduces the rst rotor angle swing and improves the damping of the subsequent power swings. It is also observed that the performance of the controller when using any of the considered input signals is very similar in this case. Figure 5 shows the excursions of angle, with respect to 3200 0.7 without−TCSC IS−Current IS−Real Power 3000 IS−Current IS−Real Power 0.65 0.6 Xe [p.u. wrt Xline] Power Flow [MW} 2800 2600 0.55 2400 0.5 2200 0.45 2000 0 3 6 9 12 15 0.4 Time [sec.] 0 3 6 9 12 15 Time [sec.] Fig. 4. Power ow variations on Line-A, Case I. Fig. 6. TCSC equivalent reactance variations, Case I. 110 without−TCSC IS−Current IS−Real Power 100 3600 IS−Current IS−Real Power 90 3200 Power Flow [MW] Machine angle [deg.] 3400 80 70 60 3000 2800 50 2600 40 2400 30 0 5 10 15 Time [sec.] 2200 Fig. 5. Excursions of machine angle, Case I. 0 3 6 9 12 15 Time [sec.] Fig. 7. Power ow variations on Line-A, Case II. the reference machine, of the machine that is most severely aected by the fault. Figure 6 depicts the variations of the TCSC fundamental frequency reactance, which correspond to unique values of ring angle as for (1). 2. Case II: The generation in Comahue is now increased, resulting in power ows on Line-A and Line-B of PA = 2100 MW and PB = 958 MW, respectively, which yield a 494 MW increment on the total power transmitted through the corridor with respect to the base case. The same fault as in Case I is applied here, i.e., Fault-2. In Fig. 7, the oscillations of active power ow through Line-A, are shown, whereas in Fig. 8, the angular excursions of the most severely aected machine are depicted for the three dierent system conditions already considered in Case I. Observe that the system without TCSC is transiently unstable, losing synchronism in the rst swing. When a TCSC is installed in Line-A, it stabilizes the system and damps the remaining oscillations. Notice that the performance of the controller when current magnitude is used as the input signal is much better than when active power is utilized. This agrees with the results of the mode Fig. 8. Excursions of machine angle, Case II. observability analysis previously discussed. 120 110 without TCSC IS−Current IS−Real Power Machine angle [deg.] 100 90 80 70 60 0 3 6 9 Time [sec.] 12 15 2000 TABLE III Parameters of TCSCs controllers IS−Current IS−Real Power TCSC Kc Tw T1 T2 T3 T4 1 1.2 5 1.1 0.08 0.05 0.5 2 0.8 5 0.9 0.05 0.08 0.7 Power flow [MW] 1800 1600 1400 1200 1000 0 3 6 9 12 15 Time [sec.] Fig. 9. Power ow variations on Line-A, Case III. 140 IS−Current IS−Real Power without TCSC 130 Machine angle [deg.] 120 110 100 90 80 70 60 50 0 3 6 9 12 15 Time [sec.] Fig. 10. Excursions of machine angle, Case III. 3. Case III: In this case, generation in the Comahue area is increased by 300 MW over the base case. The power owing on the lines that form the corridor are PA = 1955 MW and PB = 908 MW. A three-fault phase is applied on one of the circuits of Line-A near the bus Cerrito Costa, clearing it after 100 ms by tripping o the faulted circuit (Fault-1). Figure 9 shows the active power ows on Line A in this case, and Fig. 10 the angular oscillations of the most severely aected machine. The simulation results show that when TCSC is not used, the systems is transiently unstable and losses synchronism in the rst swing. When a TCSC is installed in Line-A (same location as in the previous cases), it is possible to stabilize the system. However, the eectiveness of the TCSC in damping oscillations is not as good as in Case II, due to the fact that, when a TCSC is located in Line-A, the controllability of the critical modes in the post-fault system corresponding to Fault-1 are much less than the controllability for critical modes in the post-fault system for Fault-2. In Case II, with a TCSC installed in Line-A, if Fault-1 is applied, the system losses synchronism in the rst swing, which basically means that Fault-1 is more severe than Fault-2 for these operating conditions. Therefore, Fault-1 can be considered as the most stringent condition to be considered for the determination of the stability limits of the corridor Comahue-Buenos Aires. After carrying out several simulations for dierent loading conditions, it was found that in most cases this contingency is the critical one. Hence, to be able to improve the response of the system and thus increase its stability limits, another TCSC is installed in Line-B. 4. Case IV: Two TCSCs are now installed in the system, one on Line-A (TCSC-1), as previously explained, and a second one on Line-B (TCSC-2). The characteristics of TCSC-2 are as follows: The capacitor fundamental frequency reactance (50 Hz) is assumed to be Xc = ;97 . The value of rx = Xc =XL = 10, which yields a resonant point at r = 151:5 ; hence, the adopted ring angle limits are max = 180 and min = 155, which yield Xemax = ;97 and Xemin = ;239 . The TCSC steady-state reactance (set point) adopted for simulations is Xe0 = ;130 , which corresponds to a 40% compensation level and a ring angle 0 = 160 . The parameters of the controllers for both TCSC are shown in Table III. The current magnitude is used as the input signal for both controllers. The operating conditions are the same as in Case II, i.e., the real power ow on Line-A is PA = 2100 MW, and on Line-B PB = 958 MW, for a total power owing over the corridor of 3058 MW. A three-phase fault is applied on Line-A near the bus Cerrito Costa at t = 0:1 s, and then cleared by disconnecting the faulted circuit at t = 0:2 s (Fault-1). Figures 11, 12 and 13 depict the main simulation results. As indicated before, if the TCSC in Line-B were not installed, the system would be unstable when subjected to this contingency. It is important to point out that when the two TCSCs are installed in the system, the most stringent contingency for stability limit calculations is not Fault -1, as in the previous case, but rather Fault-2. Table IV shows the stability limits obtained for the corridor Comahue-Buenos Aires, for three dierent cases, namely, for the system without TCSC, with one TCSC in Line-A, and two TCSCs on both lines of the corridor. As expected, the maximum power that can be transmitted though the corridor, considering the most severe contingency for the system, signicantly increases with the insertion of TCSCs. VI. Conclusions The eectiveness of TCSC controllers for improving system stability is clearly demonstrated in this paper. As a direct consequence of the stability enhancement achieved by TCSC utilization, the paper shows how transfer capability limits can be considerably augmented, thus signi- TABLE IV Stability limits for corridor Comahue-Buenos Aires 2200 Case Power Flow limit Increase [MW] % without TCSC 2620 { TCSC-1 2962 13 TCSC-1 and TCSC-2 3500 33.6 2000 1800 Power Flow [MW] Power Flow − Line A 1600 Power Flow − Line B 1400 1200 1000 800 600 0 3 6 9 12 15 18 Time [sec.] Fig. 11. Power ow variations on Line-A and Line-B, Case IV. 140 without TCSC 130 Machine angle [deg.] 120 110 with two TCSCs 100 90 80 0 3 6 9 Time [sec.] 12 15 18 Fig. 12. Excursions of machine angle, Case IV. cantly aecting the types of power transactions that can take place on the test system. In this paper, a real radial type power system is used to illustrate the increase in the stability limits of a main transmission corridor that can be achieved when TCSCs are properly located and controlled. An adequate model for representing TCSCs in stability studies is used, so that the relationship between the thyristor ring angles and the fundamental frequency impedance of the TCSC can be accurately represented, and thus properly represent the actual limits on the ring angle imposed by design considerations. Steady state and dynamic limits on voltages and currents can also be handled by this model. A detailed discussion regarding the fundamental aspects of proper controller design for TCSCs is provided. The limitations of using linear control techniques for control parameters setting when large disturbances are to be considered are also highlighted in this paper. Performance indices, which do not rely upon system linearization or small signal approximations, should be developed to properly account the TCSC stabilization and damping eects and for optimal tuning of control parameters. Also, special techniques for control coordination should be used when more than one TCSC are utilized in the system. Finally, comparative studies should be performed of the eects, control and design of using dierent series FACTS controllers in power system models of real networks. The authors are currently pursuing research work on all these aspects of FACTS control and design, with particular emphasis on determining the eect of these devices on power transactions in realistic power system models. [1] 0.7 [2] 0.6 [3] 0.55 [4] Xe [p.u. wrt X line ] 0.65 0.5 [5] Xe of TCSC Line A 0.45 [6] Xe of TCSC Line B 0.4 0.35 0 3 6 9 Time [sec.] 12 15 Fig. 13. TCSC-1 and TCSC-2 reactance variations, Case IV. 18 [7] References C. Gama and R. Tenorio, \Improvements for Power System Performance: Modeling, Analysis and Benets of TCSCs," Proc. IEEE/PES Winter Meeting, Singapore, January 2000. P. Kundur, \Power Systems Stability and Control," EPRI, McGraw-Hill, 1994. NERC, \Available Transfer Capability Denitions and Determination," USA, 1996. N. G. Hingorani, \Flexible AC Transmission Systems," IEEE Spectrum, April 1993, pp. 40{45. N. Yang, Q. Liu, and J. McCalley, \TCSC Controller Design for Interarea Oscillations," IEEE Trans. Power Systems, Vol. 13, No. 4, November 1998, pp. 1304-1309. X. Chen, N. Pahalawaththa, U. Annakkage, and C. Kumbe, \Output feedback TCSC controllers to improve damping of mesehed multi-machine power systems," IEE Proc. Transm. Distrib., Vol. 44, No. 3, May 1997, pp. 243-248. J. Machowski, S. Robak, and J. Bialek \Damping of Power Swings by Optimal Control of Series Compensators," 10th International Conference on Power System Automation ans Control, Bled, Slovenia, October 1997. [8] J. Gronquist, W. Sethares, F. Alvarado, and R. Lassester, \Power Oscillations Damping Control Strategies for FACTS Devices Using Locally Measurable Quantities," IEEE Trans. Power Systems, Vol. 10, No. 3, August 1995, pp. 1598-1605. [9] M. Noroozian, A. Wilk-Wilcznski, P. Halavarsson, and K. Niklasson, \Control Strategy fot Damping of Power Swings Using TCSC," 6th Symposium of Specialists in Electric and Expansion Planning (VI SEPOPE), 1998, Brazil. [10] C. A. Ca~nizares and Z. T. Faur, \ Analysis of SVC and TCSC Controllers in Voltage Collapse ," IEEE Trans. Power Systems, Vol. 14, No. 1, Frebruary 1999, pp. 158-165. [11] C. Ca~nizares, S. Corsi, and M. Pozzi, \Modeling and Implementation of TCR and VSI Based FACTS COntrollers," ATUCR no. 99/595, ENEL-Ricerca, Area Trasmissione e Dispacciamento, December 1999. [12] CIGRE Working Group 14.18, \Thyristor Controlled Series Compensation," December, 1997. [13] J. Paserba, N. Miller, E. Larsen, and R. Piwko, \A Thyristor Controlled Series Compensation Model for Power System Stability Analysis," IEEE Trans. Power Systems, Vol. 10, No. 4, November 1995, pp. 1471-1478. [14] P. Dolan, J. Smith, and W. Mittelstadt, \A Study of TCSC Optimal Damping Control Parameters for Dierent Operating Conditions," IEEE Trans. Power Systems, Vol. 10, No. 3, July 1995, pp. 1972-1978. [15] \Power System Toolbox Ver. 2.0: Dynamic Tutorial and Functions," Cherry Tree ScienticSoftware, Colborne, Ontario, 1999. Alberto Del Rosso received his Electromechanical Engineer diploma form the Universidad Tecnologica Nacional (UTN), Mendoza-Argentina, in March 1995. He is PhD student at the Instituto de Energia Electrica, Universidad Nacional de San Juan, San Juan-Argentina. Mr. Del Rosso is currently performing research activities as visiting scholar at the University of Waterloo, E&CE Department. The area of his research is concerned with dynamic security and control of FACTS devices. Claudio A. Ca~nizares received in April 1984 the Electrical Engineer diploma from the Escuela Politecnica Nacional (EPN), QuitoEcuador, where he held dierent teaching and administrative positions from 1983 to 1993. His M.Sc. (1988) and Ph.D. (1991) degrees in Electrical Engineering are from the University of Wisconsin{ Madison. Dr. Ca~nizares is currently an Associate Professor at the University of Waterloo, E&CE Department, and his research activities are mostly concentrated in studying stability, modeling and computational issues in ac/dc/FACTS systems. Victor H. Quintana received the Dipl. Ing. degree from the State Technical University of Chile in 1959, and the M.Sc. and Ph.D. degrees in Electrical Engineering from the University of Wisconsin, Madison in 1965, and University of Toronto, Ontario, in 1970, respectively. Since 1973 he has been with the University of Waterloo, Department of Electrical and Computer Engineering, where he is a full professor. His main research interests are in the areas of numerical optimization techniques, state estimation and control theory as applied to power systems. Victor Do~na obtained his Electrical Engineer diploma from the Universidad Nacional de San Juan (UNSJ), San Juan, Argentina, in March 1986. From 1986 to 1990 he worked for CONICET at the Instituto de Energa Electrica (IEE), UNSJ, San Juan, Argentina. From 1990 to 1993 he performed research tasks at IAEW at the University of Aachen, Germany. In 1993 returned to work at the IEE, and in 1996 received the Ph.D. degree in Electrical Engineering from UNSJ. Dr. Do~na is currently Professor at UNSJ and his activities include power system studies and software programming as a senior engineer, teaching and graduate supervision in the general area of security and optimization of power systems.