Example: Three Phase TrnasfomersWe have a small power system as shown in the figure:
generator, two transformers, distribution line, and load. Ratings on the equipment are shown. The
generator voltage is 13.8kV.
a. Find the load voltage without the transformers.
b. Find the load voltage WITH the tranformers.
c. Find the generator load real and reactive power.
6
MVA 10 V A
j 1
Vg 13.8 kV
VT1L 13.8 kV
SgR 50 MVA
VT1H VT1L 10 3 239.023 kV
VT2H VT1H 239.023 kV
Xg 2.7 Ω
VgLN
Zload ( 4 j 1 ) Ω
Vg
3
VT2L VT2H
VgLN 7.967 kV
1
Xline 100 Ω
XT1 0.07 Ω
13.8 kV
10 3
XT2 0.07 Ω
Without the transformers, the line and load and generator are in series. Using voltage division on a
line-to-neutral per phase circuit.
Vload VgLN
Z
Zload
Vload ( 91.239 311.929i) V
load j Xline
Vload 324.998 V
Voltage Regulation
Vout_noload VgLN
Vregulation
Vout_noload
arg Vload 73.696 deg
Vload
Vload
3
Vregulation 2.352 10 %
This is not good. Let's include the transformers. We must make a reflection of the line impedance.
Let's reflect everything to the generator side. With identical transformers, the load impedance
reflects across both transformers, cancelling out the effect.
VT1H
NT1
VT1L
NT1 17.321
Xline
Xline_eq
NT1
NT2 NT1
Again, using voltage division,
load j XT2 j Xline_eq j XT1
Zload
Vload VgLN
Z
Vload ( 7.662 0.83i) kV
Vload 7.706kV
Vregulation
arg Vload 6.184deg
VgLN Vload
Vload
Vregulation 3.386%
2
Xline_eq 0.333Ω
Find the load power.
Sload
Vload
3
2
Sload ( 41.922 10.481i ) MVA
Zload
Find the generator power.
Vload
Iload
Zload
3
Iload 1.754 10 646.022i A
NT1
Igen Iload
NT2
3
Igen 1.754 10 646.022i A
Calculate the combined real and reactive power.
Sgen 3 VgLN Igen
Sgen ( 41.922 15.441i ) MVA