2/6/EN/5 Swirl diffusers Type FD recommended room heights from 2.60 . . . 4.00 m TROX GmbH Heinrich-Trox-Platz D-47504 Neukirchen-Vluyn Telephone +49 / 28 45 / 2 02-0 Telefax +49 / 28 45 / 2 02-2 65 e-mail trox@trox.de www.troxtechnik.com Contents · Description Description Construction · Dimensions Materials Installation · Assembly 2 3 4 4 FD-Q Construction FD-R Construction The diffuser face of the type FD consists of fixed, radially arranged air control blades. The supply air design has specially arranged internal air guidance elements which are not required on the extract version. Due to the rotary swirling motion of the air discharge, induction of room air occurs very quickly, resulting in rapid decay of supply air velocity and temperature differential. Air change rates of 30 per hour can be achieved with supply air temperature differentials of +10K to –10K. To stabilise horizontal discharge, all sizes must be mounted flush with a ceiling. The minimum mounting height between floor and diffuser face is 2.60 m. Flow Visualisation 2 Nomenclature Acoustic Data Aerodynamic Data Order Details 5 6 9 13 Construction · Dimensions If a circular diffuser face is ordered, the plenum box with side entry spigot has a 35 mm extension piece fitted to the plenum. Construction Type FD swirl diffusers are available in 5 sizes. Depending on the architectural requirements, the face plate can be circular or square. The fixed air control blades on the diffuser face are arranged radially. The diffuser face can be attached or removed via a centre fix screw into the plenum box. The screw head is covered with a decorative cap. The plenum box can be supplied with either top or side entry spigots and on request, with spigot lip seals and volume control damper. For simple adjustment of the volume flow, on request the plenum box can be provided with a test connection for measurement of a reference pressure and a volume control damper operated by sheathed cables. The characteristic curve of pressure reading versus volume flow rate for each size of plenum box is supplied. Note: If a larger size side entry plenum is fitted to a diffuser face, this should be considered in relation to performance (lower noise levels and pressure drop). AK code, diffuser face 1) Square Circular Size B D L Q R H2 K P 300 280 158 250 298 300 250 290 278 AK001 AK013 400 364 198 350 398 400 295 372 362 AK002 AK014 500 462 198 450 498 500 295 476 460 AK003 AK015 600 559 248 538 598 600 345 567 557 AK004 AK016 625 559 248 538 623 623 345 567 557 AK004 AK016 1) Valid only for FD-...-H! FD-R-...-V FD-R-...-H fixing screw for diffuser face FD-Q-...-V FD-Q-...-H Plenum Boxes K 8 8 35 H2 D H2 D K P FD-Q-...-H FD-R-...-H FD-...-V 3 Materials · Installation · Assembly Materials Assembly The diffuser face is made of galvanised sheet steel. The surface is pre-treated and powder coated white (RAL 9010) The plenum box is suspended by wires or slotted strips using the drilled holes in the plenum return edge or hanging brackets, when provided. For the side entry plenum box, a self adhesive seal, supplied loose, must be fitted by the client. The diffuser face is fitted to the plenum box by means of centre fix screw locating in cross channel in the plenum box. The plenum boxes are galvanised sheet steel, the lip seal of rubber. Installation All sizes are suitable for flush mounting into a ceiling. If the diffuser is installed below a closed ceiling (i. e. freely suspended) a stable discharge can be achieved if a peripheral collar 50 mm is provided – available on request. Measurement of Reference Pressures For simple adjustment of the volume flow, on request the plenum box can be provided with a test connection for measurement of a reference pressure and a volume control damper operated by sheathed cables. The characteristic curve of pressure reading versus volume flow rate for each size of plenum box is supplied. Installation flush to ceiling Freely suspended Installation with cut out in ceiling Installation using hangers Surface mounting on ceiling Hangers by others Self adhesive seal, fitted by others Fixing of diffuser face using centre screw 4 Test nipple Inclined manometer Plastic tube Code White sheathed cable damper open Diffuser face Green sheathed cable damper closed Plenum box Nomenclature V· in l/s: Volume flow per diffuser V· in m3/h: Volume flow per diffuser A, B in m: Spacing between two diffusers X in m: Distance between diffuser centre and wall H1 in m: Distance between ceiling and occupied zone v- H1 in m/s: Time average air velocity between two diffusers at distance from ceiling H 1 L in m: (Horizontal + vertical) distance (X + H 1) discharge to the wall v- L in m/s: Time average air velocity at the wall tZ in K: Temperature difference between supply air and room air tL in K: Difference between core and room air temperature at distance L = A/2 + H 1 or L = B/2 + H 1 or L = X + H 1 A eff in m2: Effective outlet area p t in Pa: Total pressure drop (supply air) LWA in dB(A): A-weighted sound power level LWNC : NC rating of sound power level LWNR : LWNR = LWNC + 2 L pA, L pNC : A-weighting and NC rating respectively of room sound pressure level L pA L WA – 8 dB L pNC L WNC – 8 dB in °: Damper angle Nomenclature Quick Selection (Supply air) V·min V·max l/s 3 m /h l/s m3/h LWA max dB(A) LW NC max NC LWA min dB(A) LW NC min NC Aeff m2 300 055 200 40 145 40 34 31 25 0.00884 400 110 400 50 180 40 34 25 20 0.0180 500 145 520 60 215 40 34 20 20 0.0251 600 625 165 600 80 290 40 34 20 20 0.0295 Size Octave band spectrum on request! 5 Acoustic Data FD-...-V Supply Air Correction to diagram 1: Volume control damper setting Damper angle 0° 45° 90° Damper angle ∆p t x 1.0 x 1.2 x 2.5 L WA – – L WNC – – 0° 45° 90° ∆p t x 1.0 x 1.5 x 4.0 +2 L WA – +3 +7 +2 L WNC – +3 +7 Correction to diagram 2: Volume control damper setting Damper angle Correction to diagram 4: Volume control damper setting 0° 45° 90° Damper angle ∆p t x 1.0 x 1.1 x 2.1 L WA – +1 L WNC – +1 1 Sound power level and pressure drop Size 300 2 Sound power level and pressure drop Size 400 0° 45° 90° ∆p t x 1.0 x 1.1 x 2.2 +2 L WA – +1 +4 +2 L WNC – +1 +4 3 Sound power level and pressure drop Size 500 4 Sound power level and pressure drop Size 600 and 625 Pressure drop p t in Pa Pressure drop p t in Pa Pressure drop p t in Pa Pressure drop p t in Pa 6 Correction to diagram 3: Volume control damper setting Acoustic Data FD-...-H Supply Air Correction to diagram 5: Volume control damper setting Damper angle Correction to diagram 7: Volume control damper setting 0° 45° 90° Damper angle ∆p t x 1.0 x 1.1 x 2.3 L WA – +0 L WNC – +0 0° 45° 90° ∆p t x 1.0 x 1.4 x 4.3 +2 L WA – +1 +8 +2 L WNC – +1 +8 Correction to diagram 6: Volume control damper setting Damper angle Correction to diagram 8: Volume control damper setting 0° 45° 90° Damper angle ∆p t x 1.0 x 1.3 x 2.7 L WA – +1 L WNC – +1 6 Sound power level and pressure drop Size 400 45° 90° ∆p t x 1.0 x 1.4 x 3.5 +3 L WA – +1 +4 +3 L WNC – +1 +4 7 Sound power level and pressure drop Size 500 8 Sound power level and pressure drop Size 600 and 625 Pressure drop p t in Pa Sound power level and pressure drop Size 300 Pressure drop p t in Pa 5 0° 150 45 100 Pressure drop p t in Pa 50 45 40 35 50 35 in dB (A) 20 30 20 WA 25 30 L 30 40 40 15 25 15 WN C 20 10 L Pressure drop p t in Pa 70 7 30 40 m 3/h 150 50 200 70 100 300 l/s 150 400 500 300 200 900 7 Acoustic Data Extract Air Correction to diagram 9 and 10: Volume control damper setting Size 300 400 500 600/625 9 Sound power level and pressure drop FD - . . . - V 10 Damper angle 45° 90° x 1.0 x 1.1 x 2.0 L WA – – + 3.0 L WNC pt – – + 3.0 x 1.0 x 1.0 x 1.9 L WA – – + 4.0 L WNC pt – – + 4.0 x 1.0 x 1.1 x 2.5 L WA – – + 7.0 L WNC pt – – + 7.0 x 1.0 x 1.1 x 2.2 L WA – + 1.0 + 4.0 L WNC – + 1.0 + 4.0 Sound power level and pressure drop FD- . . . - H Size Pressure drop p t in Pa Pressure drop p t in Pa Size 0° pt 8 Aerodynamic Data FD 300 Correction! For an installation below the ceiling line, the values v-H1, v-L and t L / t Z must be multiplied by a factor of 0.71! Diffuser arrangement: single or more than one row if B 4.00 m H 1 = 0,9 1,2 1,6 2 m A=1 30 0, 25 0, 20 0,04 ) 0,03 ) ) 80 (1 15 ) 45 v- L in m/s 90 (2 0, ) 3 /h (m 60) (3 (2 0 (14 0,3 0 0,02 0, 10 5 0,2 0,2 0,8 1 1,5 2 3 4 0 0,1 5 6m 5 0,8 1 1,5 Spacing A 14 1,6 2 m 5 6m 0 0, 5 40 0, 30 0, 0, 15 0, 0, 2 10 0 0, 25 0, 15 v- H1 in m/s 0, 4 ) 3 /h (m 60) (3 0) l/s (29 00 · =1 0 V 8 25 0,01 5 6m 5) (21 0) (18 ) 5 (14 40 0, 4 1,6 2 m 50 20 1,2 60 V· = l/s (m 3 80 / (29 h) 70 0) (25 0) 60 (21 5) 50 (18 0) 40 (14 5) 0, 3 Square Array of Diffusers H 1 = 0,9 30 1,2 2 Distance L Diffuser arrangement: more than one row if B = 3.00 m H 1 = 0,9 v- H1 in m/s 0,05 l/s 0 10 80 0,4 5) 12 0,08 · = V 0 0,5 (1 (18 0 60 15 0,10 40 0, 3m 0 0,6 (21 0) 40 2 0,06 0,8 5) 50 1,5 tL tZ V· = l/s 10 (m 3 0 ( /h) 36 0) 80 (29 0) 60 Temperature Quotient 50 v- H1 in m/s 13 Temperature quotient t L / t Z 11 0,8 1 1,5 2 Spacing A 3 4 5 6m 0,8 1 1,5 2 3 Spacing A or B 9 Aerodynamic Data FD 400 Example Data given: 2 off type FD-Q-H-Z/400 Volume flow per diffuser V· = 70 l/s Supply air temperature difference tZ = –8K Spacing between two diffusers A = 1.20 m Distance between diffuser centre and wall X = 1.50 m Distance between ceiling and occupied zone H 1 = 1.20 m Diagram 17: L = A/2 + H 1 = 0.6 + 1.20 = 1.80 m t L / t Z = 0.08 t L = – 8 · 0.08 = – 0.64 K L = X + H 1 = 1.50 + 1.20 = 2.70 m t L / t Z = 0.053 t L = – 8 · 0.053 = – 0.4 K v- L 0.22 m/s Temperature Quotient between two diffusers at the wall Diagram 6: Sound power level and pressure drop L WA = 26 dB(A) (L WNC = 21 NC) p t = 16 Pa Diffuser arrangement: single or more than one row v- H1 = 0.10 m/s 15 Diffuser arrangement: single or more than one row if B 4.00 m H 1 = 0,9 1,2 Correction! For an installation below the ceiling line, the values v- H1, v- L and t L / t Z must be multiplied by a factor of 0.71! 17 1,6 2 m Temperature Quotient A=1 1,5 2 3m 0,20 tL tZ 0, 25 0, 20 0, 15 0, 0, 10 v- L in m/s 4 0 0,1 5 6m 5 0,8 1 1,5 18 4 5 6m 0 0, 5 40 0, 0, 15 0, 0, 2 10 0 0, 25 0, 30 v- H1 in m/s 0) 0, 0, 0, 5) (18 ) 3 /h ( m 50) (4 0) (36 ) 0 (29 0 10 (21 l/s 5 2 30 0,02 5 6m · =1 V 25 4 1,6 2 m 5) (21 ) 0 (18 50 1,2 80 60 20 3 Square Array of Diffusers H 1 = 0,9 V· = l/s 12 (m 3 5 ( /h) 45 0) 10 0( 36 0) 80 (29 0) 15 2 Distance L 1,6 2 m 0, ) ) 0,04 60 50 v- H1 in m/s ) 3 /h (m 50) (4 90 1,2 (2 0 0,03 Diffuser arrangement: more than one row if B = 3.00 m H 1 = 0,9 0,05 5 0,2 Spacing A 16 60 3 (3 2 0 1,5 0,06 ) 15 ) 80 1 0,08 (1 0,3 (2 0 0,2 0,8 10 0 0,5 0,4 0,10 l/s 5 12 ,60 80 0 0 60 50 v- H1 in m/s 0,12 0,8 · = V 30 V· = l/s 12 (m 3 5 ( /h) 45 0) 10 0( 36 0) 80 (29 70 0) (25 0) 60 (21 5) 50 (18 0) 0,16 0,8 1 1,5 2 Spacing A 10 3 4 5 6m 0,8 1 1,5 2 Spacing A or B 3 Temperature quotient t L / t Z Diagram 15: Aerodynamic Data FD 500 Correction! For an installation below the ceiling line, the values v- H1, v- L and t L / t Z must be multiplied by a factor of 0.71! Diffuser arrangement: single or more than one row if B 4.00 m H 1 = 0,9 1,2 1,6 2 m 0 0 0,06 50 (4 ) (3 60 0,05 ) 90 (2 0 0,08 (5 0 0,4 5 0 0,5 ) 0, 10 5) ) 15 0,3 (21 0 0,04 5 0,2 0,03 0,2 0,8 1 1,5 2 3 4 0 0,1 5 6m 5 0,8 1 1,5 Spacing A 22 1,6 2 m 5 6m 0 0, 0, 15 0, 0, 2 10 0 0, 25 0, ) 40 0, 5 15 30 (2 0, 30 25 4 5) (21 20 l/s 15 (m 3 0( 54 /h) 0) 12 5 (4 50 ) 10 0 (3 60 ) 80 (2 90 ) 60 15 0,02 5 6m ) 3 /h (m 40) (5 0) l/s 45 ( 50 0) · 1 (36 V = 125 0) 0 (29 10 0, 4 1,6 2 m 60 0, = 1,2 80 0, 3 Square Array of Diffusers H 1 = 0,9 V· v- H1 in m/s 1,2 2 Distance L Diffuser arrangement: more than one row if B = 3.00 m H 1 = 0,9 v- H1 in m/s 0,10 ) 3 /h ( m 40) 0,6 v- L in m/s 30 0, 0,12 0,8 (2 60 20 0,16 l/s 0 15 25 0,20 12 0, 3m · = V 20 2 80 0, 1,5 10 15 A=1 tL tZ V· = l/s 15 (m 3 / 0( 54 h) 0) 12 5( 45 0) 10 0( 36 0) 80 (29 0) 0, Temperature Quotient 60 v- H1 in m/s 21 Temperature quotient t L / t Z 19 0,8 1 1,5 2 Spacing A 3 4 5 6m 0,8 1 1,5 2 3 Spacing A or B 11 Aerodynamic Data FD 600 and FD 625 Example Data given: 4 off type FD-Q-Z-H/600 Volume flow per diffuser Spacing between two diffusers Distance between ceiling and occupied zone V· = 100 l/s A = B = 2.00 m H 1 = 1.60 m Required: air velocity in occupied zone Diagram 26: Square array of diffusers v- H1 = 0.22 m/s Correction! For an installation below the ceiling line, the values v- H1, v- L and t L / t Z must be multiplied by a factor of 0.71! 23 Diffuser arrangement: single or more than one row if B 4.00 m H 1 = 0,9 1,2 25 1,6 2 m Temperature Quotient A=1 1,5 2 3m 0,20 V· = l/s 20 (m 3/ 0( 72 h) 0) tL tZ 0,16 30 25 0, 20 0, 0) 0 0,3 0 0,04 0, 10 0,03 0,8 1 1,5 2 3 4 0 0,1 5 6m 5 0,8 1 1,5 Spacing A 26 5 6m 0 40 0, 5 15 0, 15 0, 0, 10 20 0, 25 0, 0, (2 90 ) 30 20 4 1,6 2 m 0, 25 0, 1,2 80 0, l/s 15 (m 3 0( 54 /h) 0) 12 5 (4 50 ) 10 0( 36 0) 80 0, 0,02 5 6m 0 10 30 = 4 ) 3 /h ( m 30) (6 0) l/s 5 (54 0) 7 · 1 0 (45 V = 15 0) 5 (36 ) 12 0 (29 V· 3 Square Array of Diffusers H 1 = 0,9 1,6 2 m v- H1 in m/s 1,2 2 Distance L Diffuser arrangement: more than one row if B = 3.00 m H 1 = 0,9 v- H1 in m/s 0,05 5 0,2 0,2 24 0,06 90 (29 0,4 0,08 (2 15 0) 0 36 80 0 0 0,5 80 0( 0, 0,6 0) 0,10 12 45 10 v- L in m/s 0, 0) 5( ) 3 /h ( m 0) 3 (6 0) 4 l/s 5 (5 0) 5 17 (4 0) 0 6 (3 15 5 ) 54 12 0 10 v- H1 in m/s 0,8 · = V 0( 0,8 1 1,5 2 Spacing A 12 3 4 5 6m 0,8 1 1,5 2 Spacing A or B 3 Temperature quotient t L / t Z 0,12 15 Order Details Order Code These codes do not need to be completed for standard products FD - Q - Z - V - M - L Square Circular Q R IE OEP Supply Extract Z A IE OEP Top entry plenum Side entry plenum V H IE OEP Volume control damper with single blade / 400 300 400 500 600 625 Size / 0 / 0 / Volume control damper with MN cable and measuring nipple / RAL 9016 Not used State colour L Spigot with lip seal M P1 IEE EEE EO EEE EEE P TE EE EE EE EZE EE EE EE U 0 Standard finished powder coated to RAL 9010 (GE 50 %) 1) P1 Powder coated to RAL 9006 (GE 30 %) 1) other colours to RAL . . . (GE 70 %) 1) Specification Text Fixed swirl diffusers in square and circular construction for swirling, horizontal air discharge with high induction, for air change rates up to 30 per hour, comprising the diffuser face with radially arranged air control blades, top or side entry spigot, on request with spigot lip seal and/or volume control damper. On request, to measure the reference pressure, the spigot is fitted with a cable-adjusted volume control damper and measuring nipple. The plenum with circular side entry spigot can be fitted to various TROX diffusers; however, variation in performance must be taken into account. Design changes reserved · All rights reserved © TROX GmbH (8/2008) 1) GE = gloss level Materials: Diffuser face is in galvanised sheet steel. The surfaces are pre-treated and powder coated white (RAL 9010). The plenum box is also of galvanised sheet steel, the lip seal of black rubber. Order Example Make: TROX Type: FD - Q - Z - V - M / 400 / P1 / RAL 9016 13