2010 International Conference on Power System Technology Thyristor Valve for the 12-Pulse Converter for the 3 Gorges - Shanghai II HVDC Transmission Scheme M.H. Jodeyri IET Member, J.Z. Cao IET Member, C. Zhou & G. Tang Abstract — This paper presents the design of the thyristor valve for the 3 Gorges-Shanghai II 3000MW, ±500kV HVDC scheme. The thyristor valves are based on AREVA’s H400 series valve design using 7.2kV 5” electrically-triggered thyristor technology and the scheme is the first application of the valve design for such a voltage level. Details of the valve configuration, the cooling circuit, as well as the protective strategy are presented. Detailed electrical ratings such as the steady-state and temporary overload capabilities, the fault current capability, the valve losses, as well as the valve capabilities to cope with the fault scenarios such as the loss of AC voltage are described. The thyristor valve design satisfies the requirements of the scheme. when the De-icer installation is not being used as a De-icer, it operates as a Static VAr Compensator (SVC), using the HVDC valves as a Thyristor Controlled Reactor (TCR). However during the ice storm season, the valves can be reconfigured into two parallel-connected rectifier bridges to melt the ice on the high voltage transmission lines, by passing a high DC current through them [3]. Another application of the H400 technology was the Sino-Russia back-to-back (BtB) project. This scheme is rated at 750MW DC power with a rated DC voltage of ±125kV and a rated direct current of 3000A [4]. In these schemes 5” 8.5kV electrically-trigged thyristors were used. KEYWORDS — HVDC, ±500kV, Transmission, Thyristor, Converter I. INTRODUCTION H igh Voltage DC transmission (HVDC) technology has been increasingly used for transferring bulk electricity over long distances to minimize the conduction losses of the transmission lines or connecting electricity networks of different frequencies. Additional advantages with the HVDC technology include the capability to isolate two network grids of high power capacities under fault conditions [1]. 978-1-4244-5939-1/10/$26.00©2010 IEEE Ldc 12 Pulse Converter R neutral line 510kV AC BUS The H400 technology is a relative new generation of electrically triggered thyristor valve developed by AREVA especially for HVDC applications. The first application of the technology was the Konti-Skan HVDC pole 1 replacement project between Sweden and Demark [2]. The H400 technology was then successfully applied to the Deicer project in Québec, Canada [3]. In a normal situation +500 kV / 3000A Pole 535kV AC BUS The 3 Gorges-Shanghai II ±500kV HVDC refurbishment project is one of the HVDC projects scheduled by the State Grid Corporation of China (SGCC) to reinforce the electricity grid in the Shanghai region. The 3 Gorges-Shanghai II ±500kV HVDC scheme consists of a 12 pulse bi-pole rectifier-inverter circuit installed at Jingmen and Fengjing stations respectively. The project started in 2009 and the commissioning date is scheduled for 2010. The converter valves for the scheme are based on the AREVA’s H400 thyristor valve technology and use 5” 7.2kV electrically - trigged thyristors. AREVA is responsible for the design and supply of the main components of the thyristor valves as well as the support for assembly, site installation and commissioning of the valves. II. SCHEME PARAMETERS The converters for the 3 Gorges-Shanghai II ±500kV HVDC project are to be installed indoor in climatic controlled valve halls with slightly positive pressure. The altitudes of the sites are less than 1000m above sea level and the bulk air temperatures of the valve halls are controlled between +10°C and +50°C. The external ambient temperature for the Jingmen station ranges from -14°C to 40°C and that for the Fengjing station ranges from -10°C to 38°C. The peak ground acceleration of the sites is rated at 0.1g in the horizontal direction and the peak acceleration in the vertical direction is 65% of that in the horizontal direction. R electrode Ldc Jingmen Rectifier Station -500 kV / 3000A Pole Fengjing Inverter Station Fig. 1 The Single Line Diagram for the Proposed Main Circuit Configuration of the Scheme As shown by the single line circuit diagram given in Fig. 1, the complete transmission scheme comprises four 12pulse line commutated converters (LCC). The Jingmen station is normally operated in rectifier mode and the Fengjing station in inverter mode (henceforth referred as rectifier and inverter respectively). The middle points of the rectifier and inverter are firmly earthed. The scheme is rated at 3000MW power with a rated DC voltage of ±500kV and a rated direct current of 3000A. The converters at either end of the scheme are connected to the respective AC networks via twelve single phase two winding transformers. The normal operation voltage of the AC system for the Jingmen station ranges from 500kV to 550kV (1p.u. voltage = 535kV) and the AC voltage for the Fengjing station ranges from 490kV to 525kV (1p.u. voltage = 510kV). The nominal operating frequency for both systems is 50Hz. The AC systems maximum short circuit capacity at Jingmen station is 45466MVA and is 57288MVA at the Fengjing station. The maximum temporary overvoltage factor for the converter design for Jingmen station is specified at 1.35 and is 1.15 for the Fengjing station. Under normal steady-state operation, the firing angle for the rectifier ranges between 12° and 18°, with a nominal value of 15°. The extinction angle for the inverter ranges from 16° to 18° with a nominal value of 17°. For reactive power control purpose, the rectifier and inverter are further required to operate at firing and extinction angles respectively up to 24°. The maximum fault current for the converter is specified at 36kA, occurring when there is a short-circuit fault between valve terminals. As far as the voltage stresses are concerned, the valves at the Jingmen station are more severe than the valves at Fengjing station. The valve design reported in the following sections will be based on the valve design for the Jingmen station. TABLE I summaries the key parameters of the scheme for the Jingmen converter station. TABLE I. Main Scheme Parameters for the Jingmen Converter Station DC Bridge Current Nominal Maximum continuous 2 hour overload 3s overload Pole to Neutral DC Voltage Nominal Maximum continuous Minimum continuous Transformer Valve Winding Voltage Nominal Maximum continuous Minimum continuous Maximum Fault Current 3000A 3047A 3389A 4466A 500kV 515kV 489kV 210kVrms 220kVrms 199kVrms 36000A The Switching Impulse Protection Level (SIPL) for the valve surge arresters for the Jingmen station is rated at 496.3kV and the coordination current at SIPL is 2kA. The required Lightning Impulse Protection Level (LIPL) and fast-front Impulse Protection Level (FWPL) for the valve surge arresters are 492kV and 559kV respectively. The required safety margins for the insulation levels for the thyristor valves are 15% for the switching and lightning impulse voltages and 20% for the fast-front impulse voltage. Fig. 2 Schematic Diagram for the Double-Valve MVU Structure at Jingmen Station III. H400 THYRISTOR VALVE STRUCTURE As shown by the double-valve Multivalve Unit (MVU) structure in Fig. 2, the proposed thyristor valves for the 12pulse converters at Jingmen station are assembled in six double valves (of two valves each). Individual double valves are then suspended from the suspension beams of the valve hall via valve top suspension insulators. The active components of individual MVU structures are covered by the top and bottom stress shields as well as the module corona shields to minimize the local electrical field stresses due to the high voltage application. Each valve of a 12-pulse converter for the station consists of a total of 87 series connected thyristor levels including three redundant levels. The thyristor levels of a valve are distributed over eight modules of two valve sections each. There are six or five thyristor levels per valve section. Each thyristor level comprises a single thyristor, a gate electronics unit, and associated damping and DC grading circuits. The damping and DC grading components are used for proper internal distribution of valve voltage from DC to impulse wavefronts as well as the transient voltage at recovery. The gate electronics unit provides electrical gating of the thyristor under normal and abnormal operating conditions. It provides normal triggering in response to control action and protective triggering in response to overvoltage, high dv/dt and forward recovery. Six or five thyristor levels of each valve section share a common di/dt limiting reactor to limit the rate of change of the thyristor current at turn-ON and the valve voltage at thyristor turn-OFF. See Fig. 3 for valve module mechanical structure and Fig. 4 for the simplified electrical circuit of a valve section consisting of 6 thyristor levels. di/dt Reactor Damping Capacitors Damping Resistors di/dt reactors. The coolant is routed to and returned from the top of each MVU via stainless steel (AISI 316) pipes. The coolant is then distributed between each valve sections by larger (75mm) diameter manifold pipes. The heatdissipating elements in each valve section are routed hydraulically in series as shown in Fig. 6. The three separate paths of each section are then connected in parallel to the manifold pipes. The communications between Valve Base Electronics (VBE) and each thyristor level are carried out using two optical fibres, one ‘firing’ fibre which carries the ‘startstop’ pulses and one ‘data-back’ fibre which feeds information on the status of each thyristor level such as thyristor healthy or failed back to the VBE. Gate Electronics Thyristor Clamped Assembly Fig. 3 A Valve Module Housing 2 Electrical Valve Sections Fig. 4 Basic Electrical Circuit of a Valve Section of 6 Thyristor Levels The thyristors within a valve section are held together between high-efficiency liquid cooled heatsinks as one 'clamped assembly'. Glass Reinforced Plastic (GRP) tension bands are used to tightly secure the assembly and to provide the high clamping load necessary for good electrical and thermal contacts between thyristors and heatsinks. The clamping system facilitates replacement of a thyristor without opening any power or coolant connections. The photograph in Fig. 5 illustrates a six thyristor clamped assembly for the project. GRP clamping straps Thyristor Heatsink with coolant connection Power connection Fig. 5 Clamped Assembly for 6 Active Thyristor Levels A coolant of de-ionized pure water is used to cool the thyristors, the damping and DC grading resistors, and the Fig. 6 Series Cooling Arrangement for Elements Inside a Valve Sections The auxiliary power for the gating electronics unit at each level is derived locally from the voltage across the thyristor during the OFF-state intervals. The power supply contains a storage capacitor with sufficient capacity to maintain full control of the valve for more than 1 second with no voltage appearing between valve terminals. Due to the increased operating voltage of the scheme, a large number of series connected thyristors and consequently a large valve size must be used. As the valve size increases, the voltage distribution between different levels of the series connected components will be more severely distorted by the associated stray capacitance. This is particularly true for the fast-front impulse voltage because of its higher dv/dt. The stray capacitances for a valve structure include those between valve modules and earth, between modules in the same vertical position and those between modules belonging to the same tier. Additionally, the stray capacitances between top and bottom stress shields and earth must be accounted for in voltage distribution studies. The study for the project reveals that the influence of the stray capacitance on voltage distribution is negligible if a 3nF valve section capacitance is connected in parallel with the combined thyristor and reactor branch as shown in Fig. 4. This gives the best compromise between the cost for the valve section capacitance and the voltage distribution between valve suspension insulators. The equivalent value of the stray capacitance Cs for each double-valve is equal to 94pF which is calculated as follows: Cs = Css Dv × N s × N m Where: Css = 3nF, Section stray capacitance Ns = 2, Number of sections per module Nm = 8, Number of modules per valve Dv = 2, Number of valves in a double-valve Therefore: Cs = 3 × 10 −9 = 94 pF 2× 2×8 IV. VALVE RATING The thyristor valves for HVDC application are typically designed for a lifetime of up to 40 years with minimum maintenance requirements of every few years. The thyristor valves need to withstand not only the thermal and voltage stresses under various continuous and temporary operations, but also those voltage and thermal stresses as the results of the switching, lightning, and steep front impulse voltages caused externally and internally, as well as the stresses resulting from a fault either due to disturbances originating from the AC and DC systems or due to a major insulation failure within the converter. Additionally, the valves are optimized for minimum losses at specified operating conditions and to remain operational even when the system voltage is at its minimum or when it is temporarily lost. This section discusses the most important aspects of the valve design, in connection with its reliable operation for the 3 Gorges-Shanghai II HVDC project. A. Thermal Rating The thyristor valves for this project are required to withstand the worst case thermal and voltage stresses due to the short-circuit fault in conjunction with the most unfavourable temporary overvoltage conditions. The maximum amplitude of the single and three loop fault currents for the thyristor valves for this project is estimated at 36kApk, occurring at a minimum firing angle of 5°. The associated AC system temporary overvoltage factor for fault current study was assumed at 8%. The initial thyristor junction temperature prior to the fault is defined by the 2hour overload followed by the 3 second overload. The most unfavourable cooling condition is defined at the maximum external ambient temperature in coordination with the minimum cooling flow and the maximum thyristor losses. As far as the two operating modes (rectifier and inverter) of the converter are concerned, the smaller firing angle in rectifier mode means that the fault current amplitude in rectifier mode is significantly greater than in inverter mode. The rectifier mode is therefore used to rate the fault current capability of the valve design. To allow for sufficient margins for the thyristor valves to survive the fault current conditions, the worst-case thyristor junction temperature due to the combined events of the 2-hour overload followed by the 3 second overload scenarios is limited to 90°C. The predicted thyristor junction temperatures for the proposed valves under various operating conditions are tabulated in TABLE II. The worst-case thyristor junction temperature due to the 2 hour overload followed by 3 second overload is 81.3°C, less than the 90°C limit. Due to the heat capacities of the thyristors and associated heatsinks, the thyristor junction temperature does not reach thermal equilibrium at the end of the 3 second duration. TABLE II. Thyristor Junction Temperature at Different DC Bridge Currents Condition 1) Nominal 2) Max. Continuous 3) 2h Overload 4) 3s Overload IDC, A Tj, °C 3000 3047 3389 4466 71.0 71.6 75.5 81.3 Fig. 7 and Fig. 8 illustrate the detailed simulation waveforms by using PSCAD software for the single and three loop fault currents. Uthy, Ithy, and Tj in the plots are respectively the voltage, current, and junction temperature for the worst-case thyristor assumed. The single loop fault current is assumed such that the further fault current loops are prevented by successfully blocking the healthy thyristor valves of the converter. The most critical requirement for the valve thyristors in such a scenario is that the reapplied AC voltages in the forward direction of individual thyristor levels must be less than the non repetitive forward voltage withstands capabilities of the thyristors. However, the three loop fault current occurs only when the healthy valves in the same converter fail to block the reapplied AC voltages and the system is tripped by opening the main circuit breakers. In such a scenario, only the AC voltages reapplied in the reverse direction of individual thyristor levels matter. For comparison purpose, the plots also give the rated thyristor forward/reverse voltage withstand capacities (Udsm and Ursm), specified as functions of thyristor junction temperature. The simulation results indicate that in both events, the actual voltage experienced by the worst-case thyristor remains well within the voltage blocking capabilities of the thyristor. The margins are large and thus no thyristor is at risk. The highest thyristor temperatures due to both the single and three loop fault currents are well within the withstand capabilities of the thyristors. The minimum duration from current zero to positive-going voltage zero- 40 180 35 160 30 140 25 120 20 100 15 80 10 60 Ithy 40 Tj 0 20 -5 0 0 5 10 15 20 25 30 35 40 Time (ms) (a) 8 Thyristor Voltage, Uthy & Udsm (kV) 7 6 5 4 2.2 2.0 1.8 1.6 1pu DC current =3000A Cont. overload without redundant coolers 1.4 Cont. overload with redundant coolers Temp. overload without redundant coolers 1.2 3 2 Temp. overload with redundant coolers 1.0 1 -15 0 -1 -10 -5 0 5 10 15 20 25 Ambient Air Temperature (deg C) 30 35 40 Fig. 9 Converter Over-Current Capabilities at Different Ambient Temperatures -2 -3 Udsm -4 Uthy -5 0 5 10 15 (b) 20 Time (ms) 25 30 35 40 Fig. 7 Simulation Waveforms for Single Loop Fault Current Condition (a) Thyristor Current and Temperature, (b) Thyristor Voltage Blocking Capability and Reapplied Thyristor Voltage in the Forward Direction 300 35 250 30 25 200 20 15 150 10 100 5 0 50 Ithy -5 Thyristor Junction Temperature, Tj (°C) 40 Thyristor Current, Ithy (kA) B. Overload Capability For reduced external ambient temperatures, the thyristor valves are allowed to operate at higher DC bridge current without compromising the thermal limits of the valve design. As shown by the 2 hour and 3 second over-current capabilities in Fig. 9, the maximum DC bridge current can be as high as 1.79p.u. for the 2 hour overload operation and 2.07p.u. for the 3 second overload operation, both derived by assuming the maximum continuous transformer valve winding voltage. DC bridge Current, PU 5 Thyristor Junction Temperature, Tj (°C) Thyristor Current, Ithy (kA) crossing is more than the required turn-OFF time for the thyristor at the relevant junction temperature. Tj -10 0.03 0 0.04 0.05 0.06 0.07 Time (ms) 0.08 0.09 0.1 (a) In order for the thyristor valves to operate in the optimized range of junction temperature, the coolant temperature at the inlet of the valve stacks must be maintained above a minimum limit. For the 3 GorgesShanghai II HVDC project, the minimum coolant temperature at the valve inlets is limited to 20°C. The maximum converter overload capabilities therefore do not change with the decreased external ambient temperature as soon as the coolant inlet temperature reaches the minimum. C. Valve Losses Although the efficiency of a typical thyristor converter could be as high as 99.5%, the absolute power losses consumed by the converter are still significant and majority of the utility operators generally apply a heavy capitalization factor for the losses. Thyristor Voltage, Uthy (kV) & Ursm (kV) 4 2 0 -2 -4 -6 -8 Uthy Ursm -10 0.03 0.04 0.05 0.06 0.07 Time (ms) (b) 0.08 0.09 0.1 Fig. 8 Simulation Waveforms for Three Loop Fault Current Condition (a) Thyristor Current and Temperature, (b) Thyristor Voltage Blocking Capability and Reapplied Thyristor Voltage in the Reverse Direction The capitalization factor applied by the utility operators is typically around $4800 per kW of the power consumed. Among the total losses of a converter, the majority of them are dissipated by the high voltage power thyristors due to the ON-state voltage drop and the stored charge at turnOFF. The other types of losses include those in the damping and DC grading circuits, the busbar connections as well as those in the di/dt limiting reactors. The valve losses were calculated in accordance with the methods recommended in [5]. The valve loss calculations were based on the nominal system operation but with different levels of DC bridge current. The valves were assumed to have the maximum number of thyristor levels and operate at the specified minimum coolant flow rate with a maximum coolant inlet temperature of 43°C. TABLE III 253.7kW × 12 = 3044.5kW Considering that the total DC transmission power per 12-pulse converter at 1p.u. operation is 1500MW, the efficiency for the proposed 12-pulse converter is: pulse converter in rectifier mode was estimated at 378.5kV while the PCAV in inverter mode is less than in rectifier mode. 200 100 Valve Voltage, Uv (kV) reports the evaluated losses dissipated in an individual thyristor valve of a 12-pulse converter at Jingmen station. Taking the case for 1p.u. DC bridge current for example, the total losses in an individual thyristor valve at 1p.u. current are 253.7kW. The total losses for a 12-pulse converter at 1p.u. operation are therefore: 0 -100 -200 -300 PCAV 1 – (3044.5kW / 1500000kW) = 99.8% -400 0 TABLE III. Per Valve Losses at Different DC Bridge Currents PV1: Thyristor conduction loss PV2: Thyristor spreading loss PV3: Other conduction losses PV4: DC voltagedependent loss PV5: Low-frequency damping loss PV6: High-frequency damping loss PV7: Turn-off losses PV8: Reactor loss PVT: Total valve losses No-load dc Loss No-load Damping Loss PVSB: Total No-load Losses Per valve losses at different DC bridge current in p.u. (kW) 0.25 0.5 0.75 1.0 8 Time (ms) 12 16 (a) 400 1.1 61.17 100.4 145.2 164.6 1.98 2.89 3.58 3.71 3.71 0.72 2.84 6.29 11.05 13.31 7.85 7.65 7.43 7.20 7.11 3.02 2.98 2.92 2.86 2.84 19.9 26.82 33.47 39.80 42.25 -100 15.2 4.54 80.8 22.68 4.54 131.6 30.63 4.54 189.3 3.408 1.523 39.34 4.54 253.7 43.06 4.54 281.4 -200 4.931 D. PCAV As with any other switching device, voltage overshoot exists at thyristor turn-OFF. The voltage overshoot at turnOFF is a phenomenon in association with the leakage inductance of the converter transformers, the di/dt limiting reactors and stray capacitance of the converter valves, as well as the stored charge of the valve thyristors. The scale of voltage overshoot for the HVDC converter is quantified using the Peak of the Continuous Applied Voltage (PCAV). The amplitude of PCAV is generally controlled by adding the damping circuits to individual thyristor levels. The reduced level of PCAV will be beneficial to minimize the number of series connected thyristor levels as well as the voltage and energy requirements for the associated valve surge arresters [6], [7]. As shown by the simulation waveforms in Fig. 10, the worst-case PCAV for the 12-pulse converter in rectifier mode occurs when the valve winding voltage, the rectifier firing angle, and the DC bridge current are at their continuous maxima whereas the valve transformer impedance is at the minimum. The worst-case PCAV for the converter in inverter mode occurs when the extinction angle is at maximum. The maximum PCAV for the 12- PCAV 300 27.6 Valve Voltage Uv (kV) IEC Reference 4 200 100 0 -1 1 3 Time (ms) 5 7 (b) Fig. 10 Valve Voltage Waveforms for Maximum PCAVs in (a) Rectifier Mode and (b) Inverter Mode E. Redundancy and Failure Rate As described in Section III above, the maximum number of series connected thyristor levels per valve is 87 including 3 redundant levels. The total number of thyristor levels for a 12 pulse converter is 12 x 87 = 1044. According to AREVA’s operational data from previous projects, the annual failure rate for each thyristor level including the damping circuit, the DC grading resistor and the gate electronics unit is approximately 0.283%. Therefore, the predicted number of failed thyristor levels for a 12 pulse converter for a 12 month operation is: 0.283% × 1044 = 2.96 A reliability study has shown that within any one valve, there should be no more than 3 redundant thyristor levels failure during any 12 month period of operation. For the same operating period, the number of valves with failed thyristor levels is no more than two. F. Minimum Continuous and No-Voltage Operations The H400 gate electronics unit requires a minimum voltage of approximate 1kVrms per thyristor level for continuous firing. With an assumed voltage sharing factor of 1.05, the minimum valve winding voltage for continuous operation of the converter with a maximum of 87 thyristor levels per valve is: 1kV × 1.05 × 87 levels = 91.35kVrms This is less than the minimum continuous valve winding voltage specified in TABLE I. In addition, the gate electronics power supply for the H400 valve design contains a storage capacitor with sufficient capacity to maintain full control of the valve for more than 1 second with no voltage appearing between the valve terminals. No recovery time is required if a fault lasts less than this, which is more than the 0.7 second duration specified by the client for either a single phase-to-ground fault or a 30% under-voltage operation. This is also more than the 0.2 second duration specified for a three phase-to ground fault. G. Temporary Operation at α=90° Operating at a high firing angle will result in greater heat losses in the valve thyristors and relevant damping resistors, which requires an increased cooling capacity to bring the element temperatures within limits. It is a compromise between the requirement for a high firing angle operation and the cost of the cooling system, components for the H400 series valve design have been rated to allow for maximum operation at α equal to 90° for up to 50 seconds and at 30% of the nominal DC current (3000A). However, taking account that the type test duration for maximum temporary operation is generally twice the permitted duration in operation, the acceptable duration for temporary operation at α equal to 90° shall be limited to 25 seconds. V. CONCLUSIONS Design of the electrically-triggered thyristor valves for the 3 Gorges-Shanghai II HVDC project satisfies the requirements of the scheme. The valve design uses thyristors of high voltage and high current capabilities that is a compromise between the scheme’s low cost and high efficiency requirements. Use of an efficient cooling system allows the thyristor valves to operate at their maximum ambient temperature in conjunction with the worst-case operating conditions. The valve assembly uses a doublevalve structure and will be suspended from the roof of the valve hall to ensure improved earthquake withstanding capability. In addition to the valve surge arresters, individual thyristor levels are safe-guarded by the gate electronics units. The high storage circuits for the gate electronics units at individual thyristor levels allow the valves to operate with no voltage between valve terminals for more than 1 second, which is longer than the requirement of the scheme. ACKNOWLEDGMENT The authors wish to express gratitude to SGCC and AREVA T&D for permitting the publication of this paper. REFERENCES [1] [2] [3] [4] [5] [6] [7] Willis Long and S. Nilsson, “HVDC transmission yesterday and today”, IEEE Power and Energy Magazine, pp 22-31, March/April 2007. P. L. Sorensen, B. Franzén, J. D. Wheeler, R. E. Bonchang, C. D. Barker, R. M. Preedy, and M. H. Baker, “Konti-Skan 1 HVDC pole replacement”, CIGRÉ Session, B4-207, 2004. M. Granger, A. Dutil, A. Dery, C. Horwill, and C. Davidson, “Using power electronics at Hydro-Québec to secure strategic lines during ice storms”, CIGRE, B4-101, 2006. J. Z. Cao, D. A. Jackson, J. Zhang, J. L. Wen, M. Y. Wang, “Thyristor valve for the 12-pulse converter for Sino-Russia BtB scheme”, Asia-Pacific Power and Energy Engineering Conference, APPEEC 2009, Vol. 4, pp 3369-3375, 978-1-4244-2487-0/09/$25.00 ©2009 IEEE. IEC Standard 61803, “Determination of power losses in high-voltage direct-current (HVDC) converter stations”, 1999. M. L. Woodhouse, J. P. Ballad, J. L. Haddock, and B. A. Rowe, “The control and protection of thyristors in the English terminal cross channel valves, particularly during forward recovery”, IEE Internat. Conf. TAVSET, pp158-163, 1981. J. D. Wheeler, C. C. Davidson, J. D. G. Williams, and A. K. Roy, "Design aspects of the Chandrapur 2 x 500MW Back-to-Back HVDC Scheme", CIGRÉ Session, pp14-104, 1996. BIOGRAPHIES Mohammad Hassan Jodeyri received his M.Phil. in 1994 from Swansea University, UK. He received his Ph.D. in Power Electronics in 2007 from the Staffordshire University, UK. Dr. Jodeyri joined AREVA T&D in 2007 and is working for PES with HVDC valve design department. He is a Member of the IET. His special fields of interest include power electronics, energy savings for refrigeration and Airconditioning applications, HVDC and FACTS. Junzheng Cao received his M.Sc. in 1985 from Xi’an Jiaotong University in China. He received his Ph.D. in Electrical Eng. in 1997 from the South Bank University, UK. Dr. Cao currently works as a principal engineer and HVDC expert for PES, AREVA T&D. He is a member of the IEC working group. His special fields of interest include power electronics, electromagnetics, HVDC and FACTS. Changchun Zhou received his PhD in 2004 from HVDC & FACTS Group of Zhejiang University, China. He joined AREVA T&D in 2008 and is working with HVDC Engineering in AREVA T&D (China). Dr Zhou previous work was in the area of HVDC & FACTS system study plus Wide Area control & stability. Guangfu Tang received his M.Sc. and PhD in Electrical Engineering from the Institute of Plasma Physics, Chinese Academy of Sciences (ASIPP) in 1993 and 1996 respectively. Dr. Tang currently is a vice-chief engineer of CEPRI and in charge of the HVDC engineering research institute of CEPRI. He is a member of Cigre and power electronics society of China. His major research field is application of electric power system of high power electronic technology including SVC, TCSC, STATCOM and HVDC.