Catalog HG 11.42 · 2008 Siemens Vacuum Recloser 3AD Medium-Voltage Equipment Selection and Ordering Data www.siemens.com/energy R-HG11-172.tif Siemens Vacuum Recloser 3AD 2 Siemens HG 11.42 · 2008 Siemens Vacuum Recloser 3AD Siemens Vacuum Recloser 3AD Medium-Voltage Equipment Catalog HG 11.42 · 2008 Contents Contents Page Description 5 General 6 Switch unit 7 Controller, protection functions 9 Ambient conditions, altitude correction factor and number of operating cycles 13 Product range overview and scope of delivery 14 Product Selection 1 15 Ordering data and configuration example 16 Selection of primary ratings 17 Selection of controller 20 Selection of additional equipment 24 Technical Data 2 27 3 Electrical data, dimensions and weights: Voltage level 12 kV 28 Voltage level 15.5 kV 28 Voltage level 27 kV 29 Voltage level 38 kV 29 Annex 33 Inquiry form 34 Configuration instructions 35 4 Configuration aid Foldout page © Siemens AG 2008 Siemens HG 11.42 · 2008 3 R-HG11-300.tif Siemens Vacuum Recloser 3AD 4 Siemens HG 11.42 · 2008 Siemens Vacuum Recloser 3AD Description Contents Contents Page Description 5 General 6 1 Switch unit: Recloser principle 7 Design 7 Pole assemblies 7 Operating mechanism 7 Magnetic actuator 7 Mechanical lockout 8 Recloser cycle 8 R-HG11-301.tif Controller: Vacuum recloser with cubicle and controller User interface 9 Protection functions 10 Communications 11 Protocols 11 Metering functions 11 Data records 11 Software 12 Standards 12 Ambient conditions 13 Altitude correction factor 13 Number of operating cycles 13 Product range overview 14 Scope of delivery 14 Siemens HG 11.42 · 2008 5 Siemens Vacuum Recloser 3AD Description General Siemens vacuum recloser 3AD Switch unit Controller inside the cubicle R-HG11-303.tif The recloser consists of two main components: The switch unit being the circuit-breaker and the controller as protection and control unit. It is housed inside the control cubicle. R-HG11-302.tif 1 3AD vacuum reclosers are outdoor circuit-breakers designed for frequent opening and reclosing in case of temporary faults. They fulfill this task automatically by monitoring the line and operating autonomously. The switch unit is the primary part of the recloser. It is located on top of the pole to switch the overhead line. It is permanently exposed to weather and environment. 6 Siemens HG 11.42 · 2008 As the heart of the recloser, the controller is located in a cubicle at the bottom of the pole. Siemens Vacuum Recloser 3AD Description Switch unit Recloser principle Reclosers are used in distribution systems of power supply companies (utilities). Like circuit-breakers they are capable of switching normal and fault currents. They are equipped with sensors and a controller being the protection and control device. In case of a line fault, they can break and make several times, thus avoiding longer network interruptions due to temporary faults. 1 R-HG11-304.tif As outdoor devices they are normally pole-mounted and exposed to environment and weather. A recloser consists of two components: The switch unit (circuit-breaker) and the controller (inside the control cubicle), both connected through a control cable. Design Switching operation The vacuum switching technology, proven and fully developed for more than 30 years, is the basis for the vacuum interrupters. Switch unit – front view Pole assemblies Each vacuum interrupter is embedded in an epoxy-resin pole made out of weather-proof cycloalyphatic resin. This enables a small design as well as resistance against environmental effects. The vacuum interrupter is vertically mounted inside the pole, providing a long service life. Each recloser is equipped with an integrated current transformer. For special protection purposes, a resistive voltage sensor can also be incorporated in the pole. The accuracy achieved in this way is much higher than that of capacitive dividers. The pole assemblies of the recloser are directly mounted on the operating mechanism housing. Besides the complete kinematics, it also accommodates the position indicator and a mechanical operations counter. The operating mechanism housing is made of mild steel with a special coating for outdoor applications. Optionally, a stainless-steel housing is available. R-HG11-305.tif Operating mechanism Switch unit – rear view The recloser is installed on the pole by means of a pole mounting frame. Alternatively, the recloser can be mounted directly on a frame for pad-mounting in substations. Magnetic actuator HG11-2728 eps The recloser is operated by a magnetic actuator enabling the recloser cycle, i.e. the high number of switching operations within a short period of time. The actuator is a bi-stable system, locked in the end positions by permanent magnets. If not in operation, the magnet coils do not consume any power. The operating force is transmitted to all three poles through a mechanical coupling. Structure of the switch unit Siemens HG 11.42 · 2008 7 Siemens Vacuum Recloser 3AD Description Switch unit Mechanical lockout A mechanical lockout enables tripping independently on the controller. If this handle is pulled, the recloser opens and is simultaneously locked out electrically and mechanically. The handle stays extended, thus indicating the interlocked state. 1 To close the recloser again, the operating rod must first be pushed back to the operation position in order to release the lockout. Then the recloser can be closed electrically via the control. Recloser cycle In case of a network fault, the recloser opens and recloses several times. In case of temporary faults the automatic reclosing significantly reduces the loss of power supply. The recloser cycle is optimized accordingly: R-HG11-306.tif • The first interruption of a fault is done quickly and instantaneously, so that even the fuses in the system do not operate. After approx. 300 ms (user settable), it recloses back on. Lock-out handle – pushed in (operational position) • The second and third interruption has a definite or inversetime delay. Thus, downstream fuses in the network have the chance to operate and isolate the affected network section, restoring normal operation in the remaining network. The following dead time is usually 2–10 s (user settable). • The fourth (optional up to the fifth) interruption is fast again and serves as a check. This for example utilizes the physical effect that, when the short-circuit occurs, the lines move due to the magnetic forces of the current, and foreign objects are “shaken off”. R-HG11-307.tif • If the fault still exists, the recloser turns to the lockout and can only be closed from the operator panel or via SCADA. Lock-out handle – pulled (open position) 8 Siemens HG 11.42 · 2008 Siemens Vacuum Recloser 3AD Description Controller The controller The Siemens Argus-M controller is based on the Argus-M directional overcurrent protection relay. These relays provide protection, control, monitoring, instrumentation and metering with integrated input and output logic, data logging & fault reports. 1 The controller is mounted in the control cubicle. Along with the controller, this cubicle also contains the auxiliary power supply with batteries for uninterruptible power supply, electronic boards, fuses, and a general-purpose outlet to power a laptop. R-HG11-308.tif Communication access to relay functionality is via a front USB port for local PC connection or a rear electrical RS485 port for remote connection. Additional rear port options are available. Argus-M controller The controller contains a large number of protection functions (elements) which can be selected or deselected through the menu driven display. These elements can be customized to the utilities’ needs by parameters (settings) as described below. User interface • 20-character x 4-line backlit LCD • Menu navigation keys • 3 fixed LEDs • 8 or 16 programmable tri-color LEDs are available eliminating the need for expensive panel-mounted pilot lights and associated wiring. Each LED is tri-colored (red, green, yellow) allowing for clear indication of the associated function’s state. • Each function key has an associated tri-color LED (red, green, yellow) allowing for clear indication of the associated function’s state. R-HG11-309.tif • 12 programmable function keys each with tri-color LED are available for implementing scheme control functionality. Tri-color LEDs and pushbuttons of the controller Siemens HG 11.42 · 2008 9 Siemens Vacuum Recloser 3AD Description Controller Protection functions (in order of ANSI numbering) 37 Undercurrent 1 Each element has settings for pickup level and Definite Time Lag (DTL) delays. Operates if current falls below setting for duration of delay. 46BC Broken conductor/phase unbalance Element has settings for pickup level and DTL delay. With the circuit-breaker closed, if one or two of the line currents fall below setting, this could be due to a broken conductor. 46NPS Negative phase-sequence overcurrent Each element has user settings for pickup level and Inverse Definite Minimum Time Lag (IDMTL) or DTL delay. It operates if NPS current exceeds setting and delay. NPS current elements can be used to detect unbalances on the system or remote earth faults when a delta-star transformer is in circuit. 49 Thermal overload The thermal algorithm calculates the thermal states from the measured currents and can be applied to lines, cables and transformers. Outputs are available for thermal overload and thermal capacity. 50/51 Phase fault 50 INST (instantaneous)/DTL (Definite Time Lag) and 51 IDMTL (Inverse Definite Minimum Time Lag)/DTL elements provide overcurrent protection, each with independent settings for pickup current, time-multiplier (51) and time delays. The user can select IEC or ANSI time current characteristics. The IDMT stage has a user programmable reset characteristic, either DTL or shaped current/time reset characteristic to improve grading with electromechanical protection. 50G/51G/50N/51N Earth fault/sensitive earth fault Earth-fault current is derived from the residual connection of the 3 integrated line CTs. 50 INST/DTL and 51 IDMTL/DTL elements provide overcurrent protection, each with independent settings for pickup current, time-multiplier (51) and time delays. The user can select IEC or ANSI time current characteristics. The IDMT stage has a user programmable reset characteristic, either DTL or shaped current/time reset characteristic to improve grading with electromechanical protection. 50BF Circuit-breaker fail The circuit-breaker fail function is triggered from an internal trip signal. Line currents are monitored following a trip signal and an output is issued if any current is still detected after a specified time interval. This can be used to re-trip the CB or to back-trip an upstream CB. A second back-trip time delay is available to enable another stage to be utilized if required. 10 Siemens HG 11.42 · 2008 64H Restricted earth-fault scheme The measured earth-fault input may be used in a 64H high impedance restricted earth-fault scheme. Required external series stabilizing resistor and non-linear shunt resistor can be supplied. 74TC Trip-circuit supervision The trip-circuit(s) can be monitored via binary inputs. Tripcircuit failure raises an HMI alarm and output(s). 81HBL2 Inrush restrain/second harmonic block Where second harmonic current is detected (i.e. during transformer energization) user selectable elements can be blocked. Cold load pickup If a circuit-breaker is closed onto a “cold” load, i.e. one that has not been powered for a prolonged period, this can impose a higher than normal load-current demand on the system which could exceed normal settings. These conditions can exist for an extended period and must not be interpreted as a fault. To allow optimum setting levels to be applied for normal operation, the cold load pickup feature will apply alternative settings for a limited period. The feature resets when either the circuit-breaker has been closed for a settable period, or if the current has been reduced beneath a set level for a user set period. 27/59 Under/overvoltage Each element has settings for pickup level, drop-off level and Definite Time Lag (DTL) delays. It operates if voltage exceeds setting for duration of delay. It can be applied in load shedding schemes. 47 Negative phase-sequence overvoltage Each element has settings for pickup level and Definite Time Lag (DTL) delays. It operates if NPS voltage exceeds setting for duration of delay. 59N Neutral overvoltage Each element has settings for pickup level and Definite Time Lag (DTL) delays. It operates if neutral voltage exceeds setting for duration of delay. Neutral overvoltage can be used to detect earth faults in high impedance earthed or isolated systems. 60CTS CT supervision The CT supervision considers the presence of negative phase-sequence current, without an equivalent level of negative phase-sequence voltage, for a user set time as a CT failure. The element has user operate and delay settings. Siemens Vacuum Recloser 3AD Description Controller 67/67N Directional control Metering functions Phase-fault, earth-fault and sensitive earth-fault elements can be directionalized. Each element can be user set to forward, reverse, or non-directional. Directional phase-fault elements are polarized from quadrature voltage. Earth-fault elements can be user set to be polarized from residual voltage or negative phase-sequence voltage. • Primary current phases and earth 81 Under/overfrequency • Binary input/output status Each element has settings for pickup level, drop-off level and Definite Time Lag (DTL) delays. It operates if frequency exceeds setting for duration of delay. It is typically applied in load shedding schemes. • Trip circuit healthy/failure 79 Auto-reclose • Event records Each element provides independent phase-fault and earthfault/sensitive earth-fault sequences of up to 5 trips, i.e. 4 reclose attempts before lockout. Auto-reclose sequence can be user set to be initiated from internal protection operation or via binary input from an external protection. Each trip in the sequence can be user set to be either instantaneous (fast) or delayed. The user can set each reclose (dead) time and the reclaim time. • Frequency • Secondary current phases and earth • Positive phase-sequence (PPS) current 1 • Negative phase-sequence (NPS) current • Zero phase-sequence (ZPS) current • Time and date • Starters • Fault records • Waveform records • Circuit-breaker trip counters • I²t summation for contact wear • Direction • Primary line and phase voltages • Secondary voltages Battery and capacitor check (no number) Sag/swell detection Optional protection functionality • Sync check • Fault locator • Loop automation • Single-triple operation Communications • Front USB port • Rear RS485 port Optional functions • Rear fiber optic ports • IRIG-B ports • Apparent power and power factor • Real and reactive power • W Hr forward and reverse • VAr Hr forward and reverse • Historical demand record • Positive phase-sequence (PPS) voltage • Negative phase-sequence (NPS) voltage • Zero phase-sequence (ZPS) voltage Data records Sequence of event records Up to 5000 events can be stored. Fault records • RS232 ports The last 10 fault records are displayed on the HMI, with time and date of trip, measured quantities and type of fault. Protocols Disturbance recorder • IEC 60870-5-103 The waveform recorder stores analog data for all phases, the states of protection functions, binary inputs, LEDs and binary outputs with pre & post trigger data. A record can be triggered from protection function, binary input or via data communications. The waveform recorder stores up to 10 s data. • Modbus RTU • DNP 3.0 Load profile recording A rolling record of demand over the last 24 h is stored. The demand is averaged over a user selectable period of time. A rolling record of such demand averages is stored and provides the demand history. A typical application is to record 15 min-averages for the last 7 days. Siemens HG 11.42 · 2008 11 Siemens Vacuum Recloser 3AD Description Controller, standards Software Reydisp Evolution For communication with the relay via a PC (personal computer) a user-friendly software package, Reydisp Evolution, is available to allow transfer of relay settings, waveform records, event records, fault data records, instruments/meters and control functions. Reydisp Evolution is compatible with IEC 60870-5-103. 1 R-HG11-310.tif Programmable logic Typical Reydisp Evolution screenshot The user can map binary inputs and protection operated outputs to function inhibits, logic inputs, LEDs and/or binary outputs. The user can also enter up to 16 equations defining scheme logic using standard functions e.g. timers and/or gates, inverters and counters. Each protection element output can be used for alarm & indication and/or tripping. Waveform records analysis See figure left Quick logic The “Quick logic” feature allows the user to input up to 16 logic equations (E1 to E16) in text format. Equations can be entered using Reydisp or at the relay fascia. Each logic equation is built up from text representing control characters. Each can be up to 20 characters long. Standards The recloser conforms to the following standards • ANSI C37.60 (2003) • IEC 60255 • IEC 60694 (in future IEC 62271-1) 12 Siemens HG 11.42 · 2008 Siemens Vacuum Recloser 3AD Description Ambient conditions, altitude correction factor and number of operating cycles Ambient conditions The recloser is designed for the normal operating conditions defined in ANSI C37.60. This comprises an ambient temperature from –40 °C to +55 °C plus solar radiation. 55°C Altitude correction factor The dielectric strength of air insulation decreases with increasing altitude due to low air density. The rated lightning impulse withstand voltage values specified in the chapter “Technical Data” apply to a site altitude of 1000 m above sea level. For an altitude above 1000 m, the insulation level must be corrected according to the opposite drawing. 1 max. 95% per day max. 90% per month HG11-2515a_en eps -40°C The characteristic shown applies to the rated short-duration power-frequency withstand voltage and the rated lightning impulse withstand voltage. 1.50 U Rated withstand voltage under standard reference atmosphere U0 Rated withstand voltage requested for the place of installation Ka Altitude correction factor according to the opposite diagram Example For a requested rated lightning impulse withstand voltage of 75 kV at an altitude of 2500 m, an insulation level of 90 kV under standard reference atmosphere is required as a minimum: 90 kV W 75 kV x 1.2 1.40 1.30 1.20 HG11-2517c_en eps U W U0 x Ka Altitude correction factor To select the devices, the following applies: 1.10 1.00 1000 1500 2000 2500 3000 3500 m 4000 Site altitude Number of operating cycles The recloser is designed for 10,000 operating cycles at normal current. According to the standard IEEE C37.60, the recloser has been tested for 116 short-circuit breaking operations. The actual number of short-circuit breaking operations is higher than that, and can be even more than 200 depending on the parameters of the short-circuit current (amplitude, DC component). Siemens HG 11.42 · 2008 13 Siemens Vacuum Recloser 3AD Description Product range overview and scope of delivery Product range overview Rated voltage 1 Rated short-circuit breaking current Rated lightning impulse withstand voltage kV kA kV 12 15.5 12.5 12.5 16 12.5 12.5 16 12.5 16 27 38 Rated normal current 400 A 95 110 110 125 150 150 170 170 n n n 630 A 800 A n n n n n n n n n n n n n n n n Scope of delivery Standard equipment Switch unit Operating mechanism Operating mechanism housing Switching medium Insulation Power supply Position indicator Operations counter Interlocking Configuration Sensors Controller and control cubicle Cubicle Socket outlet Controller size Number of inputs/ outputs for customer use Temperature range Control keys Controller interfaces 14 Siemens HG 11.42 · 2008 Electrical operating mechanism (magnetic actuator) Mild steel with outdoor protection coating IP 55 with lifting eyes and earthing connection Vacuum interrupters Cycloaliphatic epoxy resin/air Auxiliary power input OPEN: green CLOSED: red Mechanical in the switch unit; electronical in the controller Electrical; mechanical lockout Pole mounting and 6 m control cable Integrated current transformers Mild steel with outdoor protection coating IP 65 with lifting eyes and earthing connection USA version E10 (= 10" width) 5 x BI, 8 x BO 12 function keys 8 user-definable LEDs Up to –30 °C 5 navigation keys, 12 function keys, 2 pushbuttons USB (front), RS485 (rear) Optional available Remarks Stainless steel Auxiliary transformer for supply from HV line Customer-specific color or inscription Other cable lengths and/or substation frame Integrated voltage sensors Stainless steel Country-specific design E12 (= 12" width) Additional BI/BO and 12 LEDs –40 °C Customer-specific pushbuttons or rotary CLOSE/OPEN switches RS232, fiber optic, IRIG-B Siemens Vacuum Recloser 3AD Product Selection Contents Contents Page Product Selection 15 Ordering data and configuration example 16 Selection of primary ratings: Voltage level 12 kV 17 Voltage level 15.5 kV 17 Voltage level 27 kV 18 Voltage level 38 kV 19 R-HG11-311.tif Selection of controller: 20 Current and voltage measuring 20 Controller size 21 Auxiliary voltage 21 Control and sensor cables 22 Communication protocols 22 Communication interfaces 22 Function packages 23 Languages and power socket 23 Selection of additional equipment 24 Accessories and spare parts 25 2 R-HG11-312.tif Switch unit – bottom view Recloser configuration Control cubicle Siemens HG 11.42 · 2008 15 Siemens Vacuum Recloser 3AD Product Selection Ordering data and configuration example « Order number structure Mounting parts and special versions ( ) The vacuum reclosers consist of a primary part as well as of a controller or secondary part. The relevant data make up the 16-digit order number. The primary part covers the main electrical data of the circuit-breaker poles. The controller and secondary part covers all auxiliary devices and the controller, which are necessary for operating and controlling the recloser. In case of special versions, “- Z” is added to the order number and a descriptive order code follows. If several special versions are required, the suffix “- Z” is only listed once. If a requested special version is not in the catalog and can therefore not be ordered via order code, it has to be identified with Y 9 9 after consultation. The agreement hereto is made between your responsible sales partner and the order processing department in our Switchgear Factory in Berlin. Order codes Individual equipment versions, marked with 9 or Z in the 8th to 16th position, are explained more in detail by a 3-digit order code. Several order codes can be added to the order number in succession and in any sequence. 2 a: alphabetical Position: Order No.: 1st position 2 3 n: numerical 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 3 A D n n n n – n a a n n n – a a n Order codes – « n n n Primary part Superior group Switching devices 2nd position Main group Circuit-breaker 3rd position Subgroup Outdoor vacuum recloser 4th to 7th position Basic equipment Design and ratings of the vacuum recloser 8th to 16th position 1 Secondary part Controller, sensors, cables and other necessary data Order codes Group of 3 after the Order No. Format: a n a « Special versions ( ) Initiated with “-Z” Group of 3 after the Order No. Format: a n n Configuration example In order to simplify the selection of the correct order number for the requested recloser type, you will find a configuration example on each page of the chapter “Equipment Selection”. For the selection of the auxiliary voltages, the fixing options, the controller, etc. always the last example of the primary part was taken over and continued, so that at the end of the equipment selection (page 24) a completely configured recloser results as an example. Example for Order No.: Order codes: 16 Siemens HG 11.42 · 2008 On the foldout page we offer a configuring aid. Here you can fill in the order number you have determined for your recloser. 3 A D 6 2 3 2 – n n n n n – n n n n Siemens Vacuum Recloser 3AD Product Selection Selection of primary ratings 12 kV Position: Order No.: 50/60 Hz 7 – 8 3 A D 1 2 3 n n n n 4 5 6 – n n n n n 9 10 11 12 – 3 3 3 3 3 3 3 3 A A A A A A A A D D D D D D D D 1 3 4 6 1 3 4 6 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 A A A A A A A A A A A A A A A A A A A A D D D D D D D D D D D D D D D D D D D D 1 3 4 6 1 3 4 6 1 3 4 6 1 3 4 6 1 3 4 6 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 1 1 1 1 2 2 2 2 3 3 3 3 2 2 2 2 3 3 3 3 6 2 3 2 3 A D 6 2 3 2 – 13 14 15 16 n n n n Order codes – « n n n kV kV kV kA A 12 75 42 12.5 630 800 n n n n n n n n See page 24 See page 23 See page 23 See page 22 See page 22 See page 22 See page 21 See page 21 See page 20 Ir See page 20 Rated normal current Isc Three-phase for loop automation Rated short-circuit breaking current Ud 3 x single-phase/ single-triple Rated short-duration power-frequency withstand voltage Up Three-phase Rated lightning impulse withstand voltage Ur Single-phase Rated voltage Type 2 15.5 kV 50/60 Hz Ur Up Ud Isc Ir kV kV kV kA A 15.5 110 50 12.5 400 630 800 16 630 800 n n n n n n n n n n n n n n n n n n n n Configuration example Siemens vacuum recloser 3AD Rated voltage Ur = 15.5 kV Rated lightning impulse withstand voltage Up = 110 kV Rated short-duration power-frequency withstand voltage Ud = 50 kV Rated short-circuit breaking current Isc = 16 kA Rated normal current Ir = 630 A Type: Three-phase recloser for loop automation Example for Order No.: Order codes: 3 A D – n n n n n – n n n n Siemens HG 11.42 · 2008 17 Siemens Vacuum Recloser 3AD Product Selection Selection of primary ratings 27 kV Position: Order No.: 50/60 Hz 2 3 – 8 n n n n 4 5 6 – n n n n n kV kV kA A 125 60 12.5 400 630 2 800 60 12.5 400 630 800 16 630 800 n n n n n n n n n 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 1 3 2 1 3 3 2 1 4 3 2 1 6 3 2 1 1 3 2 2 3 3 2 2 4 3 2 2 6 3 2 2 1 3 2 3 3 3 2 3 4 3 2 3 6 3 2 3 On request On request On request On request On request On request On request On request On request On request On request On request On request On request On request On request On request On request On request On request n n n n n n n n n n n n n n n n n n n n n n n Configuration example Siemens vacuum recloser 3AD Rated voltage Ur = 27 kV Rated lightning impulse withstand voltage Up = 125 kV Rated short-duration power-frequency withstand voltage Ud = 60 kV Rated short-circuit breaking current Isc = 12.5 kA Rated normal current Ir = 400 A Type: Three-phase Example for Order No.: Order codes: Siemens HG 11.42 · 2008 9 A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D 10 11 12 – – 13 14 15 16 n n n n Order codes – « n n n 3 A D 3 3 2 1 3 A D 3 3 2 1 – n n n n n – n n n n See page 24 See page 23 See page 23 See page 22 See page 22 See page 22 See page 21 See page 21 See page 20 See page 20 Rated normal current kV 27 Three-phase for loop automation Rated short-circuit breaking current Ir 3 x single-phase/ single-triple Rated short-duration power-frequency withstand voltage Isc Three-phase Rated lightning impulse withstand voltage Ud Single-phase Rated voltage Up 18 1 Type Ur 150 7 3 A D Siemens Vacuum Recloser 3AD Produt Selection Selection of primary ratings 38 kV Position: Order No.: 50/60 Hz 1 2 3 3 A D 7 – 8 n n n n 4 5 6 – n n n n n 9 10 11 12 – – 13 14 15 16 n n n n Order codes – « n n n kV kV kV kA A 38 170 70 12.5 630 800 16 630 800 n n n n n n n n n n n n n n n n Configuration example Siemens vacuum recloser 3AD Rated voltage Ur = 38 kV Rated lightning impulse withstand voltage Up = 170 kV Rated short-duration power-frequency withstand voltage Ud = 70 kV Rated short-circuit breaking current Isc = 16 kA Rated normal current Ir = 800 A Type: Single-phase Example for Order No.: Order codes: 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 A A A A A A A A A A A A A A A A D D D D D D D D D D D D D D D D See page 24 See page 23 See page 23 See page 22 See page 22 See page 22 See page 21 See page 21 See page 20 Ir See page 20 Rated normal current Isc Three-phase for loop automation Rated short-circuit breaking current Ud 3 x single-phase/ single-triple Rated short-duration power-frequency withstand voltage Up Three-phase Rated lightning impulse withstand voltage Ur Single-phase Rated voltage Type On request On request On request On request On request On request On request On request On request On request On request On request On request On request On request On request 2 3 A D on request 3 A D – n n n n n – n n n n Siemens HG 11.42 · 2008 19 Siemens Vacuum Recloser 3AD Product Selection Selection of controller 7 – – 8 9 Options Recloser for pole mounting 1) incl. cubicle, controller and control cable Recloser for substation application incl. cubicle and controller Switch unit only (w/o cubicle, controller and control cable) 2) 10 11 12 – n n n n n 1 2 3 – 13 14 15 16 n n n n Y 0 0 0 Y Y 1) Pole mounting according to list of accessories 2) This option is only possible in the stated order number 2 9th position Current and voltage measuring Current transformers 1 integrated CT per pole Voltage sensors 1 integrated sensor per pole (including sensor cables) n n n 1) n n 1) 3 x external VTs (to be defined as accessories) A B C n 1) 1) Necessary for recloser type: Three-phase for loop automation Configuration example Siemens vacuum recloser 3AD 3 A D (Ur = 27 kV, Up = 125 kV, Ud = 60 kV, Isc = 12.5 kA, Ir = 400 A) Type: Three-phase 3 Recloser for pole mounting incl. control cubicle and control cable Current and voltage measuring: current transformers, 1 integrated CT per pole Example for Order No.: Order codes: 20 Siemens HG 11.42 · 2008 3 A D 3 3 2 1 – 1 A 3 2 1 – 1 A n n n – n n n n Order codes – « n n n See page 24 6 See page 23 5 See page 23 4 n n n n See page 22 3 See page 22 2 See page 22 1 3 A D See page 21 Position: Order No.: See page 21 8th position Recloser configuration Siemens Vacuum Recloser 3AD Product Selection Selection of controller 8 16 13 23 33 43 For 3-phase and single-phase applications n n n n n n n n n n For loop automation n n n n n n n 14 n n n n n n 6 7 – – 8 9 10 11 12 – n n n n n n n n 22 See page 22 13 14 15 16 n n n n Order codes – « n n n 30 A B C D E n n – See page 24 5 See page 23 4 n n n n See page 23 3 See page 22 2 See page 22 1 3 A D Number of binary outputs (partly for customer use) 12 Number of binary inputs (partly for customer use) Function keys E10 E12 Position: Order No.: Number of tri-color LEDs Controller size 10th position Controller size n n 2 F Without controller (refers to switch unit only) Y 11th position Auxiliary voltage DC voltage AC voltage Without auxiliary voltage supply (need for switch unit only) 48 V 60 V 110 V 220 V 110/120 V 220/240 V With auxiliary transformer and rated voltage as below: Rated voltage 11 kV Rated voltage 12 kV Rated voltage 13.8 kV Rated voltage 15 kV Configuration example Siemens vacuum recloser 3AD (Ur = 27 kV, Up = 125 kV, Ud = 60 kV, Isc = 12.5 kA, Ir = 400 A) Type: Three-phase Controller size: E12, 12 function keys, 16 tri-color LEDs, 33 binary inputs, 30 binary outputs Auxiliary voltage 110/120 V AC Example for Order No.: Order codes: 0 On request On request 3 4 5 6 9 9 9 9 With order code With order code With order code With order code T T T T 3 3 3 3 A B C D 3 A D 3 3 2 1 – 1 A D 5 3 A D 3 3 2 1 – 1 A D 5 n – n n n n Siemens HG 11.42 · 2008 21 Siemens Vacuum Recloser 3AD Product Selection Selection of controller 2 3 4 5 6 7 n n n n – – 8 9 10 11 12 – n n n n n – 13 14 15 16 n n n n Options (also comprises sensor cables for external voltage sensors if selected) Without (need for switch unit only) Cable length 6 m Cable with special length (to be specified in clear text) 0 1 9 Options Without communication protocol (need for switch unit only) IEC 60870-5-103 and Modbus RTU DNP 3.0 0 1 2 n n n ST plug (multiple mode) n n n n ST plug (single mode) 1 x RS232 (rear) n 2 x optical n n 1 x IRIG-B n n 2 x RS485 (rear) 1 x RS485 (rear) 1 x USB (front) 14th position Communication interfaces n n n n n A B C D E Y n Without communication interface (need for switch unit only) Configuration example Siemens vacuum recloser 3AD (Ur = 27 kV, Up = 125 kV, Ud = 60 kV, Isc = 12.5 kA, Ir = 400 A) Type: Three-phase Length of control and sensor cable 6 m Communication protocol IEC 60870-5-103 and Modbus RTU Communication interfaces 1 x USB, 2 x RS485, 1 x IRIG-B Example for Order No.: Order codes: 22 Siemens HG 11.42 · 2008 3 A D 3 3 2 1 – 1 A D 5 1 – 1 C 3 A D 3 3 2 1 – 1 A D 5 1 « n n n M 1 13th position Communication protocols 2 Order codes – See page 24 1 3 A D See page 23 Position: Order No.: See page 23 12th position Control and sensor cables – 1 C n n Y Siemens Vacuum Recloser 3AD Product Selection Selection of controller 15th position Function packages Position: 1 2 3 3 A D 4 5 6 7 n n n n – – 8 9 10 11 12 – n n n n n – 13 14 15 16 n n n n Order codes – « n n n See page 24 Order No.: Options Standard protection and monitoring functions Standard protection and monitoring functions plus synchro-check and fault locator Standard protection and monitoring functions for loop automation Standard protection and monitoring functions for loop automation with synchro-check and fault locator Standard protection and monitoring functions for single-triple application Standard protection and monitoring functions for single-triple application with synchro-check and fault locator Without protection functions (need for switch unit only) A C D E F 2 G Y 16th position Languages and power socket Language of operating instructions and nameplate Standard of power socket English American English Spanish Portuguese Other languages on request UK USA Mexico Brazil Configuration example Siemens vacuum recloser 3AD (Ur = 27 kV, Up = 125 kV, Ud = 60 kV, Isc = 12.5 kA, Ir = 400 A) Type: Three-phase Controller with standard protection and monitoring functions Language of operating instructions and nameplate: English Standard of power socket: UK Example for Order No.: Order codes: 1 2 3 4 9 R 1 Y 3 A D 3 3 2 1 – 1 A D 5 1 – 1 C A 1 3 A D 3 3 2 1 – 1 A D 5 1 – 1 C A 1 Siemens HG 11.42 · 2008 23 Siemens Vacuum Recloser 3AD Product Selection Selection of additional equipment Selection of additional equipment Position: Order No.: 1 2 3 3 A D 4 5 6 7 n n n n – – 8 9 10 11 12 – n n n n n – 13 14 15 16 n n n n Order codes – « n n n – – – – – Z Z Z Z Z A F T T T 3 0 0 0 0 8 2 1 2 3 – Z T 2 1 – Z T 2 2 – Z Y 9 9 – – Z Z F T 0 0 2 1 – Z Options Ambient temperature down to –40 °C Seaworthy packing inside Germany Stainless steel for tank, control cubicle Radio modem power supply 12 V DC Serial to Ethernet converter Pole mounting frame with bracket for surge arrester (source and load side) Pole mounting frame – Siemens design – (with bracket for surge arresters, source and load side) Further non-listed special versions (only after consultation with your responsible sales partner). Information additionally in clear text 2 Configuration example Siemens vacuum recloser 3AD 3 A D Rated voltage Ur = 27 kV Rated lightning impulse withstand voltage Up = 125 kV Rated short-duration power-frequency withstand voltage Ud = 60 kV Rated short-circuit breaking current Isc = 12.5 kA Rated normal current Ir = 400 A Type: Three-phase 3 Recloser for pole mounting incl. control cubicle and control cable Current and voltage measuring: current transformers, 1 CT integrated per pole Controller size: E12, 12 function keys, 16 tri-color LEDs, 33 binary inputs, 30 binary outputs Auxiliary voltage 110/120 V AC Length of control and sensor cable 6 m Communication protocol IEC 60870-5-103 and Modbus RTU Communication interfaces 1 x USB, 2 x RS485, 1 x IRIG-B Controller with standard protection and monitoring functions Language of operating instructions and nameplate: English Standard of power socket: UK Seaworthy packing inside Germany Stainless steel for tank, control cubicle Example for Order No.: Order codes: 24 Siemens HG 11.42 · 2008 3 2 1 1 A D 5 1 C A 1 3 2 1 F T 0 1 2 + – 1 3 A D 3 0 – – 1 A D 5 1 – 1 C A 1 Siemens Vacuum Recloser 3AD Product Selection Accessories and spare parts Accessories and spare parts A wide range of spare parts and accessories is available. Please contact your responsible sales partner and the order processing department in our Switchgear Factory in Berlin. HG11-2732_en eps Data on the nameplate Note: For any request regarding spare parts, subsequent deliveries, etc. the following details are necessary: – Type designation – Serial No. – Design code – Year of manufacture Siemens HG 11.42 · 2008 2 25 R-HG11-313.tif Siemens Vacuum Recloser 3AD 26 Siemens HG 11.42 · 2008 Siemens Vacuum Recloser 3AD Technical Data Contents Contents Page Technical Data 27 Electrical data, dimensions and weights: 28 Voltage level 15.5 kV 28 Voltage level 27 kV 29 Voltage level 38 kV 29 R-HG11-314.tif Voltage level 12 kV Switch unit driver - discarge switch for the capacitor R-HG11-315.tif 3 Controller with protective cap Siemens HG 11.42 · 2008 27 Siemens Vacuum Recloser 3AD Technical Data Rated short-circuit breaking current Rated short-circuit making current Rated lightning impulse withstand voltage Rated short-duration power-frequency withstand voltage Voltage drop ΔU between connections Creepage distance, phase-to-earth Clearance, phase-to-phase Minimum clearance, phase-to-earth Weight Line charging current Cable charging current Ir tk Isc Ima Up Ud A s kA kA kV kV mV mm mm mm kg A A 12 kV Rated normal current 50/60 Hz Order No. ¨ 3AD¨123 … 3AD 122 … 15.5 kV 50/60 Hz ¨ 3AD¨222 … 3AD¨223 … 3AD¨232 … 3AD¨233 … 3AD 221 … 3 28 Siemens HG 11.42 · 2008 Rated operating sequence: O - 0.2s - CO 2s - CO - 2s - CO (-30s - CO) - Lock-out Rated duration of short-circuit Electrical data, dimensions and weights 630 n 3 12.5 31.5 75 42 24 810 312 287 142 2 10 800 n 3 12.5 31.5 75 42 24 810 312 287 142 2 10 Ir tk Isc Ima Up Ud A s kA kA kV kV mV mm mm mm kg A A 400 n 3 12.5 31.5 110 50 24 810 312 287 142 2 10 630 n 3 12.5 31.5 110 50 24 810 312 287 142 2 10 800 n 3 12.5 31.5 110 50 24 810 312 287 142 2 10 630 n 3 16 40 110 50 24 810 312 287 142 2 10 800 n 3 16 40 110 50 24 810 312 287 142 2 10 Siemens Vacuum Recloser 3AD Technical Data Rated short-circuit breaking current Rated short-circuit making current Rated lightning impulse withstand voltage Rated short-duration power-frequency withstand voltage Voltage drop ΔU between connections Creepage distance, phase-to-earth Clearance, phase-to-phase Minimum clearance, phase-to-earth Weight Line charging current Cable charging current Ir tk Isc Ima Up Ud A s kA kA kV kV mV mm mm mm kg A A 27 kV Rated normal current 50/60 Hz Order No. ¨ 3AD¨322 … 3AD¨323 … 3AD¨¨¨¨ ... 3AD¨¨¨¨ … 3AD¨¨¨¨ … 3AD¨¨¨¨ … 3AD¨¨¨¨ … 3AD 321 … 38 kV 50/60 Hz ¨¨¨¨ … 3AD¨¨¨¨ … 3AD¨¨¨¨ … 3AD¨¨¨¨ … 3AD Rated operating sequence: O - 0.2s - CO 2s - CO - 2s - CO (-30s - CO) - Lock-out Rated duration of short-circuit Electrical data, dimensions and weights 400 n 3 12.5 31.5 125 60 24 810 312 287 142 5 25 630 n 3 12.5 31.5 125 60 24 810 312 287 142 5 25 800 n 3 12.5 31.5 125 60 24 810 312 287 142 5 25 400 n 3 12.5 31.5 150 60 On request 5 25 630 n 3 12.5 31.5 150 60 On request 5 25 800 n 3 12.5 31.5 150 60 On request 5 25 630 n 3 16 40 150 60 On request 5 25 800 n 3 16 40 150 60 On request 5 25 3 Ir tk Isc Ima Up Ud A s kA kA kV kV mV mm mm mm kg A A 630 n 3 12.5 31.5 170 70 On request 5 40 800 n 3 12.5 31.5 170 70 On request 5 40 630 n 3 16 40 170 70 On request 5 40 800 n 3 16 40 170 70 On request 5 40 Siemens HG 11.42 · 2008 29 Siemens Vacuum Recloser 3AD Technical Data Dimension drawings Dimension drawings HG11-2729 eps 638 600 600 350 365 HG11-2730_en eps 615 3 10 962 250 597 Dimensions of control cubicle 460 520.5 Dimensions of switch unit Maßbild 2 Maßbild 1 30 Siemens HG 11.42 · 2008 Siemens Vacuum Recloser 3AD Technical Data Dimension drawings Dimension drawings 901 600 1341 962 407 357 1334 Maßbild 2 HG11-2731 eps 425 1173 425 3 Dimensions of switch unit with pole mounting frame Siemens HG 11.42 · 2008 31 R-HG11-181.tif Siemens Vacuum Recloser 3AD 32 Siemens HG 11.42 · 2008 Siemens Vacuum Recloser 3AD Annex Contents Contents Page Annex 33 Inquiry form 34 Configuration instructions 35 Foldout page R-HG11-180.eps Configuration aid Switchgear Factory in Berlin, Germany 4 Siemens HG 11.42 · 2008 33 Siemens Vacuum Recloser 3AD Annex Inquiry form Please copy, fill in and return to your Siemens partner Inquiry concerning o Siemens vacuum Technical data Rated voltage recloser 3AD Rated lightning impulse withstand voltage Please o Submit an offer o Call us o Visit us Your address Rated short-duration power-frequency withstand voltage Rated short-circuit breaking current Rated normal current Other values o 12 kV o 27 kV o 15.5 kV o 38 kV o 75 kV o 150 kV o 110 kV o 170 kV o 42 kV o 60 kV o 50 kV o 70 kV o _ _ _ kV o 12.5 kA o 16 kA o _ _ _ kA o 400 A o 630 A o _ _ _ kV o 125 kV o _ _ _ kV o 800 A o ___A Secondary equipment For possible combinations see pages 20 to 23 Company Recloser configuration o Recloser for o Dept. Name Current and voltage sensing pole mounting Without control cubicle o Integrated current o Made of o o Integrated voltage transformers Street Controller equipment Postal code/city Phone Fax 4 binary inputs 34 binary inputs 9 binary outputs ___ transformers o 14 binary inputs o 24 binary inputs o 17 binary outputs o 25 binary outputs o _ _ _ V AC, _ _ _ Hz Control and sensor cable o Without o 6m o ___m o USB o Optical o RS485 o IRIG-B o RS232 o Synchronizing and o Fault locating Function packages additional to standard functions Siemens AG o _ _ _ V DC synchro-check Loop automation o Single-triple Dept. Application and other requirements Name Street Postal code/city Fax o Please check off Siemens HG 11.42 · 2008 o External voltage sensors o Communication interfaces 34 substation Auxiliary voltage E-mail 4 o o o o o Application in stainless steel Others _ _ _ Please fill in For configuration of your Siemens vacuum recloser 3AD 12 kV to 38 kV 75 kV to 170 kV 42 kV to 70 kV 12.5 kA and 16 kA 400 A to 800 A 3 A D – 13 14 15 16 – + + + + + + + + These ratings define the positions 4 to 7 of the order number. 3 A D 2nd step: Definition of the secondary equipment (see pages 20 to 23) – + + + + + + + + 3 A D Please specify the following equipment features: Possible options: Recloser configuration (position 8) Sensors (position 9) Controller (position 10) Auxiliary voltage (position 11) Cable length of control and sensor cable (position 12) Communication protocol (position 13) Communication interfaces (position 14) Functions of the controller (position 15) Language of operating instructions and nameplate (position 16) Recloser incl. control cubicle and cables, recloser without control cubicle and cables, recloser for transformer substation, retrofit recloser Integrated current transformers, integrated voltage transformers, external voltage transformers Housing size, number of function keys and three-color LEDs, number of available binary inputs and outputs Voltages from 48 V DC to 240 V AC – – + + + + + + + + 3 A D Standard length 6 m, special lengths possible – – – + + + + + + + + IEC 60870-5-103 and Modbus RTU, DNP 3.0 3 A D – – USB, RS485, RS232, IRIG-B, optical, ST plug Standard protection and monitoring functions, synchronizing and synchro-check, fault location English, American English, Spanish and Portuguese + + + + + + + + 3 A D – – These equipment features define the positions 8 to 16 of the order number. + + + + + + + + 3rd step: Do you have any further requirements concerning the equipment? (Please refer to page 24) 3 A D Should you still need more options than the possible special equipment like country-specific mains sockets, weather resistance down to –40 °C, stainless-steel design, etc. please contact your responsible sales partner. – + + + + + + + + 3 A D – 35 – + + + + + + + + 3 A D Siemens HG 11.42 · 2008 – – – + + + + + + + + – Z See page 24 See page 23 n n n n See page 23 Ur: Up: Ud: Isc: Ir: – See page 22 Rated voltage (Ur) Rated lightning impulse withstand voltage (Up) Rated short-duration power-frequency withstand voltage (Ud) Rated short-circuit breaking current (Isc) Rated normal current (Ir) 9 10 11 12 – See page 22 Possible options: 6 See page 22 8 n n n n n See page 17 Please specify the following ratings: 5 See page 21 – – 1st step: Definition of the primary part (see pages 17 to 19) 4 See page 21 3 See page 20 2 See page 20 1 Instruction for configuration of the Siemens vacuum recloser 3AD 7 n n n n n n n See page 19 Please follow the steps for configuration and enter the order number in the configuration aid. Alternatively you can also use your prompted online configurator under www.siemens.com/energy to You prefer to configure your Siemens vacuum recloser 3AD on your own? If not stated otherwise on the individual pages of this catalog, we reserve the right to include modifications, especially regarding the stated values, dimensions and weights. Drawings are not binding. All product designations used are trademarks or product names of Siemens AG or other suppliers. If not stated otherwise, all dimensions in this catalog are given in mm. Siemens AG Energy Sector Medium Voltage Division Nonnendammallee 104 13623 Berlin Germany www.siemens.com/energy General editing: Siemens AG, Dept. PTD CC M Erlangen Subject to change without notice Order No. E50001-K1511-A421-A1-7600 Printed in Germany Dispo 31601 KG 03.08 1.0 36 En 103063 6101/6519 The information in this document contains general descriptions of the technical options available, which do not always have to be present in individual cases. The required features should therefore be specified in each individual case at the time of closing the contract. R-HG11-182.tif Responsible for Technical contents: Siemens AG, Dept. PTD M C PPM Berlin For questions concerning Power Transmission and Distribution: You can contact our Customer Support Center 24 hours a day, 365 days a year. Tel.: +49 180/524 70 00 Fax: +49 180/524 24 71 (Charges depending on provider) E-Mail: support.energy@siemens.com www.siemens.com/energy-support