X00-A Standard: SRPS N.C5.250 Nominal voltage Uo/U: 0.6/1 kV Test voltage: 3 kV CONSTRUCTION Conductor: Strand made from aluminum wires Insulation: polyethylene. Core: wires are bundle stranded. Wire labeling: The cores of the phase conductors are marked with numbers: 1,2,3. Neutral supporting core has got a triangular bulge along the whole length. APPLICATION For distributive low-voltage air networks in urban areas. For supply of facilities and villages of temporary and permanent character. For air household connections. It can be placed on concrete, steel or wooden poles, the console attached to the facade of the building, next to the facade, onto wooden or steel construction. TECHNICAL DATA Permissible temperature of the conductor - maximum working temperature 90°C - in short circuit (max 5 s), max 250°C Working temperature at laying and handling, min. -20oC Bending radius at bundle laying - for cable – min 14D (D - cable diameter) - for wire – min 6d (d – wire diameter) Bending radius after laying - for cable - 6D (D - cable diameter) - for wire - 4d (d – wire diameter) Data for standard construction nxq mm2 2x16 2x25 4x16 4x25 n – number of wires, q – nominal cross section of the conductor, D – Bundle diameter, Q – Bundle weight Al – kg/km 93 145 186 290 D∼ mm Q∼ kg/km 15.7 18.4 18.9 22.2 136 208 273 415