White Paper Digital Cellular Communications and NFPA 72

advertisement
White Paper
Digital Cellular Communications and NFPA 72
How the XR150/XR550 Panel meets UL and NFPA commercial fire requirements with a
single digital cellular communications link
Advances in digital cellular communications technology have enabled powerful new capabilities in alarm
transmission that are reflected in important changes to National Fire Protection Association and Underwriters
Laboratories standards for commercial fire alarm systems. This white paper explains those capabilities,
available on DMP’s Model XR150/XR550 Panel when used with DMP 263C or 263H Digital Cellular Communicator.
It also details how these new digital cellular communication capabilities can reduce the ongoing cost of system
operation while also enhancing system security in a manner that conforms to NFPA and UL requirements.
NFPA 72 and Underwriters Laboratories
When authorities having jurisdiction (AHJs) establish requirements for commercial fire alarm systems in their
city, state or municipality, they rely heavily on the NFPA’s National Fire Alarm and Signaling Code, commonly
known as NFPA 72. From time to time, the NFPA updates the NFPA 72 code to reflect new developments in
technology. There is no set schedule for when the code is updated, but updates tend to occur every few years.
The latest version of the code was issued in 2010. The two previous versions were issued in 2002 and 2007.
AHJs are not required to adopt the most recent version of the NFPA code. Today, some authorities require
systems to meet the NFPA 72 2010 code, but others may still use earlier versions of the code as the basis for
their code requirements.
The NFPA does not play the role of certifying specific products for use in NFPA 72-compliant systems. Instead
that task has been assigned to Underwriters Laboratories, which conducts tests to confirm that products meet
specified performance requirements and that the products include instructions that clearly specify
requirements for installation in a manner compliant with NFPA 72.
Like the NFPA, Underwriters Laboratories also updates its requirements from time to time. When a particular
UL standard is updated, a date is established for when the new requirements will go into effect. Products
manufactured after that date must conform to the requirements of the new version. (Although AHJs have
flexibility in determining when and if they want to implement new versions of the NFPA 72 code,
manufacturers do not have the same flexibility in meeting UL requirements. After a certain date, all products
manufactured must meet the requirements for the latest version of the standard).
The ANSI/UL 864 standard covers control units and accessories for fire alarm systems. ANSI/UL 864, 9th edition
is the version of the standard that fire alarm control panels and communicators manufactured today must
obtain for use in systems requiring compliance with NFPA 72, regardless of which version of NFPA 72 an AHJ is
using.
The DMP XR150/XR550 Panel used with the DMP 263C or 263H Digital Cellular Communicator has earned the
ANSI/UL 864, 9th edition listing. As this white paper will explain, that listing enables the DMP 263C or 263H to
serve as the only communications link with the central monitoring station when used with the DMP
XR150/XR550 in commercial fire systems to meet requirements for 2002, 2007 and 2010 versions of the NFPA 72
code.
In addition, the Fire Slave input option of the XR150/XR550 is also ANSI/UL 864, 9th edition-listed. This enables
the DMP 263C and 263H to meet commercial fire requirements operating as the slave communications link to
the central station when an XR150/XR550 is used as the slave communicator for a separate fire alarm control
panel (FACP).
DMP White Paper
Digital Cellular Communications and NFPA 72
Reliability of the communications link
One important goal of NFPA 72 is to help ensure the integrity of the communications link between the fire
alarm system installed at the customer premises and the central monitoring station. Older versions of NFPA 72
require a customer to have two dedicated phone lines for commercial fire alarm systems. The idea behind this
approach is that if one phone line should fail, the other likely would still be functional. But redundant phone
lines are costly, requiring commercial accounts to pay as much as $700 to $1200 per year in phone charges for
every one of their locations. In addition, redundant phone lines can and sometimes do fail simultaneously.
Fire systems that rely on redundant phone lines for communication are required to send test messages to the
central station once every 24 hours to confirm that the system is capable of transmitting an alarm. If the
central station does not receive a signal from the system at the expected time, the business is alerted so that
the problem can be addressed. The downside of this approach, however, is that if a problem were to occur
shortly after a test message, it would not be detected for nearly 24 hours.
Over the last 10 to 20 years, alternative communications technologies using wired or wireless digital data
communications have been developed—and increasingly these technologies are being used in security and fire
alarm systems. The availability of these alternative communications methods for fire systems caused the NFPA
to rethink its requirements for commercial fire systems. One option that the NFPA has allowed in the most
recent versions of the NFPA 72 code is to use a combination of two technologies, such as a cellular network and
a networked data connection—as long as both connections are verified once every 24 hours.
In addition, the most recent versions of NFPA 72 allows a single communications link to the central station to
be used if the integrity of the entire communications path is verified more frequently—once every five minutes
instead of once every 24 hours. The relevant section of the NFPA 72 2002 code is 8.5.4.4. The relevant section
of the 2007 code is 8.6.4.4. The relevant section of the NFPA 72 2010 code is 26.6.3.1.4.1.
The NFPA 72 code does not specify what type of link is appropriate for use as the single communications link—
only that it meets the requirement to test the integrity of the entire communications path every five minutes.
The DMP Model XR150/XR550 Panel used with DMP 263C or 263H Digital Cellular Communicator meets this
requirement when check-in and fail time settings are programmed for five minutes.
When technicians install the system, they establish a connection with the central monitoring station by
programming the IP address of the central station receiver and obtaining an account number from the central
station, which is also programmed into the system. As part of the programming process, the system prompts
technicians to enter the number of minutes for check-in and fail time. Both settings should be programmed for
five minutes.
When the initial communication from the system is sent to the central station, the central station receiver
records the check-in and fail times for the account number. Those settings trigger the receiver to
automatically look for a check-in from the system every five minutes and if the receiver does not receive an
check-in message from the communicator, an alert signal is sent to the commercial account through the
central station personnel.
The net result is a higher level of system reliability in comparison with traditional systems that rely on
redundant phone lines and the substantially less frequent 24-hour supervision reports associated with that
approach.
DMP products can save costs, enhance reliability
The DMP XR150 Panel has 142 inputs, 8 doors of access, up to 106 Form C relays, 8 areas, and 10,000 users. The
DMP XR550 Panel has 574 inputs, 16 doors of access, up to 506 Form C relays, 32 areas, and 10,000 users.
The DMP 263C or 263H Digital Cellular Communicator creates a direct cellular path to any DMP central station
receiver using the digital CDMA or HSPA+ network. En route, it does not go through a third party, such as
another central station or server.
DMP White Paper
Digital Cellular Communications and NFPA 72
Today’s cellular networks support voice and data communications using digital technology and do not rely on a
wired connection to the customer premises that can be damaged or sabotaged. Cellular networks operated by
wireless service providers are designed and built to high reliability standards, with proactive monitoring and
redundancy provided by the wireless carrier. Because the cellular connection to the customer premises is
fixed, unlike with mobile cellular network connections, no hand-offs are involved, minimizing the occurrence
of dropped connections. And because the size of the data messages sent between the cellular communicator
and the central station require relatively low bandwidth, the likelihood of communications not going through
because of congestion also is minimized.
The 263C and 263H do not require external power supplies, enclosures, batteries, cabling or conduit
connections, simplifying installation and strengthening system security. Both models are ready for activation,
via the SIM Card or MEID number, with SecureCom Wireless, LLC, the DMP-provided digital cellular service
based on advanced data communications technology.
DMP bills the security dealer that handles the account for SecureCom service. The dealer typically builds this
cost into its monthly charges for the account, which also include monitoring and maintenance, both of which
are mandatory for NFPA 72 systems. The portion of the monthly cost that goes toward communications is
typically between 50% and 75% less using a single digital cellular communicator and SecureCom than using
redundant telephone lines. When redundant telephone lines are used, the commercial account pays the
telephone service provider between $60 and $100 a month in addition to the monthly monitoring and
maintenance costs that go to the dealer.
The total ongoing monthly costs paid to the security dealer for NFPA 72 systems using SecureCom typically are
between one-third and one-half of the combined cost that the commercial user would pay to the dealer and
the telephone service provider to support a redundant phone line approach.
The Right Choice
The DMP XR150/XR550 Panel used with the DMP 263C or 263H Digital Cellular Communicator has earned the
ANSI/UL 864, 9th edition listing. As this white paper has explained, that listing enables the DMP 263C or 263H
to serve as the only communications link with the central monitoring station when used with the DMP
XR150/XR550 in commercial fire systems to meet requirement for 2002, 2007 and 2010 versions of the NFPA 72
code.
Alternatively, the Fire Slave input option of the XR150/XR550 is ANSI/UL 864 9th edition-listed when used with
the DMP 263C or 263H Digital Cellular Communicator and a fire alarm control panel (FACP) that also has
received the ANSI/UL 864 9th edition listing.
LT-1352 (2/14) © 2014 Digital Monitoring Products, Inc.
Giving commercial users the option of using a single dedicated cellular connection for fire alarm
communications can result in savings of as much as 75% for monthly communications costs, while at the same
time enhancing system reliability. A single cellular link, with its more stringent notification requirement for a
communication problem, provides a higher level of life safety protection for commercial users—and for anyone
with whom they do business.
Download