CONTACTORS - AUTOMATION 1. So called “3-wires control” to realize - the base connection for contactors automation; being used the ON and OFF push buttons, as control elements. The As. motor protections are respected (it’s got enough in the diagram, only). L1 L2 L3 N QM1 0 1 FU1 FA1 KM1 M FU2 SB0 SB1 FA1 KM1 1KM1 2 Reversing Rotation – 3-phase As. motor to realize the connection for contactors automation – for Reversing Rotation – 3-phase As. motor. The reversing is realised as the change of the phases sequence (to exchange 2 phases between themselves). The breaking contacts 2KM1 and 2KM2 are used as blocking – to be prevented the contemporary switching - the contactors KM1 and KM2. L1 L2 L3 N QM1 0 1 KM1 M KM2 SB0 SB1 KM1 2KM2 1KM1 SB2 2KM1 1KM2 KM2 3. The Y/delta change-over switching - by As. motor Automatic start To realize the connection for contactors automation - by As. motor Automatic start (using the Y/delta change-over switch). The contactors KM1 and KM3 realize the star connection; and the contactors KM1 and KM2 – the delta connection. If, the contemporary switching-on – all 3 contactors – the inlets short connection would be realized, so that this hazard has to be excluded by the optional contacts using. To be ensured the NO-error operation, it’s necessary – the breaking contact (contactor KM3) to be disconnected earlier, then the making contact switch-on (BBM - break before make). The time relay KT1 ensures the disconnecting the contactor KM3 (after the preset time – what is respecting the supposed time for starting motor); and KM2 switching. The breaking contact 2KM2 is blocking the KM3 re-connecting. (For the special starters-sets Y/delta, the mechanical blocking way (the rod) – is used – to be excluded the contemporary switching-on – the contactors KM2 and KM3, too. To be prolonged the time between the KM3 switching-off; and the KM2 switching-on – it’s possible to do it by the other optional relay KA using (in the KM2 position). If, relay KA is ON; then the power contactor KM2 is switching. Note: The line-to-line voltage 230V has to be set for the used As. motor. L1 L2 L3 N QM1 KM3 KM1 0 1 M KM2 SB0 SB1 KT1 2KM2 2KT1 KM3 KM1 1KM3 1KM1 KM2 2KM3