NFPA 101A-2013 and Proposed 2016 Editions Guide on Alternative Approaches to Life Safety TIA Log No.: 1166 Reference: Worksheet 7.5.4A Comment Closing Date: February 20, 2015 Submitter: Joseph Versteeg, Versteeg Associates and William Koffel, Koffel Associates, Inc. 1. Revise Worksheet 7.5.4A to read as follows: Worksheet 7.5.4.A MANDATORY SAFETY REQUIREMENTS – NEW LARGE FACILITY Stories in Height Egress Refuge General Fire Safety Control Requirement Requirement Requirement Requirement (Sd) (Sb) (Sc) (Sa) 1 Story 15 17 15 21 2 Stories 17 17.5 17 18 17 13 23 24 ≥3 Stories 19.5 18 15 26 SUBSTANTIATION and EMERGENCY NATURE: The Mandatory Values for New, Large Residential Board and Care with second story zone location were miscalculated. It is expected that CMS will adopt NFPA 101-2012. NFPA 101A-2013 will come into greater use. The errors need to be fixed to make NFPA 101A an acceptable equivalency method for alternative compliance with NFPA 101-2012. The errors need to be fixed in NFPA 101A-2013 and in the proposed 2016 edition. The Safety Parameter Values that correspond to minimal compliance with NFPA 101 Section 32.3 requirements for New, Large Residential Board and Care – all of which must be sprinklered – are as follows: Zone location: 1 Story Parameter Required Feature Points 1. Construction V(000) -2 2. Hazardous Areas No deficiency 0 3. Manual Fire Alarm Manual alarm with fire department 3 notification 4. Smoke Detection and Alarm Interconnected bedroom/suite detectors, 6 plus Note p 5. Automatic Sprinklers Total building QRS 10 6. Segregation of Sleeping Rooms from Door closing expectation high; ½-hr walls, 2 Exit Access 20-min doors 7. Exit System Multiple routes; without horizontal exits 0 8. Exit Access (from living unit) No dead end >30 ft; Travel is >125 ft to -1 ≤250 ft 9. Interior Finish Exit route >25 to ≤75; Rooms/suites ≤75 1 10. Vertical Openings Note h for 1-story building 0 11. Smoke Control Smoke barriers 2 Zone location: 2 Stories Parameter 1. Construction 2. Hazardous Areas 3. Manual Fire Alarm 4. Smoke Detection and Alarm 5. Automatic Sprinklers 6. Segregation of Sleeping Rooms from Exit Access 7. Exit System 8. Exit Access (from living unit) 9. Interior Finish 10. Vertical Openings 11. Smoke Control Required Feature V(111) No deficiency Manual alarm with fire department notification Interconnected bedroom/suite detectors, plus Note p Total building QRS Door closing expectation high; ½-hr walls, 20-min doors Multiple routes; without horizontal exits No dead end >30 ft; travel is >125 ft to ≤250 ft Exit route >25 to ≤75; rooms/suites ≤75 Enclosed; ≥1 hr Smoke barriers Points 0 0 3 6 10 2 Zone location: ≥3 Stories Parameter 1. Construction 2. Hazardous Areas 3. Manual Fire Alarm 4. Smoke Detection and Alarm 5. Automatic Sprinklers 6. Segregation of Sleeping Rooms from Exit Access 7. Exit System 8. Exit Access (from living unit) 9. Interior Finish 10. Vertical Openings 11. Smoke Control Required Feature II(111) No deficiency Manual alarm with fire department notification Interconnected bedroom/suite detectors, plus Note p Total building QRS Door closing expectation high; ½-hr walls, 20-min doors Multiple routes; without horizontal exits No dead end >30 ft; travel is >125 ft to ≤250 ft Exit route >25 to ≤75; rooms/suites ≤75 Enclosed; ≥1 hr Smoke barriers Points 2 0 3 6 10 2 0 -1 1 1 2 0 -1 1 1 2 The Mandatory Safety Requirements values are calculated by inserting into the Worksheet 7.5.3 matrix the minimal compliance Safety Parameter Values from above as follows: Zone location: 1 Story Parameter 1. Construction 2. Hazardous Areas 3. Manual Fire Alarm 4. Smoke Detection and Alarm 5. Automatic Sprinklers Control Requirem ent (Sa) -2 0 3 / 2 = 1.5 6/2=3 Egress Requirement (Sb) 10 10 / 2 = 5 0/2=0 3 6 Refuge Requirement (Sc) General Fire Safety Requirement (Sd) -2 0 -2 0 3 6 6/2=3 10 (per Note, no /2) 10 6. Segregation of Sleeping Rooms from Exit Access 7. Exit System 8. Exit Access (from living unit) 9. Interior Finish 10. Vertical Openings 11. Smoke Control Total 2 1 / 2 = 0.5 0/2=0 15 Zone location: 2 Stories Parameter Control Requirem ent (Sa) 1. Construction 0 2. Hazardous Areas 0 3. Manual Fire Alarm 3 / 2 = 1.5 4. Smoke Detection 6/2=3 and Alarm 5. Automatic 10 Sprinklers 6. Segregation of 2 Sleeping Rooms from Exit Access 7. Exit System 8. Exit Access (from living unit) 9. Interior Finish 1 / 2 = 0.5 10. Vertical Openings 1 / 2 = 0.5 11. Smoke Control 17.5 Total Zone location: ≥3 Stories Parameter Control Requirem ent (Sa) 1. Construction 2 2. Hazardous Areas 0 3. Manual Fire Alarm 3 / 2 = 1.5 4. Smoke Detection 6 / 2 =3 and Alarm 2/2=1 2 2 0 -1 0/2=0 0 -1 1 0 2 17 Egress Requirement (Sb) 0 2 15 1 0 2 21 Refuge Requirement (Sc) General Fire Safety Requirement (Sd) 0 0 0/2=0 3 6 6/2=3 0 0 3 6 10 / 2 = 5 10 / 2 = 5 10 2/2=1 2 2 0 -1 0/2=0 0 -1 1 1 2 18 Egress Requirement (Sb) 0/2=0 3 6 1 2 13 1 1 2 24 Refuge Requirement (Sc) General Fire Safety Requirement (Sd) 2 0 2 0 3 6 6/2=3 5. Automatic Sprinklers 6. Segregation of Sleeping Rooms from Exit Access 7. Exit System 8. Exit Access (from living unit) 9. Interior Finish 10. Vertical Openings 11. Smoke Control Total 10 10 / 2 = 5 10 / 2 = 5 10 2 2/2=1 2 2 0 -1 0/2=0 0 -1 1 / 2 = 0.5 1 / 2 = 0.5 19.5 1 1 2 18 1 2 15 1 1 2 26 Anyone may submit a comment by the closing date indicated above. To submit a comment, please identify the number of the TIA and forward to the Secretary, Standards Council, 1 Batterymarch Park, Quincy, MA 02169‐7471.