Specifications and Ordering Information 200130 Dual Pressure flexiTIM Module and 200132 Pressure Transducer Description The Dual Pressure flexiTIM™ module interfaces two individual pressure transducers to the Trendmaster 2000 System and is intended for nondynamic pressure applications. The flexiTIM™ module, and cable, interfaces with pressure transducers using a four-pin, locking bayonet connection. Intended transducers for interface are standard, millivolt output type devices having an output sensitivity of 10 mV/V. This flexibility allows measurement of a wide range of pressures over a variety of operating conditions. A standard transducer is offered for use with the flexiTIM™ module for convenience. Specifications All specifications are at 25°C (77°F) unless otherwise specified. Operation outside the specified limits will result in false or inaccurate readings. 200130 Dual Pressure flexiTIM Electrical For Reference Only – See Document #141576 Full Scale Range: The Trendmaster full scale pressure range is set by the pressure transducer. The transducer's full scale range is entered into the Trendmaster software. Accuracy: ±8.5% of the transducer's full scale rating (transducer's accuracy not included). Transducer Excitation Voltage: 4.98 Vdc ±65 mVdc. Maximum Transducer Supply Current: 2.5 mA ABS MAX available over temperature. Transducer OK Range: 1 V to 3 Vdc bias from transducer (nominal). Resolution: 0.025% of transducer's full scale rating. Transducer: Bridge type meeting stated requirements. Page 1 of 6 Installed without barriers per drawing 136926 Environmental Limits Operating Temperature: -40°C to +100°C (-40°F to +212°F). Humidity: 100% Condensing on exposed surfaces. 100% Non-condensing on surfaces inside conduit. Class I, Div 2, Groups A, B, C & D T4, Ta = 100°C CENELEC: 4 Installed with intrinsically safe zener barriers per drawing 136925 Housing Materials: Powder-Coated Aluminum. 200131 Cables Weight: 554 grams (20 oz) not including conduit body Dimensions: See diagram Enclosure Type: Ex nA IIC, Class I, Zone 2 T4, Ta = 100°C II 1 G EEx ia IIC T4, Ta = 100°C LCIE 99 ATEX 6001X Mechanical Operating Temperature: Minimum Bend Radius: -20°C to +100° C (-4°F to +212°F). 25.4 mm (1 in). Construction: Four conductor (22 AWG) with foil shield and drain wire (100% coverage), yellow PVC outer jacket. Connectors: Screw-on, five-pin, keyed connector on the flexiTIM end and a PT06F8-4S (or equivalent) on the transducer end. The environmental boot should be installed over the transducer’s connector and body. Electromagnetic Compatibility Radiated Emissions: EN 55022 (1994). Class A. Electrostatic Discharge: EN 61000-4-2 (1995), Criteria A. Radiated Susceptibility: EN 61000-4-3 (1997) (ENV 50140 : 1993), Criteria A. Conducted Susceptibility: ENV 50141 (1993), Criteria A. Electrical Fast Transient: EN 61000-4-4 (1995), Criteria A. 200132 Pressure Transducer Surge Capability: ENV 50142 (1994), Criteria A. 30, 50, 100, 300, and 500. Magnetic Field: EN 61000-4-8 (1994), Criteria A. Pressure Ranges PSI SG: Sensitivity: 10 mV/V ±1%. Hazardous Area Approvals Absolute Accuracy: CSA: Installed with intrinsically safe zener barriers per drawing 136925 ± 4% over compensated temperature range. Class I, Div 1 Groups A, B, C & D Class II, Div 1 Groups E, F & G Class III, Div 1 Excitation: 5-10 VDC (nominal). Input Resistance: > 2 K Ω. Ex ia IIC; T4, Ta = 100°C Class I, Zone 0 Output Resistance: < 6 K Ω. Operating Temperature: -54°C to +121°C (-65°F to +250°F). For Reference Only – See Document #141576 Page 2 of 6 Compensated Temperature: +10°C to +93°C (+50°F to +200°F). Connector: MS3113H8-4P, 4-position male or equivalent: Transducer Cables A = + Excitation B = + Out C = - Out D = - Excitation Proof Pressure: 2X Full Pressure Scale. Burst Pressure: 3X Full Pressure Scale Pressure Fitting: 1/4 - 18 NPT male. Case Material: 316 Stainless Steel. Insulation resistance: > 50 M @ 50 VDC. 200131-05 0.5 metre (1.6 feet) cable. 200131-10 1 metre (3.3 feet) cable. 200131-15 1.5 metres (4.9 feet) cable. 200131-20 2 metres (6.6 feet) cable. 200131-40 4 metres (13.1 feet) cable. 200131-60 6 metres (19.7 feet) cable. 200131-90 9 metres (29.53 feet) cable Pressure Transducer 200132-030 0-30 PSI SG Ordering Information 200132-050 0-50 PSI SG 200130 Dual Pressure flexiTIM module (all conduit bodies have 1-inch hubs). 200132-100 0-100 PSI SG 200130-AXX-BXX 200132-300 0-300 PSI SG A: Conduit body style -00 No conduit body 200132-500 0-500 PSI SG -01 Appleton Style C body, Malleable Iron -02 Appleton Style E body, Malleable Iron -03 Appleton Style C body, Aluminum -04 -05 Accessories 126709-04 Trendmaster 2000 Installation Guide (flexiTIM™ installation guide is included) Appleton Style E body, Aluminum 137230-01 flexiTIM™ installation Guide Weatherproof housing mount 01620085 Extra terminal plugs for SPA line connection. 3 terminal plugs provided with each flexiTIMTM module. -00 CSA, Class 1 DIV 2, no barriers 03814231 -01 CSA approvals installed with barriers Compression fitting for 1-inch conduit body hubs. Seals for cables when installing flexiTIMTM modules without conduit. -02 CENELEC approvals installed with barriers 04500006 Dow Corning 4, Electrical Insulating Compound (5.3 Oz) B: Approvals 2001 Bently Nevada LLC used in this document are registered marks of Bently Nevada LLC For Reference Only – See Document #141576 Page 3 of 6 Dimensional diagrams 134.6 (5.30) 122.9 (4.84) CHANNEL B R CHANNEL A 106.5 (4.19) 46.0 (1.81) Top Powder Coated Aluminum Housing 1/2-20 5 Pole Female Receptacle 50.8 (2.00) Side *Allow 127 mm(5 in) for total Height with connector and cable bend. Gasket 2 16 8 4 64 32 128 EXAMPLE CH A=12 CH B=13 SHIELD RED PWR BLACK COM WHITE SIG- GREEN SIG+ S R B W G IN/OUT S R B W G IN/OUT S R B WG OFF S S R B WG ON S R B WG CHANNEL A ADDRESS ADD NUMBERS BELOW "ON" SWITCHES CHANNEL B ADDRESS = CHANNEL A + 1 63.3 * (2.49) S R B W G IN/OUT Bottom All dimensions are in millimeters (inches) Figure 1: Dimensional diagram and wiring connection details For Reference Only – See Document #141576 Page 4 of 6 Style C Conduit Body Style E Conduit Body Figure 2: Conduit Body Styles provided with the flexiTIM™ modules Transducers Transducer cables with environmental boots TM FlexiTIM Module Conduit body Rigid conduit SPA Line Figure 3: Installed Pressure flexiTIM™ module For Reference Only – See Document #141576 Page 5 of 6 MS3113H8-4P, 4-position male or equivalent: A = + Excitation B = + Out A D C = - Out D = - Excitation C B 1.00 [25.4] 0.85 [21.59] 29.21 [1.15] 22.00 [0.87] 6.86 [0.27] 1/4-18 NPT Figure 4: Pressure Transducers For Reference Only – See Document #141576 Page 6 of 6 A D B C