Rating of Transformers supplying Harmonic-Rich Loads David Chapman Copper Development Association david.chapman@copperdev.co.uk Copper Development Association Losses in Transformers No-load loss (‘iron loss’) – energy consumed in eddy current and hysteresis loss – present 100% of the time Load losses Resistive loss (‘copper loss’) – dependent on square of load current – most important during high load periods Eddy current loss Copper Development Association www.leonardo-energy.org www.cda.org.uk Distribution transformer efficiency standards HD 428 & 538 Load Losses for Distribution Transformers RATED POWER No-Load Losses for Distribution Transformers OIL-FILLED (HD428) UP TO 24kV2) DRY TYPE (HD538) LIST A 12kV PRIMARY LIST B LIST C OIL-FILLED (HD428) UP TO 24kV2) LIST A’ LIST B’ DRY TYPE (HD538) LIST C’ 12kV PRIMARY 3) 3) kVA W W W W W W W W 50 1,100 1,350 875 N/A 190 145 125 N/A 100 1,750 2,150 1,475 2,000 320 260 210 440 160 2,350 3,100 2,000 2,700 460 375 300 610 250 3,250 4,200 2,750 3,500 650 530 425 820 400 4,600 6,000 3,850 4,900 930 750 610 1,150 630 /4% 6,500 8,400 5,400 7,300 1,300 1,030 860 1,500 630 /6% 6,750 8,700 5,600 7,600 1,200 940 800 1,370 1000 10,500 13,000 9,500 10,000 1,700 1,400 1,100 2,000 1600 17,000 20,000 14,000 14,000 2,600 2,200 1,700 2,800 2500 26,500 32,000 22,000 21,000 3,800 3,200 2,500 4,300 Source: CENELEC Copper Development Association www.leonardo-energy.org www.cda.org.uk Distribution transformer efficiency standards HD 428 & 538 Load Losses for Distribution Transformers RATED POWER No-Load Losses for Distribution Transformers OIL-FILLED (HD428) UP TO 24kV2) DRY TYPE (HD538) LIST A 12kV PRIMARY LIST B LIST C OIL-FILLED (HD428) UP TO 24kV2) LIST A’ LIST B’ DRY TYPE (HD538) LIST C’ 12kV PRIMARY 3) 3) kVA W W W W W W W W 50 1,100 1,350 875 N/A 190 145 125 N/A 100 1,750 2,150 1,475 2,000 320 260 210 440 160 2,350 3,100 2,000 2,700 460 375 300 610 250 3,250 4,200 2,750 3,500 650 530 425 820 400 4,600 6,000 3,850 4,900 930 750 610 1,150 630 /4% 6,500 8,400 5,400 7,300 1,300 1,030 860 1,500 630 /6% 6,750 8,700 5,600 7,600 1,200 940 800 1,370 1000 10,500 13,000 9,500 10,000 1,700 1,400 1,100 2,000 1600 17,000 20,000 14,000 14,000 2,600 2,200 1,700 2,800 2500 26,500 32,000 22,000 21,000 3,800 3,200 2,500 4,300 BA’ Source: CENELEC Copper Development Association www.leonardo-energy.org www.cda.org.uk Distribution transformer efficiency standards HD 428 & 538 Load Losses for Distribution Transformers RATED POWER No-Load Losses for Distribution Transformers OIL-FILLED (HD428) UP TO 24kV2) DRY TYPE (HD538) LIST A 12kV PRIMARY LIST B LIST C OIL-FILLED (HD428) UP TO 24kV2) LIST A’ LIST B’ DRY TYPE (HD538) LIST C’ 12kV PRIMARY 3) 3) kVA W W W W W W W W 50 1,100 1,350 875 N/A 190 145 125 N/A 100 1,750 2,150 1,475 2,000 320 260 210 440 160 2,350 3,100 2,000 2,700 460 375 300 610 250 3,250 4,200 2,750 3,500 650 530 425 820 400 4,600 6,000 3,850 4,900 930 750 610 1,150 630 /4% 6,500 8,400 5,400 7,300 1,300 1,030 860 1,500 630 /6% 6,750 8,700 5,600 7,600 1,200 940 800 1,370 1000 10,500 13,000 9,500 10,000 1,700 1,400 1,100 2,000 1600 17,000 20,000 14,000 14,000 2,600 2,200 1,700 2,800 2500 26,500 32,000 22,000 21,000 3,800 3,200 2,500 4,300 C-C’ Source: CENELEC Copper Development Association www.leonardo-energy.org www.cda.org.uk Full load losses in a 100kVA C-C’ transformer 12% Winding Magnetic 88% Total loss = 1685 W Copper Development Association www.leonardo-energy.org www.cda.org.uk Full load losses in a 100kVA C-C’ transformer 12% 9% Resistance Magnetic 79% Eddy current (10%) Total loss = 1685 W Copper Development Association www.leonardo-energy.org www.cda.org.uk Full load losses in a 100kVA C-C’ transformer 12% 4% Resistance Magnetic Eddy Current (5%) 84% Total loss = 1685 W Copper Development Association www.leonardo-energy.org www.cda.org.uk Current waveform for a typical PC 2.0000 1.5000 1.0000 Current (A) 0.5000 0.0000 0 90 180 270 360 -0.5000 -1.0000 -1.5000 -2.0000 Degrees Copper Development Association www.leonardo-energy.org www.cda.org.uk Harmonic profile of a typical PC 0.6000 0.5000 Current (A) 0.4000 0.3000 0.2000 0.1000 0.0000 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Harmonic Copper Development Association www.leonardo-energy.org www.cda.org.uk 17 Typical harmonic profile - 6 pulse converter 25 20 15 % 10 5 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 Harmonic number Copper Development Association www.leonardo-energy.org www.cda.org.uk Effect of harmonics on transformers There are two issues that affect Transformers supplying harmonic-rich loads: • Triple-n harmonic currents circulate in delta windings, increasing resistive losses, operating temperature and reducing effective load capacity • Harmonic currents, being of higher frequency, cause increased magnetic losses in the core and increased eddy current and skin effect losses in the windings Copper Development Association www.leonardo-energy.org www.cda.org.uk Effect of triple-n harmonics in transformers Triple-n harmonic currents circulate in delta windings - they do not propagate back onto the supply network Copper Development Association www.leonardo-energy.org www.cda.org.uk Harmonic mitigation by transformer Delta-star transformers Copper Development Association www.leonardo-energy.org www.cda.org.uk Effect of harmonics on transformers There are two issues that affect Transformers supplying harmonic-rich loads: • Triple-n harmonic currents circulate in delta windings, increasing resistive losses, operating temperature and reducing effective load capacity • Harmonic currents, being of higher frequency, cause increased magnetic losses in the core and increased eddy current and skin effect losses in the windings Copper Development Association www.leonardo-energy.org www.cda.org.uk Increased Eddy current losses in transformers Increased eddy current loss can be calculated by: Peh = Pef h = h max ∑ h =1 I h2 h 2 where: Peh is the total eddy current loss Pef is the eddy current loss at fundamental frequency h is the harmonic order is the per unit RMS current at harmonic h Ih Copper Development Association www.leonardo-energy.org www.cda.org.uk K-Rating of Transformers There are two approaches to rating transformers supplying harmonic rich load:• Designing for the anticipated duty - e.g.the American system, established by UL and manufacturers, which specifies harmonic capability of the transformer - known as K-factor. • De-rating to survive the anticipated duty - e.g. the European system, developed by IEC, which defines de-rating factor for standard transformers - known as factor K. Copper Development Association www.leonardo-energy.org www.cda.org.uk K-Rating of Transformers - US System First, calculate the K factor of the load according to: K= h = h max ∑ h =1 I h2 h 2 where: h is the harmonic order Ih is the RMS current at h in per unit of total current Copper Development Association www.leonardo-energy.org www.cda.org.uk K-Rating of Transformers - US System p y 0.6000 0.5000 Current (A) 0.4000 0.3000 0.2000 0.1000 0.0000 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 Harmonic For this typical PC load, the K factor is 11.6 (For worked examples see LPQI AN 3.5.2 or IEE 1100 1992) Copper Development Association www.leonardo-energy.org www.cda.org.uk K-Rating of Transformers - US System Next, a transformer with a higher K rating is selected from the standard range: 4, 9, 13, 20, 30, 40, 50 Copper Development Association www.leonardo-energy.org www.cda.org.uk K-Rating of Transformers - European System In Europe, the transformer de-rating factor is calculated according to the formulae in BS 7821 Part 4. The factor K is given by: 2 n=N ⎛ ⎡ ⎞⎤ ⎛ ⎞ I e ⎛ I1 ⎞ q n ⎜ ⎟⎥ ⎜ ⎟ K = ⎢1 + n ⎜ ⎟ ∑ 1 + e ⎝ I ⎠ n + 2 ⎜ ⎜⎝ I 1 ⎟⎠ ⎟ ⎥ ⎢ ⎝ ⎠⎦ ⎣ 2 0 .5 e is ratio of eddy current loss (50 Hz) to resistive loss n is the harmonic order q is dependent on winding type & frequency, typically 1.5 to 1.7 Copper Development Association www.leonardo-energy.org www.cda.org.uk K-Rating of Transformers - European System p y 0.6000 0.5000 Current (A) 0.4000 0.3000 0.2000 0.1000 0.0000 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 Harmonic For the same PC load, the de-rating factor is 78% Copper Development Association www.leonardo-energy.org www.cda.org.uk Harmonic Diversity - K Factor 16 14 12 K Factor 10 8 6 4 2 0 1 2 5 10 20 41 No of Units (pairs) Copper Development Association www.leonardo-energy.org www.cda.org.uk K-Rating - Calculation software Copper Development Association www.leonardo-energy.org www.cda.org.uk K-Rating - Calculation software Copper Development Association www.leonardo-energy.org www.cda.org.uk K-Rating - Calculation software Copper Development Association www.leonardo-energy.org www.cda.org.uk K-Rating - Calculation software Copper Development Association www.leonardo-energy.org www.cda.org.uk Full load losses in a 100kVA C-C’ transformer 53% 41% Resistance Magnetic Eddy Current 6% Total loss = 3245 W Copper Development Association www.leonardo-energy.org www.cda.org.uk 80% load losses in a 100kVA C-C’ transformer 51% 39% Resistance Magnetic Eddy Current 10% Total loss = 2156 W Copper Development Association www.leonardo-energy.org www.cda.org.uk Effect of additional losses on life-time 80 % load Working temp = t × Life − time = T × 2 Life − time = T × 2 Pk = 90 × 1.28 = 115°C Pf ⎛ ∂t ⎞ −⎜ ⎟ ⎝ 10 ⎠ ⎛ (Pk − Pf ) ⎞ ⎟ ⎜ t× Pf ⎟ ⎜ −⎜ ⎟ 10 ⎟⎟ ⎜⎜ ⎠ ⎝ = 40 × 2− 2.5 = 7 years Copper Development Association www.leonardo-energy.org www.cda.org.uk 70% load losses in a 100kVA C-C’ transformer 50% 38% Resistance Magnetic Eddy Current 12% Total loss = 1699 W Copper Development Association www.leonardo-energy.org www.cda.org.uk Effect of additional losses on life-time 70 % load Working temp = t × Life − time = T × 2 Life − time = T × 2 Pk = 90 × 1.0083 = 90.75°C Pf ⎛ ∂t ⎞ −⎜ ⎟ ⎝ 10 ⎠ ⎛ (Pk − Pf ) ⎞ ⎟ ⎜ t× Pf ⎟ ⎜ −⎜ ⎟ 10 ⎟⎟ ⎜⎜ ⎠ ⎝ = 40 × 2− 0.075 = 38 years Copper Development Association www.leonardo-energy.org www.cda.org.uk The real world Selection and management small change in loading - large effect on lifetime. derate then add the ‘headroom’ management practices must maintain derating for the life of the transformer when – adding new loads – making changes to any harmonic filters within the installation Copper Development Association www.leonardo-energy.org www.cda.org.uk David Chapman Copper Development Association david.chapman@copperdev.co.uk www.cda.org.uk Copper Development Association