Circulation Pumps

advertisement
PIPE CONNECTIONS AND DIMENSIONS
INSTALLATION POSITIONS
NOT PERMITTED
PERMITTED
Automatic Speed Controlled
Pump shaft must not be vertical position.
Pump shaft must be parallel position.
Circulation Pumps
Connect the pump to the installation as shown in the figure by making it parallel to the ground.
Use isolating valves in the inlet and outlet in order to facilitate the removal of pump during repair or
maintenance.
Use a thermic relay when connecting the pump to electric supply.
CORRECT OPERATION
PUMP TYPE
PN6
øk
ød
Weight øD
(mm) (mm) (mm)
~(kg)
9
130
100
40
PN10
PN6
10
12,5
150
130
110
100
14
18
150
160
110
130
88
110
PN10
PN6
19
18
185
160
145
130
112
110
PN10
PN6
22
20
185
140
145
110
112
90
PN10
PN6
22
32,5
165
110
125
130
99
67,5
PN10
35,5
118
145
67,5
HCPO 6/6
Low performance
due to cavitation
T su
HCPO 4/5
HCPO 4/7
HCPO 6/6
HCPO 6/8
Pump Types
50°C
75°C
95°C
110°C
120°C
2,1
6,9
9,9
16,2
22,2
1,9
6,8
9,8
16
22
2,9
7,8
11
17
23
3
2,3 3,2
7,9 7,1 8,1
11 10,2 11
17 16,4 17
23 22,4 23
Pump Data
Minimum required suction height in 40°C
ambient temperature at the suction side
of the pump to prevent cavitation noise.
(mWc)
HCPO-Al 6/13
When there is cavitation in a circulation pump, the following problems arise:
Low performance: Since the required flow conditions are not met, pump
cannot create the necessary flow rate and pressure. Upper floors cannot be
heated.
Vibration: Turbulent flow caused by air bubbles causes vibration.
Pump life is reduced: Air bubbles in the system or in the pump corrode the
pump material causes erosion.
Noise: Air bubbles, turbulence and striking of water on surfaces create noise.
HCPO 5/10
When the pressure at the suction end of
the circulation pump is not enough, water
changes phase to turn into gas. Gas bubbles
are carried to high pressure areas by the
flow. Vapour turns into water again and
gas bubbles causes turbulence in the flow
and water strikes the surfaces. This process
is called cavitation.
124,5
124,5
40
280
220,8
124,5
87
280
221,8
135,5
98,5
340
266,8
4x19
4x14
4x19
Flange
6-10
DN 40 DN100 (
as per
DIN 2531
0,48
0,24
0,18
0,63
0,36
0,27
0,86
0,51
0,35
1,07
0,73
0,48
1,37
0,98
0,7
2,4
1,95
1,35
-
-
-
-
-
-
215
120
80
326
200
153
352
290
240
560
430
270
750
580
420
1420
1200
990
-
-
-
-
-
-
Max. Pumping Head (m)
Rated Coupling
Diameter
Pump Type
The right to amend specifications under technologic developments is reserved
GOSB-Gebze Organize Sanayi Bölgesi
Max.
ambient
pressure
2430
2070
1860
2260
1950
1700
2900
2820
2700
2820
2680
2440
2670
2390
2080
2740
2490
2190
Nominal Capacitor
I(A)
Power Capacity
220V Consump.
(μF)
50Hz
(W)
ORDER NOTATION
fiahabettin Bilgisu Cad. 41480 Gebze-Kocaeli/TURKEY
Motor
Motor
insulation protection
Phone : (90)(262) 648 60 00 PBX
Telefax : (90)(262) 648 61 01
120
220,8
I(A)
380V
50Hz
For Automatic Speed Controlled Circulation Pumps
HCPO 5 / 10
AUTOMATIC SPEED CONTROLLED
HCPO 4/5
HCPO 4/7
HCPO 6/6
HCPO 6/8
HCPO 5/10
HCPO-AI 6/13
280
92,5
• Location of usage and liquid;
- Clean, cleared of solid particles,
- Hot-water heating systems
Max.
ambient
temp.
184
III
II
I
III
II
I
III
II
I
III
II
I
III
II
I
III
II
I
H›z
d/d
Capacitor voltage of circulation pumps must to be 400 V.
TECHNICAL SPECIFICATIONS
Max.
water
temp
250
92,5
80
4x18
4x14
65
HCPO 6/13
185
75
80
4x18
4x14
50
220
71
4x18
4x14
65
HCPO 5/10
65
117,5
65
HCPO 6/8
Q
110,5
44
PN10
PN6
b
c
h
L
Speed
(mm) (mm) (mm) (mm) Step
4x18
4x14
88
80
HCPO 4/7
H
nxm
4x14
80
HCPO 4/5
CAVITATION
DN
H
IP44
ALARKO CARRIER
SANAY‹ VE T‹CARET A.fi.
web
: www.alarko-carrier.com.tr
e-mail : info@alarko-carrier.com.tr
A.7.1.4i 220811 MiNERAL
Do not operate the pump without water.
NEVER LUBRICATE THE PUMP
Rods and bearings of ALARKO circulation pumps are water lubricated and they do not need
maintenance. New or idle pump rods may be throttled due to the pollutants and particles in
the water. In such cases, close the main electric switch. Remove the rotor end cap and rotate
the shaft a few rounds via screwdriver. Put the rotor end cap in place and operate the pump.
Single speed pumps can be modified into three speed pumps by way of an adaptor. Notify this
in your orders.
PUMP SELECTION
It is essential to know the flow rate (Q) and necessary pressure (Hm) value for the
selection of circulation pump. These values are given in the heating project of the
building and circulation pump selection is made according to these values. If no
heating project is available, the following evaluation methods can be applied for
pump selection.
• Full conformity with Regulation for Energy-Performance
Buildings clause 12/6
• Thermal protection
• Counter rotation warning and protection
• Locked rotor detection and fault signal
• Missing phase and phase sequence control
• IP44 protection class
GENERAL SELECTION CHART FOR AUTOMATIC SPEED CONTROLLED
CIRCULATION PUMPS
H(m)
Enhanced, superior
features in HCPO types.
Evaluation of the Necessary Flow Rate (Q)
The pump should be able to carry the heated water from the boiler to the radiators
with a suitable flow rate. Flow rate is determined using the formula below;
Q
Qk
Tg
Td
High reliability and long life cycle through control
algorithm varying according to fluctuating mains supply.
: Necessary pump flow rate (m3/hour)
: The capacity of the boiler (kcal/hour)
: The temperature of water flowing out of the boiler (°C)
: The temperature of water returning to the boiler (°C)
A
Qk
• Remote control
• On-demand automatic or manual speed control
• Connecting operating signal light with external
signal light
Q=
(Tg – Td) x 1.000
Q(m3/h)
Evaluation of the Required Pressure (Hm)
The pump should have sufficient pressure to be able to push the water to the most
distant point of the installation by defeating the resistance of the heating installation.
Here, the pump should defeat the total pressure that is caused by the resistance
of the pipes, connection components, valves, radiators. While the same water
height will be at the inlet and outlet of the pump, the height of the building has
no effect to the pump selection procedure.
ensure high comfort.
INDEPENDENT CHARACTERISTIC CURVES FOR AUTOMATIC SPEED
CONTROLLED CIRCULATION PUMPS
H (mVc)
H
R
L
Z
For Q=16-m3/h, H=5 mSS;
a point (A) is available in “General
Selection Chart for Automatic
speed controlled Circulation
Pumps” as specified in selection
example of one-speed circulation
pumps. Point (A) is in the zone of
HCP0-Al 6-8 type of pump. This
type of pump will be selected. In
order to determine speed level of
the pump, point (A) will be marked
on the curve of HCPO- Al 6-8 type
among “Independent
Characteristic Curves of Automatic
Speed Controlled Circulation
Pumps”. For the values in the
example, point (A) is in the centre
of speed curves (II) and (III). Pump
selection can be made.
H (mVc)
: Pump pressure (mWc)
: Pressure loss per square meter at pipe diameter (mWc/meter)
: Total lengths of pipe components in the installation (meter)
: Resistance of connection components, valves and special devices (mWc)
H ≥ ∑ (R x L) + ∑ (Z)
If the project of the building is not available, it is almost impossible to determine
correctly the values mentioned above. In this case, following tables can be used
to determine the required pressure approximately.
2. Pump casing
Cast iron GG 20
3. Rotor can
Stainless steel
4. Impeller
Noryl
5. Bearings
Radial - Carbon / Axial - Stainless steel
6. O-ring
CR
7. Shaft
Stainless steel
8. Rotor and cap
Brass
9. Stator windings
Enamelled copper wire
4
5
6
7
8
9
New design pump shaft is splined, and
fixing will be carried out using a segment
after fitting fan onto pump. Therefore, fan
and shaft can easily be detached from one
another on demand.
It is approved and certified by the Netherlands originating independent KEMA organization which test the electromagnetic
conformity of electrical devices and has the authority of approval, that our circulation pumps conform to EMC Directive
89/336/EEC.
Installation Length
Up to 100 meters
500 meters
1000 meters
Necessary Pressure of the Pump
1–2 mWc
4–6 mWc
6–12 mWc
H (mVc)
H (mVc)
Q(m3/h)
Tsu
50 ºC
75 ºC
95 ºC
110 ºC
120 ºC
HCPO 6/13
2
3
HCPO 5/10
GD - AlSi9Cu3
HCPO 6/8
1. Stator housing
Necessary Pressure of the Pump
0,5–3 mWc
2–5 mWc
5–10 mWc
HCPO 6/6
1
Boiler Capacity
Up to 50 kW
Between 50-100 kW
Above 100 kW
HCPO 4/7
NAME OF PART
MATERIAL SPECIFICATIONS
HCPO 4/5
MAIN PARTS (Standard Type)
Q(m3/h)
Q(m3/h)
2,1
6,9
9,9
16,2
22,2
1,9
6,8
9,8
16
22
2,9
7,8
11
17
22
3
7,9
11
17
23
2,3
7,1
10
16
22
3,2
8,1
11
17
23
H (mVc)
Q(m3/h)
H (mVc)
A
Q(m3/h)
Q(m3/h)
PUMP SELECTION
It is essential to know the flow rate (Q) and necessary pressure (Hm) value for the
selection of circulation pump. These values are given in the heating project of the
building and circulation pump selection is made according to these values. If no
heating project is available, the following evaluation methods can be applied for
pump selection.
• Full conformity with Regulation for Energy-Performance
Buildings clause 12/6
• Thermal protection
• Counter rotation warning and protection
• Locked rotor detection and fault signal
• Missing phase and phase sequence control
• IP44 protection class
GENERAL SELECTION CHART FOR AUTOMATIC SPEED CONTROLLED
CIRCULATION PUMPS
H(m)
Enhanced, superior
features in HCPO types.
Evaluation of the Necessary Flow Rate (Q)
The pump should be able to carry the heated water from the boiler to the radiators
with a suitable flow rate. Flow rate is determined using the formula below;
Q
Qk
Tg
Td
High reliability and long life cycle through control
algorithm varying according to fluctuating mains supply.
: Necessary pump flow rate (m3/hour)
: The capacity of the boiler (kcal/hour)
: The temperature of water flowing out of the boiler (°C)
: The temperature of water returning to the boiler (°C)
A
Qk
• Remote control
• On-demand automatic or manual speed control
• Connecting operating signal light with external
signal light
Q=
(Tg – Td) x 1.000
Q(m3/h)
Evaluation of the Required Pressure (Hm)
The pump should have sufficient pressure to be able to push the water to the most
distant point of the installation by defeating the resistance of the heating installation.
Here, the pump should defeat the total pressure that is caused by the resistance
of the pipes, connection components, valves, radiators. While the same water
height will be at the inlet and outlet of the pump, the height of the building has
no effect to the pump selection procedure.
ensure high comfort.
INDEPENDENT CHARACTERISTIC CURVES FOR AUTOMATIC SPEED
CONTROLLED CIRCULATION PUMPS
H (mVc)
H
R
L
Z
For Q=16-m3/h, H=5 mSS;
a point (A) is available in “General
Selection Chart for Automatic
speed controlled Circulation
Pumps” as specified in selection
example of one-speed circulation
pumps. Point (A) is in the zone of
HCP0-Al 6-8 type of pump. This
type of pump will be selected. In
order to determine speed level of
the pump, point (A) will be marked
on the curve of HCPO- Al 6-8 type
among “Independent
Characteristic Curves of Automatic
Speed Controlled Circulation
Pumps”. For the values in the
example, point (A) is in the centre
of speed curves (II) and (III). Pump
selection can be made.
H (mVc)
: Pump pressure (mWc)
: Pressure loss per square meter at pipe diameter (mWc/meter)
: Total lengths of pipe components in the installation (meter)
: Resistance of connection components, valves and special devices (mWc)
H ≥ ∑ (R x L) + ∑ (Z)
If the project of the building is not available, it is almost impossible to determine
correctly the values mentioned above. In this case, following tables can be used
to determine the required pressure approximately.
2. Pump casing
Cast iron GG 20
3. Rotor can
Stainless steel
4. Impeller
Noryl
5. Bearings
Radial - Carbon / Axial - Stainless steel
6. O-ring
CR
7. Shaft
Stainless steel
8. Rotor and cap
Brass
9. Stator windings
Enamelled copper wire
4
5
6
7
8
9
New design pump shaft is splined, and
fixing will be carried out using a segment
after fitting fan onto pump. Therefore, fan
and shaft can easily be detached from one
another on demand.
It is approved and certified by the Netherlands originating independent KEMA organization which test the electromagnetic
conformity of electrical devices and has the authority of approval, that our circulation pumps conform to EMC Directive
89/336/EEC.
Installation Length
Up to 100 meters
500 meters
1000 meters
Necessary Pressure of the Pump
1–2 mWc
4–6 mWc
6–12 mWc
H (mVc)
H (mVc)
Q(m3/h)
Tsu
50 ºC
75 ºC
95 ºC
110 ºC
120 ºC
HCPO 6/13
2
3
HCPO 5/10
GD - AlSi9Cu3
HCPO 6/8
1. Stator housing
Necessary Pressure of the Pump
0,5–3 mWc
2–5 mWc
5–10 mWc
HCPO 6/6
1
Boiler Capacity
Up to 50 kW
Between 50-100 kW
Above 100 kW
HCPO 4/7
NAME OF PART
MATERIAL SPECIFICATIONS
HCPO 4/5
MAIN PARTS (Standard Type)
Q(m3/h)
Q(m3/h)
2,1
6,9
9,9
16,2
22,2
1,9
6,8
9,8
16
22
2,9
7,8
11
17
22
3
7,9
11
17
23
2,3
7,1
10
16
22
3,2
8,1
11
17
23
H (mVc)
Q(m3/h)
H (mVc)
A
Q(m3/h)
Q(m3/h)
PUMP SELECTION
It is essential to know the flow rate (Q) and necessary pressure (Hm) value for the
selection of circulation pump. These values are given in the heating project of the
building and circulation pump selection is made according to these values. If no
heating project is available, the following evaluation methods can be applied for
pump selection.
• Full conformity with Regulation for Energy-Performance
Buildings clause 12/6
• Thermal protection
• Counter rotation warning and protection
• Locked rotor detection and fault signal
• Missing phase and phase sequence control
• IP44 protection class
GENERAL SELECTION CHART FOR AUTOMATIC SPEED CONTROLLED
CIRCULATION PUMPS
H(m)
Enhanced, superior
features in HCPO types.
Evaluation of the Necessary Flow Rate (Q)
The pump should be able to carry the heated water from the boiler to the radiators
with a suitable flow rate. Flow rate is determined using the formula below;
Q
Qk
Tg
Td
High reliability and long life cycle through control
algorithm varying according to fluctuating mains supply.
: Necessary pump flow rate (m3/hour)
: The capacity of the boiler (kcal/hour)
: The temperature of water flowing out of the boiler (°C)
: The temperature of water returning to the boiler (°C)
A
Qk
• Remote control
• On-demand automatic or manual speed control
• Connecting operating signal light with external
signal light
Q=
(Tg – Td) x 1.000
Q(m3/h)
Evaluation of the Required Pressure (Hm)
The pump should have sufficient pressure to be able to push the water to the most
distant point of the installation by defeating the resistance of the heating installation.
Here, the pump should defeat the total pressure that is caused by the resistance
of the pipes, connection components, valves, radiators. While the same water
height will be at the inlet and outlet of the pump, the height of the building has
no effect to the pump selection procedure.
ensure high comfort.
INDEPENDENT CHARACTERISTIC CURVES FOR AUTOMATIC SPEED
CONTROLLED CIRCULATION PUMPS
H (mVc)
H
R
L
Z
For Q=16-m3/h, H=5 mSS;
a point (A) is available in “General
Selection Chart for Automatic
speed controlled Circulation
Pumps” as specified in selection
example of one-speed circulation
pumps. Point (A) is in the zone of
HCP0-Al 6-8 type of pump. This
type of pump will be selected. In
order to determine speed level of
the pump, point (A) will be marked
on the curve of HCPO- Al 6-8 type
among “Independent
Characteristic Curves of Automatic
Speed Controlled Circulation
Pumps”. For the values in the
example, point (A) is in the centre
of speed curves (II) and (III). Pump
selection can be made.
H (mVc)
: Pump pressure (mWc)
: Pressure loss per square meter at pipe diameter (mWc/meter)
: Total lengths of pipe components in the installation (meter)
: Resistance of connection components, valves and special devices (mWc)
H ≥ ∑ (R x L) + ∑ (Z)
If the project of the building is not available, it is almost impossible to determine
correctly the values mentioned above. In this case, following tables can be used
to determine the required pressure approximately.
2. Pump casing
Cast iron GG 20
3. Rotor can
Stainless steel
4. Impeller
Noryl
5. Bearings
Radial - Carbon / Axial - Stainless steel
6. O-ring
CR
7. Shaft
Stainless steel
8. Rotor and cap
Brass
9. Stator windings
Enamelled copper wire
4
5
6
7
8
9
New design pump shaft is splined, and
fixing will be carried out using a segment
after fitting fan onto pump. Therefore, fan
and shaft can easily be detached from one
another on demand.
It is approved and certified by the Netherlands originating independent KEMA organization which test the electromagnetic
conformity of electrical devices and has the authority of approval, that our circulation pumps conform to EMC Directive
89/336/EEC.
Installation Length
Up to 100 meters
500 meters
1000 meters
Necessary Pressure of the Pump
1–2 mWc
4–6 mWc
6–12 mWc
H (mVc)
H (mVc)
Q(m3/h)
Tsu
50 ºC
75 ºC
95 ºC
110 ºC
120 ºC
HCPO 6/13
2
3
HCPO 5/10
GD - AlSi9Cu3
HCPO 6/8
1. Stator housing
Necessary Pressure of the Pump
0,5–3 mWc
2–5 mWc
5–10 mWc
HCPO 6/6
1
Boiler Capacity
Up to 50 kW
Between 50-100 kW
Above 100 kW
HCPO 4/7
NAME OF PART
MATERIAL SPECIFICATIONS
HCPO 4/5
MAIN PARTS (Standard Type)
Q(m3/h)
Q(m3/h)
2,1
6,9
9,9
16,2
22,2
1,9
6,8
9,8
16
22
2,9
7,8
11
17
22
3
7,9
11
17
23
2,3
7,1
10
16
22
3,2
8,1
11
17
23
H (mVc)
Q(m3/h)
H (mVc)
A
Q(m3/h)
Q(m3/h)
PIPE CONNECTIONS AND DIMENSIONS
INSTALLATION POSITIONS
NOT PERMITTED
PERMITTED
Automatic Speed Controlled
Pump shaft must not be vertical position.
Pump shaft must be parallel position.
Circulation Pumps
Connect the pump to the installation as shown in the figure by making it parallel to the ground.
Use isolating valves in the inlet and outlet in order to facilitate the removal of pump during repair or
maintenance.
Use a thermic relay when connecting the pump to electric supply.
CORRECT OPERATION
PUMP TYPE
PN6
øk
ød
Weight øD
(mm) (mm) (mm)
~(kg)
9
130
100
40
PN10
PN6
10
12,5
150
130
110
100
14
18
150
160
110
130
88
110
PN10
PN6
19
18
185
160
145
130
112
110
PN10
PN6
22
20
185
140
145
110
112
90
PN10
PN6
22
32,5
165
110
125
130
99
67,5
PN10
35,5
118
145
67,5
HCPO 6/6
Low performance
due to cavitation
T su
HCPO 4/5
HCPO 4/7
HCPO 6/6
HCPO 6/8
Pump Types
50°C
75°C
95°C
110°C
120°C
2,1
6,9
9,9
16,2
22,2
1,9
6,8
9,8
16
22
2,9
7,8
11
17
23
3
2,3 3,2
7,9 7,1 8,1
11 10,2 11
17 16,4 17
23 22,4 23
Pump Data
Minimum required suction height in 40°C
ambient temperature at the suction side
of the pump to prevent cavitation noise.
(mWc)
HCPO-Al 6/13
When there is cavitation in a circulation pump, the following problems arise:
Low performance: Since the required flow conditions are not met, pump
cannot create the necessary flow rate and pressure. Upper floors cannot be
heated.
Vibration: Turbulent flow caused by air bubbles causes vibration.
Pump life is reduced: Air bubbles in the system or in the pump corrode the
pump material causes erosion.
Noise: Air bubbles, turbulence and striking of water on surfaces create noise.
HCPO 5/10
When the pressure at the suction end of
the circulation pump is not enough, water
changes phase to turn into gas. Gas bubbles
are carried to high pressure areas by the
flow. Vapour turns into water again and
gas bubbles causes turbulence in the flow
and water strikes the surfaces. This process
is called cavitation.
124,5
124,5
40
280
220,8
124,5
87
280
221,8
135,5
98,5
340
266,8
4x19
4x14
4x19
Flange
6-10
DN 40 DN100 (
as per
DIN 2531
0,48
0,24
0,18
0,63
0,36
0,27
0,86
0,51
0,35
1,07
0,73
0,48
1,37
0,98
0,7
2,4
1,95
1,35
-
-
-
-
-
-
215
120
80
326
200
153
352
290
240
560
430
270
750
580
420
1420
1200
990
-
-
-
-
-
-
Max. Pumping Head (m)
Rated Coupling
Diameter
Pump Type
The right to amend specifications under technologic developments is reserved
GOSB-Gebze Organize Sanayi Bölgesi
Max.
ambient
pressure
2430
2070
1860
2260
1950
1700
2900
2820
2700
2820
2680
2440
2670
2390
2080
2740
2490
2190
Nominal Capacitor
I(A)
Power Capacity
220V Consump.
(μF)
50Hz
(W)
ORDER NOTATION
fiahabettin Bilgisu Cad. 41480 Gebze-Kocaeli/TURKEY
Motor
Motor
insulation protection
Phone : (90)(262) 648 60 00 PBX
Telefax : (90)(262) 648 61 01
120
220,8
I(A)
380V
50Hz
For Automatic Speed Controlled Circulation Pumps
HCPO 5 / 10
AUTOMATIC SPEED CONTROLLED
HCPO 4/5
HCPO 4/7
HCPO 6/6
HCPO 6/8
HCPO 5/10
HCPO-AI 6/13
280
92,5
• Location of usage and liquid;
- Clean, cleared of solid particles,
- Hot-water heating systems
Max.
ambient
temp.
184
III
II
I
III
II
I
III
II
I
III
II
I
III
II
I
III
II
I
H›z
d/d
Capacitor voltage of circulation pumps must to be 400 V.
TECHNICAL SPECIFICATIONS
Max.
water
temp
250
92,5
80
4x18
4x14
65
HCPO 6/13
185
75
80
4x18
4x14
50
220
71
4x18
4x14
65
HCPO 5/10
65
117,5
65
HCPO 6/8
Q
110,5
44
PN10
PN6
b
c
h
L
Speed
(mm) (mm) (mm) (mm) Step
4x18
4x14
88
80
HCPO 4/7
H
nxm
4x14
80
HCPO 4/5
CAVITATION
DN
H
IP44
ALARKO CARRIER
SANAY‹ VE T‹CARET A.fi.
web
: www.alarko-carrier.com.tr
e-mail : info@alarko-carrier.com.tr
A.7.1.4i 220811 MiNERAL
Do not operate the pump without water.
NEVER LUBRICATE THE PUMP
Rods and bearings of ALARKO circulation pumps are water lubricated and they do not need
maintenance. New or idle pump rods may be throttled due to the pollutants and particles in
the water. In such cases, close the main electric switch. Remove the rotor end cap and rotate
the shaft a few rounds via screwdriver. Put the rotor end cap in place and operate the pump.
Single speed pumps can be modified into three speed pumps by way of an adaptor. Notify this
in your orders.
PIPE CONNECTIONS AND DIMENSIONS
INSTALLATION POSITIONS
NOT PERMITTED
PERMITTED
Automatic Speed Controlled
Pump shaft must not be vertical position.
Pump shaft must be parallel position.
Circulation Pumps
Connect the pump to the installation as shown in the figure by making it parallel to the ground.
Use isolating valves in the inlet and outlet in order to facilitate the removal of pump during repair or
maintenance.
Use a thermic relay when connecting the pump to electric supply.
CORRECT OPERATION
PUMP TYPE
PN6
øk
ød
Weight øD
(mm) (mm) (mm)
~(kg)
9
130
100
40
PN10
PN6
10
12,5
150
130
110
100
14
18
150
160
110
130
88
110
PN10
PN6
19
18
185
160
145
130
112
110
PN10
PN6
22
20
185
140
145
110
112
90
PN10
PN6
22
32,5
165
110
125
130
99
67,5
PN10
35,5
118
145
67,5
HCPO 6/6
Low performance
due to cavitation
T su
HCPO 4/5
HCPO 4/7
HCPO 6/6
HCPO 6/8
Pump Types
50°C
75°C
95°C
110°C
120°C
2,1
6,9
9,9
16,2
22,2
1,9
6,8
9,8
16
22
2,9
7,8
11
17
23
3
2,3 3,2
7,9 7,1 8,1
11 10,2 11
17 16,4 17
23 22,4 23
Pump Data
Minimum required suction height in 40°C
ambient temperature at the suction side
of the pump to prevent cavitation noise.
(mWc)
HCPO-Al 6/13
When there is cavitation in a circulation pump, the following problems arise:
Low performance: Since the required flow conditions are not met, pump
cannot create the necessary flow rate and pressure. Upper floors cannot be
heated.
Vibration: Turbulent flow caused by air bubbles causes vibration.
Pump life is reduced: Air bubbles in the system or in the pump corrode the
pump material causes erosion.
Noise: Air bubbles, turbulence and striking of water on surfaces create noise.
HCPO 5/10
When the pressure at the suction end of
the circulation pump is not enough, water
changes phase to turn into gas. Gas bubbles
are carried to high pressure areas by the
flow. Vapour turns into water again and
gas bubbles causes turbulence in the flow
and water strikes the surfaces. This process
is called cavitation.
124,5
124,5
40
280
220,8
124,5
87
280
221,8
135,5
98,5
340
266,8
4x19
4x14
4x19
Flange
6-10
DN 40 DN100 (
as per
DIN 2531
0,48
0,24
0,18
0,63
0,36
0,27
0,86
0,51
0,35
1,07
0,73
0,48
1,37
0,98
0,7
2,4
1,95
1,35
-
-
-
-
-
-
215
120
80
326
200
153
352
290
240
560
430
270
750
580
420
1420
1200
990
-
-
-
-
-
-
Max. Pumping Head (m)
Rated Coupling
Diameter
Pump Type
The right to amend specifications under technologic developments is reserved
GOSB-Gebze Organize Sanayi Bölgesi
Max.
ambient
pressure
2430
2070
1860
2260
1950
1700
2900
2820
2700
2820
2680
2440
2670
2390
2080
2740
2490
2190
Nominal Capacitor
I(A)
Power Capacity
220V Consump.
(μF)
50Hz
(W)
ORDER NOTATION
fiahabettin Bilgisu Cad. 41480 Gebze-Kocaeli/TURKEY
Motor
Motor
insulation protection
Phone : (90)(262) 648 60 00 PBX
Telefax : (90)(262) 648 61 01
120
220,8
I(A)
380V
50Hz
For Automatic Speed Controlled Circulation Pumps
HCPO 5 / 10
AUTOMATIC SPEED CONTROLLED
HCPO 4/5
HCPO 4/7
HCPO 6/6
HCPO 6/8
HCPO 5/10
HCPO-AI 6/13
280
92,5
• Location of usage and liquid;
- Clean, cleared of solid particles,
- Hot-water heating systems
Max.
ambient
temp.
184
III
II
I
III
II
I
III
II
I
III
II
I
III
II
I
III
II
I
H›z
d/d
Capacitor voltage of circulation pumps must to be 400 V.
TECHNICAL SPECIFICATIONS
Max.
water
temp
250
92,5
80
4x18
4x14
65
HCPO 6/13
185
75
80
4x18
4x14
50
220
71
4x18
4x14
65
HCPO 5/10
65
117,5
65
HCPO 6/8
Q
110,5
44
PN10
PN6
b
c
h
L
Speed
(mm) (mm) (mm) (mm) Step
4x18
4x14
88
80
HCPO 4/7
H
nxm
4x14
80
HCPO 4/5
CAVITATION
DN
H
IP44
ALARKO CARRIER
SANAY‹ VE T‹CARET A.fi.
web
: www.alarko-carrier.com.tr
e-mail : info@alarko-carrier.com.tr
A.7.1.4i 220811 MiNERAL
Do not operate the pump without water.
NEVER LUBRICATE THE PUMP
Rods and bearings of ALARKO circulation pumps are water lubricated and they do not need
maintenance. New or idle pump rods may be throttled due to the pollutants and particles in
the water. In such cases, close the main electric switch. Remove the rotor end cap and rotate
the shaft a few rounds via screwdriver. Put the rotor end cap in place and operate the pump.
Single speed pumps can be modified into three speed pumps by way of an adaptor. Notify this
in your orders.
Download