PIPE CONNECTIONS AND DIMENSIONS INSTALLATION POSITIONS NOT PERMITTED PERMITTED Automatic Speed Controlled Pump shaft must not be vertical position. Pump shaft must be parallel position. Circulation Pumps Connect the pump to the installation as shown in the figure by making it parallel to the ground. Use isolating valves in the inlet and outlet in order to facilitate the removal of pump during repair or maintenance. Use a thermic relay when connecting the pump to electric supply. CORRECT OPERATION PUMP TYPE PN6 øk ød Weight øD (mm) (mm) (mm) ~(kg) 9 130 100 40 PN10 PN6 10 12,5 150 130 110 100 14 18 150 160 110 130 88 110 PN10 PN6 19 18 185 160 145 130 112 110 PN10 PN6 22 20 185 140 145 110 112 90 PN10 PN6 22 32,5 165 110 125 130 99 67,5 PN10 35,5 118 145 67,5 HCPO 6/6 Low performance due to cavitation T su HCPO 4/5 HCPO 4/7 HCPO 6/6 HCPO 6/8 Pump Types 50°C 75°C 95°C 110°C 120°C 2,1 6,9 9,9 16,2 22,2 1,9 6,8 9,8 16 22 2,9 7,8 11 17 23 3 2,3 3,2 7,9 7,1 8,1 11 10,2 11 17 16,4 17 23 22,4 23 Pump Data Minimum required suction height in 40°C ambient temperature at the suction side of the pump to prevent cavitation noise. (mWc) HCPO-Al 6/13 When there is cavitation in a circulation pump, the following problems arise: Low performance: Since the required flow conditions are not met, pump cannot create the necessary flow rate and pressure. Upper floors cannot be heated. Vibration: Turbulent flow caused by air bubbles causes vibration. Pump life is reduced: Air bubbles in the system or in the pump corrode the pump material causes erosion. Noise: Air bubbles, turbulence and striking of water on surfaces create noise. HCPO 5/10 When the pressure at the suction end of the circulation pump is not enough, water changes phase to turn into gas. Gas bubbles are carried to high pressure areas by the flow. Vapour turns into water again and gas bubbles causes turbulence in the flow and water strikes the surfaces. This process is called cavitation. 124,5 124,5 40 280 220,8 124,5 87 280 221,8 135,5 98,5 340 266,8 4x19 4x14 4x19 Flange 6-10 DN 40 DN100 ( as per DIN 2531 0,48 0,24 0,18 0,63 0,36 0,27 0,86 0,51 0,35 1,07 0,73 0,48 1,37 0,98 0,7 2,4 1,95 1,35 - - - - - - 215 120 80 326 200 153 352 290 240 560 430 270 750 580 420 1420 1200 990 - - - - - - Max. Pumping Head (m) Rated Coupling Diameter Pump Type The right to amend specifications under technologic developments is reserved GOSB-Gebze Organize Sanayi Bölgesi Max. ambient pressure 2430 2070 1860 2260 1950 1700 2900 2820 2700 2820 2680 2440 2670 2390 2080 2740 2490 2190 Nominal Capacitor I(A) Power Capacity 220V Consump. (μF) 50Hz (W) ORDER NOTATION fiahabettin Bilgisu Cad. 41480 Gebze-Kocaeli/TURKEY Motor Motor insulation protection Phone : (90)(262) 648 60 00 PBX Telefax : (90)(262) 648 61 01 120 220,8 I(A) 380V 50Hz For Automatic Speed Controlled Circulation Pumps HCPO 5 / 10 AUTOMATIC SPEED CONTROLLED HCPO 4/5 HCPO 4/7 HCPO 6/6 HCPO 6/8 HCPO 5/10 HCPO-AI 6/13 280 92,5 • Location of usage and liquid; - Clean, cleared of solid particles, - Hot-water heating systems Max. ambient temp. 184 III II I III II I III II I III II I III II I III II I H›z d/d Capacitor voltage of circulation pumps must to be 400 V. TECHNICAL SPECIFICATIONS Max. water temp 250 92,5 80 4x18 4x14 65 HCPO 6/13 185 75 80 4x18 4x14 50 220 71 4x18 4x14 65 HCPO 5/10 65 117,5 65 HCPO 6/8 Q 110,5 44 PN10 PN6 b c h L Speed (mm) (mm) (mm) (mm) Step 4x18 4x14 88 80 HCPO 4/7 H nxm 4x14 80 HCPO 4/5 CAVITATION DN H IP44 ALARKO CARRIER SANAY‹ VE T‹CARET A.fi. web : www.alarko-carrier.com.tr e-mail : info@alarko-carrier.com.tr A.7.1.4i 220811 MiNERAL Do not operate the pump without water. NEVER LUBRICATE THE PUMP Rods and bearings of ALARKO circulation pumps are water lubricated and they do not need maintenance. New or idle pump rods may be throttled due to the pollutants and particles in the water. In such cases, close the main electric switch. Remove the rotor end cap and rotate the shaft a few rounds via screwdriver. Put the rotor end cap in place and operate the pump. Single speed pumps can be modified into three speed pumps by way of an adaptor. Notify this in your orders. PUMP SELECTION It is essential to know the flow rate (Q) and necessary pressure (Hm) value for the selection of circulation pump. These values are given in the heating project of the building and circulation pump selection is made according to these values. If no heating project is available, the following evaluation methods can be applied for pump selection. • Full conformity with Regulation for Energy-Performance Buildings clause 12/6 • Thermal protection • Counter rotation warning and protection • Locked rotor detection and fault signal • Missing phase and phase sequence control • IP44 protection class GENERAL SELECTION CHART FOR AUTOMATIC SPEED CONTROLLED CIRCULATION PUMPS H(m) Enhanced, superior features in HCPO types. Evaluation of the Necessary Flow Rate (Q) The pump should be able to carry the heated water from the boiler to the radiators with a suitable flow rate. Flow rate is determined using the formula below; Q Qk Tg Td High reliability and long life cycle through control algorithm varying according to fluctuating mains supply. : Necessary pump flow rate (m3/hour) : The capacity of the boiler (kcal/hour) : The temperature of water flowing out of the boiler (°C) : The temperature of water returning to the boiler (°C) A Qk • Remote control • On-demand automatic or manual speed control • Connecting operating signal light with external signal light Q= (Tg – Td) x 1.000 Q(m3/h) Evaluation of the Required Pressure (Hm) The pump should have sufficient pressure to be able to push the water to the most distant point of the installation by defeating the resistance of the heating installation. Here, the pump should defeat the total pressure that is caused by the resistance of the pipes, connection components, valves, radiators. While the same water height will be at the inlet and outlet of the pump, the height of the building has no effect to the pump selection procedure. ensure high comfort. INDEPENDENT CHARACTERISTIC CURVES FOR AUTOMATIC SPEED CONTROLLED CIRCULATION PUMPS H (mVc) H R L Z For Q=16-m3/h, H=5 mSS; a point (A) is available in “General Selection Chart for Automatic speed controlled Circulation Pumps” as specified in selection example of one-speed circulation pumps. Point (A) is in the zone of HCP0-Al 6-8 type of pump. This type of pump will be selected. In order to determine speed level of the pump, point (A) will be marked on the curve of HCPO- Al 6-8 type among “Independent Characteristic Curves of Automatic Speed Controlled Circulation Pumps”. For the values in the example, point (A) is in the centre of speed curves (II) and (III). Pump selection can be made. H (mVc) : Pump pressure (mWc) : Pressure loss per square meter at pipe diameter (mWc/meter) : Total lengths of pipe components in the installation (meter) : Resistance of connection components, valves and special devices (mWc) H ≥ ∑ (R x L) + ∑ (Z) If the project of the building is not available, it is almost impossible to determine correctly the values mentioned above. In this case, following tables can be used to determine the required pressure approximately. 2. Pump casing Cast iron GG 20 3. Rotor can Stainless steel 4. Impeller Noryl 5. Bearings Radial - Carbon / Axial - Stainless steel 6. O-ring CR 7. Shaft Stainless steel 8. Rotor and cap Brass 9. Stator windings Enamelled copper wire 4 5 6 7 8 9 New design pump shaft is splined, and fixing will be carried out using a segment after fitting fan onto pump. Therefore, fan and shaft can easily be detached from one another on demand. It is approved and certified by the Netherlands originating independent KEMA organization which test the electromagnetic conformity of electrical devices and has the authority of approval, that our circulation pumps conform to EMC Directive 89/336/EEC. Installation Length Up to 100 meters 500 meters 1000 meters Necessary Pressure of the Pump 1–2 mWc 4–6 mWc 6–12 mWc H (mVc) H (mVc) Q(m3/h) Tsu 50 ºC 75 ºC 95 ºC 110 ºC 120 ºC HCPO 6/13 2 3 HCPO 5/10 GD - AlSi9Cu3 HCPO 6/8 1. Stator housing Necessary Pressure of the Pump 0,5–3 mWc 2–5 mWc 5–10 mWc HCPO 6/6 1 Boiler Capacity Up to 50 kW Between 50-100 kW Above 100 kW HCPO 4/7 NAME OF PART MATERIAL SPECIFICATIONS HCPO 4/5 MAIN PARTS (Standard Type) Q(m3/h) Q(m3/h) 2,1 6,9 9,9 16,2 22,2 1,9 6,8 9,8 16 22 2,9 7,8 11 17 22 3 7,9 11 17 23 2,3 7,1 10 16 22 3,2 8,1 11 17 23 H (mVc) Q(m3/h) H (mVc) A Q(m3/h) Q(m3/h) PUMP SELECTION It is essential to know the flow rate (Q) and necessary pressure (Hm) value for the selection of circulation pump. These values are given in the heating project of the building and circulation pump selection is made according to these values. If no heating project is available, the following evaluation methods can be applied for pump selection. • Full conformity with Regulation for Energy-Performance Buildings clause 12/6 • Thermal protection • Counter rotation warning and protection • Locked rotor detection and fault signal • Missing phase and phase sequence control • IP44 protection class GENERAL SELECTION CHART FOR AUTOMATIC SPEED CONTROLLED CIRCULATION PUMPS H(m) Enhanced, superior features in HCPO types. Evaluation of the Necessary Flow Rate (Q) The pump should be able to carry the heated water from the boiler to the radiators with a suitable flow rate. Flow rate is determined using the formula below; Q Qk Tg Td High reliability and long life cycle through control algorithm varying according to fluctuating mains supply. : Necessary pump flow rate (m3/hour) : The capacity of the boiler (kcal/hour) : The temperature of water flowing out of the boiler (°C) : The temperature of water returning to the boiler (°C) A Qk • Remote control • On-demand automatic or manual speed control • Connecting operating signal light with external signal light Q= (Tg – Td) x 1.000 Q(m3/h) Evaluation of the Required Pressure (Hm) The pump should have sufficient pressure to be able to push the water to the most distant point of the installation by defeating the resistance of the heating installation. Here, the pump should defeat the total pressure that is caused by the resistance of the pipes, connection components, valves, radiators. While the same water height will be at the inlet and outlet of the pump, the height of the building has no effect to the pump selection procedure. ensure high comfort. INDEPENDENT CHARACTERISTIC CURVES FOR AUTOMATIC SPEED CONTROLLED CIRCULATION PUMPS H (mVc) H R L Z For Q=16-m3/h, H=5 mSS; a point (A) is available in “General Selection Chart for Automatic speed controlled Circulation Pumps” as specified in selection example of one-speed circulation pumps. Point (A) is in the zone of HCP0-Al 6-8 type of pump. This type of pump will be selected. In order to determine speed level of the pump, point (A) will be marked on the curve of HCPO- Al 6-8 type among “Independent Characteristic Curves of Automatic Speed Controlled Circulation Pumps”. For the values in the example, point (A) is in the centre of speed curves (II) and (III). Pump selection can be made. H (mVc) : Pump pressure (mWc) : Pressure loss per square meter at pipe diameter (mWc/meter) : Total lengths of pipe components in the installation (meter) : Resistance of connection components, valves and special devices (mWc) H ≥ ∑ (R x L) + ∑ (Z) If the project of the building is not available, it is almost impossible to determine correctly the values mentioned above. In this case, following tables can be used to determine the required pressure approximately. 2. Pump casing Cast iron GG 20 3. Rotor can Stainless steel 4. Impeller Noryl 5. Bearings Radial - Carbon / Axial - Stainless steel 6. O-ring CR 7. Shaft Stainless steel 8. Rotor and cap Brass 9. Stator windings Enamelled copper wire 4 5 6 7 8 9 New design pump shaft is splined, and fixing will be carried out using a segment after fitting fan onto pump. Therefore, fan and shaft can easily be detached from one another on demand. It is approved and certified by the Netherlands originating independent KEMA organization which test the electromagnetic conformity of electrical devices and has the authority of approval, that our circulation pumps conform to EMC Directive 89/336/EEC. Installation Length Up to 100 meters 500 meters 1000 meters Necessary Pressure of the Pump 1–2 mWc 4–6 mWc 6–12 mWc H (mVc) H (mVc) Q(m3/h) Tsu 50 ºC 75 ºC 95 ºC 110 ºC 120 ºC HCPO 6/13 2 3 HCPO 5/10 GD - AlSi9Cu3 HCPO 6/8 1. Stator housing Necessary Pressure of the Pump 0,5–3 mWc 2–5 mWc 5–10 mWc HCPO 6/6 1 Boiler Capacity Up to 50 kW Between 50-100 kW Above 100 kW HCPO 4/7 NAME OF PART MATERIAL SPECIFICATIONS HCPO 4/5 MAIN PARTS (Standard Type) Q(m3/h) Q(m3/h) 2,1 6,9 9,9 16,2 22,2 1,9 6,8 9,8 16 22 2,9 7,8 11 17 22 3 7,9 11 17 23 2,3 7,1 10 16 22 3,2 8,1 11 17 23 H (mVc) Q(m3/h) H (mVc) A Q(m3/h) Q(m3/h) PUMP SELECTION It is essential to know the flow rate (Q) and necessary pressure (Hm) value for the selection of circulation pump. These values are given in the heating project of the building and circulation pump selection is made according to these values. If no heating project is available, the following evaluation methods can be applied for pump selection. • Full conformity with Regulation for Energy-Performance Buildings clause 12/6 • Thermal protection • Counter rotation warning and protection • Locked rotor detection and fault signal • Missing phase and phase sequence control • IP44 protection class GENERAL SELECTION CHART FOR AUTOMATIC SPEED CONTROLLED CIRCULATION PUMPS H(m) Enhanced, superior features in HCPO types. Evaluation of the Necessary Flow Rate (Q) The pump should be able to carry the heated water from the boiler to the radiators with a suitable flow rate. Flow rate is determined using the formula below; Q Qk Tg Td High reliability and long life cycle through control algorithm varying according to fluctuating mains supply. : Necessary pump flow rate (m3/hour) : The capacity of the boiler (kcal/hour) : The temperature of water flowing out of the boiler (°C) : The temperature of water returning to the boiler (°C) A Qk • Remote control • On-demand automatic or manual speed control • Connecting operating signal light with external signal light Q= (Tg – Td) x 1.000 Q(m3/h) Evaluation of the Required Pressure (Hm) The pump should have sufficient pressure to be able to push the water to the most distant point of the installation by defeating the resistance of the heating installation. Here, the pump should defeat the total pressure that is caused by the resistance of the pipes, connection components, valves, radiators. While the same water height will be at the inlet and outlet of the pump, the height of the building has no effect to the pump selection procedure. ensure high comfort. INDEPENDENT CHARACTERISTIC CURVES FOR AUTOMATIC SPEED CONTROLLED CIRCULATION PUMPS H (mVc) H R L Z For Q=16-m3/h, H=5 mSS; a point (A) is available in “General Selection Chart for Automatic speed controlled Circulation Pumps” as specified in selection example of one-speed circulation pumps. Point (A) is in the zone of HCP0-Al 6-8 type of pump. This type of pump will be selected. In order to determine speed level of the pump, point (A) will be marked on the curve of HCPO- Al 6-8 type among “Independent Characteristic Curves of Automatic Speed Controlled Circulation Pumps”. For the values in the example, point (A) is in the centre of speed curves (II) and (III). Pump selection can be made. H (mVc) : Pump pressure (mWc) : Pressure loss per square meter at pipe diameter (mWc/meter) : Total lengths of pipe components in the installation (meter) : Resistance of connection components, valves and special devices (mWc) H ≥ ∑ (R x L) + ∑ (Z) If the project of the building is not available, it is almost impossible to determine correctly the values mentioned above. In this case, following tables can be used to determine the required pressure approximately. 2. Pump casing Cast iron GG 20 3. Rotor can Stainless steel 4. Impeller Noryl 5. Bearings Radial - Carbon / Axial - Stainless steel 6. O-ring CR 7. Shaft Stainless steel 8. Rotor and cap Brass 9. Stator windings Enamelled copper wire 4 5 6 7 8 9 New design pump shaft is splined, and fixing will be carried out using a segment after fitting fan onto pump. Therefore, fan and shaft can easily be detached from one another on demand. It is approved and certified by the Netherlands originating independent KEMA organization which test the electromagnetic conformity of electrical devices and has the authority of approval, that our circulation pumps conform to EMC Directive 89/336/EEC. Installation Length Up to 100 meters 500 meters 1000 meters Necessary Pressure of the Pump 1–2 mWc 4–6 mWc 6–12 mWc H (mVc) H (mVc) Q(m3/h) Tsu 50 ºC 75 ºC 95 ºC 110 ºC 120 ºC HCPO 6/13 2 3 HCPO 5/10 GD - AlSi9Cu3 HCPO 6/8 1. Stator housing Necessary Pressure of the Pump 0,5–3 mWc 2–5 mWc 5–10 mWc HCPO 6/6 1 Boiler Capacity Up to 50 kW Between 50-100 kW Above 100 kW HCPO 4/7 NAME OF PART MATERIAL SPECIFICATIONS HCPO 4/5 MAIN PARTS (Standard Type) Q(m3/h) Q(m3/h) 2,1 6,9 9,9 16,2 22,2 1,9 6,8 9,8 16 22 2,9 7,8 11 17 22 3 7,9 11 17 23 2,3 7,1 10 16 22 3,2 8,1 11 17 23 H (mVc) Q(m3/h) H (mVc) A Q(m3/h) Q(m3/h) PIPE CONNECTIONS AND DIMENSIONS INSTALLATION POSITIONS NOT PERMITTED PERMITTED Automatic Speed Controlled Pump shaft must not be vertical position. Pump shaft must be parallel position. Circulation Pumps Connect the pump to the installation as shown in the figure by making it parallel to the ground. Use isolating valves in the inlet and outlet in order to facilitate the removal of pump during repair or maintenance. Use a thermic relay when connecting the pump to electric supply. CORRECT OPERATION PUMP TYPE PN6 øk ød Weight øD (mm) (mm) (mm) ~(kg) 9 130 100 40 PN10 PN6 10 12,5 150 130 110 100 14 18 150 160 110 130 88 110 PN10 PN6 19 18 185 160 145 130 112 110 PN10 PN6 22 20 185 140 145 110 112 90 PN10 PN6 22 32,5 165 110 125 130 99 67,5 PN10 35,5 118 145 67,5 HCPO 6/6 Low performance due to cavitation T su HCPO 4/5 HCPO 4/7 HCPO 6/6 HCPO 6/8 Pump Types 50°C 75°C 95°C 110°C 120°C 2,1 6,9 9,9 16,2 22,2 1,9 6,8 9,8 16 22 2,9 7,8 11 17 23 3 2,3 3,2 7,9 7,1 8,1 11 10,2 11 17 16,4 17 23 22,4 23 Pump Data Minimum required suction height in 40°C ambient temperature at the suction side of the pump to prevent cavitation noise. (mWc) HCPO-Al 6/13 When there is cavitation in a circulation pump, the following problems arise: Low performance: Since the required flow conditions are not met, pump cannot create the necessary flow rate and pressure. Upper floors cannot be heated. Vibration: Turbulent flow caused by air bubbles causes vibration. Pump life is reduced: Air bubbles in the system or in the pump corrode the pump material causes erosion. Noise: Air bubbles, turbulence and striking of water on surfaces create noise. HCPO 5/10 When the pressure at the suction end of the circulation pump is not enough, water changes phase to turn into gas. Gas bubbles are carried to high pressure areas by the flow. Vapour turns into water again and gas bubbles causes turbulence in the flow and water strikes the surfaces. This process is called cavitation. 124,5 124,5 40 280 220,8 124,5 87 280 221,8 135,5 98,5 340 266,8 4x19 4x14 4x19 Flange 6-10 DN 40 DN100 ( as per DIN 2531 0,48 0,24 0,18 0,63 0,36 0,27 0,86 0,51 0,35 1,07 0,73 0,48 1,37 0,98 0,7 2,4 1,95 1,35 - - - - - - 215 120 80 326 200 153 352 290 240 560 430 270 750 580 420 1420 1200 990 - - - - - - Max. Pumping Head (m) Rated Coupling Diameter Pump Type The right to amend specifications under technologic developments is reserved GOSB-Gebze Organize Sanayi Bölgesi Max. ambient pressure 2430 2070 1860 2260 1950 1700 2900 2820 2700 2820 2680 2440 2670 2390 2080 2740 2490 2190 Nominal Capacitor I(A) Power Capacity 220V Consump. (μF) 50Hz (W) ORDER NOTATION fiahabettin Bilgisu Cad. 41480 Gebze-Kocaeli/TURKEY Motor Motor insulation protection Phone : (90)(262) 648 60 00 PBX Telefax : (90)(262) 648 61 01 120 220,8 I(A) 380V 50Hz For Automatic Speed Controlled Circulation Pumps HCPO 5 / 10 AUTOMATIC SPEED CONTROLLED HCPO 4/5 HCPO 4/7 HCPO 6/6 HCPO 6/8 HCPO 5/10 HCPO-AI 6/13 280 92,5 • Location of usage and liquid; - Clean, cleared of solid particles, - Hot-water heating systems Max. ambient temp. 184 III II I III II I III II I III II I III II I III II I H›z d/d Capacitor voltage of circulation pumps must to be 400 V. TECHNICAL SPECIFICATIONS Max. water temp 250 92,5 80 4x18 4x14 65 HCPO 6/13 185 75 80 4x18 4x14 50 220 71 4x18 4x14 65 HCPO 5/10 65 117,5 65 HCPO 6/8 Q 110,5 44 PN10 PN6 b c h L Speed (mm) (mm) (mm) (mm) Step 4x18 4x14 88 80 HCPO 4/7 H nxm 4x14 80 HCPO 4/5 CAVITATION DN H IP44 ALARKO CARRIER SANAY‹ VE T‹CARET A.fi. web : www.alarko-carrier.com.tr e-mail : info@alarko-carrier.com.tr A.7.1.4i 220811 MiNERAL Do not operate the pump without water. NEVER LUBRICATE THE PUMP Rods and bearings of ALARKO circulation pumps are water lubricated and they do not need maintenance. New or idle pump rods may be throttled due to the pollutants and particles in the water. In such cases, close the main electric switch. Remove the rotor end cap and rotate the shaft a few rounds via screwdriver. Put the rotor end cap in place and operate the pump. Single speed pumps can be modified into three speed pumps by way of an adaptor. Notify this in your orders. PIPE CONNECTIONS AND DIMENSIONS INSTALLATION POSITIONS NOT PERMITTED PERMITTED Automatic Speed Controlled Pump shaft must not be vertical position. Pump shaft must be parallel position. Circulation Pumps Connect the pump to the installation as shown in the figure by making it parallel to the ground. Use isolating valves in the inlet and outlet in order to facilitate the removal of pump during repair or maintenance. Use a thermic relay when connecting the pump to electric supply. CORRECT OPERATION PUMP TYPE PN6 øk ød Weight øD (mm) (mm) (mm) ~(kg) 9 130 100 40 PN10 PN6 10 12,5 150 130 110 100 14 18 150 160 110 130 88 110 PN10 PN6 19 18 185 160 145 130 112 110 PN10 PN6 22 20 185 140 145 110 112 90 PN10 PN6 22 32,5 165 110 125 130 99 67,5 PN10 35,5 118 145 67,5 HCPO 6/6 Low performance due to cavitation T su HCPO 4/5 HCPO 4/7 HCPO 6/6 HCPO 6/8 Pump Types 50°C 75°C 95°C 110°C 120°C 2,1 6,9 9,9 16,2 22,2 1,9 6,8 9,8 16 22 2,9 7,8 11 17 23 3 2,3 3,2 7,9 7,1 8,1 11 10,2 11 17 16,4 17 23 22,4 23 Pump Data Minimum required suction height in 40°C ambient temperature at the suction side of the pump to prevent cavitation noise. (mWc) HCPO-Al 6/13 When there is cavitation in a circulation pump, the following problems arise: Low performance: Since the required flow conditions are not met, pump cannot create the necessary flow rate and pressure. Upper floors cannot be heated. Vibration: Turbulent flow caused by air bubbles causes vibration. Pump life is reduced: Air bubbles in the system or in the pump corrode the pump material causes erosion. Noise: Air bubbles, turbulence and striking of water on surfaces create noise. HCPO 5/10 When the pressure at the suction end of the circulation pump is not enough, water changes phase to turn into gas. Gas bubbles are carried to high pressure areas by the flow. Vapour turns into water again and gas bubbles causes turbulence in the flow and water strikes the surfaces. This process is called cavitation. 124,5 124,5 40 280 220,8 124,5 87 280 221,8 135,5 98,5 340 266,8 4x19 4x14 4x19 Flange 6-10 DN 40 DN100 ( as per DIN 2531 0,48 0,24 0,18 0,63 0,36 0,27 0,86 0,51 0,35 1,07 0,73 0,48 1,37 0,98 0,7 2,4 1,95 1,35 - - - - - - 215 120 80 326 200 153 352 290 240 560 430 270 750 580 420 1420 1200 990 - - - - - - Max. Pumping Head (m) Rated Coupling Diameter Pump Type The right to amend specifications under technologic developments is reserved GOSB-Gebze Organize Sanayi Bölgesi Max. ambient pressure 2430 2070 1860 2260 1950 1700 2900 2820 2700 2820 2680 2440 2670 2390 2080 2740 2490 2190 Nominal Capacitor I(A) Power Capacity 220V Consump. (μF) 50Hz (W) ORDER NOTATION fiahabettin Bilgisu Cad. 41480 Gebze-Kocaeli/TURKEY Motor Motor insulation protection Phone : (90)(262) 648 60 00 PBX Telefax : (90)(262) 648 61 01 120 220,8 I(A) 380V 50Hz For Automatic Speed Controlled Circulation Pumps HCPO 5 / 10 AUTOMATIC SPEED CONTROLLED HCPO 4/5 HCPO 4/7 HCPO 6/6 HCPO 6/8 HCPO 5/10 HCPO-AI 6/13 280 92,5 • Location of usage and liquid; - Clean, cleared of solid particles, - Hot-water heating systems Max. ambient temp. 184 III II I III II I III II I III II I III II I III II I H›z d/d Capacitor voltage of circulation pumps must to be 400 V. TECHNICAL SPECIFICATIONS Max. water temp 250 92,5 80 4x18 4x14 65 HCPO 6/13 185 75 80 4x18 4x14 50 220 71 4x18 4x14 65 HCPO 5/10 65 117,5 65 HCPO 6/8 Q 110,5 44 PN10 PN6 b c h L Speed (mm) (mm) (mm) (mm) Step 4x18 4x14 88 80 HCPO 4/7 H nxm 4x14 80 HCPO 4/5 CAVITATION DN H IP44 ALARKO CARRIER SANAY‹ VE T‹CARET A.fi. web : www.alarko-carrier.com.tr e-mail : info@alarko-carrier.com.tr A.7.1.4i 220811 MiNERAL Do not operate the pump without water. NEVER LUBRICATE THE PUMP Rods and bearings of ALARKO circulation pumps are water lubricated and they do not need maintenance. New or idle pump rods may be throttled due to the pollutants and particles in the water. In such cases, close the main electric switch. Remove the rotor end cap and rotate the shaft a few rounds via screwdriver. Put the rotor end cap in place and operate the pump. Single speed pumps can be modified into three speed pumps by way of an adaptor. Notify this in your orders.