70L-IDC - Grayhill, Inc.

advertisement
DC Input Modules
FEATURES
• Fast Switching Polarized Input
Types
• UL, CSA, CE, TÜV Certified (TÜV
not available on OpenLine ®)
• Optical Isolation
• OpenLine® and G5 Modules have
Built-in Status LED
70L-IDC
70G-IDC
70-IDC
70M-IDC
CIRCUITRY
OpenLine®
Standard, Mini, G5
+
I/O MODULE
PIN #
Rx
1
TYPICAL WIRING FOR MODULE 0
VDC
2
INPUT
DEVICE
1
1
FILTER
OPTICAL
ISOLATION
FILTER
OPTICAL
ISOLATION
–
+VCC
3
INPUT
VOLTAGE
HYST. CIRC.
CURRENT
REGULATING
OUTPUT
INPUT
DEVICE
+
2
2
3
3
+
DC
SUPPLY
4
–
GROUND
5
4
4
TERMINAL
BLOCK #
Status LED in G5 modules only.
6
Vcc
A
+
HYSTERESIS
B
7
CH. A STATUS
5
GND
8
CH. B STATUS
9
MODULE ID
HYSTERESIS
–
BASE
OR
RACK
0Ω
MODULE
SPECIFICATIONS: By Package Style
Package Style
I/O Modules
1
2
3
Specifications
Units
Output Current Range
Minimum Output Breakdown Voltage
Isolation Voltage1
Vibration2
Mechanical Shock3
Storage Temp. Range
Operating Temp. Range
Warranty
mA
Vdc
Vrms
°C
°C
Std (70-)
Mini (70M-)
G5 (70G-)
OL (70L-)
1-50
50
4000
MIL-STD-202
MIL-STD-202
-40 to 125
-40 to 100
Lifetime
1-50
50
4000
MIL-STD-202
MIL-STD-202
-40 to 125
-40 to 100
Lifetime
1-50
50
4000
MIL-STD-202
MIL-STD-202
-40 to 125
-40 to 100
Lifetime
1-50
50
2500
IEC68-2-6
IEC68-2-27
-40 to 100
-40 to 85
Lifetime
Field to logic and channel-to-channel if Grayhill racks are used.
MIL-STD-202, Method 204, 20G, 10-2000 Hz or IEC68-2-6, 0.15 mm/sec2, 10-150 Hz.
MIL-STD-202, Method 213, Condition F, 1500G or IEC68-2-27, 11 mS, 15g.
I/O
18
Grayhill, Inc. • 561 Hillgrove Avenue • LaGrange, Illinois
60525-5997 • USA • Phone: 708-354-1040 • Fax: 708-354-2820 • www.grayhill.com
DC Input Modules
SPECIFICATIONS: By Part Number
Standard and Miniature Modules
Type/Function
Grayhill Part Number
Miniature, Polarized
Standard, Non-Polarized
Specifications
Units
Maximum Input Voltage
Input Voltage Range1
Input Current @ Maximum Input Voltage
Maximum Turn-On Time
Maximum Turn-Off Time
Nominal Input Resistance (Rx)
Maximum Pick-Up Voltage (Output Low)
Minimum Drop-Out Voltage (Output High)
Nominal Logic Voltage (Vcc)
Logic Voltage Range
Max. Logic Supply Current @ Nominal Vcc
Vdc
Vdc
mA
mSec
mSec
Ω
Vdc
Vdc
Vdc
Vdc
mA
70M-IDC5
70-IDC5
70-IDC5B
32
3-32
18
0.20
0.40
1.8K
3
1
5
3-6
10
32
3-32
18
0.050
0.075
1.8K
3
1
5
3-6
18
70-IDC5K
16
2.5-16
30
0.025
0.030
500
2.5
1
5
3.5-6
18
70M-IDC15
70-IDC15
32
3-32
18
0.20
0.40
1.8K
3
1
15
8-18
10
70M-IDC24
70-IDC24
32
3-32
18
0.20
0.40
1.8K
3
1
24
15-30
10
G5 Modules
Type/Function
Grayhill Part Number
G5, Polarized, Status LED
70G-IDC5
Specifications
Units
Maximum Input Voltage
Input Voltage Range1
Input Current @ Maximum Input Voltage
Maximum Turn-On Time
Maximum Turn-Off Time
Nominal Input Resistance (Rx)
Maximum Pick-Up Voltage (Output Low)
Minimum Drop-Out Voltage (Output High)
Nominal Logic Voltage (Vcc)
Logic Voltage Range
Max. Logic Supply Current @ Nominal Vcc
Vdc
Vdc
mA
mSec
mSec
Ω
Vdc
Vdc
Vdc
Vdc
mA
32
3-32
18
0.20
0.40
1.8K
3
1
5
4.5-6
10
70G-IDC5B
70G-IDC5D 70G-IDC5K
32
3-32
18
0.050
0.075
1.8K
3
1
5
4.5-6
18
28
2.5-28
23
0.050
0.075
1.2K
2.5
1
5
4.5-6
10
16
2.5-16
30
0.025
0.030
500
2.5
1
5
4.5-6
18
70G-IDC15 70G-IDC24
32
3-32
18
0.20
0.40
1.8K
3
1
15
10-18
10
32
3-32
18
0.20
0.40
1.8K
3
1
24
17-30
10
OpenLine® Modules
Type/Function
Grayhill Part Number
Dual, Polarized
70L-IDCB
Specifications
Units
Maximum Input Voltage
Input Voltage Range1
Input Current @ Max. Input Voltage
Maximum Turn-on Time
Maximum Turn-off Time
Nominal Input Resistance (Rx)
Maximum Pick-Up Voltage (Output Low)
Minimum Drop-Out Voltage (Output High)
Nominal Logic Voltage (Vcc)
Logic Voltage Range
Max. Logic Supply Current
@ Nominal Vcc
Module ID Resistance to Logic Ground
Vdc
Vdc
mA
mSec
mSec
Ω
Vdc
Vdc
Vdc
Vdc
32
0-32
18
0.20
0.40
1800
3
0.9
5
4.5-28
32
0-32
18
0.05
0.075
900
3
0.9
5
4.5-28
mA
Ω
6/CH
0
6/CH
0
I/O Modules
1
70L-IDC
Available from your local Grayhill Distributor.
For prices and discounts, contact a local Sales
Office, an authorized local Distributor or Grayhill.
For input voltages in the range of 90 to 140 Vdc, use AC input modules 70-IAC5, 70M-IAC5,
70G-IAC5 or 70L-IAC. For input voltages in the range of 180 to 280 Vdc, use AC input modules
70-IAC5A, 70M-IAC5A, 70G-IAC5A or 70L-IACA.