Powerohm Instruction Manual for Type PW-NC High Current Braking Modules Part Numbers Covered: PWA450NC, PWA600NC, PWA900NC, PWA1200NC PWB450NC, PWB600NC, PWB900NC, PWB1200NC PWC450NC, PWC600NC, PWC900NC, PWC1200NC PWD450NC, PWD600NC, PWD900NC, PWD1200NC PWE450NC, PWE600NC, PWE900NC, PWE1200NC Technical Assistance: +01-859-384-8088 IMPORTANT: These instructions should be read thoroughly before installation. All warnings and precautions should be observed for both personal safety and for proper equipment performance and longevity. Failure to follow these instructions could result in equipment failure and/or serious injury to personnel. Braking modules contain lethal voltages when connected to the inverter. It is very important to remove power to the inverter before installing or servicing this unit. Always allow adequate time (approximately 5 minutes) after removing power before touching any components. The LED’s must be completely out before servicing the unit. product Overview AC variable frequency drives are commonly used with general purpose AC induction motors to form reliable variable speed drive systems. Problems with these drive systems can occur when an application requires a deceleration rate faster than what can be managed by the drive alone, or when motor speeds exceed the synchronous speed set by the output frequency of the drive (which is called an overhauling load condition). Both of these conditions create regenerated power which flows from the motor back into the drive, causing its DC Bus to rise. To manage the regenerated power and avoid shutting the drive down due to an over-voltage trip, this power must be dissipated by an external braking resistor. Powerohm Type BM Braking Modules can be used in conjunction with any AC drive to monitor the DC bus of the drive and activate external braking resistor as needed not only to avoid over-voltage trips, but to greatly improve the performance of the drive system. The use of Braking Modules and resistors increase the braking torque capability of a variable frequency drive, allowing faster and more controlled deceleration times. To accommodate system horsepower requirements beyond the capability of a single Module, the Modules are all Master/Slave programmable. This allows an arrangement of multiple Modules to effectively function as a single higher rated module. Technical Assistance: +01-859-384-8088 Inspection upon Receipt Upon receipt of your Powerohm Braking Module, be sure to carefully unpack the module and inspect the unit carefully for any shipping damage. The module contains electronics that can be damaged by static electricity, so handle in accordance with industry standards. Check for loose, broken or otherwise damaged parts due to shipping. Report any shipping damage immediately to the freight carrier. Be sure to verify that the part number and ratings listed on the nameplate match the order specification and the capabilities of the drive system. The ratings listed on the nameplate are critical – installing and energizing the incorrect part number could damage the braking module and/or the drive! Environmental Conditions The Powerohm Type BM Braking Module should be installed in an environment protected from moisture and excessive dust. Dust buildup can reduce the electrical insulation characteristics of the unit and moisture can cause arching or shorting. Air must be free of combustible gases and corrosive vapors. Ambient Temperature Range: -10ºC to 40ºC Maximum Altitude: 3300 feet (1000m) Electrical Ratings The Powerohm Type BM Braking Module is available in line voltages ranging from 208 to 720 volts. Peak currents up to the maximum are allowed at intermittent duty cycles (reference the below tables for details). TABLE 1: General Specifications for 450 amp Type BM Braking Modules Powerohm Part Number Nominal AC Line Voltage PWA-450NC 240 450 375 600 PWB-450NC 480 450 750 600 PWC-450NC 600 450 940 600 PWD-450NC 690 450 1090 600 PWE-450NC 720 450 1120 600 RMS Continuous Turn ON Load Current Voltage Max Peak Current Technical Assistance: +01-859-384-8088 TABLE 2: General Specifications for 600 amp Type BM Braking Modules Powerohm Part Number Nominal AC Line Voltage PWA-600NC 240 600 375 900 PWB-600NC 480 600 900 PWC-600NC 600 600 750 940 PWD-600NC 690 600 1090 900 PWE-600NC 720 600 1120 900 RMS Continuous Turn ON Load Current Voltage Max Peak Current 900 TABLE 3: General Specifications for 900 amp Type BM Braking Modules Powerohm Part Number Nominal AC Line Voltage PWA-900NC 240 900 375 1350 PWB-900NC 480 900 750 1350 PWC-900NC 600 900 940 1350 PWD-900NC 690 900 1090 1350 PWE-900NC 720 900 1120 1350 RMS Continuous Turn ON Load Current Voltage Max Peak Current TABLE 4: General Specifications for 1200 amp Type BM Braking Modules Powerohm Part Number Nominal AC Line Voltage RMS Continuous Turn ON Load Current Voltage Max Peak Current PWA-1200NC 240 1200 375 1800 PWB-1200NC 480 1200 750 1800 PWC-1200NC 600 1200 940 1800 PWD-1200NC 690 1200 1090 1800 PWE-1200NC 720 1200 1120 1800 Technical Assistance: +01-859-384-8088 Equipment Installation The Powerohm Type BM Braking Module should be installed on a low vibration surface that is non-flammable. Maximum Vibration: 10 to 20Hz, 32ft/sec/sec; 20 to 50Hz, 6.5 ft/sec/sec Attention: Installation and removal of this equipment should be done by qualified personnel only. Equipment must be installed in accordance with all applicable national and local electrical codes and regulations. MOUNTING REQUIREMENTS To allow proper cooling, it is very important to install the fan cooled Powerohm braking modules in an ambient not exceeding 40 degrees Celsius or below 0 degrees Celsius. Modules should be installed in an environment with sufficient circulation of clean, dry air. The module should be installed in an area allowing a minimum of 6 inches of free space above and below the frame to allow proper airflow and cooling. Technical Assistance: +01-859-384-8088 DIMENSIONS FOR 450 AMP AND 600 AMP MODULES DC POWER CONNECTIONS Remove this protective cover to access both the DC bus and braking resistor connections. W CONTR OL POWER DC BUS BRAKE AC TIVE CONTR OL ENABLED FAU LT POWEROHM BRAKING MODULE 19.00 20.00 20.00 DANGER: HIGH VOLTAGE Braking module contains lethal voltages when connected to the inverter. Power to the inverter must be removed before servicing the braking module. Allow adequate time (approximately 5 minutes ) after removing power before touching any components. Both the CONTROL POWER and DC BUS indicators must be completely out before servicing the unit. CONTROL POWER CONNECTIONS Remove this protective cover to access all control power and logic connections. 5.00 7.13 5/16 SLOTS 10.00 10.00 7.13 Weight: The weight of the unit is approximately 30 lbs. Technical Assistance: +01-859-384-8088 DIMENSIONS FOR 900 AMP AND 1200 AMP MODULES DC POWER CONNECTIONS Remove this protective cover to access both the DC bus and braking resistor connections. W POWEROHM BRAKING MODULE CONTROL POWER DC BUS BRAKE ACTIVE 23.00 24.00 24.00 CONTROL ENABLED FAULT DANGER: HIGH VOLTAGE Braking module contains lethal voltages when connected to the inverter. Power to the inverter must be removed before servicing the braking module. Allow adequate time (approximately 5 minutes) after removing power before touching any components. Both the CONTROL POWER and DC BUS indicators must be completely out before servicing the unit. CONTROL POWER CONNECTIONS Remove this protective cover to access all control power and logic connections. 7.00 10.06 7/16 SLOTS 10.00 10.00 10.06 Weight: The weight of the unit is approximately 55 lbs. Technical Assistance: +01-859-384-8088 WIRING RECOMMENDATIONS It is recommended that the AC drive manual, braking resistor instructions and any other pertinent documentation be thoroughly reviewed before proceeding. Note that control and power wiring should be separated to avoid electrical noise and interference problems. The wiring between the drive and braking module should not exceed 15 feet and between the braking resistor and braking module should not exceed 30 feet. Important: Always properly ground each module to earth. If possible, ground Braking Module to AC Drive Module Power ground. Figure 3: Wiring Lengths Between Drive System Components DC POWER CONNECTIONS Remove this protective cover to access both the DC bus and braking resistor connections. W CONTROL POWER DC BUS BRAKE ACTIVE CONTROL ENABLED FAU LT POWEROHM BRAKING MODULE DANGER: HIGH VOLTAGE Braking module contains lethal voltages when connected to the inverter. Power to the inverter must be removed before servicing the braking module. Allow adequate time (approximately 5 minutes) after removing power before touching any components. Both the CONT ROL POWER and DC BUS indicators must be completely out before serv ic ing the unit. CONTROL POWER CONNECTIONS DC+ DC- Remove this protective cover to access all control power and logic connections. 30 ft. max 15 ft. max WARNING: Never install a braking resistor directly across the DC bus of the drive. Drive damage or failure may occur upon applied power. Additionally, without the braking module to activate and deactivate the braking resistor, the resistor will dissipate power continuously and be subject to overheating and failure. Technical Assistance: +01-859-384-8088 POWER CONNECTIONS The Powerohm Type BM Braking Module features a total of five power connections. Reference Table 5 for a description of each terminal’s function. ATTENTION: The National Electric Code (NEC) and local regulations govern the installation and wiring of electrical equipment such as braking resistors and modules. DC power wiring, AC power wiring, control wiring and conduit must be installed in accordance with all applicable codes and regulations. TABLE 5: Description of Power Connections Max.Torque Terminal Terminal Description (lb-ft) for Number 450A/600A Max.Torque (lb-ft) for 900A/1200A DC - DC Bus Connection (Negative) 20 50 DC+ DC Bus Connection (Positive) 20 50 G Ground Connection 6 50 RES Braking Resistor Connection 20 50 RES Braking Resistor Connection 20 50 Technical Assistance: +01-859-384-8088 CONTROL CONNECTIONS The Powerohm Type BM Braking Module features three terminal blocks for all input, output and control power wiring. All three terminal blocks are located at the bottom of the braking module, above the fan compartment and accept 30 to 14 gage wire. The outputs are located on TB1 featuring 16 poles. The inputs are located on TB2 featuring 12 poles. The control power (115VAC) terminations are located on TB3 featuring 2 poles. Reference Tables 6, 7 and 8 for a description of all terminations. TABLE 6: OUTPUT TERMINATIONS Terminal Number Maximum Torque (lb-in) Terminal Description (TB1) 1 Control Enabled 2.2 2 Control Enabled 2.2 3 Power Section Ready 2.2 4 Power Section Ready 2.2 5 Master Slave Status 2.2 6 Master Slave Status 2.2 7 Instantaneous Over Current Protection (IOC) 2.2 8 Instantaneous Over Current Protection (IOC) 2.2 9 IOV/ IUV 2.2 10 IOV/ IUV 2.2 11 OT 2.2 12 OT 2.2 13 SUPPLY VALID 2.2 14 SUPPLY VALID 2.2 15 IGBT SHORTED 2.2 16 IGBT SHORTED 2.2 The Output Contacts are rated 170mA maximum (250VAC or DC). Technical Assistance: +01-859-384-8088 TABLE 7: INPUT TERMINATIONS Terminal Number Maximum Torque (lb-in) Terminal Description (TB2) 1 Enable 2.2 2 Common 2.2 3 Master or Slave Select 2.2 4 Common 2.2 5 IOC/ IOV, IUV Reset 2.2 6 Common 2.2 7 DC Bus Discharge 2.2 8 Common 2.2 9 Signal +IN/ OUT 2.2 10 Signal +IN/ OUT 2.2 11 Signal Common 2.2 12 Signal Common 2.2 The Inputs are activated via contact closure. Contacts should be rated at 10mA (24VDC). TABLE 8: CONTROL POWER TERMINATIONS Terminal Number Terminal Description (TB3) Maximum Torque (lb-in) 1 115VAC Input Power 2.2 2 115VAC Input Power 2.2 The control power input requires 115VAC (1.0 amp). Technical Assistance: +01-859-384-8088 MINIMUM RECOMMENDED TB2 INPUT CONNECTIONS USED WITH OPTIONAL COMMUNICATION MODULES (PROFIBUS, ETHERNET, DEVICENET, ETC.) ENABLE 1 2 CLOSE TO ENABLE MASTER/ SLAVE SELECT 3 4 CLOSE TO SELECT MASTER FAULT RESET 5 DISCHARGE 6 PUSH TO RESET 7 8 CLOSE TO DISCHARGE NOTE: DISCHARGE INPUT FUNCTIONS ONLY IN MASTER MODE. WARNING: It is important to check the DC Bus Voltage before servicing a braking module. Do not fully rely upon the DC Bus Discharge feature as an absolute means of discharging the DC Bus. Technical Assistance: +01-859-384-8088 TYPICAL MASTER SLAVE TB2 WIRING CONNECTIONS 9 MASTER SLAVE SLAVE SIGNAL SIGNAL SIGNAL 10 11 12 9 10 11 12 9 10 11 12 CONTINUES TO OTHER SLAVES IF PRESENT SIGNAL NOTE: Braking modules should be no closer together than 6 inches to allow for adequate cooling. Interconnecting wiring should not exceed 5 feet between modules. Technical Assistance: +01-859-384-8088 TYPICAL MASTER SLAVE FIBER OPTIC CONNECTIONS MASTER SLAVE SLAVE FIBER OPTIC FIBER OPTIC FIBER OPTIC TX RX TX RX TX RX CONTINUES TO OTHER SLAVES IF PRESENT TABLE 9: FIBER OPTIC SPECIFICATIONS Component Specification Maximum Torque (lb-in) CABLE 1mm plastic, 60 ft. maximum length 9 CONNECTOR SMA (Threaded Connection Type) 9 NOTE: Slave will produce a TX pulse even if fed from the Master or previous Slave via copper signal connections. Technical Assistance: +01-859-384-8088 Optional communication modulES – profibus & ETHERNET COMMUNICATION MODULE INPUTS AND OUTPUTS TABLE 10: COMMUNICATION MODULE INPUTS Input Description 1 Enable 2 Master or Slave Select 3 Fault Reset 4 DC Bus Discharge TABLE 11: COMMUNICATION MODULE OUTPUTS Output Description 1 Control Enabled 2 Power Section Ready 3 Master Slave Status 4 Instantaneous Over Current Protection (IOC) 5 IOV/ IUV 6 OT 7 SUPPLY VALID 8 IGBT SHORTED Technical Assistance: +01-859-384-8088 Note: Reference appropriate Phoenix Contact Instruction Manual available through Powerohm or online at phoenixcontact.com. OPTIONAL INLINE PROFIBUS COUPLER Technical Assistance: +01-859-384-8088 CONNECTING TO THE PROFIBUS MODULE Technical Assistance: +01-859-384-8088 OPTIONAL INLINE ETHERNET/IP BUS COUPLER Technical Assistance: +01-859-384-8088 CONNECTING TO THE OPTIONAL ETHERNET MODULE Technical Assistance: +01-859-384-8088 Technical Assistance: +01-859-384-8088 Module Setup JUMPER SETTINGS The Powerohm Type BM Braking Module has eight jumper settings located on the main control board that are accessible by removing the center front cover that contains the LED indicators. The 8 position program jumper is located in the top right corner of the main control board. The jumper allows for a wide range of drive input voltages as listed in Table 12. Note that the measurement of line voltage should be done by qualified personnel only. Do not make jumper changes while the power is applied! Note: Generally speaking, it is best to operate the module with the highest allowable jumper setting to allow for upward drift of the AC line during lightly loaded conditions. This will minimize the possibility of the upward drift causing unnecessary action from the braking module. TABLE 12 Description of Jumper Settings Jumper Position Line Voltage DC Bus Voltage 1 208VAC 336VDC 2 240VAC 390VDC 3 380VAC 612VDC 4 415VAC 670VDC 5 480VAC 775VDC 6 600VAC 970VDC 7 690VAC 1090VDC 8 710VAC 1120VDC Warning: Do not make jumper changes while power is applied! Change as required only when power is removed and the green power indicator and amber dc bus indicator is off! Technical Assistance: +01-859-384-8088 Module Setup Power Connections for a Single Braking Module Braking Resistor Braking Module A.C. Drive L1 THERMAL SWITCH TO DRIVE LOGIC DC POWER CONNECTIONS L2 Remove this protective cover to access both the DC bus and braking resistor connections. L3 W CO NTR OL POW ER DC BUS BRAKE ACTIVE CO NTR OL ENABL ED FAULT RES RES POWEROHM BRAKING MODULE T1 DANGER: HIGH VOLTAGE B raking module contains lethal voltages when connected to the inverter. Power to the inverter m ust be removed before servicing the braking module. Allow adequate time ( approxim ately 5 minutes) after r emoving power before touching any c omponents. B oth the CONTROL P OWE R and DC BUS indic ators m ust be com pletely out before ser vicing the unit. T2 AC MOTOR T3 CONTROL POWER CONNECTIONS DC+ DC- Remove this protective cover to access all control power and logic connections. Wiring Notes: All DC power wiring between the drive, braking module and braking resistor should be twisted (if possible) and run separate from all control wiring. All control wiring must be twisted and run separate from all power wiring. Technical Assistance: +01-859-384-8088 Power Connections for Multiple Braking Modules Braking Resistor Braking Module A.C. Drive L1 THERMAL SWITCH TO DRIVE LOGIC DC POWER CONNECTIONS L2 Re move t his pr ot ect ive co ve r to ac ces s bo th the D C b us an d b ra kin g r es isto r c on ne ction s. L3 W CO NTRO L POW ER DC BUS BRAKE ACTIVE CO NTRO L ENABLED FAUL T RES RES POWEROHM BRAKING M ODULE T1 DANG ER: HIGH VOLT AG E Brakin g mod ule con tains leth al voltage s wh en c onnect ed to the inve rter. Po wer to the inve rter must b e rem oved befor e ser vicing the b raking modu le . Allow ad equa te time (app roxima tely 5 m in utes) after r emoving power befor e tou ching a ny comp onen ts. Both the CONT RO L POWER an d DC BUS indicat ors m ust be complet ely out b efor e servicing the u nit. T2 AC MOTOR T3 CONTROL POWER CONNECTIONS DC+ DC- R emov e th is p ro te ctive c ov er to a cce ss a ll con tr ol p ow er an d log ic co nn ec tion s. THERMAL SWITCH TO DRIVE LOGIC DC POWER CONNECTIONS Re move t his pr ot ect ive co ve r to ac ces s bo th the D C b us an d b ra kin g r es isto r c on ne ction s. W CO NTRO L POW ER DC BUS BRAKE ACTIVE CO NTRO L ENABLED FAUL T RES RES POWEROHM BRAKING M ODULE DANG ER: HIGH VOLT AG E Brakin g mod ule con tains leth al voltage s wh en c onnect ed to the inve rter. Po wer to the inve rter must b e rem oved befor e ser vicing the b raking modu le . Allow ad equa te time (app roxima tely 5 m in utes) after r emoving power befor e tou ching a ny comp onen ts. Both the CONT RO L POWER an d DC BUS indicat ors m ust be complet ely out b efor e servicing the u nit. CONTROL POWER CONNECTIONS R emov e th is p ro te ctive c ov er to a cce ss a ll con tr ol p ow er an d log ic co nn ec tion s. THERMAL SWITCH TO DRIVE LOGIC DC POWER CONNECTIONS Re move t his pr ot ect ive co ve r to ac ces s bo th the D C b us an d b ra kin g r es isto r c on ne ction s. W CO NTRO L POW ER DC BUS BRAKE ACTIVE CO NTRO L ENABLED FAUL T RES RES POWEROHM BRAKING M ODULE DANG ER: HIGH VOLT AG E Brakin g mod ule con tains leth al voltage s wh en c onnect ed to the inve rter. Po wer to the inve rter must b e rem oved befor e ser vicing the b raking modu le . Allow ad equa te time (app roxima tely 5 m in utes) after r emoving power befor e tou ching a ny comp onen ts. Both the CONT RO L POWER an d DC BUS indicat ors m ust be complet ely out b efor e servicing the u nit. CONTROL POWER CONNECTIONS R emov e th is p ro te ctive c ov er to a cce ss a ll con tr ol p ow er an d log ic co nn ec tion s. Master - Slave Settings: In the example above, the top braking module is set as the Master and the lower two modules are in Slave Mode. Wiring Notes: All DC power wiring between the drive, braking module and braking resistor should be twisted (if possible) and run separate from all control wiring. All control wiring must be twisted and run separate from all power wiring. Spacing: Braking modules should be no closer than 6 inches to allow for adequate cooling. Technical Assistance: +01-859-384-8088 LED INDICATORS The Powerohm Type BM Braking Module has five LED indicators on the front panel that allow the user to verify the following: CONTROL POWER: An illuminated green LED indicates that control power is applied to the braking module. DC BUS: An illuminated amber LED indicates that DC bus voltage is present BRAKE ACTIVE: An illuminated red LED indicates that the module is braking. CONTROL ENABLE: An illuminated green LED indicates that the control has been enabled. FAULT: An illuminated red LED can indicate any number of possible system faults. Refer to Table 6 and check the status of all outputs to help identify the problem. Likewise, if using a communications module, refer to Table 11 to check the status of the outputs. Technical Assistance: +01-859-384-8088