Product group data DIL00AM General Main conducting paths See

advertisement
Product group data DIL00AM
General
Standards and specifications
IEC/EN 60947, VDE 0660, UL, CSA
Lifespan, mechanical
AC operated
DC operated
Operations
× 106
10
Operations
106
10
×
Operating frequency, mechanical
AC operated
Operations/h
7000
DC operated
Operations/h
9000
Maximum operating frequency
Operating frequency
See Page 5/6
Damp heat, constant, to IEC 60068-2-3/Damp heat,
cyclical, to IEC 60068-2-30
Climatic proofing
Ambient temperature
Open
°C
-25/50
enclosed
°C
-25/40
Mounting position
See Page 10
Mechanical shock resistance (IEC/EN 60068-2-27)
Half-sinusoidal shock, 20 ms
Main contacts
Make contact
g
10
Make contact
g
10
Break contact
g
6
Auxiliary contacts
Degree of protection
IP20
Protection against direct contact from the front when actuated by a
perpendicular test finger (IEC 536)
Finger and back-of-hand proof
Weight
AC operated
kg
0,32
DC operated
kg
0,5
Terminal capacity Main cable
Solid
mm2
1 × (0.75 – 4)
2 × (0.75 – 4)
Flexible with ferrule
mm2
1 × (0.75 – 4)
2 × (0.75 – 4)
Solid or stranded
AWG
18 – 10
Terminal screw
M3.5
Nm
1.2
Solid
mm2
1 × (0.75 – 4)
2 × (0.75 – 4)
Flexible with ferrule
mm2
1 × (0.75 – 2.5)
2 × (0.75 – 2.5)
Solid or stranded
AWG
18 – 12
Tightening torque
Terminal capacity Control circuit cables
Terminal screw
M3.5
Tightening torque
Nm
1.2
Size
2
Size
2
V AC
8000
Tool
Main cable
Pozidriv screwdriver
Control circuit cables
Pozidriv screwdriver
Main conducting paths
Rated impulse withstand voltage
Uimp
Overvoltage category/pollution degree
III/3
Rated insulation voltage
AC
Rated operational voltage
Ui
V AC
690
Ue
V AC
690
Safe isolation to VDE 0106 Part 101 and Part 101/A1
between coil and contacts
V AC
440
between the contacts
V AC
440
A
200
220/230 V
A
130
380/400 V
A
120
500 V AC
A
120
660/690 V
A
100
Making capacity (cos
to IEC/EN 60947)
Breaking capacity
Component lifespan
AC-3 component lifespan
See Page 8
AC-4 component lifespan
See Page 9
AC-1 component lifespan
See Page 7
Short-circuit rating
Short-circuit protection Maximum fuse
Type “2” coordination
400 V
gG/gL 500 V
A
20
gG/gL 500 V
A
25
at 40 °C
A
22
at 50 °C
A
20
at 55 °C
A
19
A
16
open
A
50
Enclosed
A
40
Type “1” coordination
400 V
AC
AC-1 duty
conv. therm. current 3-pole 50 – 60 Hz
open
Enclosed
Conventional thermal current, 1-pole
AC-3 duty
Rated operational current AC-3 open, 50 – 60 Hz, 3-pole
220/230 V
Ie
A
12
240 V
Ie
A
12
380/400 V
Ie
A
12
415 V
Ie
A
12
440V
Ie
A
12
500 V
Ie
A
12
660/690 V
Ie
A
9
220/230 V
P
kW
3
240V
P
kW
3,5
380/400 V
P
kW
5,5
415 V
P
kW
6,1
440 V
P
kW
6,4
500 V
P
kW
7,5
660/690 V
P
kW
7,5
220/230 V
Ie
A
8,7
240 V
Ie
A
8,7
380/400 V
Ie
A
8,5
415 V
Ie
A
8,5
Motor rating
AC-4 duty
Rated operational current AC-4 open, 50 – 60 Hz, 3-pole
440 V
Ie
A
8,5
500 V
Ie
A
9
660/690 V
Ie
A
6,7
220/230 V
P
kW
2,2
240 V
P
kW
2,5
380/400 V
P
kW
4
415 V
P
kW
4,2
440 V
P
kW
4,4
500 V
P
kW
5,5
660/690 V
P
kW
5,5
Motor rating
Condensor operation
Individual compensation, rated operational current Ie of three-phase
capacitors
open
525 V
A
6
690 V
A
7
525 V
A
6
690 V
A
7
enclosed
Max. inrush current peak
Component lifespan
mA
× Ie
<30
Operations
× 106
0,1
Operations/h
200
DC
Operations
Switching DC current
See Pages 5/6
Rated operational current, open
DC-1 operation
60 V
A
20
110 V
A
20
220 V
A
15
440 V
A
3
60 V
A
20
110 V
A
20
220 V
A
8
60 V
A
16
110 V
A
16
Current heat loss (3-pole) at Ith
W
2,3
Current heat losses (3-pole) at Ie to AC-3/400 V
W
0,8
DC-3 operation
DC-5 operation
Current heat loss (3-pole)
Magnet systems
Voltage tolerance
AC operated
× Uc
0,8 – 1,1
DC operated
× Uc
0,85 – 1,1
Power consumption of the coil at cold coil and 1.0 × Uc
Pick-up AC
VA
67
Pick-up AC
W
52
Single-voltage coil 50 Hz, sealing
VA
8,5
Single-voltage coil 50 Hz, sealing
W
2,5
Dual-voltage coil 50 Hz, 60 Hz, sealing
VA
8,6
Dual-voltage coil 50 Hz, 60 Hz, sealing
W
2,5
Dual-frequency coil 50/60 Hz at 50 Hz
Sealing
VA
10
Dual-frequency coil 50/60 Hz at 50 Hz
Sealing
W
3
Dual-frequency coil 50/60 Hz at 60 Hz
Sealing
VA
8,5
Dual-frequency coil 50/60 Hz at 60 Hz
Sealing
W
2,5
Pick-up DC
W
9,5
Sealing DC
W
9,5
Duty factor
% DF
100
Switching times at 100 % Uc (approximate values)
Main contacts
AC operated
Closing delay
ms
14 – 22
Opening delay
ms
5 – 14
ms
13 – 21
ms
10
DC operated
Reversing contactors
Changeover time at 100 % Uc
Arcing time
Lifespan, mechanical of the coil 50/60 Hz
at 50 Hz
Mechanical lifespan at 50 Hz approx. 30 % less than
listed under General technical data
Notes
See Page 10
Dimensions
See Page 10
© 2003 by Moeller GmbH
06/084
Moeller HPL0211-2002
Engineering notes
DIL contactors
Determination of the maximum number of operations per hour in relation to rating and utilization category (approximate values), at 400 V
PN = Max. motor rating (kW) of the relevant contactor
Ops./h = Maximum number of switching operations per hour
Type
Ops./h
9000
Contactors
6000
DILE(E)M
DIL00M(-G)
DIL00AM(-G)
DIL0M(-G)
DIL0AM(-G)
DIL1M(-G)
DIL1AM(-G)
DIL2M(-G)
DIL2AM(-G)
5000
4000
3000
a
2000
b
1500
Tripping
characteristic
AC-1
AC-3
AC-2
AC-4
2
2
2
2
2
2
2
2
2
1
1
1
1
1
1
1
1
1
3
3
3
3
3
3
3
3
3
1000
800
c
600
500
400
300
200
150
100
0
10
20
30
40
50
60
70
80
90
100 %
N [kW]
Determination of the maximum number of operations per hour in relation to rating and utilization category (approximate values), at 400 V
PN = Max. motor rating (kW) of the relevant contactor
Ops./h = Maximum number of switching operations per hour
Type
Ops./h
4000
a
b
c
3000
2000
1500
d
1000
e
DIL3M80
DIL3AM85
DIL4M115
DIL4AM145
DILM185
DILM225
DILM250
DILM300
DILM400
DILM500
DILM580
DILM650
DILM750
DILM820
800
600
f
500
g
400
h
300
200
i
150
100
50
0
10
20
30
40
50
60
70
80
90
100 %
PN [kW]
Tripping
characteristic
AC-1-1
AC-3
AC-4
2
2
2
2
2
2
2
3
3
3
3
3
3
3
1
1
3
3
1
1
1
2
2
2
4
4
4
4
5
5
6
6
8
8
8
9
9
9
7
7
7
7
06/085
Moeller HPL0211-2002
Engineering notes
DIL contactors
Switching DC
DILEEM to DILM820
Without overload relay
60 V DC
60 V DC
With overload relay
60V DC
1-pole
Contactors
– – – – conductor can be
installed by the customer as
required
2-pole
DILEM4
DIL00M4
DILP160 to DILP800
1-pole
2-pole
06/082
Moeller HPL0211-2002
Tripping characteristics
DIL contactors
Switching duty for non-motor loads, 3-pole, 4-pole
Operating characteristics
Non-inductive or slightly inductive loads
Electrical characteristics
Make:
1 rated current
Break:
1 rated current
Typical applications
Electric heaters
Breaking cuzrrent A
Contactors
Utilization category
100 % AC-1
AC-1/400 V
850
DILM580-820
700
550
DILM300-500
400
DILM185-250
300
200
DIL4 AM145
DIL4 M115
DIL3(A)M80/85
DIL2(A)M
DIL2M
DIL1AM
DIL1M
DIL0AM
DIL0M
160
100
70
50
40
30
DIL00AM
DIL00M
DILEM
20
10
7
5
4
3
maximum conventional thermal
current I th for enclosed type
2
1
0.1
0.2
0.3
0.5
0.7
1
2
3
5
7
10
Component lifespan (Millions of operations)
Breaking current A
AC-1/400V
850
800
700
630
500
DILP800
DILP630
DILP500
315
250
200
DILP315
DILP250
160
DILP160
100
70
50
30
20
10
0.1
0.2
0.3
0.5
0.7
1
2
3
5
7
10
Component lifespan (Millions of operations)
06/080
Moeller HPL0211-2002
Rated output of three-phase motors 50–60 HZ
kW
30
22
18.5
15
11
Rated operational current Ie 50 – 60 Hz
Normal switching duty
Squirrel-cage motors
Operating characteristics
Starting: from rest
Stopping: after attaining full running speed
Electrical characteristics
Make:
up to 6 rated motor current
Break:
up to 1 rated motor current
Utilization category
100 % AC-3
Typical applications
Compressors
Lifts
Mixers
Pumps
Escalators
Agitators
Fans
Conveyor belts
Centrifuges
Valves
Bucket elevators
Air-conditioning systems
Drives in general in manufacturing and processing machines
AC-3/400 V
A
58 DIL2AM
43 DIL2M
36 DIL1AM
30 DIL1M
23 DIL0AM
7.5
16 DIL0M
DIL00BM
5.5
12 DIL00AM
4
8.8 DIL00M
DILEM
3
6.5 DILEEM
2.2
5
1.5
3.5
1.1
2.5
0.8
2
0.55
1.6
DIL00BM
DILE(E)M-G
DIL00M
DILE(E)M
0.01
0.02
0.04 0.06 0.1
0.2
0.4 0.6 0.75 1
2
3
4 5 6
8 10
Component lifespan (millions of operations)
AC-3/400 V
A
820
750
DILM820
DILM750
650
580
DILM650
DILM580
500
400
300
DILM500
DILM400
DILM300
250
225
DILM250
DILM225
90
185
DILM185
75
142
DIL4AM145
55
104
DIL4M115
45
85
DIL3AM85
37
72
DIL3M80
30
58
kW
450
400
355
315
250
200
160
132
110
Rated operational current Ie 50–60 Hz
Rated output of three-phase motors 50–60 HZ
Contactors
Tripping characteristics
DIL contactors
22
43
18.5
36
15
30
11
7.5
23
16
0.01
0.02
0.04 0.06 0.1
0.2
0.4 0.6 0.75 1
2
3
4 5 6
8 10
Component lifespan (millions of operations)
Moeller HPL0211-2002
06/081
Tripping characteristics
DIL contactors
kW
22
18.5
15
11
7.5
5.5
Rated operational current Ie 50 – 60 Hz
Rated output of three-phase motors 50–60 HZ
Extreme switching duty
Squirrel-cage motors
Operating characteristics
Inching, plugging, reversing
Electrical characteristics
Make:
up to 6 rated motor current
Break:
up to 6 rated motor current
Utilization category
100 % AC-4
4
Contactors
Typical applications
Printing presses
Wire-drawing machines Centrifuges
Special drives for manufacturing and processing machines
AC-4/400 V
A
43
DIL2AM
36
DIL2M
30
DIL1AM
23
DIL1M
16
DIL0AM
12
DIL0M
8.8
DIL00AM
3
6.5
DIL00M
DILEM
2.2
5
DILEEM
1.5
3.5
1.1
2.5
0.8
2
0.55
1.6
0.37
1.2
0.25
0.8
0.02 0.03 0.04 0.06 0.1
0.01
0.2 0.3
0.4 0.6
1
2
3
4 5 6
8 10
Rated output of three-phase motors 50–60 HZ
kW
355
315
280
250
200
160
132
Rated operational current Ie 50–60 Hz
Component lifespan (millions of operations)
AC-4/400 V
A
656
DILM820
576
512
456
360
DILM750
DILM650
DILM580
DILM500
296
DILM400
240
DILM300
110
200
DILM250
90
75
164
140
DILM225
DILM185
55
104
DIL4AM145
45
37
85
72
DIL4M115
DIL3AM85
DIL3M80
30
58
22
18.5
43
36
15
30
11
23
7.5
16
5.5
12
4
8.8
3
6.5
2.2
5
1.5
3.5
0.01
0.02 0.03 0.04 0.06 0.1
0.2 0.3 0.4 0.6
1
2
3
4 5 6
8 10
Component lifespan (millions of operations)
From DILM3M80 upwards mechanical shock resistance, half-sinusoidal shock; 10 ms
The following applies for the solid main conductor cross-sections: Maximum of one size difference admissible when using 2
conductors
The following applies for flat main conductor cross-sections: From DILM185, fix with flat conductor clamps or cable terminal blocks
The following applies for the short-circuit rating and fusing of the main: See the "Fuses" transparent overlay for time/current
characteristics (please enquire).
The following applies to the voltage tolerance of the DC operated magnet system as well as the magnet system switching times with
100 % DC actuated main circuit. Smoothed DC or three-phase current bridge rectifier; at least two-pulse bridge rectifier
following values apply with the max. permissible ambient temperature:
AC voltage
AC-1 duty, conv. therm. current, enclosed
AC-1 duty 1-pole, open
AC-1 duty 1-pole, enclosed
AC-3 duty, rated operational current, open
AC-4 duty, rated operational current, open
The following applies to magnet system switching times with 100 % AC operated reversing contactors Changeover time at 100 % Uc.
DIL00(A)M can be reversed at 660/690 V with a zero-current pause 25 ms
The following applies to magnet system, voltage tolerance, AC operated, pick-up voltages. With 50/60 Hz coil: 0.85 – 1.1
Mounting Position
Download