15 10 5 0 10 20 30 30 1"=10' 20 10 0 20 40 60 45 1"=20' 30 15 0 30 60 90 60 1"=30' 40 20 0 40 80 120 75 1"=40' 50 25 0 50 100 150 150 1"=50' 100 50 0 100 200 300 1"=100' CEILING PLAN GENERAL NOTES A. B. CEILING PLAN LEGEND REFER TO DWG A5-5x SERIES FOR CEILING DETAILS SMOKE BARRIER - 1 HR FIRE RESISTANCE RATED (UNLESS ACCOMPANIED BY HIGHER DESIGNATION) WHERE NO FINISH CEILING IS INDICATED, THE ROOM/SPACE SHALL BE EXPOSED TO THE STRUCTURE ABOVE. REFER TO ROOM FINISH SCHEDULE FOR FINISHING REQUIREMENTS. 1HR FIRE RESISTANCE RATED BARRIER 2HR FIRE RESISTANCE RATED BARRIER COORDINATE FINAL SIZE AND FINAL LOCATION OF ALL ACCESS PANELS WITH TRADE REQUIRING SAME. CUBICLE CURTAIN TRACK, SEE SHT A5-51 C. COORDINATE CEILING SUSPENSION SYSTEMS WITH OTHER CEILING SPACE EQUIPMENT SUPPORTING DEVICES. I.V. TRACK, SEE SHT A5-51 D. FOR PARTITION TYPES, SEE SHEET A5-71 AND A5-72. E. SEE ELECTRICAL DRAWINGS FOR FIXTURE TYPES AND NIGHT LIGHT LOCATIONS F. CEILING GRID LAYOUT - SYSTEM TO BE CENTERED IN ROOM, IN BOTH DIRECTIONS, UNO. CEILING GRID AREAS DIVIDED BY SOFFITS/DOORS TO BE ALIGNED. WORKPOINT MARKERS / DIMENSIONS SHALL SUPERCEDE, WHERE PROVIDED. ASSUME WORKPOINT STARTER PANELS TO BE FULL SIZE OR 6", UNLESS DIMENSIONED. C.H. ELEVATION OF FINISH CEILING AFF (8'-0" UNO) C.J. GYPSUM BOARD CONTROL JOINT, SEE SHT A5-71 GYPSUM BOARD CEILING ON MTL FRAMING ELEVATION AS NOTED. COORD ELEV OF GYPSUM BD SOFFITS ABOVE CABINETS WITH A4-3XX SERIES, A5-81, & A5-82 DWGS. ACOUSTIC LAY-IN CEILING PANEL, TYPE AS SCHEDULED ON A6-1x SERIES G. NO CEILING PANEL TO BE CUT TO LESS THAN 6" WIDTH, TYPICAL AT CONDITIONS WHERE CEILING PANELS EXCEED 2'-0" TRIM 2' X 4' CEILING PANELS AS REQ'D TO FIT. WOOD VENEER LAY-IN CEILING PANEL, ACT-2 AS SCHEDULED ON A6-1x SERIES H. COORDINATE THE LOCATION OF ESCUTCHEON PLATES AT CEILING PANEL PENETRATIONS WITH ELECTRICAL AND MECHANICAL TRADES. PATTERN INDICATES FIELD CUT PANEL/GRID BASED ON FIELD CONDITIONS. CUT PANELS FROM 2x4 CEILING PANELS (TYPICAL) I. SPRINKLER HEADS TO BE LOCATED IN THE CENTER OF CEILING PANELS, UNO. J. PAINT ALL VISIBLE, EXPOSED CONSTRUCTION ABOVE CEILINGS INCLUDING BUT NOT LIMITED TO MECH & ELEC ITEMS. SEE NOTES ON A6-1x SERIES DWGS FOR EXTENT. RETURN AIR DIFFUSER FIELD VERIFY LOCATIONS OF SOFFIT & CEILING CONTROL JOINTS WITH THE A/E REP. LINEAR DIFFUSER Cardiovascular Institute & Harper-Hutzel Specialty Center 311 Mack Avenue Detroit, Michigan 48201 SUPPLY AIR DIFFUSER B-2 B-1 K. 1 L. A5-05 REFER TO AQ-XX SERIES DRAWINGS FOR ADDITIONAL INFO ON CEILING MOUNTED EQUIPMENT. CLG MTD MED GAS SEE DETAIL 8/A5-52 M. PATCH AND REPAIR EXISTING CEILING PANELS AND GRID WHERE WALLS ARE REMOVED. 2.2 CLG MTD POWER SEE DETAIL 9/A5-52 N. CONTRACTOR SHALL MAINTAIN THE FIRE RATING INTEGRITY OF ALL EXISTING PARTITIONS INDICATED AS FIRE RESISTANCE RATED. ADVISE THE ARCHITECT OF ANY PREEXISTING BREACHES DISCOVERED IN COURSE OF WORK. C.J. DOWN LIGHT FIXTURE FLUORESCENT FIXTURE O. GYPSUM BD CEILINGS & SOFFITS TO BE CONSTRUCTED W/ 5/8" THK GYPSUM BOARD, AS INDICATED ON TYP DETAILS OF SHT A5-51, TO COORD WITH LT FIXTURE REQUIREMENTS. 5 A4-501 3 P/R 5 11030E 8' - 6" C.H. CONSULT 11017 SHELLED P/R AREA 11030-0 SEC/FIRE COMMAND 11003 9' - 0" C.H. A.5 C.J. C.J. C.J. SUPPLEMENTAL GRID @ SPLIT PANEL CEILING CJ'S CLARIFIED IN C.J. PRE-AWARD RFI 083 RESPONSE C.J. 15' - 4" C.H. 15' - 4" C.H. 9' - 0" C.H. 9' - 0" C.H. 7' - 2" C.H. 9' - 0" C.H. S INTER P/R 11030 A.4 9' - 0" C.H. 7' - 2" C.H. REFER TO DWG A9-31 FOR ALT. #3 FIT-OUT TYP POCKET DET E/A5-51 9' - 4" C.H. 12' - 0" C.H. PUB TLT 11016 8' - 0" C.H. 62'-0" 2 A5-04 TYP POCKET DET 'E'/A5-51 13'-4" 13'-4" VESTIBULE 11001 8' - 6" C.H. C.J. OVERHEAD EXAM LIGHT REFER TO DETAILS RECEPTION 11010 10' - 0" C.H. 13'-4" 15' - 6" C.H. D.E.F.S. CONTROL JOINT, TYP. COMPOSITE METAL PANEL 15' - 4" C.H. 18' - 10 1/2" C.H. 12' - 0" C.H. PROCEDURE 1 11026 18' - 10 1/2" C.H. SCRUB 8 11082 C.J. 1'-0" SKYLIGHT, TYP. OF 2 (ALUM. FRAMING SYSTEM 'E') 18' - 10 1/2" C.H. 15' - 6" C.H. B.7 ACCESS DOOR 17' - 10 1/2" C.H. 12' - 0" C.H. ELEC 11021 SCRUB 9 11083 COMPOSITE METAL PANEL ACCESS DOOR 6 A5-27 TYP. 12'-0" SCRUB 7 11081 8' - 6" C.H. 1'-0" 16' - 10 1/2" C.H. C.J. COMM 11020 18' - 10 1/2" C.H. B.6 1'-0" TYP. 8' - 6" C.H. 8' - 6" C.H. 18' - 10 1/2" C.H. 1 7' - 2" C.H. 8' - 6" C.H. REFER TO DWG A9-51 FOR ALT. #5 FIT-OUT 11' - 0" C.H. SHELLED CATH LAB 3 11074-0 COMPOSITE METAL PANEL FUTURE CATH LAB 4/5 11025 COMPOSITE METAL PANEL JOINT TYP. 5'-8 1/2" 2 A5-52 REFER TO DWG A9-41 FOR ALT. #4 FIT-OUT 8'-0" 18' - 10 1/2" C.H. CLG POCKET 13'-4" 13'-4" C.3 1'-0" 16' - 10 1/2" C.H. C.J. 1'-0" 10' - 8" C.H. 1'-0" CONTROL 11069B CATH LAB 2 11069 C A5-04 CLG POCKET 3'-0" 8' - 6" C.H. STF TLT 11060 CLEAN SUPPLY 11059 C.J. CORRIDOR 110Z5 8' - 6" C.H. 16' - 10 1/2" C.H. C.J. 17' - 10 1/2" C.H. 1'-0" B.2 C.J. HSKG 11031 INVENT COORD 11058 TYP POCKET DET 'E'/A5-51 B TYP. 12'-0" 15' - 6" C.H. RETAIL COFFEE 11012 1'-0" 6 A5-27 TECH WORKROOM 11011 A.9 1'-0" 9' - 0" C.H. C.J. 3'-0" SOILED UTILITY 11034 CONT. SOFFIT VENT, TYP. 3'-0" A5-52 13'-4" 16' - 10 1/2" C.H. 5 9' - 0" C.H. 13'-4" 8'-0" P/R 6 11030F PUB TLT 11015 VALET 11002 12'-0" P/R 7 11030G GREETER 11004 0 4'-0" 8' - 6" C.H. 10' - 2" C.H. 10' - 0" C.H. 4'-0" 8' - 6" C.H. CAMERA A 12'-0" 8' - 6" C.H. JUNCTION BOX IN CEILING 1'-0" 8' - 0" C.H. 10' - 2" C.H. 16' - 10 1/2" C.H. 12' - 0" C.H. NURSE CALL DOME LIGHT TYP POCKET DET E/A5-51 A4-05 15' - 4" C.H. 10' - 0" C.H. SPEAKER (GRILLE) 3'-0" 10' - 0" C.H. S 1'-0" 10' - 0" C.H. 22'-0" 10' - 0" C.H. 10' - 0" C.H. EQ. SMOKE DETECTORS 13'-4" 13'-4" 26913 Northwestern Hwy Suite 200 Southfield, Michigan 48033-3476 | USA NOTE: COMPOSITE METAL PANEL JOINTS ALIGN WITH D.E.F.S. CONTROL JOINTS, U.O.N. 13'-4" 15' - 6" C.H. (tel) (248) 262.1500 (fax) (248) 262.1515 harleyellisdevereaux.com 14 CEILING CJ'S CLARIFIED IN PRE-AWARD RFI 083 RESPONSE C.J. C.J. A5-72 EQUIP 11069A Issue Progress Set 2 Construction Issue 10 Scope Review Set Construction Issue 12 Construction Issue 13 1'-0" EQ. S 4 15' - 4" C.H. 1'-11 1/2" 10' - 0" C.H. EQ. 2'-0" 22'-0" 5'-8" 10' - 0" C.H. EQ. 7'-11 1/2" EQ. A5-52 22'-0" Date 12/21/11 05/30/12 06/27/12 07/18/12 08/08/12 Planning Architecture Engineering Interior Architecture Landscape Architecture Construction Services D D.1 8' - 6" C.H. 4 A4-501 Copyright © 2011 2008 D.4 D.5 6 5 4 3 2 1.8 1.5 1.2 1.1 1 A FIRST FLOOR REFLECTED CEILING PLAN - AREA A N 0 1 1-1/2"=1'0" 1 0 1 2 3/4"=1'0" 2 1 0 2 4 1/4"=1'0" 1/8"=1'0" 8 4 0 5 10 2011-10001-000 M.J.Bednarczyk K.Doyle E.G.Essique Title First Floor Reflected Ceiling Plan - Area A N SCALE: 1/8" = 1'-0" 3"=1'0" 8/29/2013 11:17:55 AM Project No. Drawn Checked Approved KEYPLAN Sheet No. AR-1A 1/16"=1'0" 6 0 10 20 30 12 0 20 40 C:\Revit60Local\CQO_Arch_Model_kpdoyle_local.rvt 15 10 5 0 10 20 30 30 1"=10' 20 10 0 20 40 60 45 1"=20' 30 15 0 30 60 90 60 1"=30' 40 20 0 40 80 120 75 1"=40' 50 25 0 50 100 150 150 1"=50' 100 50 0 100 200 300 1"=100' CEILING PLAN GENERAL NOTES 2 A4-12 A. WHERE NO FINISH CEILING IS INDICATED, THE ROOM/SPACE SHALL BE EXPOSED TO THE STRUCTURE ABOVE. REFER TO ROOM FINISH SCHEDULE FOR FINISHING REQUIREMENTS. B. COORDINATE FINAL SIZE AND FINAL LOCATION OF ALL ACCESS PANELS WITH TRADE REQUIRING SAME. A 11 A4-04 C. COORDINATE CEILING SUSPENSION SYSTEMS WITH OTHER CEILING SPACE EQUIPMENT SUPPORTING DEVICES. WATER METER RM B1002 D. FOR PARTITION TYPES, SEE SHEET A5-71 AND A5-72. E. SEE ELECTRICAL DRAWINGS FOR FIXTURE TYPES AND NIGHT LIGHT LOCATIONS F. CEILING GRID LAYOUT - SYSTEM TO BE CENTERED IN ROOM, IN BOTH DIRECTIONS, UNO. CEILING GRID AREAS DIVIDED BY SOFFITS/DOORS TO BE ALIGNED. WORKPOINT MARKERS / DIMENSIONS SHALL SUPERCEDE, WHERE PROVIDED. ASSUME WORKPOINT STARTER PANELS TO BE FULL SIZE OR 6", UNLESS DIMENSIONED. A.3 SHAFT #8 A.6 G. NO CEILING PANEL TO BE CUT TO LESS THAN 6" WIDTH, TYPICAL AT CONDITIONS WHERE CEILING PANELS EXCEED 2'-0" TRIM 2' X 4' CEILING PANELS AS REQ'D TO FIT. A.7 H. COORDINATE THE LOCATION OF ESCUTCHEON PLATES AT CEILING PANEL PENETRATIONS WITH ELECTRICAL AND MECHANICAL TRADES. 12.4 12.1 11.9 11.4 11.3 SPRINKLER HEADS TO BE LOCATED IN THE CENTER OF CEILING PANELS, UNO. J. PAINT ALL VISIBLE, EXPOSED CONSTRUCTION ABOVE CEILINGS INCLUDING BUT NOT LIMITED TO MECH & ELEC ITEMS. SEE NOTES ON A6-1x SERIES DWGS FOR EXTENT. K. FIELD VERIFY LOCATIONS OF SOFFIT & CEILING CONTROL JOINTS WITH THE A/E REP. L. REFER TO AQ-XX SERIES DRAWINGS FOR ADDITIONAL INFO ON CEILING MOUNTED EQUIPMENT. 11 BASEMENT REFLECTED CEILING PLAN 2 A2-02 I. SCALE: 1/8" = 1'-0" M. PATCH AND REPAIR EXISTING CEILING PANELS AND GRID WHERE WALLS ARE REMOVED. N. CONTRACTOR SHALL MAINTAIN THE FIRE RATING INTEGRITY OF ALL EXISTING PARTITIONS INDICATED AS FIRE RESISTANCE RATED. ADVISE THE ARCHITECT OF ANY PREEXISTING BREACHES DISCOVERED IN COURSE OF WORK. 2 A5-01 O. GYPSUM BD CEILINGS & SOFFITS TO BE CONSTRUCTED W/ 5/8" THK GYPSUM BOARD, AS INDICATED ON TYP DETAILS OF SHT A5-51, TO COORD WITH LT FIXTURE REQUIREMENTS. 3 EQ. A5-52 21'-10 1/2" EQ. EQ. 8'-0" 1 A4-501 12' - 0" C.H. 12' - 0" C.H. A.3 N ELEV 2 FUTURE 110V6 N ELEV 4 PUBLIC 110V8 N ELEV 3 SERVICE 110V7 SHAFT #8 . A5-04 OFFICE 11046 OFFICE 11045 8' - 6" C.H. 8' - 6" C.H. P/R 16 11040H 8' - 6" C.H. P/R 15 11040G 8' - 6" C.H. P/R 14 11040F 8' - 6" C.H. P/R 13 11040E 10' - 0" C.H. P/R 12 11040D 8' - 6" C.H. 8' - 6" C.H. 8' - 6" C.H. P/R 11 11040C P/R 10 11040B P/R 9 11040A 1HR FIRE RESISTANCE RATED BARRIER 2HR FIRE RESISTANCE RATED BARRIER CUBICLE CURTAIN TRACK, SEE SHT A5-51 8' - 6" C.H. NOURISH 11041 8' - 6" C.H. 8' - 6" C.H. 8' - 6" C.H. 8' - 6" C.H. P/R 8 11030H P/R 7 11030G P/R 6 11030F P/R 5 11030E I.V. TRACK, SEE SHT A5-51 C.H. ELEVATION OF FINISH CEILING AFF (8'-0" UNO) C.J. GYPSUM BOARD CONTROL JOINT, SEE SHT A5-71 GYPSUM BOARD CEILING ON MTL FRAMING ELEVATION AS NOTED. COORD ELEV OF GYPSUM BD SOFFITS ABOVE CABINETS WITH A4-3XX SERIES, A5-81, & A5-82 DWGS. 5 NW ELEV LOBBY 110Z10 S REWORK EX CLG AS REQ'D BY WALL WORK A5-51 9' - 6" C.H. 11.3 7' - 0" C.H. 7' - 10" C.H. OFFICE 11047 8' - 6" C.H. B.1 OFFICE 11048 8' - 6" C.H. P/R 24 11040N 8' - 6" C.H. 8' - 6" C.H. P/R 23 11040M P/R 22 11040L NURSE STATION 11043 PAT TLT 11044 7' - 2" C.H. 8' - 6" C.H. 8' - 0" C.H. 8' - 6" C.H. CORRIDOR 110Z7 SOILED UTILITY 11053 SCRUB 1 11075 S 8' - 0" C.H. 7' - 2" C.H. 7' - 0" C.H. 8' - 6" C.H. 9' - 1" C.H. 8' - 6" C.H. 8' - 6" C.H. CONTROL 11061B SCRUB 3 11077 LOCKERS G713 97 C.4 CATH LAB LARGE 11064 EP LAB 2 11062 SCRUB 5 11079 APRON 11057 SCRUB 6 11080 8' - 6" C.H. CONTROL 11065B 8' - 6" C.H. SWING LAB 1A 11066 CATH LAB 1 11065 9' - 6" C.H. 9' - 4" C.H. 8' - 6" C.H. SWING LAB 1B 11067 CONTROL 11068 12.5 12.4 12.2 12.1 DOWN LIGHT FIXTURE S SMOKE DETECTORS S SPEAKER (GRILLE) CONTROL 11069B NURSE CALL DOME LIGHT CATH LAB 2 11069 JUNCTION BOX IN CEILING 10' - 8" C.H. CAMERA 9' - 6 3/8" C.H. 9' - 6 3/8" C.H. 9' - 4" C.H. EQUIP 11062C 11.9 SCRUB 7 11081 8' - 6" C.H. 8' - 6" C.H. 8' - 6" C.H. 8' - 0" 8' - 0" C.H. C.H. G715 CLG MTD POWER SEE DETAIL 9/A5-52 8' - 6" C.H. C 8' - 6" C.H. 8' - 6" C.H. WORKROOM 11063 OFFICE REWORK EX CLG AS REQ'D BY WALL WORK INVENT COORD 11058 FLUORESCENT FIXTURE CONTROL 11064B 9' - 9" C.H. EP LAB 1 11061 CLG MTD MED GAS SEE DETAIL 8/A5-52 7' - 2" C.H. 8' - 6" C.H. 2" CEILING EXP. JT. TYPE 'CA-2' DEVELOP TRANSITION SOFFIT FROM REMAINING WALL 8' - 6" C.H. 8' - 0" C.H. CONTROL DESK 11056 8' - 6" C.H. 8' - 6" C.H. CONTROL 11062B LINEAR DIFFUSER SCRUB 4 11078 STF TLT 11055 SCRUB 2 11076 CHANGE IN CLG PLANE @ GRID LINE CR EX C.H. 7'-0" 7' - 6" C.H. RETURN AIR DIFFUSER 5'-8 1/2" G719 HSKG 11054 SUPPLY AIR DIFFUSER 7' - 2" C.H. 8' - 0" C.H. 8' - 6" C.H. STF TLT 11052 PATTERN INDICATES FIELD CUT PANEL/GRID BASED ON FIELD CONDITIONS. CUT PANELS FROM 2x4 CEILING PANELS (TYPICAL) SOILED UTILITY 11034 PAT TLT 11036 NURSE STATION 11037 CORRIDOR 110Z5 PACS READING 11085 FELLOWS 11084 P/R 21 ISO 11040K CLEAN SUPPLY 11035 MEDS 11042 SATELLITE PHARMACY 11049 WOOD VENEER LAY-IN CEILING PANEL, ACT-2 AS SCHEDULED ON A6-1x SERIES B 8' - 6" C.H. 9' - 0" C.H. S WOMEN ACOUSTIC LAY-IN CEILING PANEL, TYPE AS SCHEDULED ON A6-1x SERIES 9' - 0" C.H. EX C.H. 7'-10" EX C.H. 7'-10" S INTER P/R 11030 A5-51 S 7' - 10" C.H. VC 5 26913 Northwestern Hwy Suite 200 Southfield, Michigan 48033-3476 | USA 14 8' - 6" C.H. A5-72 (tel) (248) 262.1500 (fax) (248) 262.1515 harleyellisdevereaux.com 9' - 6 3/8" C.H. 9' - 4" C.H. 9' - 6" C.H. STORAGE 8' - 6" C.H. G714 8' - 6" C.H. EQUIP 11061A 8' - 6" C.H. EQUIP 11061A 8' - 6" C.H. EQUIP 11064A EQUIP 11062A EQUIP 11064A 8' - 6" C.H. EQUIP 11065A 9' - 6 3/8" C.H. D EQUIP 11069A 8' - 6" C.H. EQUIP 11066A 8' - 6" C.H. 1 A4-502 Planning Architecture Engineering Interior Architecture Landscape Architecture Construction Services 8' - 6" C.H. 3 A4-502 4 A4-502 2 A4-502 D.4 11.4 11 10 9 8 7 Copyright © 2011 2008 6 B Project No. Drawn Checked Approved 2011-10001-000 M.J.Bednarczyk K.Doyle E.G.Essique Title First Floor Reflected Ceiling Plan - Area B FIRST FLOOR REFLECTED CEILING PLAN - AREA B SCALE: 1/8" = 1'-0" N 3"=1'0" 8/29/2013 11:18:20 AM 0 1 Issue Progress Set 2 Scope Review Set Construction Issue 12 Construction Issue 15 Construction Issue 18 SMOKE BARRIER - 1 HR FIRE RESISTANCE RATED (UNLESS ACCOMPANIED BY HIGHER DESIGNATION) A.7 N INTER P/R 11040 9' - 6" C.H. Date 12/21/11 06/27/12 07/18/12 01/23/13 05/24/13 REFER TO DWG A5-5x SERIES FOR CEILING DETAILS 9' - 0" C.H. TV EX BRUSH BLDG N ELEV 1 PATIENT 110V5 A.6 4 8' - 6" C.H. 8' - 6" C.H. 10' - 0" C.H. 7'-11 1/2" 8' - 0" C.H. N STAIR 110X5 8' - 0" C.H. 10' - 0" C.H. NE ELEV LOBBY 110Z9 10' - 0" C.H. 311 Mack Avenue Detroit, Michigan 48201 CEILING PLAN LEGEND A 10' - 0" C.H. Cardiovascular Institute & Harper-Hutzel Specialty Center 1-1/2"=1'0" 1 0 1 2 3/4"=1'0" 2 1 0 2 4 1/4"=1'0" 1/8"=1'0" 8 4 0 5 10 KEYPLAN Sheet No. AR-1B 1/16"=1'0" 6 0 10 20 30 12 0 20 40 C:\Revit60Local\CQO_Arch_Model_kpdoyle_local.rvt 15 10 5 0 10 20 30 30 1"=10' 20 10 0 20 40 60 45 1"=20' 30 15 0 30 60 90 60 1"=30' 40 20 0 40 80 120 75 1"=40' 50 25 0 50 100 150 1"=50' 150 100 50 0 100 200 300 1"=100' CEILING PLAN GENERAL NOTES A. WHERE NO FINISH CEILING IS INDICATED, THE ROOM/SPACE SHALL BE EXPOSED TO THE STRUCTURE ABOVE. REFER TO ROOM FINISH SCHEDULE FOR FINISHING REQUIREMENTS. B. COORDINATE FINAL SIZE AND FINAL LOCATION OF ALL ACCESS PANELS WITH TRADE REQUIRING SAME. C. COORDINATE CEILING SUSPENSION SYSTEMS WITH OTHER CEILING SPACE EQUIPMENT SUPPORTING DEVICES. D. FOR PARTITION TYPES, SEE SHEET A5-71 AND A5-72. E. SEE ELECTRICAL DRAWINGS FOR FIXTURE TYPES AND NIGHT LIGHT LOCATIONS F. CEILING GRID LAYOUT - SYSTEM TO BE CENTERED IN ROOM, IN BOTH DIRECTIONS, UNO. CEILING GRID AREAS DIVIDED BY SOFFITS/DOORS TO BE ALIGNED. WORKPOINT MARKERS / DIMENSIONS SHALL SUPERCEDE, WHERE PROVIDED. ASSUME WORKPOINT STARTER PANELS TO BE FULL SIZE OR 6", UNLESS DIMENSIONED. G. NO CEILING PANEL TO BE CUT TO LESS THAN 6" WIDTH, TYPICAL AT CONDITIONS WHERE CEILING PANELS EXCEED 2'-0" TRIM 2' X 4' CEILING PANELS AS REQ'D TO FIT. H. COORDINATE THE LOCATION OF ESCUTCHEON PLATES AT CEILING PANEL PENETRATIONS WITH ELECTRICAL AND MECHANICAL TRADES. 1 B-2 A5-05 B-1 2.2 I. SPRINKLER HEADS TO BE LOCATED IN THE CENTER OF CEILING PANELS, UNO. J. PAINT ALL VISIBLE, EXPOSED CONSTRUCTION ABOVE CEILINGS INCLUDING BUT NOT LIMITED TO MECH & ELEC ITEMS. SEE NOTES ON A6-1x SERIES DWGS FOR EXTENT. K. FIELD VERIFY LOCATIONS OF SOFFIT & CEILING CONTROL JOINTS WITH THE A/E REP. L. REFER TO AQ-XX SERIES DRAWINGS FOR ADDITIONAL INFO ON CEILING MOUNTED EQUIPMENT. M. PATCH AND REPAIR EXISTING CEILING PANELS AND GRID WHERE WALLS ARE REMOVED. 3 N. CONTRACTOR SHALL MAINTAIN THE FIRE RATING INTEGRITY OF ALL EXISTING PARTITIONS INDICATED AS FIRE RESISTANCE RATED. ADVISE THE ARCHITECT OF ANY PREEXISTING BREACHES DISCOVERED IN COURSE OF WORK. EXPANSION JOINT 'PB-4', 3 FACES OF GYP BD ENCLOSURE, EACH SIDE A5-52 O. GYPSUM BD CEILINGS & SOFFITS TO BE CONSTRUCTED W/ 5/8" THK GYPSUM BOARD, AS INDICATED ON TYP DETAILS OF SHT A5-51, TO COORD WITH LT FIXTURE REQUIREMENTS. A 9' - 6" C.H. 9' - 6" C.H. 9' - 6" C.H. 9' - 6" C.H. CORRIDOR/WTG 210Z1 CEILING CJ'S CLARIFIED IN PRE-AWARD RFI 083 RESPONSE CORRIDOR/WTG 210Z1 MALE GOWNED WTG 21036 7' - 2" C.H. 9' - 0" C.H. ECHO 3 21044C EQUIPMENT 21040B 9' - 0" C.H. 9' - 0" C.H. 8' - 6" C.H. 5 8' - 6" C.H. A5-51 PASSAGE 21044 ECHO 2 21044A PASSAGE 21040 ECHO 1 21040C FEMALE GOWNED WTG 21037 9' - 0" C.H. TECH WORKROOM 21040A CHNG 21035 CHNG 21034 C.J. ALIGN W/ 1ST FLOOR JT 7' - 2" C.H. CHNG 21033 PUB TLT 21016 A5-51 8' - 6" C.H. 9' - 0" C.H. EKG 21038 STRESS ECHO 3 21045 STRESS ECHO 2 21043 PAT TLT 21032 8' - 6" C.H. I.V. TRACK, SEE SHT A5-51 A.9 8' - 6" C.H. C.H. ELEVATION OF FINISH CEILING AFF (8'-0" UNO) C.J. GYPSUM BOARD CONTROL JOINT, SEE SHT A5-71 GYPSUM BOARD CEILING ON MTL FRAMING ELEVATION AS NOTED. COORD ELEV OF GYPSUM BD SOFFITS ABOVE CABINETS WITH A4-3XX SERIES, A5-81, & A5-82 DWGS. B CLG MTD CAMERA, TYP 8' - 6" C.H. A4-301 22 C.J. ALIGN W/ 1ST FLOOR JT ACOUSTIC LAY-IN CEILING PANEL, TYPE AS SCHEDULED ON A6-1x SERIES B.2 CONSULT 21012 RETAIL PHARMACY 21013 9' - 0" C.H. PAT SHWR 21031 VENIPUNCTURE 2 21061 CUBICLE CURTAIN TRACK, SEE SHT A5-51 A5-52 7' - 2" C.H. 8' - 0" C.H. 8' - 0" C.H. STRESS ECHO 1 21042 VENIPUNCTURE 1 21060 2HR FIRE RESISTANCE RATED BARRIER 5 8' - 6" C.H. EKG WORKROOM 21041 9' - 0" C.H. SMOKE BARRIER - 1 HR FIRE RESISTANCE RATED (UNLESS ACCOMPANIED BY HIGHER DESIGNATION) 1HR FIRE RESISTANCE RATED BARRIER 8'-0" 8' - 6" C.H. 5 8' - 6" C.H. LOCATE PENDANT FIXT'S IN CENTER OF 3RD FLOOR CLG TILE (ABOVE), TYP OPEN TO BELOW . CONNECTED LOBBY UPPER 210Z3 HSKG 21011 A.5 10' - 6" C.H. 10' - 6" C.H. RECEPTION 21010 CORRIDOR 210Z4 WOOD VENEER LAY-IN CEILING PANEL, ACT-2 AS SCHEDULED ON A6-1x SERIES ? ? SHAFT #3 . CORRIDOR 210Z5 C.J. 7' - 2" C.H. B.6 PATTERN INDICATES FIELD CUT PANEL/GRID BASED ON FIELD CONDITIONS. CUT PANELS FROM 2x4 CEILING PANELS (TYPICAL) B.7 SUPPLY AIR DIFFUSER C.J. 4 RETURN AIR DIFFUSER A5-51 9' - 0" C.H. PHYS READING 21063 9' - 0" C.H. STF TLT 21025P OFFICE 21013B 8' - 0" C.H. LINEAR DIFFUSER C.J. CLG MTD MED GAS SEE DETAIL 8/A5-52 C TREADMILL 1 21074 8' - 6" C.H. CORRIDOR 210Z7 9' - 0" C.H. 9' - 0" C.H. HOT LAB 21062 9' - 0" C.H. STRESS READING 21064 8' - 0" C.H. 7' - 2" C.H. SHAFT #2 . PROF ALLOW 21025N 9' - 0" C.H. 10' - 0" C.H. DOWN LIGHT FIXTURE 10' - 0" C.H. 8' - 0" C.H. 8' - 0" C.H. CLG MTD POWER SEE DETAIL 9/A5-52 CEILING CJ'S CLARIFIED IN PRE-AWARD RFI 083 RESPONSE RECEPT 21025A 9' - 0" C.H. WORKROOM 21025B STF TLT 21025R PROF ALLOW 21025Q Issue Progress Set 2 Scope Review Set Construction Issue 12 Construction Issue 15 REFER TO DWG A5-5x SERIES FOR CEILING DETAILS PUB TLT 21015 8' - 6" C.H. Date 12/21/11 06/27/12 07/18/12 01/23/13 A.4 STF LOUNGE 21013A 8'-0" 10' - 6" C.H. 311 Mack Avenue Detroit, Michigan 48201 CEILING PLAN LEGEND C.J. WORKROOM 21044B Cardiovascular Institute & Harper-Hutzel Specialty Center C.3 FLUORESCENT FIXTURE C.J. CONF 21025C 9' - 0" C.H. S ELEV LOBBY 210Z2 S SMOKE DETECTORS S SPEAKER (GRILLE) NURSE CALL DOME LIGHT NM EQUIPMENT 21069 2 8' - 6" C.H. INJECTED WTG 21065 JUNCTION BOX IN CEILING A5-52 8' - 6" C.H. CAMERA SEC 21025E STF TLT 21068 8' - 6" C.H. DIRECTOR 21025M DIRECTOR 21066 DIRECTOR 21025L 5 8' - 6" C.H. 8' - 6" C.H. DIRECTOR 21025K 8' - 6" C.H. DIRECTOR 21025J 8' - 6" C.H. DIRECTOR 21025H VICE PRESIDENT 21025F DIRECTOR 21025G D (tel) (248) 262.1500 (fax) (248) 262.1515 harleyellisdevereaux.com D.1 5 ROLLER SHADES (EA WINDOW, THIS AREA), SEE 12/A5-65 A5-51 26913 Northwestern Hwy Suite 200 Southfield, Michigan 48033-3476 | USA 9' - 0" PRESIDENT 21025D C.H. 8' - 6" C.H. C.J. INJECTED TLT 21067 8' - 6" C.H. 9' - 0" C.H. C.J. 8' - 6" C.H. A5-51 4 Planning Architecture Engineering Interior Architecture Landscape Architecture Construction Services A2-01 3 A2-01 D.4 D.5 Copyright © 2011 2008 1 A2-02 6 5 4 3 2 1.8 1.5 1.2 1.1 1 A SECOND FLOOR REFELECTED CEILING PLAN - AREA A Project No. Drawn Checked Approved 2011-10001-000 M.J.Bednarczyk K.Doyle E.G.Essique Title Second Floor Reflected Ceiling Plan - Area A SCALE: 1/8" = 1'-0" N 3"=1'0" 8/29/2013 11:18:40 AM 0 1 1-1/2"=1'0" 1 0 1 2 3/4"=1'0" 2 1 0 2 4 1/4"=1'0" 1/8"=1'0" 8 4 0 5 10 KEYPLAN Sheet No. AR-2A 1/16"=1'0" 6 0 10 20 30 12 0 20 40 C:\Revit60Local\CQO_Arch_Model_kpdoyle_local.rvt 15 10 5 0 10 20 30 30 1"=10' 20 10 0 20 40 60 45 1"=20' 30 15 0 30 60 90 60 1"=30' 40 20 0 40 80 120 75 1"=40' 50 25 0 50 100 150 150 1"=50' 100 50 0 100 200 300 1"=100' CEILING PLAN GENERAL NOTES A. WHERE NO FINISH CEILING IS INDICATED, THE ROOM/SPACE SHALL BE EXPOSED TO THE STRUCTURE ABOVE. REFER TO ROOM FINISH SCHEDULE FOR FINISHING REQUIREMENTS. B. COORDINATE FINAL SIZE AND FINAL LOCATION OF ALL ACCESS PANELS WITH TRADE REQUIRING SAME. C. COORDINATE CEILING SUSPENSION SYSTEMS WITH OTHER CEILING SPACE EQUIPMENT SUPPORTING DEVICES. D. FOR PARTITION TYPES, SEE SHEET A5-71 AND A5-72. E. SEE ELECTRICAL DRAWINGS FOR FIXTURE TYPES AND NIGHT LIGHT LOCATIONS F. CEILING GRID LAYOUT - SYSTEM TO BE CENTERED IN ROOM, IN BOTH DIRECTIONS, UNO. CEILING GRID AREAS DIVIDED BY SOFFITS/DOORS TO BE ALIGNED. WORKPOINT MARKERS / DIMENSIONS SHALL SUPERCEDE, WHERE PROVIDED. ASSUME WORKPOINT STARTER PANELS TO BE FULL SIZE OR 6", UNLESS DIMENSIONED. G. NO CEILING PANEL TO BE CUT TO LESS THAN 6" WIDTH, TYPICAL AT CONDITIONS WHERE CEILING PANELS EXCEED 2'-0" TRIM 2' X 4' CEILING PANELS AS REQ'D TO FIT. H. COORDINATE THE LOCATION OF ESCUTCHEON PLATES AT CEILING PANEL PENETRATIONS WITH ELECTRICAL AND MECHANICAL TRADES. REFER TO DWG AP-1.5 FOR RCP PLAN OF CONNECTOR LEVEL (BELOW) A5-52 9' - 6" C.H. 9' - 6" C.H. 9' - 6" C.H. 9' - 6" C.H. 9' - 6" C.H. 9' - 6" C.H. A.3 P/R 5 21052E P/R 4 21052D P/R 3 21052C P/R 2 21052B 9' - 6" C.H. 9' - 6" C.H. 9' - 6" C.H. 9' - 6" C.H. 9' - 6" C.H. 9' - 6" C.H. 9' - 6" C.H. 7' - 2" C.H. 7' - 2" C.H. A5-04 8' - 6" C.H. 9' - 0" C.H. 9' - 0" C.H. ECHO 4 21045B PASSAGE 21044 ECHO 3 21044C 2721 CLEAN SUPPLY 21055 P/R 8 21052H ECHO 2 21044A ROLLER SHADE (EA WINDOW, THIS AREA), SEE 12/A5-65 VIP PATIENT RM 01 2706 4 A2-02 3 A5-04 ISOLATION PATIENT ROOM C.4 2707 9' - 0" C.H. P/R 9 21052J P/R 10 21052K 9' - 0" C.H. CORRIDOR 210Z8 NURSE STATION 21054 8' - 6" C.H. 12.2 12.1 ELEVATION OF FINISH CEILING AFF (8'-0" UNO) C.J. GYPSUM BOARD CONTROL JOINT, SEE SHT A5-71 GYPSUM BOARD CEILING ON MTL FRAMING ELEVATION AS NOTED. COORD ELEV OF GYPSUM BD SOFFITS ABOVE CABINETS WITH A4-3XX SERIES, A5-81, & A5-82 DWGS. ECHO 1 21040C B 9' - 0" C.H. 9' - 0" C.H. 8' - 0" C.H. 8' - 6" C.H. TEE 2 21049 STRESS ECHO 4 21045A SOILED SCOPE/UTILITY 21047 STRESS ECHO 3 21045 STRESS ECHO 2 21043 CORRIDOR 210Z5 8' - 6" C.H. SHAFT #1 . 4 FEMALE PHYS LOCKERS 21095 8' - 6" C.H. 7' - 2" C.H. 9' - 0" C.H. 9' - 0" C.H. 9' - 0" C.H. TREADMILL 3 21076 TREADMILL 2 21075 TREADMILL 1 21074 9' - 0" C.H. CLG MTD POWER SEE DETAIL 9/A5-52 9' - 0" C.H. DOWN LIGHT FIXTURE FLUORESCENT FIXTURE 8' - 6" C.H. CORRIDOR 210Z7 9' - 0" C.H. HOT LAB 21062 FUTURE SPECT / CT 21080 S SPEAKER (GRILLE) NURSE CALL DOME LIGHT 9' - 0" C.H. 8' - 0" C.H. GAMMA CAMERA 1 21077 GAMMA CAMERA 2 21079 SMOKE DETECTORS JUNCTION BOX IN CEILING MEDS 21073 STF TLT 21098 S 8' - 6" C.H. 7' - 2" C.H. 8' - 6" C.H. MALE PHYS LOCKERS 21096 8' - 0" C.H. NM OFFICE 21072 STRESS READING 21064 CAMERA NM EQUIPMENT 21069 8' - 0" C.H. 11.9 9' - 0" C.H. 8' - 6" C.H. STAFF LOUNGE 21090 SIM/TRAINING 21094 9' - 0" C.H. COMM 21050 8' - 0" C.H. 9' - 0" C.H. 9' - 0" C.H. 8' - 0" C.H. C A5-51 9' - 0" C.H. CLG MTD MED GAS SEE DETAIL 8/A5-52 HSKG 21081 ELEC 21051 9' - 0" PHYS C.H. LOUNGE 21093 RETURN AIR DIFFUSER VENIPUNCTURE 2 21061 LINEAR DIFFUSER FEMALE STF LOCKERS 21099 8' - 6" C.H. 8' - 6" C.H. PATTERN INDICATES FIELD CUT PANEL/GRID BASED ON FIELD CONDITIONS. CUT PANELS FROM 2x4 CEILING PANELS (TYPICAL) STRESS ECHO 1 21042 VENIPUNCTURE 1 21060 7' - 2" 8' - 0" C.H. C.H. STF TLT 21091 7' - 2" C.H. STF TLT 21092 WOOD VENEER LAY-IN CEILING PANEL, ACT-2 AS SCHEDULED ON A6-1x SERIES 9' - 0" C.H. SUPPLY AIR DIFFUSER P/R 11 21052L 8' - 0" C.H. 12.5 12.4 C.H. ACOUSTIC LAY-IN CEILING PANEL, TYPE AS SCHEDULED ON A6-1x SERIES 8' - 6" C.H. B.8 9' - 0" C.H. 8' - 6" C.H. CLEAN SCOPE 21047A STAFF BATHROOM 2707A 1HR FIRE RESISTANCE RATED BARRIER I.V. TRACK, SEE SHT A5-51 A5-51 8' - 6" C.H. 8' - 6" C.H. 8' - 6" C.H. 6" CEILING EXP. JT. TYPE 'CA-6' 2708A SMOKE BARRIER - 1 HR FIRE RESISTANCE RATED (UNLESS ACCOMPANIED BY HIGHER DESIGNATION) 10' - 6" C.H. 5 8' - 0" C.H. BATHROOM CEILING PLAN LEGEND 9' - 0" C.H. 8' - 6" C.H. 8' - 0" C.H. Issue Progress Set 2 Scope Review Set Construction Issue 12 Construction Issue 13 Construction Issue 15 CUBICLE CURTAIN TRACK, SEE SHT A5-51 TEE 1 21048 NON-INV P/R 21052 Date 12/21/11 06/27/12 07/18/12 08/08/12 01/23/13 2HR FIRE RESISTANCE RATED BARRIER PAT TLT 21053 8' - 6" C.H. NW ELEV LOBBY 210Z10 BATHROOM REFER TO AQ-XX SERIES DRAWINGS FOR ADDITIONAL INFO ON CEILING MOUNTED EQUIPMENT. EQUIPMENT 21046 9' - 0" C.H. 2 A4-501 2706A 9' - 6" C.H. 9' - 6" C.H. WORKROOM 21044B 8' - 6" C.H. PAT TLT 21056 A.7 2722 L. 9' - 0" C.H. 4 STORAGE FIELD VERIFY LOCATIONS OF SOFFIT & CEILING CONTROL JOINTS WITH THE A/E REP. 311 Mack Avenue Detroit, Michigan 48201 REFER TO DWG A5-5x SERIES FOR CEILING DETAILS 10' - 6" C.H. P/R 1 21052A 8' - 0" C.H. BATHROOM K. CORRIDOR/WTG 210Z1 P/R 7 P/R 6 21052G 21052F 8' - 0" C.H. 9' - 6" C.H. 8' - 0" C.H. 8' - 0" C.H. A.7 PAINT ALL VISIBLE, EXPOSED CONSTRUCTION ABOVE CEILINGS INCLUDING BUT NOT LIMITED TO MECH & ELEC ITEMS. SEE NOTES ON A6-1x SERIES DWGS FOR EXTENT. O. GYPSUM BD CEILINGS & SOFFITS TO BE CONSTRUCTED W/ 5/8" THK GYPSUM BOARD, AS INDICATED ON TYP DETAILS OF SHT A5-51, TO COORD WITH LT FIXTURE REQUIREMENTS. A NE ELEV LOBBY 210Z9 8' - 0" C.H. A.6 J. N. CONTRACTOR SHALL MAINTAIN THE FIRE RATING INTEGRITY OF ALL EXISTING PARTITIONS INDICATED AS FIRE RESISTANCE RATED. ADVISE THE ARCHITECT OF ANY PREEXISTING BREACHES DISCOVERED IN COURSE OF WORK. 3 EX BRUSH BLDG SPRINKLER HEADS TO BE LOCATED IN THE CENTER OF CEILING PANELS, UNO. M. PATCH AND REPAIR EXISTING CEILING PANELS AND GRID WHERE WALLS ARE REMOVED. 11.3 N STAIR 210X5 I. Cardiovascular Institute & Harper-Hutzel Specialty Center NM WORKROOM 21070 CONTROL 21078 STF TLT 21068 7' - 2" C.H. 8' - 6" C.H. 7' - 2" C.H. 8' - 6" C.H. MALE STF LOCKERS 21097 8' - 6" C.H. INJECTED TLT 21067 7' - 2" C.H. STF TLT 21071 26913 Northwestern Hwy Suite 200 Southfield, Michigan 48033-3476 | USA DIRECTOR 21066 9' - 0" C.H. (tel) (248) 262.1500 (fax) (248) 262.1515 harleyellisdevereaux.com D 5 A5-51 VIP PATIENT RM 01 Planning Architecture Engineering Interior Architecture Landscape Architecture Construction Services ROLLER SHADE (EA WINDOW, THIS AREA), SEE 12/A5-65 2708 D.4 Copyright © 2011 2008 11.4 11 10 9 8 7 6 B SECOND FLOOR REFELECTED CEILING PLAN - AREA B Project No. Drawn Checked Approved 2011-10001-000 M.J.Bednarczyk K.Doyle E.G.Essique Title Second Floor Reflected Ceiling Plan - Area B SCALE: 1/8" = 1'-0" N 3"=1'0" 8/29/2013 11:20:00 AM 0 1 1-1/2"=1'0" 1 0 1 2 3/4"=1'0" 2 1 0 2 4 1/4"=1'0" 1/8"=1'0" 8 4 0 5 10 KEYPLAN Sheet No. AR-2B 1/16"=1'0" 6 0 10 20 30 12 0 20 40 C:\Revit60Local\CQO_Arch_Model_kpdoyle_local.rvt 15 10 5 0 10 20 30 30 1"=10' 20 10 0 20 40 60 45 1"=20' 30 15 0 30 60 90 60 1"=30' 40 20 0 40 80 120 75 1"=40' 50 25 0 50 100 150 150 1"=50' 100 50 0 100 200 300 1"=100' CEILING PLAN GENERAL NOTES A. WHERE NO FINISH CEILING IS INDICATED, THE ROOM/SPACE SHALL BE EXPOSED TO THE STRUCTURE ABOVE. REFER TO ROOM FINISH SCHEDULE FOR FINISHING REQUIREMENTS. B. COORDINATE FINAL SIZE AND FINAL LOCATION OF ALL ACCESS PANELS WITH TRADE REQUIRING SAME. C. COORDINATE CEILING SUSPENSION SYSTEMS WITH OTHER CEILING SPACE EQUIPMENT SUPPORTING DEVICES. D. FOR PARTITION TYPES, SEE SHEET A5-71 AND A5-72. E. SEE ELECTRICAL DRAWINGS FOR FIXTURE TYPES AND NIGHT LIGHT LOCATIONS F. CEILING GRID LAYOUT - SYSTEM TO BE CENTERED IN ROOM, IN BOTH DIRECTIONS, UNO. CEILING GRID AREAS DIVIDED BY SOFFITS/DOORS TO BE ALIGNED. WORKPOINT MARKERS / DIMENSIONS SHALL SUPERCEDE, WHERE PROVIDED. ASSUME WORKPOINT STARTER PANELS TO BE FULL SIZE OR 6", UNLESS DIMENSIONED. G. NO CEILING PANEL TO BE CUT TO LESS THAN 6" WIDTH, TYPICAL AT CONDITIONS WHERE CEILING PANELS EXCEED 2'-0" TRIM 2' X 4' CEILING PANELS AS REQ'D TO FIT. H. COORDINATE THE LOCATION OF ESCUTCHEON PLATES AT CEILING PANEL PENETRATIONS WITH ELECTRICAL AND MECHANICAL TRADES. B-2 B-1 2.2 I. SPRINKLER HEADS TO BE LOCATED IN THE CENTER OF CEILING PANELS, UNO. J. PAINT ALL VISIBLE, EXPOSED CONSTRUCTION ABOVE CEILINGS INCLUDING BUT NOT LIMITED TO MECH & ELEC ITEMS. SEE NOTES ON A6-1x SERIES DWGS FOR EXTENT. K. FIELD VERIFY LOCATIONS OF SOFFIT & CEILING CONTROL JOINTS WITH THE A/E REP. L. REFER TO AQ-XX SERIES DRAWINGS FOR ADDITIONAL INFO ON CEILING MOUNTED EQUIPMENT. M. PATCH AND REPAIR EXISTING CEILING PANELS AND GRID WHERE WALLS ARE REMOVED. N. CONTRACTOR SHALL MAINTAIN THE FIRE RATING INTEGRITY OF ALL EXISTING PARTITIONS INDICATED AS FIRE RESISTANCE RATED. ADVISE THE ARCHITECT OF ANY PREEXISTING BREACHES DISCOVERED IN COURSE OF WORK. 3 A5-52 O. GYPSUM BD CEILINGS & SOFFITS TO BE CONSTRUCTED W/ 5/8" THK GYPSUM BOARD, AS INDICATED ON TYP DETAILS OF SHT A5-51, TO COORD WITH LT FIXTURE REQUIREMENTS. A 10' - 0" C.H. 10' - 0" C.H. CORRIDOR/WTG 410Z1 10' - 0" C.H. 10' - 0" C.H. 10' - 0" C.H. 10' - 0" C.H. 10' - 0" C.H. 10' - 0" C.H. 311 Mack Avenue Detroit, Michigan 48201 Date 12/21/11 06/27/12 07/18/12 02/15/13 04/05/13 05/24/13 Issue Progress Set 2 Scope Review Set Construction Issue 12 Construction Issue 16 Construction Issue 17 Construction Issue 18 CEILING PLAN LEGEND CORRIDOR/WTG 410Z1 2'-0"2'-0" Cardiovascular Institute & Harper-Hutzel Specialty Center REFER TO DWG A5-5x SERIES FOR CEILING DETAILS 12' - 0" C.H. 12' - 0" C.H. 12' - 0" C.H. PAT TLT 41036 SMOKE BARRIER - 1 HR FIRE RESISTANCE RATED (UNLESS ACCOMPANIED BY HIGHER DESIGNATION) A.4 1HR FIRE RESISTANCE RATED BARRIER 8' - 6" C.H. 8' - 6" C.H. 8' - 6" C.H. 8' - 6" C.H. 8' - 6" C.H. 8' - 6" C.H. CORRIDOR/WTG 410Z3 8' - 6" C.H. A.5 2HR FIRE RESISTANCE RATED BARRIER CUBICLE CURTAIN TRACK, SEE SHT A5-51 P/R 18 41040C P/R 17 41040B P/R 16 41040A P/R 8 41030H P/R 7 41030G P/R 6 41030F PUB TLT 41015 7' - 2" C.H. MEDS 41035-0 P/R 5 41030E PUB TLT 41016 7' - 2" C.H. I.V. TRACK, SEE SHT A5-51 RECEPT/ REG 41010 WORKROOM 41012 5 8' - 6" C.H. 8' - 6" C.H. SPEC HOLD/POC 41042 P/R 1 41030A NOURISH 41041 8' - 6" C.H. P/R 28 41040P P/R 2 ISO 41030B 8' - 6" C.H. 7' - 2" C.H. STF TLT 41056 6'-6" C.H. P/R 3 41030C ANES WORKROOM 41054 TRACKING ALCOVE 41065 C.J. 9' - 0" C.H. ACOUSTIC LAY-IN CEILING PANEL, TYPE AS SCHEDULED ON A6-1x SERIES WOOD VENEER LAY-IN CEILING PANEL, ACT-2 AS SCHEDULED ON A6-1x SERIES PATTERN INDICATES FIELD CUT PANEL/GRID BASED ON FIELD CONDITIONS. CUT PANELS FROM 2x4 CEILING PANELS (TYPICAL) B.2 CORRIDOR 410Z4 CONF/TRAINING 41013 PAT TLT 41031 8' - 6" C.H. 9' - 6" C.H. B.6 9' - 6" C.H. RETURN AIR DIFFUSER 8' - 6" C.H. STERILE STORAGE 41059 B.7 C.J. ELEC 41021 COMM 41020 LINEAR DIFFUSER C.J. CLG MTD MED GAS SEE DETAIL 8/A5-52 12' - 0" C.H. STF TLT 41060 CLG MTD POWER SEE DETAIL 9/A5-52 C.J. HSKG 41017 DOWN LIGHT FIXTURE C S ELEV 1 - FLUORESCENT FIXTURE 2 A5-52 SCRUB 5-6 41063 CRASH CART ALCOVE 41065A GYPSUM BOARD CEILING ON MTL FRAMING ELEVATION AS NOTED. COORD ELEV OF GYPSUM BD SOFFITS ABOVE CABINETS WITH A4-3XX SERIES, A5-81, & A5-82 DWGS. B EQUIP 41061 CLEAN SUPPLY 41058 9' - 0" C.H. GYPSUM BOARD CONTROL JOINT, SEE SHT A5-71 SUPPLY AIR DIFFUSER P/R 4 41030D SHAFT #6 - C.J. A.9 A5-51 8' - 6" C.H. REFER TO DWG A9-61 FOR ALT. #6 FIT-OUT 9' - 6" C.H. SOILED UTILITY 41057 CONTROL STATION 41055 10' - 0" C.H. CONSULT 41011 3 SHELLED S SURG P/R 41030-0 NURSE STATION 41030K SOILED UTILITY 41034 8' - 6" C.H. P/R 29 41040Q 8' - 6" C.H. CLEAN SUPPLY 41033 UNIT SEC 41043 8' - 6" C.H. P/R 30 41040R 8' - 6" C.H. ELEVATION OF FINISH CEILING AFF (8'-0" UNO) 9' - 0" C.H. A5-51 9' - 6" C.H. GOWN/WARMER ALCOVE 7' - 2" 41030J C.H. C.H. 8' - 6" C.H. A/V CLOSET 41082 SHAFT #7 - SMOKE DETECTORS S SPEAKER (GRILLE) C.3 C.J. S ELEV 2 - S NURSE CALL DOME LIGHT JUNCTION BOX IN CEILING 11' - 0" C.H. CAMERA DECON 41079 9' - 0" C.H. A5-72 26913 Northwestern Hwy Suite 200 Southfield, Michigan 48033-3476 | USA FUTURE S ELEV 4 - FLASH STERILE 41080 9' - 0" C.H. S ELEV LOBBY 410Z2 10' - 0" C.H. SCOPE CLEAN 41079A REFER TO DWG A9-62 FOR O.R. 6 FIT-OUT OR 5 41081 C.J. 14 TYP OVER LENGTH OF STAIR PASSAGE S ELEV 3 - FUTURE OR 7/8 41025 OR 6 41083-0 D C.J. EQUIP 41078 (tel) (248) 262.1500 (fax) (248) 262.1515 harleyellisdevereaux.com D.1 Planning Architecture Engineering Interior Architecture Landscape Architecture Construction Services 12 A4-501 M D.4 D.5 Copyright © 2011 2008 6 5 4 3 2 1.8 1.5 1.2 1.1 1 A FOURTH FLOOR REFLECTED CEILING PLAN - AREA A Project No. Drawn Checked Approved 2011-10001-000 M.J.Bednarczyk K.Doyle E.G.Essique Title Fourth Floor Reflected Ceiling Plan - Area A SCALE: 1/8" = 1'-0" N 3"=1'0" 8/29/2013 11:20:27 AM 0 1 1-1/2"=1'0" 1 0 1 2 3/4"=1'0" 2 1 0 2 4 1/4"=1'0" 1/8"=1'0" 8 4 0 5 10 KEYPLAN Sheet No. AR-4A 1/16"=1'0" 6 0 10 20 30 12 0 20 40 C:\Revit60Local\CQO_Arch_Model_kpdoyle_local.rvt 15 10 5 0 10 20 30 30 1"=10' 20 10 0 20 40 60 45 1"=20' 30 15 0 30 60 90 60 1"=30' 40 20 0 40 80 120 75 1"=40' 50 25 0 50 100 150 150 1"=50' 100 50 0 100 200 300 1"=100' CEILING PLAN GENERAL NOTES A. WHERE NO FINISH CEILING IS INDICATED, THE ROOM/SPACE SHALL BE EXPOSED TO THE STRUCTURE ABOVE. REFER TO ROOM FINISH SCHEDULE FOR FINISHING REQUIREMENTS. B. COORDINATE FINAL SIZE AND FINAL LOCATION OF ALL ACCESS PANELS WITH TRADE REQUIRING SAME. C. COORDINATE CEILING SUSPENSION SYSTEMS WITH OTHER CEILING SPACE EQUIPMENT SUPPORTING DEVICES. D. FOR PARTITION TYPES, SEE SHEET A5-71 AND A5-72. E. SEE ELECTRICAL DRAWINGS FOR FIXTURE TYPES AND NIGHT LIGHT LOCATIONS F. CEILING GRID LAYOUT - SYSTEM TO BE CENTERED IN ROOM, IN BOTH DIRECTIONS, UNO. CEILING GRID AREAS DIVIDED BY SOFFITS/DOORS TO BE ALIGNED. WORKPOINT MARKERS / DIMENSIONS SHALL SUPERCEDE, WHERE PROVIDED. ASSUME WORKPOINT STARTER PANELS TO BE FULL SIZE OR 6", UNLESS DIMENSIONED. G. NO CEILING PANEL TO BE CUT TO LESS THAN 6" WIDTH, TYPICAL AT CONDITIONS WHERE CEILING PANELS EXCEED 2'-0" TRIM 2' X 4' CEILING PANELS AS REQ'D TO FIT. H. COORDINATE THE LOCATION OF ESCUTCHEON PLATES AT CEILING PANEL PENETRATIONS WITH ELECTRICAL AND MECHANICAL TRADES. I. SPRINKLER HEADS TO BE LOCATED IN THE CENTER OF CEILING PANELS, UNO. J. PAINT ALL VISIBLE, EXPOSED CONSTRUCTION ABOVE CEILINGS INCLUDING BUT NOT LIMITED TO MECH & ELEC ITEMS. SEE NOTES ON A6-1x SERIES DWGS FOR EXTENT. K. FIELD VERIFY LOCATIONS OF SOFFIT & CEILING CONTROL JOINTS WITH THE A/E REP. L. REFER TO AQ-XX SERIES DRAWINGS FOR ADDITIONAL INFO ON CEILING MOUNTED EQUIPMENT. M. PATCH AND REPAIR EXISTING CEILING PANELS AND GRID WHERE WALLS ARE REMOVED. N. CONTRACTOR SHALL MAINTAIN THE FIRE RATING INTEGRITY OF ALL EXISTING PARTITIONS INDICATED AS FIRE RESISTANCE RATED. ADVISE THE ARCHITECT OF ANY PREEXISTING BREACHES DISCOVERED IN COURSE OF WORK. 3 A5-52 O. GYPSUM BD CEILINGS & SOFFITS TO BE CONSTRUCTED W/ 5/8" THK GYPSUM BOARD, AS INDICATED ON TYP DETAILS OF SHT A5-51, TO COORD WITH LT FIXTURE REQUIREMENTS. A NE ELEV LOBBY 410Z9 10' - 0" C.H. 10' - 0" C.H. 10' - 0" C.H. 10' - 0" C.H. 10' - 0" C.H. 10' - 0" C.H. 10' - 0" C.H. 2'-0" N STAIR 410X5 10' - 0" C.H. CORRIDOR/WTG 410Z1 2'-0" A.3 NURSE MGR 41097 FUTURE N ELEV 2 - N ELEV 3 SERVICE - N ELEV 4 PUBLIC - MED GAS STOR 41098 A.7 CLINICAL COORD 41096 8' - 6" C.H. 8' - 6" C.H. PUB TLT 41094 PUB TLT 41093 8' - 0" C.H. SMOKE BARRIER - 1 HR FIRE RESISTANCE RATED (UNLESS ACCOMPANIED BY HIGHER DESIGNATION) 8' - 6" C.H. 8' - 6" C.H. 8' - 6" C.H. 7' - 2" C.H. 8' - 6" C.H. 8' - 6" C.H. 8' - 6" C.H. P/R 23 41040H P/R 22 41040G P/R 21 41040F P/R 18 41040C P/R 19 41040D SUPPLY COORD 41087 8' - 6" C.H. MEDS 41047 MALE LOCKERS 41086 MALE TLT 41086A P/R 24 8' - 6" 41040J C.H. STF LOUNGE 41092 PHYS LOUNGE 41091 7' - 2" C.H. 8' - 0" C.H. B.8 FEMALE LOCKERS 41089 FEMALE TLT 41089A C.J. GYPSUM BOARD CONTROL JOINT, SEE SHT A5-71 CLEAN CART 41069 UNIT SEC 41043 8' - 6" C.H. P/R 30 41040R WOOD VENEER LAY-IN CEILING PANEL, ACT-2 AS SCHEDULED ON A6-1x SERIES SPEC HOLD/POC 41042 PATTERN INDICATES FIELD CUT PANEL/GRID BASED ON FIELD CONDITIONS. CUT PANELS FROM 2x4 CEILING PANELS (TYPICAL) SUPPLY AIR DIFFUSER P/R 27 41040N PAT TLT 41044 8' - 6" C.H. 8' - 6" C.H. CLEAN SUPPLY 41046 COMM 41050 ELEC 41051 P/R 28 41040P P/R 29 41040Q STERILE STORAGE 41052 CHARTING 41040M SHAFT #5 - 8' - 6" C.H. RETURN AIR DIFFUSER STF TLT 41056 6'-6" C.H. ANES WORKROOM 41054 STF TLT 41053 LINEAR DIFFUSER CONTROL STATION 41055 CLG MTD MED GAS SEE DETAIL 8/A5-52 CLG MTD POWER SEE DETAIL 9/A5-52 DOWN LIGHT FIXTURE C HSKG 41090 A5-51 ACOUSTIC LAY-IN CEILING PANEL, TYPE AS SCHEDULED ON A6-1x SERIES 7' - 2" C.H. 8' - 0" C.H. 6 8' - 0" C.H. 8' - 6" C.H. APPROX 9' - 8" C.H. SHAFT #4 - 7' - 2" C.H. ELEVATION OF FINISH CEILING AFF (8'-0" UNO) B 8' - 6" C.H. 7' - 2" C.H. PASSAGE 41084 C.H. 8' - 6" C.H. P/R 26 41040L 9' - 0" C.H. 8' - 6" C.H. 9' - 6" C.H. P/R 25 41040K 9' - 0" C.H. STAFF SHOWER 41085 SOILED UTILITY 41045 8' - 6" C.H. 6 A5-51 P/R 16 41040A GYPSUM BOARD CEILING ON MTL FRAMING ELEVATION AS NOTED. COORD ELEV OF GYPSUM BD SOFFITS ABOVE CABINETS WITH A4-3XX SERIES, A5-81, & A5-82 DWGS. GOWN/WARMER ALCOVE 41040T 7' - 2" C.H. 8' - 0" C.H. 8' - 0" C.H. B.1 7' - 2" C.H. P/R 17 41040B A5-51 9' - 6" C.H. 7' - 2" C.H. 2HR FIRE RESISTANCE RATED BARRIER 5 NW ELEV LOBBY 410Z10 11.3 8' - 6" C.H. CUBICLE CURTAIN TRACK, SEE SHT A5-51 P/R 20 41040E 3 A4-501 GOWN VENDING 41088 8' - 6" C.H. I.V. TRACK, SEE SHT A5-51 8' - 6" C.H. CORRIDOR 410Z6 8' - 6" C.H. Issue Progress Set 2 Scope Review Set Construction Issue 12 Construction Issue 16 Construction Issue 18 REFER TO DWG A5-5x SERIES FOR CEILING DETAILS PAT TLT 41048 8' - 6" C.H. Date 12/21/11 06/27/12 07/18/12 02/15/13 05/24/13 1HR FIRE RESISTANCE RATED BARRIER SOILED UTILITY 41049 MED DIRECTOR 41095 311 Mack Avenue Detroit, Michigan 48201 CEILING PLAN LEGEND 10' - 0" C.H. 2'-0"2'-0" 12' - 0" C.H. M N ELEV 1 PATIENTA.6 - 10' - 0" C.H. Cardiovascular Institute & Harper-Hutzel Specialty Center FLUORESCENT FIXTURE C-ARM ALCOVE 41068 COORDINATE CUT PANEL W/ LIGHTING LOCATION & TLT. COMP. SCRUB 1-2 41067 8' - 6" C.H. 9' - 0" C.H. SCRUB 3-4 41066 A/V CLOSET 41073 C.4 CORRIDOR 410Z5 CRASH CART ALCOVE 41065A 9' - 0" C.H. A/V CLOSET 41076 S SMOKE DETECTORS S SPEAKER (GRILLE) NURSE CALL DOME LIGHT JUNCTION BOX IN CEILING 8' - 0" C.H. CAMERA 12.5 12.4 12.2 12.1 EQUIP 41078 SOILED CART 41070 11.9 DECON 41079 9' - 0" C.H. 14 CLEAN CART LARGE 41071 10 A4-501 SHELLED OR 1 41072 TYP OVER LENGTH OF STAIR PASSAGE A5-72 10' - 0" C.H. OR 2 41074 10' - 0" C.H. 10' - 0" C.H. OR 3 41075 FIT-OUT O.R. 6 IN LIEU OF O.R. 1, REFER TO DWG A9-62, RM INFO REMAINS FOR REFERENCE ONLY 9' - 0" C.H. OR 4 41077 11 A4-501 26913 Northwestern Hwy Suite 200 Southfield, Michigan 48033-3476 | USA SCOPE CLEAN 41079A (tel) (248) 262.1500 (fax) (248) 262.1515 harleyellisdevereaux.com D Planning Architecture Engineering Interior Architecture Landscape Architecture Construction Services M D.4 PROVIDE NO CEILING IN ROOM Copyright © 2011 2008 11.4 11 10 9 8 7 6 B FOURTH FLOOR REFLECTED CEILING PLAN - AREA B SCALE: 1/8" = 1'-0" N N 3"=1'0" 8/29/2013 11:20:53 AM 0 1 1-1/2"=1'0" 1 0 1 2 3/4"=1'0" 2 1 0 2 4 1/4"=1'0" 1/8"=1'0" 8 4 0 5 10 KEYPLAN Project No. Drawn Checked Approved 2011-10001-000 M.J.Bednarczyk K.Doyle E.G.Essique Title Fourth Floor Reflected Ceiling Plan - Area B Sheet No. AR-4B 1/16"=1'0" 6 0 10 20 30 12 0 20 40 C:\Revit60Local\CQO_Arch_Model_kpdoyle_local.rvt 15 10 5 0 10 20 30 30 1"=10' 20 10 0 20 40 60 45 1"=20' 30 15 0 30 60 90 60 1"=30' 40 20 0 40 80 120 75 1"=40' 50 25 0 50 100 150 150 1"=50' 100 50 0 100 200 300 1"=100' ENLARGED O.R. CLG PLAN NOTES: C.J. 7' - 0 7/8" 9' - 1 1/8" 7' - 0 7/8" 7' - 0 7/8" 7' - 0 7/8" 9' - 1 1/8" C.J. C.J. REFER TO SHT A5-75 FOR A/V CLOSET CLG CLG MTD LIGHT FIXTURES (TYP) C.J. C.J. 7' - 0 7/8" C.J. ACCESS PANEL TYP. 1. SEE EQUIPMENT PLANS FOR MOUNT LOCATIONS & STRUC SUPPORT TYPE. 2. SEE 10/A5-52 FOR TYPICAL EQUIP DETAIL @ CLG PLANE. 3. * = CRIT ENV CLG C/L TO C/L DIMENSION. 4. GYP BD CLG OPENING TO BE * PLUS 3/4". SINGLE MOUNT: SURG LT FLAT PANEL CLG MTD HVAC DIFFUSER (TYP) FUTURE SINGLE MOUNT: SURG LT (PROVIDE SOLID INFILL CLG PANEL, PROVIDE STRUC SUPPORT - ABOVE) 16'-2" * 9' - 1 1/8" 7' - 0 7/8" EMER LT FIXT IN CLG PANEL CEILING CJ'S CLARIFIED IN PRE-AWARD RFI 083 RESPONSE OR 5 41081 C.J. 2' - 8 1/4" 16'-2" * TANDEM MOUNT: EQUIP BOOM SURG LT FLAT PANEL OR 4 41077 C.J. C.J. 10' - 0" C.H. REFER TO TYP. O.R. 10/A4-501 FOR TYP CEILING LAYOUT NOTES 311 Mack Avenue Detroit, Michigan 48201 C.J. 10' - 0" C.H. D D CLG MOUNTED SPEAKER (TYP FOR 2) REFER TO TYP. O.R. 10/A4-501 FOR TYP CEILING LAYOUT NOTES CEILING CJ'S CLARIFIED IN PRE-AWARD RFI 083 RESPONSE O.R. 5 ENLARGED REFLECTED CEILING PLAN 12 AR-4A CRITICAL ENVIRONMENT CEILING (ACT-10), SEE 1/A5-52 SHELLED OR 1 41072 C.J. C.J. D 5 2' - 8 1/4" Cardiovascular Institute & Harper-Hutzel Specialty Center CEILING SYSTEM ACCESS PANEL TYP. 9' - 1 1/8" 2' - 8 1/4" SINGLE MOUNT: ANES BOOM 9' - 1 1/8" 9' - 1 1/8" TABLE CENTER LAYOUT BENCHMARK 11 AR-4B SCALE: 1/4" = 1'-0" CEILING CJ'S CLARIFIED IN PRE-AWARD RFI 083 RESPONSE 9 TYP O.R. 3 & 4 ENLARGED REFLECTED CEILING PLAN 10 AR-4A SCALE: 1/4" = 1'-0" TYP O.R. 1 & 2 ENLARGED REFLECTED CEILING PLAN Date 06/27/12 07/18/12 08/08/12 02/15/13 SCALE: 1/4" = 1'-0" 1.8 Issue Scope Review Set Construction Issue 12 Construction Issue 13 Construction Issue 16 B.6 B.7 1 A4-10 T REFER TO AR-x SERIES DRAWINGS FOR RELATED PLAN GENERAL NOTES AND KEYNOTES. CEILING PLAN LEGEND C REFER TO DWG A5-5x SERIES FOR CEILING DETAILS 1 SMOKE BARRIER - 1 HR FIRE RESISTANCE RATED (UNLESS ACCOMPANIED BY HIGHER DESIGNATION) A5-04 1HR FIRE RESISTANCE RATED BARRIER 2HR FIRE RESISTANCE RATED BARRIER CUBICLE CURTAIN TRACK, SEE SHT A5-51 I.V. TRACK, SEE SHT A5-51 C.3 3 C.H. ELEVATION OF FINISH CEILING AFF (8'-0" UNO) C.J. GYPSUM BOARD CONTROL JOINT, SEE SHT A5-71 A4-10 GYPSUM BOARD CEILING ON MTL FRAMING ELEVATION AS NOTED. COORD ELEV OF GYPSUM BD SOFFITS ABOVE CABINETS WITH A4-3XX SERIES, A5-81, & A5-82 DWGS. ACOUSTIC LAY-IN CEILING PANEL, TYPE AS SCHEDULED ON A6-1x SERIES WOOD VENEER LAY-IN CEILING PANEL, ACT-2 AS SCHEDULED ON A6-1x SERIES TYP 2 PATTERN INDICATES FIELD CUT PANEL/GRID BASED ON FIELD CONDITIONS. CUT PANELS FROM 2x4 CEILING PANELS (TYPICAL) A5-52 SUPPLY AIR DIFFUSER CONT COVE LT FIXTS, SEE SECTION RETURN AIR DIFFUSER LINEAR DIFFUSER CLG MTD MED GAS SEE DETAIL 8/A5-52 CLG MTD POWER SEE DETAIL 9/A5-52 DOWN LIGHT FIXTURE 26913 Northwestern Hwy Suite 200 Southfield, Michigan 48033-3476 | USA FLUORESCENT FIXTURE S SMOKE DETECTORS S SPEAKER (GRILLE) D D.1 (tel) (248) 262.1500 (fax) (248) 262.1515 harleyellisdevereaux.com NURSE CALL DOME LIGHT JUNCTION BOX IN CEILING CAMERA 1.5 4 . HOLD 6" TO INSIDE FACE OF CURTAIN WALL @ 1ST & 2ND, EXT WALL @ 4TH 8'-0" CLERESTORY, SEE DET. 17/A5-65 FP SPRINKLER HEAD 4 A5-52 DROPPED ACOUSTIC CLG LT FIXT ACOUSTIC CLG GYP BD SOFFIT EQUAL 1" CLR PROVIDE INTERMEDIATE GRID AS REQ'D FOR DIFFUSER FP SPRINKLER HEAD FP SPRINKLER HEAD SUPPLY DIFFUSER SUPPLY DIFFUSER SUPPLY DIFFUSER LIGHT FIXTURE, TYP. LIGHT FIXTURE, TYP. M 48" LG I.V. TRACK, TYP TV LAY-IN CLG. LIGHT FIXTURE, TYP. LAY-IN CLG. LAY-IN CLG. 8' - 0" C.H. 8' - 6" C.H. 1" CLR GYP. BD. SOFFIT GYP. BD. SOFFIT CUBICLE CURTAIN TRACK 8' - 0" C.H. GYP. BD. SOFFIT 1" CLR CUBICLE CURTAIN TRACK Project No. Drawn Checked Approved 2011-10001-000 KCade K.Doyle E.G.Essique Title Enlarged Reflected Ceiling Plans CUBICLE CURTAIN TRACK 3 5 TYP 3"=1'0" 8/29/2013 11:16:46 AM 8' - 6" C.H. 8' - 6" C.H. 4" 4 HEAD LIGHT FIXTURE 2'-0" HEAD LIGHT FIXTURE 8' - 6" C.H. CLERESTORY, SEE DET. 17/A5-65 HEAD LIGHT FIXTURE 1" CLR A5-52 CLERESTORY, SEE DET. 17/A5-65 TV PROVIDE CUT CLG PANELS EA SIDE OF CENTERED DIFFUSER, ORIENT MAIN SUSPENSION MEMBERS AS NECESSARY J 4 ALIGN, TYP Copyright © 2011 2008 COORD ALIGN, TYP SCALE: 1/4" = 1'-0" F A5-52 22'-0" (COORD FULL PANELS) TYPICAL ELEVATOR LOBBY .2"-0" 3 EQUAL TYP Planning Architecture Engineering Interior Architecture Landscape Architecture Construction Services 1.2 0 3 A9-61 TYPICAL CORRIDOR/WTG TYP P/R REFLECTED CEILING PLAN-4th FLOOR 2 AR-2A SCALE: 1/4" = 1'-0" TYP P/R REFLECTED CEILING PLAN -2nd FLOOR SCALE: 1/4" = 1'-0" 1 A9-31 10 TYP P/R REFLECTED CEILING PLAN-1st FLOOR SCALE: 1/4" = 1'-0" SCALE: 1/4" = 1'-0" Sheet No. 1 1-1/2"=1'0" 1 0 1 2 3/4"=1'0" 2 1 0 2 4 1/4"=1'0" 1/8"=1'0" 8 4 0 5 10 A4-501 1/16"=1'0" 6 0 10 20 30 12 0 20 40 C:\Revit60Local\CQO_Arch_Model_kpdoyle_local.rvt