AUSTIN JOB # 10214D SHEET NO. 480V, 3 POWER SUPPLY. SEE SINGLE LINE DWG. HEE003 01-14-11 FAN MOTOR DISCONNECT SWITCH SUPPLIED WITH FAN COMBINATION CIRCUIT BREAKER-MAGNETIC STARTER. SEE SYMBOL LEGEND FOR DESCRIPTION. 480V 100 VA OFF AUTO MAN OL OL OL MOTORIZED BACKDRAFT DAMPER 06-25-09 PUSH-TO-TEST LAMP PKM 0 ISSUED FOR CONSTRUCTION 120V RP 3A LV1 SEE INTERLOCK TABLE BELOW TYPICAL EXHAUST FAN CONTROL DIAGRAM EF# HP EF-1 EF-2 EF-3 EF-4 2 2 2 2 V 480 480 480 480 RELAY NO2/CO CONTACT CONTACT CR1 CR1 CR2 CR2 CR3 CR3 CR3 CR3 TYPE "SA" SITE LIGHT POLE DETAIL TYPE "SC" SITE LIGHT POLE DETAIL TYPE "SB" SITE LIGHT POLE DETAIL DAMPER MOTOR LV1 LV2 LV3 SEE EF-4 BLOCK DIAGRAM N H CR3 CR3 ** TO EF-1 TO EF-2 NO2/CO PANEL CR3 CR3 TO EF-3 TO EF-4 TO EF-1 TO EF-2 TO EF-3 TO EF-4 ** THERMOSTAT-T1 ** THERMOSTAT-T2 EF-4 RUNNING FROM VFD SCHEMATIC DIAGRAM FOR EF1-EF4 CONTROL TYPE "SD" SITE LIGHT POLE DETAIL 480V, 3 POWER AS PER SINGLE LINE DRAWINGS BAR JOIST POWER FEEDER AS SPECIFIED ON SINGLE LINE DWG. (HEE003) EXISTING FACP ANGLE BAR F F F F F F F F F F V NUMBER OF DEVICES SHALL BE AS PER FLOOR PLANS. (TYPICAL) 120V - RPN-13 SEE SITE PLAN (DWG. HES001) FOR LOCATION EXISTING F.A.C.P. IS MFG. BY EDWARDS TECHNOLOGY SYSTEM MODEL EST-2 MOTOR RUNNING VARIABLE FREQUENCY DRIVE (VFD) F FS VFD CONTROL DEVICE (S) ZM ZM FS TS SEE NOTE 2. FS PS AIR COMPRESSOR PRESSURE SWITCH FLOW SWITCH @ SPRINKLER RISER ELECTRIC BELL, FEDERAL SIGNAL CAT#504WB 2 #14 'CP1' CR2 CONTROL WIRING IN 1" C. NUMBER & SIZE OF WIRES AS REQUIRED PER EQUIPMENT VENDOR 1. NOTES: 2. CR3 MOUNTING HEIGHT = 27' A.F.F. METAL POLE BASE CONNECTION DETAIL 3. Scale: NTS CONTRACTOR SHALL VERIFY EXISTING FACP, ADD MODULES AS REQUIRED. ADD POWER EXTENDER AS REQUIRED. TEST & VERIFY COMPLETE SYSTEM AFTER INSTALLATION. SUBMIT REQUIRED DRAWINGS & DETAILS TO LOCAL AUTHORITY HAVING JURISDICTION AS REQUIRED. CONTRACTOR SHALL COORDINATE SPRINKLER CONTRACTOR FOR REQUIRED NUMBER OF SWITCHES AS PER SPRINKLER CONTRACTOR'S SHOP DRAWING. INCLUDE WIRING OF ADDITIONAL SWITCHES AND ZONE MODELS AS REQUIRED. SHUTDOWN AND REPROGRAMMING FOR MODIFICATIONS OF EXISTING FIRE ALARM CONTROL PANEL SHALL BE COORDINATED WITH OWNER. EXTRA COST ASSOCIATED WITH THESE SHALL BE INCLUDED. SEAL ALL RIGHTS RESERVED. THIS DRAWING IS THE PROPERTY OF FEDEX GROUND, INC. AND IS LOANED WITH THAT UNDERSTANDING AND SHALL NOT BE COPIED, REPRODUCED, OR OTHERWISE DISPOSED OF DIRECTLY OR INDIRECTLY. TO DAMPER MOTOR LV-4 F PACKAGE DISTRIBUTION CENTER 8951 YOSEMITE STREET COMMERCE CITY, COLORADO 80022 ELECTRICAL DETAILS & SCHEMATICS 1. CONTROL RELAYS 'CR1', 'CR2', AND 'CR3' - SQUARE-D CLASS 8501, TYPE KU-13P14-V20-3PDT, 5 AMPERE, 120V FUSE WITH FUSE BLOCK. MOUNT RELAY AND FUSE AND TERMINAL STRIP IN 8" x 8" NEMA-1 ENCLOSURE WITH LIFT-OFF TYPE COVER. PANEL TAG SHALL BE "CP1". (#802) NOTES: E.T.C. SHALL PROVIDE THE FOLLOWING: SHEET NO. AUSTIN JOB # 10214D LATEST PRINT January 14, 2011 SUPERCEDES ALL PREVIOUS HEE004.dwg