TYPICAL EXHAUST FAN CONTROL DIAGRAM SCHEMATIC

AUSTIN JOB # 10214D
SHEET NO.
480V, 3
POWER SUPPLY.
SEE SINGLE LINE
DWG. HEE003
01-14-11
FAN
MOTOR
DISCONNECT SWITCH
SUPPLIED WITH FAN
COMBINATION CIRCUIT
BREAKER-MAGNETIC
STARTER. SEE SYMBOL
LEGEND FOR DESCRIPTION.
480V
100 VA
OFF
AUTO
MAN
OL
OL
OL
MOTORIZED
BACKDRAFT
DAMPER
06-25-09
PUSH-TO-TEST LAMP
PKM
0 ISSUED FOR CONSTRUCTION
120V
RP
3A
LV1
SEE INTERLOCK
TABLE BELOW
TYPICAL EXHAUST FAN CONTROL DIAGRAM
EF#
HP
EF-1
EF-2
EF-3
EF-4
2
2
2
2
V
480
480
480
480
RELAY
NO2/CO
CONTACT CONTACT
CR1
CR1
CR2
CR2
CR3
CR3
CR3
CR3
TYPE "SA" SITE LIGHT POLE DETAIL
TYPE "SC" SITE LIGHT POLE DETAIL
TYPE "SB" SITE LIGHT POLE DETAIL
DAMPER
MOTOR
LV1
LV2
LV3
SEE EF-4 BLOCK
DIAGRAM
N
H
CR3
CR3
**
TO EF-1
TO EF-2
NO2/CO
PANEL
CR3
CR3
TO EF-3
TO EF-4
TO EF-1
TO EF-2
TO EF-3
TO EF-4
**
THERMOSTAT-T1
**
THERMOSTAT-T2
EF-4 RUNNING
FROM VFD
SCHEMATIC DIAGRAM FOR EF1-EF4 CONTROL
TYPE "SD" SITE LIGHT POLE DETAIL
480V, 3 POWER AS
PER SINGLE LINE
DRAWINGS
BAR
JOIST
POWER FEEDER AS SPECIFIED ON
SINGLE LINE DWG. (HEE003)
EXISTING
FACP
ANGLE BAR
F
F
F
F
F
F
F
F
F
F
V
NUMBER OF DEVICES SHALL BE AS PER
FLOOR PLANS. (TYPICAL)
120V - RPN-13
SEE SITE PLAN
(DWG. HES001) FOR
LOCATION
EXISTING F.A.C.P. IS MFG.
BY EDWARDS TECHNOLOGY
SYSTEM MODEL EST-2
MOTOR
RUNNING
VARIABLE
FREQUENCY
DRIVE (VFD)
F
FS
VFD CONTROL
DEVICE (S)
ZM
ZM
FS
TS
SEE NOTE 2.
FS
PS
AIR COMPRESSOR
PRESSURE SWITCH
FLOW SWITCH @
SPRINKLER RISER
ELECTRIC BELL,
FEDERAL SIGNAL
CAT#504WB
2 #14
'CP1'
CR2
CONTROL WIRING IN 1" C.
NUMBER & SIZE OF WIRES AS
REQUIRED PER EQUIPMENT
VENDOR
1.
NOTES:
2.
CR3
MOUNTING HEIGHT = 27' A.F.F.
METAL POLE BASE CONNECTION DETAIL
3.
Scale: NTS
CONTRACTOR SHALL VERIFY EXISTING FACP, ADD MODULES AS REQUIRED. ADD POWER EXTENDER AS
REQUIRED. TEST & VERIFY COMPLETE SYSTEM AFTER INSTALLATION. SUBMIT REQUIRED DRAWINGS &
DETAILS TO LOCAL AUTHORITY HAVING JURISDICTION AS REQUIRED.
CONTRACTOR SHALL COORDINATE SPRINKLER CONTRACTOR FOR REQUIRED NUMBER OF SWITCHES AS
PER SPRINKLER CONTRACTOR'S SHOP DRAWING. INCLUDE WIRING OF ADDITIONAL SWITCHES AND ZONE
MODELS AS REQUIRED.
SHUTDOWN AND REPROGRAMMING FOR MODIFICATIONS OF EXISTING FIRE ALARM CONTROL PANEL
SHALL BE COORDINATED WITH OWNER. EXTRA COST ASSOCIATED WITH THESE SHALL BE INCLUDED.
SEAL
ALL RIGHTS RESERVED. THIS DRAWING IS THE PROPERTY OF FEDEX GROUND, INC. AND IS LOANED WITH THAT
UNDERSTANDING AND SHALL NOT BE COPIED, REPRODUCED, OR OTHERWISE DISPOSED OF DIRECTLY OR INDIRECTLY.
TO DAMPER
MOTOR LV-4
F
PACKAGE DISTRIBUTION CENTER
8951 YOSEMITE STREET
COMMERCE CITY, COLORADO 80022
ELECTRICAL DETAILS & SCHEMATICS
1. CONTROL RELAYS 'CR1', 'CR2', AND 'CR3' - SQUARE-D CLASS 8501, TYPE KU-13P14-V20-3PDT, 5 AMPERE, 120V FUSE
WITH FUSE BLOCK. MOUNT RELAY AND FUSE AND TERMINAL STRIP IN 8" x 8" NEMA-1 ENCLOSURE
WITH LIFT-OFF TYPE COVER. PANEL TAG SHALL BE "CP1".
(#802)
NOTES:
E.T.C. SHALL PROVIDE THE FOLLOWING:
SHEET NO.
AUSTIN JOB # 10214D
LATEST PRINT January 14, 2011 SUPERCEDES ALL PREVIOUS
HEE004.dwg