Catalog Number Notes Type FEATURES & SPECIFICATIONS HOUSING OPTIONS Shipped installed SF Single Fuse. Use with 120, 277, 347V. Not available with Multi-tap ballast. In-line fusing isolates faulty luminaire from circuit. Externally accessible. DF Double Fuse. Use with 208, 240, 480V. Not available with Multi-tap ballast. In-line fusing isolates faulty luminaire from circuit. Externally accessible. EC Emergency Circuit. Factory-installed, double-contact, bayonetbase quartz socket with socket leads for use with separate external emergency power system. (See chart at left.) (150W maximum on acrylic opticals with lensed bottom.) HA High Ambient. Allows the industrial luminaires to be operated in high-ambient temperatures. TX-A30, TX-A26, TX-A20, TX-A23, TXA165: 55°C; TH-A14, TH-A15, TH-A16, TH-A17, TE, TPG, TPGE: 65°C. QRS Quartz Restrike System. Automatically switches 120V quartz lamp on if there is a power interruption or brownout significant enough to cause the primary HID lamp to drop out. The 120V quartz lamp stays on until the HID fixture restrikes. QRS does not energize during cold start of HID luminaires. Wiring for the quartz lamp is internal to the ballast assembly; the 120V required to operate the quartz lamp is supplied by the ballast. Wattage of quartz lamp should not exceed that of HID source. (See chart at left.) (150W maximum on acrylic opticals with lensed bottom.) QRSTD Quartz Restrike System Time Delay. Functions as does QRS, but 120V quartz lamp energizes under hot and cold starting conditions. Quartz lamp will come on when luminaire is energized and remain on for two minutes after start-up or restrike of HID lamp. Wiring for the quartz lamp is internal to the ballast assembly; the 120V required to operate the quartz lamp is supplied by the ballast. (See chart at left.) (150W maximum on acrylic opticals with lensed bottom.) MOUNTING/HOUSING OPTIONS Shipped installed TOB Through-Wire Outlet Box. A combination outlet box and splice compartment. Permits entry of 1-1/4" or 3/4" rigid or thin-wall conduit through easily-removable knockouts. TOB may be suspension or surface mounted. Height 2-7/8"; width 4-1/2". TOBP Through-Wire Outlet Box Plug-In. Provides plug-in flexibility of conventional power hook and reduces overall height. Female receptacle part of TOBP box. Male plug is factory installed to ballast housing. This option is not rated as a load break device. Height 2-7/8"; width 4-1/2". Permits entry of rigid 3/4" or thin-wall conduit through easily removable knockout. PBP Pendant Box Plug-In. Pendant-mount plug-in outlet box is identical in function to TOBP, except for pendant mounting. Height 4-1/2" width and depth 4-1/2". PSB Pendant Splice Box. Use with TG. Permits rigid pendant mounting. PMB Pendant Mount Box. Use with TGL, TGR. Permits rigid pendant mounting. HID Lighting Industrial Options SF DF Factory Installed QRS HID Wattage 150 & below 175 250 Quartz Wattage Quartz Lamp Type (Lamp by Others) 100 150 Double Contact Bayonet Base 120V Lamp 250 400 250 1000 500 TOBP TOB PBP PSB (TG) PM (TGL, TGR) Indoor H.I.D. Sheet # OPT1 OPAC-120 OPT1 Industrial Options REMOTE BALLAST OPTIONS Shipped installed TR Remote Ballast. Includes ballast housing and remote optical with RSBA or RSBB. Does not include interconnecting wiring. Add TR to the end of fixture line item. RSBA Remote Splice Box. Adjustable for TH A16, TH A17, TH A14, TH A15, TH-PA22/PA25 high bay optical assemblies; 4-7/8" x 4-1/4" x 3-3/8". RSBB Remote Splice Box. Bolt-on for TE, TX A30, TX A26, TX A20, TX A23, TX A165, TX-PA22/PA25 and enclosed or low bay optical assemblies; 4-7/8" x 4-1/4" x 3-3/8". RC3NP Remote Ballast with Prewired cable. Includes ballast housing and remote optical with RPMA or RPMB and 3 feet of prewired cable harness with Male and Female 20-amp twist lock plug (C3NP). Add RC3NP to the end of fixture line item. TR RSBB RSBA Ballast Options Shipped installed CWI MRB ENC RLB LLRPSL SCWA Constant-Wattage Isolated Ballast. 120, 208, 240V in Canada. Not available in all fixtures. Consult factory. Magnetic Regulator Ballast. 70–400W HPS. Not available in all voltages. Consult factory. Encapsulated Ballast. Use with 120/277V for 175W, 250W and 400W metal halide and 250W HPS. Not available TG/TGR. Regulated Lag Pulse Start Ballast. Use with 175-450W metal halide fixtures. Consult factory. Low Loss Reactor Pulse Start Ballast. Use with 150-450W-277V pulse start metal halide fixtures only. Consult factory. Super Constant-Wattage Autotransformer Pulse Start Ballast. Use with 150-1000W pulse start metal halide fixtures only. 120-480V. Consult factory. RC3NP FIXTURE FINISHES CR Corrosion-Resistant Finish. Clear polyester coating for additional protection against some corrosive atmospheres. Consult factory for corrosive compatibility. CRT Corrosion-Resistant Finish. Teflon coating of all external luminaire surfaces. Optical assemblies have a clear coat. Ballast housing/mounting accessories are black. TE, TH A17, TX A20, TPGE, TX A26 and TPG ballast housing only. TEF Teflon. Finished reflectors are coated with one-mil layer of Teflon to provide superior corrosion-resistance and ease of maintenance. TE, TH A17, TX A20 and TX A26. For optional architectural colors see architectural color chart for options. Add as suffix to catalog number. Lithonia Lighting Sheet#: OPT1 ©2001 Acuity Lighting Group, Inc. 05/06 Indoor HID One Lithonia Way, Conyers, GA 30012 Phone: 800-315-4963, Fax: 770-602-1531 www.lithonia.com