Element C Interiors Interior Finishes C3030 Ceiling Finishes PART 1 - GENERAL 1.01 OVERVIEW A. Includes acoustical tiles, gypsum wallboard, plaster, and exposed ceiling finishes. PART 2 - DESIGN CRITERIA 2.01 GENERAL A. The following table indicates finishes for various room types within Owner’s facilities. Confirm finishes with Owner’s Project Manager / Planner Designer. Room Type Conference Rooms, Dining Areas, Public Lobbies Offices, Work Rooms, Staff Corridors, Public Spaces, Clinical Areas, Public and Clinic Restrooms, Storage, Building Services, Shops, Telecommunication MDF Rooms, Service Elevator Lobbies Mechanical/Electrical Equipment Rooms, Dock Receiving, Security, Telecommunication IDF Rooms Patient Bedroom Toilets, Isolation and Procedure Rooms, Clean Workrooms/Clean Supply, Soiled Workrooms/Soiled Holding, Janitor Closets, Shower Rooms Operating Rooms Pharmacy, Nutrition Selected Imaging Rooms Laboratories Vivarium and Vivarium Support Functions Tissue Culture Rooms Shell Space The University of Texas MD Anderson Cancer Center ODG013113 Ceiling Finish Combination of 2 x 2 lay-in acoustical tile and suspended gypsum wallboard; painted, flat finish. 2 x 2 lay-in acoustical tile. Painted exposed concrete structure, satin finish, no finish at exposed steel/fire-proofing structure. Gypsum wallboard with semi-gloss paint. Gypsum wallboard with epoxy paint. 2x2 cleanable acoustical tile. Combination of acoustical tile, 2’X2’ and unistrut metal grid to support overhead equipment Combination of acoustical tile, 2’X2’ grid and suspended gypsum wallboard; painted, satin finish; to coordinate with ceiling service panel. Suspended gypsum wallboard; painted, water-base epoxy. Cleanable ceiling tile, 2’x2’ grid No finish. CEILING FINISHES C3030 1 OF 3 Element C Interiors Interior Finishes C3030 Ceiling Finishes PART 3 - SPECIAL CONTRACT DOCUMENT REQUIREMENTS 3.01 GENERAL A. In addition to incorporating all applicable life safety and building code requirements, provisions described within this Element shall be included within the Project Contract Documents. B. Typically, at lay-in ceilings provide a suspended white galvanized exposed tee, intermediate duty system. Provide aluminum grid at areas subject to high humidity or wash-down conditions. C. Avoid conditions where drywall ceilings/furring intersects lay-in ceilings at the same plane. D. Detail terminations of partitions at continuous grid ceilings. E. Where suspended “floating” ceiling elements are used, provide a design which conceals or shields from view all related supports, mechanical items, lighting fixtures, conduit, and piping, etc. PART 4 - PRODUCTS 4.01 GENERAL A. Obtain approval from Owner’s Project Manager/Planner Designer for all finish schedules prior to issuance of Construction Documents. B. For renovation projects, refer to Owner’s Master Construction Specifications and Interior Finishes Standards. These are available on the Owner’s Design Guidelines website: Construction Specifications - http://www2.mdanderson.org/depts/cpm/standards/specs.html Interior Finish Standards - http://www2.mdanderson.org/depts/cpm/standards/interiors.html The University of Texas MD Anderson Cancer Center ODG013113 CEILING FINISHES C3030 2 OF 3 Element C Interiors Interior Finishes C3030 Ceiling Finishes PART 5 - DOCUMENT REVISION HISTORY Issue Date Revision Description Reviser 01-01-07 Initial Adoption of Element Rev. 1 05-03-07 Updated room types for 2x2 lay-in acoustical tile; revised finishes at equipment rooms, dock, etc. SAK Rev. 2 08-14-08 Various revisions throughout document incorporating interior standards and eliminating project specific requirements. LN, JC, DB Rev. 3 07-08-10 Revised Laboratory finishes. KB Rev. 4 04-17-12 Added Operating Rooms to table; Added 3.01 B, 3.01 C, 3.01 D, and 3.01 E JC Rev. 5 10-30-12 Revised Service Elevator Lobbies finish to be 2x2 lay-in acoustical tile. Article 2.01 A. JC Rev. 6 01-31-13 Clarified ceiling finish for toilet rooms. Article 2.01 A. JC END OF ELEMENT C3030 The University of Texas MD Anderson Cancer Center ODG013113 CEILING FINISHES C3030 3 OF 3