Packaged Fresh Air Unit

advertisement

Packaged Fresh Air Unit

For 100% Outdoor Air Applications

Model FADA/FAHA Product Catalog

December 2002

MUA-PRC004-EN

Introduction

The Packaged Fresh Air Unit...

Trane’s DX Packaged Rooftop unit for 100% outside air applications leads the industry in:

• Indoor Air Quality (IAQ) Features

• High Quality and Durability

• Advanced Controls

Unit mounted IntelliPak ™ microprocessor control with easy-to-read human interface

2’’ Pleated filter section with adjustable rack to 4’’

Horizontal or vertical discharge openings

Hi-rise electric

(or gas) heat

1’’ Solid double-wall panels of foamed-inplace construction

Quiet FC fan

© 2002 American Standard Inc.

Non-corrosive IAQ drain pan sloped in two directions

Optional condenser reheat coil with modulating control

Standard protective bird screen on inlet hood

Traq ® damper available for airflow measurement

Optional return air damper for unoccupied recirculation

MUA-PRC004-EN

MUA-PRC004-EN

Table of

Contents

Features and Benefits

Application Considerations

Selection Procedure

General Data

15

20

4

6

Performance Data

Controls

Electrical Data

Dimensions & Weights

Mechanical Specifications 112

21

77

86

90

3

Features and

Benefits

Features and Benefits

We designed the Packaged Fresh Air unit based on customer requirements from across the country. Thorough analysis of the performance requirements resulted in a robust design with the ability to effectively operate over an expansive performance envelope required for the year-round treatment of outdoor air.

Also, we took into account today’s HVAC market issues, such as indoor air quality

(IAQ). We equipped the Packaged Fresh

Air unit to meet your ventilation needs

— in direct response to the ventilation and humidity control requirements of

ASHRAE standard 62.1-1999.

Trane’s Packaged Fresh Air unit leads the industry in the key areas of:

• indoor air quality (IAQ)

• high quality and durability

• advanced, integrated controls

• flexibility

• enhanced serviceability

Indoor Air Quality (IAQ) Features

• Non-corrosive drain pan sloped in two directions to ensure proper drainage to reduce the potential for microbial growth

• Double-wall foamed panel construction throughout the indoor section of unit to provide, non-porous, cleanable interior surfaces

• High efficiency throwaway filter option with standard 2” or 4” adjustable filter rack

• Traq™ outdoor airflow measurement damper

• total energy wheel option for recovered energy from centralized building exhaust

• Easy filter access encourages frequent changing

High Quality and Durability

• Robust unit construction with 1” double-wall panels and access doors.

• High quality, long-lasting latches and hinges for all access doors.

• Protective standard prepainted finish on cabinet exterior with optional corrosion inhibiting coatings available for the unit exterior, interior and coils.

• Assured dehumidification performance and control with capability of providing low dew point supply air.

• Optional modulating recovered refrigerant reheat for unit supply air.

Advanced Controls

• All controls are factory-engineered, mounted, configured and tested to minimize field startup time.

• IntelliPak™ microprocessor control with easy-to-read human interface clear language display (English,

French, or Spanish).

• Human interface with 16-button keypad for monitoring, setting, editing and controlling.

• Capable of supply-air control or zone control of both temperature and relative humidity

• Occupied and unoccupied control sequences including unoccupied economizer logic.

• Additional control sequences including demand limit, exhaust control and

CO2 monitoring.

• Optional remote human interface for ease of control access without going outdoors.

• Optional LonTalk® communications interface (LCI-I) communication link with a Tracer Summit™ building management system or other control systems that support the LonTalk discharge air control (DAC) profile.

• Generic BAS and ventilation override capability for added control flexibility

Flexibility

• Modular Intellipak controller design…you only pay for what you need

• Vertical or horizontal discharge available

• Numerous heater options and temperature rise capabilities available.

• Standardized roof curb

Figure FB-1. Fan side view of the Trane Packaged fresh air unit

4 MUA-PRC004-EN

Features and

Benefits

Enhanced Serviceability

• Five hinged access doors with safety chains for ease of maintenance and service

• Easy-open door latches

• Human Interface (HI) door provides access without opening control panel door

• Modular control board design with ability to swing out HI during service

Standard Unit Features

• Four unit sizes (031, 040, 051, 066) with airflow range of 1800-6600 cfm

• Double-wall construction with 18g outer and 20g inner galvanized metal skin.

• Outdoor air inlet hood

• Prepainted exterior finish

• Air-cooled DX refrigeration system

• Completely factory-piped and leaktested refrigeration system

• Non-corrosive drain pans sloped in two planes

• Centrifugal double-width, double-inlet

FC fan with permanently lubricated bearings

• Scroll compressors

• Terminal block for power connection

• Single-point power connections for non-electric heat units

• Filter rack adjustable for two or four inch filters

• UL listing on all standard options

Standard Control Features

• Fully integrated, factory-installed and commissioned microelectronic controls

• Unit mounted human interface panel

• FROSTAT™ coil frost protection

• Supply airflow proving

• Emergency stop

• Mappable sensors and setpoint sources

• Occupied/unoccupied control modes

• Timed override for unoccupied mode

Optional Features

• Vertical or horizontal discharge

• Low or high rise gas heaters (single bank and dual bank)

• Staged or modulating gas heat control

(4:1 max turndown)

• 409 or 321 stainless steel gas burner

• Three or seven stage electric heat

• Hydronic heat interface (heat coil fieldprovided)

• Condenser reheat with modulating control

• Low-leak parallel blade or Traq™ outdoor airflow damper

• Return air damper with comparative or reference enthalpy

• Standard or high-efficiency fan motor

• total energy wheel

• Protective coatings for the unit and/or coils

• Two inch pleated media filters (30% efficiency)

• Dirty filter switch

• Supply air or zone control

• Larger, more efficient fan option available for high airflow, low external static pressure points

• LonTalk® Communications Interface module

• Generic BAS module

• Ventilation override from up to five external inputs

• Remote human interface

• Exhaust interface with exhaust opening integral to unit cabinet

• Through-the-door, non-fused disconnect switch

• Factory or field-wired convenience outlet

• Extended fan grease lines

Field-Installed Accessories

• Roof curb in 14” or 24” height

• Remote human interface controls up to four units

• 2” cleanable filters

• Time clock

• Zone sensors with a variety of different features and functions

• Field-installed module kits available for field upgrade of controls

• Remote minimum potentiometer control

• CO

2

sensor available with Traq™ only

• Duct-mounted temperature sensor

Figure FB-2. Compressor side view of the Trane Packaged fresh air unit

MUA-PRC004-EN 5

Application

Considerations

6

Overview

Fresh Air Unit Functions

The Packaged Fresh Air unit (FAU) provides conditioned outdoor air suitable for mechanical ventilation or make-up air. The FAU conditions outdoor air as necessary to meet system performance requirements by filtration, cooling, dehumidification, and/ or heating. The FAU may deliver ventilation air in a number of ways. See the System Configurations section and

Figures AC-1 through AC-3 for more information.

Filtration

Filtration is necessary for the FAU to maintain system operating efficiency, meet occupant comfort and health needs, and provide adequate building filtration to aid indoor air quality. The

Packaged FAU offers a variety of filter options to meet most application needs.

Cooling

When the outdoor air dry-bulb temperature is warmer than space conditions, the unit cools the outdoor air to the appropriate supply air dry-bulb temperature. The Packaged FAU provides cooling using an air-cooled, directexpansion (DX) refrigeration system with scroll compressors.

Dehumidification (Drying)

The Packaged FAU dehumidifies the outdoor air when it is more humid than the required space target conditions.

This helps prevent high relative humidity levels in the space. Occasionally, the outdoor air may require sub-cooling to remove excess moisture. When necessary, the FAU reheats discharge air to meet space comfort conditions.

The Packaged FAU recovers energy from the cooling process to reheat the sub-cooled air as necessary.

Heating

When the outdoor air dry-bulb temperature is colder than space conditions require, the FAU heats the outdoor air to meet space temperature requirements.

The Packaged FAU has electric or gas heat options available.

System Configurations

Dedicated outdoor air systems can deliver conditioned outdoor air in one of the following ways:

1. Directly to the occupied space, with the local terminal unit controlling the space dry-bulb temperature. See

Figure AC-1.

2. Directly to local terminal units, which deliver a mixture of the conditioned outdoor air and (conditioned) recirculated return air to the space. See

Figure AC-2.

3. Directly to a single space and control the space temperature directly. For example, this application will provide temperature control of a hotel hallway and ventilation of the adjacent rooms.

See Figure AC-3.

Supply Air Temperature

Give careful consideration when selecting the FAU supply air temperature. Many current system designs control the fresh air unit discharge air to a “space neutral” dry-bulb condition, typically about 75°F. At some operating conditions, reheating the FAU supply air will add cooling load to the space, thus requiring the local terminal units to “recool” the conditioned outdoor air to meet the space setpoint. Therefore, to help lower energy costs, use reheat only when required to maintain occupant comfort and space relative humidity. The Capacity Control section discusses this issue in more detail.

Airside Economizers

Often fresh air units are sized to deliver the minimum ventilation air required for the space it serves. However, ventilation air is typically only a portion of the space supply air. Airside economizing can provide up to 100% of the space supply air when outdoor air conditions are suitable for “free cooling” capability.

It’s important to remember that airside economizer capability can be lost if dedicated outdoor air systems are sized for minimum ventilation air only. To provide economizer capability on a dedicated outdoor air system, the terminal units must be able to introduce

100% outdoor air during the economizer-cooling mode. The terminal unit’s outdoor air damper should modulate between fully closed and fully open to allow the FAU to deliver the ventilation air design volume to the space. The terminal unit should enable economizing only if the outdoor dry-bulb and dew point conditions are sufficiently low to justify economizing.

Figure AC-1. Direct discharge to conditioned space

Figure AC-2. Indirect discharge to fan-coil units

Figure AC-3. Direct hall discharge with fancoil or PTAC units

MUA-PRC004-EN

Application

Considerations

Packaged FAU Operation

The Packaged FAU can use either DX cooling, condenser reheat, electric or gas heat to condition the outdoor air.

The unit controls cooling and heating capacity in stages with the exception of the modulated heat options. Cooling and heating staging result in supply air temperature swings. The unit controls deliver the desired supply air conditions on a time-based, weighted average.

FAU with Reheat

Figure AC-4 shows the FAU system with a DX refrigerant circuit design using reheat.

Dehumidification

Consider Chart AC-1. If the outdoor air dew point is above the drying setpoint

(or in the case of zone control, the zone

RH is above the RH setpoint), the FAU will:

• cool the outdoor air to remove required moisture and

• reheat to meet the discharge temperature setpoint.

At h1, 100% outdoor air enters the FAU.

The FAU filters, cools, and dehumidifies the air as it moves through the evaporator coil. Air leaves the evaporator coil saturated at the preset dew point condition (h3) and is reheated by the reheat condenser to the pre-set reheat temperature setpoint (h4). The reheat evaporator transfers energy to the reheat condenser. A liquid solenoid valve effectively modulates the reheat condenser capacity. The reheat outdoor condenser rejects surplus heat. The reheat evaporator circuit is first on and last off, so reheat energy is available at full and part load conditions. For those conditions where the reheat condenser capacity is insufficient to meet reheat demand, optional electric or gas heat can provide additional reheat capacity.

Since both the dew point setpoint and discharge temperature setpoint are fully adjustable, the desired supply air conditions are maintained at all load conditions.

Cooling or Heating

Consider Chart AC-2. If the outdoor air dew point or zone RH is equal to or below the drying setpoint, the FAU will heat or cool the outdoor air to separate and adjust cooling or heating setpoints.

At t1 or t3, 100% outdoor air enters the

FAU. The FAU filters, and cools or heats the air as it is drawn through the evaporators and heating section. The air leaves the FAU at the cooling or heating setpoint (t2 or t4) and equal to or below the dew point setpoint.

h3 h2 h4

W et Bulb T emperature t3 heating t4 t2 cooling t1

Dry Bulb Temperature h1

Chart AC-1. Psychrometric dhart with dehumidification and reheat

Chart AC-2. Psychrometric chart with cooling and heating only

Figure AC-4. Refrigeration system diagram with reheat

MUA-PRC004-EN

Subcooler

Receiver

7

Application

Considerations

FAU Without Reheat

Figure AC-5 shows the Packaged FAU

DX system, using a refrigerant circuit design without reheat.

Dehumidification (Drying)

Consider Chart AC-3. If the outdoor air dew point or zone RH is above the drying setpoint, the FAU will dehumidify the outdoor air. 100% outdoor air enters the FAU (h1). The unit filters, cools (h2) and dehumidifies the air as it is drawn through the evaporator coils. Air leaves the evaporator coils saturated at a preset dew point setpoint (h3). Since the dew point setpoint is fully adjustable, the desired dew point condition is maintained at all load conditions.

Cooling or Heating

Consider Chart AC-4. If the outdoor air dew point is equal to or below the dew point setpoint, the FAU will heat or cool the outdoor air to separate and adjust cooling or heating setpoints. 100% outdoor air enters the FAU (t1). The unit filters and cools or heats the air as it is drawn through the evaporators and heating section. The air leaves the FAU at the cooling or heating setpoint and equal to or below the dew point setpoint.

Wet Bulb Temperature

Dehumidification h3 h2

W et Bulb T em pe rature t3 heating t4 t2 h1

Dry Bulb Temperature

Chart AC-3. Psychrometric chart with dehumidification, no reheat cooling t1

Dry Bulb Temperature

Chart AC-4. Psychrometric chart with cooling and heating only

Evaporator 1

Circuit 2 Compressors

Circuit 1 Compressor

Condenser 1

Subcooler

Evaporator 2

Condenser 2

FIgure AC-5. Refrigeration system diagram without reheat

8

MUA-PRC004-EN

Application

Considerations

Establishing Capacity

Requirements

Determining the FAU capacity requirements requires careful thought. Airhandling equipment is typically selected based on design sensible conditions.

Since latent loads drive the need for the

FAU, base the selection on design latent conditions.

Cooling & Dehumidification

Selection Criteria

Evaporator Design Entering Conditions

For many climates the peak outdoor air enthalpy occurs at a time when the outdoor dry-bulb temperature is not the highest. Refer to the chapter on climatic design information in the ASHRAE

Handbook of Fundamentals. The cooling and dehumidification design condition data is provided three ways:

1. Design dry-bulb temperature with mean coincident wet bulb temperature

2. Design wet-bulb temperature with mean coincident dry-bulb temperature

3. Design dew point temperature with single bank option is 50% and the dual bank is 25%. Calculate the minimum temperature rise to determine the heating control capability. mean coincident dry-bulb temperature

The design wet-bulb condition typically represents a significantly higher outdoor air enthalpy than the design dry-bulb condition. Use the condition that represents the highest enthalpy as the entering evaporator selection condition.

Evaporator Design Leaving Conditions

Due to the uncertainty of the local terminal unit’s latent capacity at part load, it is usually most straightforward to size the FAU to handle the entire latent load on the system, both indoor and outdoor. With this design approach, the terminal units may do some latent cooling (dehumidification) during periods of higher sensible load. At these times, the space will run slightly drier than the design RH limit. This is why it makes sense to select the FAU to limit the space RH to a maximum allowable level for those conditions when the terminal units are providing no space latent cooling. ASHRAE standards 62.1

and 55 recommend using 60% RH design limit for comfort cooling. Using lower design limits may result in an unnecessary increase in system operating energy use.

Use Tables AC-1, AC-2, and AC-3, on pages 9 and 10, to identify the appropriate supply air dew point for specific design conditions. For a more detailed discussion on determining the selection criteria of a FAU, reference Trane publications SYS-EB-3 or SYS-APM-

004.

Reheat

The Trane FAU utilizes recovered energy from the cooling process to reheat the air leaving the cooling coil as required to meet the discharge air setpoint. The reheat refrigerant circuit is adequate to deliver enough reheat to supply space temperature neutral air

(e.g. 75°F dry-bulb) under most operating conditions. On very low load days, the reheat circuit may not contain enough energy to meet the desired reheat setpoint. Under those operating conditions, the FAU can use supplemental heat provided in the heating section.

Because the heat section is sized for the design heating condition, larger than normal supply air temperature swings may occur when using it for incremental reheat energy.

Table AC-1. Supply air dew point temperature, 75°F at 60% RH space limit latent load

Btu/h per Person

100

120

140

160

180

10

54.6

53.3

52.0

50.6

49.2

400

420

440

460

480

500

300

320

340

360

380

200

220

240

260

280

47.7

46.1

Note: Minimum dew point selectable is 45°F.

52.5

51.6

50.6

49.7

48.7

47.7

46.6

45.5

15

56.6

55.8

55.0

54.2

53.3

55.8

55.3

54.8

54.3

53.8

53.3

52.8

52.3

51.7

51.2

50.6

50.1

49.5

48.9

48.3

47.7

25

58.1

57.6

57.2

56.7

56.3

54.6

54.0

53.3

52.7

52.0

51.3

50.6

49.9

49.2

48.5

47.7

46.9

46.1

45.3

20

57.5

57.0

56.4

55.8

55.2

56.6

56.2

55.8

55.4

55.0

54.6

54.2

53.8

53.3

52.9

52.5

52.0

51.6

51.1

50.6

50.2

30

58.4

58.1

57.7

57.3

57.0

cfm per person

35

58.7

58.4

58.1

57.8

57.4

57.1

56.8

56.5

56.1

55.8

55.5

55.1

54.8

54.4

54.1

53.7

53.3

53.0

52.6

52.2

51.8

57.5

57.2

57.0

56.7

56.4

56.1

55.8

55.5

55.2

54.9

54.6

54.3

54.0

53.6

53.3

53.0

40

58.9

58.6

58.3

58.1

57.8

58.4

58.3

58.1

57.9

57.7

57.5

57.3

57.1

57.0

56.8

56.6

56.4

56.2

56.0

55.8

55.6

60

59.3

59.2

59.0

58.8

58.6

58.3

58.1

57.9

57.7

57.5

57.3

57.1

56.8

56.6

56.4

56.2

56.0

55.8

55.6

55.4

55.1

55

59.2

59.1

58.9

58.7

58.5

58.1

57.9

57.6

57.4

57.2

57.0

56.7

56.5

56.3

56.0

55.8

55.6

55.3

55.1

54.8

54.6

50

59.2

58.9

58.7

58.5

58.3

57.8

57.6

57.3

57.1

56.8

56.6

56.3

56.1

55.8

55.5

55.3

55.0

54.7

54.4

54.2

53.9

45

59.0

58.8

58.6

58.3

58.1

MUA-PRC004-EN 9

Application

Considerations

Table AC-2. Supply air dew point temperature, 75°F at 55% RH space limit latent Load

Btu/h per Person

200

220

240

260

280

100

120

140

160

180

400

420

440

460

480

500

300

320

340

360

380

25

55.5

55.0

54.5

54.0

53.5

53.0

52.4

51.9

51.4

50.8

50.2

49.7

49.1

48.5

47.9

47.2

46.6

46.0

45.3

20

54.9

54.2

53.6

53.0

52.3

51.6

50.9

50.2

49.5

48.8

48.0

47.2

46.4

45.6

15

53.8

53.0

52.1

51.2

50.2

49.3

48.3

47.2

46.2

45.1

10

51.6

50.2

48.8

47.2

45.6

30

55.9

55.5

55.1

54.6

54.2

53.8

53.4

53.0

52.5

52.1

51.6

51.2

50.7

50.2

49.8

49.3

48.8

48.3

47.8

47.2

46.7

cfm per person

35

56.1

55.8

55.5

55.1

54.8

54.4

54.1

53.7

53.3

53.0

52.6

52.2

51.8

51.4

51.0

50.6

50.2

49.8

49.4

49.0

48.6

40

56.3

56.1

55.8

55.5

55.2

54.9

54.5

54.2

53.9

53.6

53.3

53.0

52.6

52.3

52.0

51.6

51.3

50.9

50.6

50.2

49.9

Table AC-3. Supply air dew point temperature, 75° at 50% RH space limit latent Load

Btu/h per Person

200

220

240

260

280

100

120

140

160

180

10

48.4

46.8

45.2

300

320

340

360

380

400

420

440

460

480

500

Note: Minimum dew point selectable is 45°F.

15

50.8

49.8

48.9

47.9

46.8

45.7

30

53.0

52.6

52.2

51.7

51.3

50.8

50.3

49.8

49.4

48.9

48.4

47.9

47.3

46.8

46.3

45.7

45.2

25

52.6

52.1

51.5

51.0

50.4

49.8

49.3

48.7

48.1

47.4

46.8

46.2

45.5

20

51.9

51.3

50.6

49.8

49.1

48.4

47.6

46.8

46.0

45.2

— cfm per person

35

53.3

53.0

52.6

52.2

51.8

51.5

51.1

50.7

50.3

49.8

49.4

49.0

48.6

48.2

47.7

47.3

46.8

46.3

45.9

45.4

40

53.6

53.3

52.9

52.6

52.3

51.9

51.6

51.3

50.9

50.6

50.2

49.8

49.5

49.1

48.7

48.4

48.0

47.6

47.2

46.8

46.4

55

54.0

53.8

53.5

53.3

53.1

52.8

52.6

52.4

52.1

51.9

51.6

51.4

51.1

50.9

50.6

50.4

50.1

49.8

49.6

49.3

49.1

50

53.9

53.6

53.4

53.1

52.9

52.6

52.3

52.1

51.8

51.5

51.3

51.0

50.7

50.4

50.1

49.8

49.6

49.3

49.0

48.7

48.4

45

53.8

53.5

53.2

52.9

52.6

52.3

52.0

51.7

51.4

51.1

50.8

50.5

50.2

49.8

49.5

49.2

48.9

48.5

48.2

47.9

47.5

60

56.8

56.6

56.4

56.2

56.1

55.9

55.7

55.5

55.3

55.1

54.9

54.6

54.4

54.2

54.0

53.8

53.6

53.4

53.2

53.0

52.7

55

56.7

56.5

56.3

56.1

55.9

55.7

55.5

55.2

55.0

54.8

54.6

54.3

54.1

53.9

53.7

53.4

53.2

53.0

52.7

52.5

52.2

50

56.6

56.4

56.2

55.9

55.7

55.5

55.2

55.0

54.7

54.5

54.2

54.0

53.7

53.5

53.2

53.0

52.7

52.4

52.2

51.9

51.6

45

56.5

56.2

56.0

55.7

55.5

55.2

54.9

54.6

54.4

54.1

53.8

53.5

53.3

53.0

52.7

52.4

52.1

51.8

51.5

51.2

50.9

Heating

The FAU has electric or gas heat options. The electric heat option is available in 30-70°F temperature rise offerings with three to seven capacity control stages. This means that the lowest temperature rise provided using one stage depends on heater size, unit airflow, and the number of stages selected. Calculate the temperature rise to confirm that it provides acceptable control. The electric heat will cycle to maintain heating setpoint.

If using hot water heat, install it in the optional rack within the Packaged FAU or in the supply ductwork of the fresh air system. The unit controller will modulate a coil control valve. Provide an ethylene glycol and water mixture or other means of freeze protection for the hot water coil if the FAU will be subject to sub-freezing temperatures.

Capacity Control

The capacity control system on the

Packaged Fresh Air unit is flexible enough to accommodate a variety of system applications. These applications include:

• treating outdoor air to supply a single space or multiple spaces or

• simultaneously meet building makeup air needs while controlling the temperature and relative humidity of a single space.

Each of these applications requires careful consideration to achieve the desired results.

60

54.1

53.9

53.7

53.5

53.3

53.0

52.8

52.6

52.4

52.2

51.9

51.7

51.5

51.3

51.0

50.8

50.6

50.3

50.1

49.8

49.6

10

MUA-PRC004-EN

Application

Considerations

Supply Air Control

For many multiple space systems, the

FAU will continuously supply outdoor air at a dry-bulb setpoint and a dew point that does not exceed its dew point setpoint. This control approach is simple because it allows the FAU to function independent of local terminal unit operation or actual space conditions. If the unit selection criteria is determined using the method suggested in the

Establishing Capacity Requirements section, the fresh air unit will limit the space relative humidity to the target level.

When space sensible loads are relatively high, the local terminal unit may perform some latent cooling and drive the space relative humidity level lower than the FAU selection limit. Resetting the supply air dew point from the FAU will offer system operating cost savings.

See the Dew Point Reset section for resetting strategies.

Many fresh air systems supply reheated air directly to terminal units or to spaces that have terminal units performing local sensible cooling. This results in the local terminal units recooling the previously re-heated outdoor air. Resetting the supply air drybulb temperature of the fresh air unit offers the opportunity to minimize the amount of time re-cooling occurs. See the Dry-Bulb Reset section for more information.

Dew Point Reset

The local terminal unit provides sensible control of the space and as a result may coincidentally provide latent cooling to the space. The latent loads in the space can vary, especially if occupant density changes. Since the FAU can provide latent cooling to the space as well, it may be beneficial to reset the FAU supply air dew point to prevent overdehumidifying the space and unnecessarily wasting cooling energy. One way to do this is to place a relative humidity sensor in the space served by the FAU or in a common relief air path (like a return corridor) if the FAU serves multiple spaces. This relative humidity sensor can reset the supply air dew point setpoint of the FAU by responding to actual space latent conditions. The

Packaged FAU offers this control capability.

An alternative dew point control strategy is to reset the leaving dew point of the fresh air unit based on the zone with the highest relative humidity.

The building automation system will determine the zone requiring the driest

(lowest dew point) air and reset the dew point of the air leaving on the FAU accordingly. With this approach, the control and setpoint selection of the fresh air system is dynamically optimized based on actual demand of the controlled space. Comfort and indoor air quality requirements are met while minimizing system energy consumption. A Trane Integrated Comfort TM system can provide this control capability.

Dry-Bulb Reset

Because the Trane FAU dehumidifies the outdoor air by cooling it, this cool outdoor air can reduce the sensible cooling load on the local terminal unit. At low space sensible loads, the cool outdoor air may sub-cool the space, causing the local terminal unit to add heat (new energy heat). Therefore, reset the dry-bulb temperature of the dehumidified outdoor air to minimize space sensible re-cooling so the terminal unit with the lowest sensible load is almost at zero cooling capacity

(within the limit of the dew point setpoint). For chilled water terminal units (such as fan-coils), determine this by monitoring the chilled water valve position. For DX terminal units (such as water-source heat pumps or packaged rooftops), determine by monitoring compressor operation. To take full advantage of space demand based drybulb reset, size the local terminal units based on neutral outdoor air temperature. This strategy will more effectively manage occupant comfort during seasonal changeover for two-pipe terminal unit systems. Because the FAU is not connected to the chiller or boiler plant, accomplish this by resetting the fresh air unit dry-bulb temperature to keep the critical zone at zero heating capacity when the boiler is off and zero cooling capacity when the chiller is off. A

Trane Integrated Comfort™ system can provide this control capability.

Unoccupied Space Humidity Control

The Packaged FAU provides conditioned outdoor air for the ventilation and/or make-up air needs of a building during occupied hours. It can also limit building relative humidity during unoccupied hours. To do this, provide a return air path to the FAU and place a relative humidity sensor in the space served by the FAU or in a common relief air path (like a return corridor) if the FAU serves multiple spaces. The unit will cycle as required to limit the space relative humidity to the unoccupied relative humidity setpoint. Reheat and return air damper options are required for this operation. For dedicated outdoor air systems ducted to terminal units, these units must cycle with the operation of the Packaged FAU.

A Trane Integrated™ Comfort system can provide this control capability.

Space Control

For single space applications, the

Packaged FAU can control space temperature and limit space relative humidity. To do this, size the airflow to meet whichever is the highest: the space loads and ventilation and/or make-up air needs of the application.

Install a temperature sensor in the space to provide temperature control and reset the supply air temperature. If reset of the supply air dew point is desired, install a space relative humidity sensor in the space to provide relative humidity limit control.

Outdoor Airflow Balancing

Establish final unit airflow through a field air balancing procedure. Change the fan speed through replacement or fan sheave adjustment.

To simplify this procedure, optional

Traq TM outdoor airflow measuring dampers are available for continuous airflow sensing feedback. The dampers monitor the outdoor airflow intake and can help validate and troubleshoot system airflow issues. Do not use them for building pressure control.

MUA-PRC004-EN 11

Application

Considerations

Air to Air Energy Recovery

Energy recovery can significantly reduce HVAC system first-cost and operating energy costs. You can use recovered energy for two purposes:

1. to temper or reheat supply air for independent control of sensible and latent capacity, or

2. to precondition outdoor air as it enters the building for ventilation.

The Packaged FAU offers refrigerant heat recovery for reheating the supply air. To precondition the outdoor air, use the total energy wheel option to recover energy from building exhaust.

Controlling an Energy Recovery

Ventilator

One way to control an energy recovery device is to turn it on and off with the

FAU system exhaust fan. In this case, the total energy wheel enables when the unit is in occupied mode and the exhaust fan is running. While this control method is certainly simple and effective in some applications, it may not provide the expected energy saving benefit, particularly when cold air (vs. neutral air) is supplied to the building.

Another more effective approach is to use the outdoor air dry-bulb to determine when to energize or de-energize the energy recovery device. See Figure

AC-7 for an example of this simplified version of energy recovery. In addition to being more effective from a control standpoint, it’s also a very simple control method because the total energy wheel (only) enables when all of the following are true:

• unit is in occupied mode

• exhaust fan is enabled

• outside air temperature is above the upper limit setpoint (default setpoint

80°F) or below the lower limit setpoint

(default setpoint 45°F)

• outside air temperature is above the frost protection setpoint (default setpoint 12°F).

Set the upper limit setpoint to the anticipated return air dry-bulb temperature. Set the lower limit setpoint to 10°F less than the supply air dry-bulb setpoint. This control strategy prevents the energy recovery device from potentially adding to the load seen by the cooling and/or heating system of the unit, but rather utilizing the device only at those times when it provides true operating energy savings.

If using the FAU to deliver cold, dry conditioned air to the building (outdoor air is cooled to a low dew point but not reheated), use the dry-bulb control option.

Cross Leakage

All energy wheels have some cross leakage. Therefore, do not use energy wheels in applications involving toxic or hazaradous air streams. The percentage of cross leakage depends on the pressure differentials across the wheel section. With Trane Packaged FAU energy wheels, the exhaust air transfer ratios are typically low (<4%).

Figure AC-6. Dry-bulb control in a cold DB/dry DP application Figure AC-7. Dry-bulb control in a neutral DB/dry DP application

12

MUA-PRC004-EN

Application

Considerations

Drain Pan Trapping

FAU units are selected based on dehumidification capability. As such, condensate can form at an enormous rate. Therefore, the Packaged FAU drain pan and condensate line are sized and designed accordingly. However, an often-overlooked element of proper condensate drainage is trapping. An incorrectly designed and installed trap on the piping exiting the drain pan can restrict condensate flow or cause condensate to ‘‘spit’’ or “geyser.” This can dampen the air handler interior and/ or ductwork, creating an opportunity for mold infestation. Carefully install and trap the drain pan to ensure adequate condensate removal under all conditons. See Figure AC-8 for the proper p-trap design for the drain pan.

H = (1’’ for each 1’’ of maximum negative static pressure) + 1’’

J = half of H

L = H + J+ pipe diameter + insulation

Figure AC-8. P-trap design for drain pan

Acoustical Considerations

Proper unit placement is critical to reducing transmitted sound levels from the FAU to the building. Therefore, consider acoustic concerns during the design phase and place the unit accordingly. The most economical means of avoiding an acoustical problem is to place the unit(s) away from acoustically critical areas. If possible, do not locate units directly above areas such as: offices, conference rooms, executive office areas, and classrooms. Instead, ideal locations to consider are: over corridors, utility rooms, toilets, or other areas where higher sound levels directly below the unit(s) are acceptable.

Follow these basic guidelines for unit placement to minimize sound transmission through the building structure.

1. Never cantilever the compressor side of the unit. A structural cross member must support this side of the unit.

2. Locate the unit’s center of gravity close to or over column or main support beam.

3. If the roof structure is very light, replace roof joists by a structural shape in the critical areas described above.

4. If several units are to be placed on one span, stagger them to reduce deflection over that span.

It is impossible to totally quantify the building structure effect on sound transmission because it is dependent on how the roof and building members respond to the FAU ’s sound and vibration. However, following the guidelines listed above will help reduce sound transmissions.

Clearance Requirements

Follow the recommended unit clearances to assure adequate serviceability, maximum capacity, and peak operating efficiency. Reducing unit clearances may result in condenser coil starvation or warm condenser air recirculation. If the recommended clearances are not possible on a particular job, consider the following:

• Do the clearances available allow for major service work, such as changing compressors or coils?

• Do the clearances available allow for proper outside air intake, exhaust air removal, and condenser airflow?

• If screening around the unit is used, is there a possibility of air recirculation from the exhaust to the outside air intake or from condenser exhaust to condenser intake.

Review any actual clearances that appear inadequate with your local

Trane sales engineer.

When two or more units are placed side by side, increase the distance between the units to 150% of the recommended single unit clearance. Stagger the units for these two reasons:

1.To reduce span deflection if more than one unit is placed on a single span.

Reducing deflection discourages sound transmission.

2.To assure proper exhaust air diffusion before contact with the adjacent unit’s outside air intake.

Duct Design

It is important to note that the rated capacities of the FAU can be met only if the unit is properly installed. A welldesigned duct system is essential to meet these capacities.

Satisfactory air distribution throughout the system requires an unrestricted and uniform airflow from the rooftop discharge duct.

However, when job conditions dictate installation of elbows near the FAU outlet, using guide vanes may reduce capacity and static pressure loss.

MUA-PRC004-EN 13

Selection

Procedure

Model Number

Description

Packaged Fresh Air unit Model Number Description

Following is a complete description of the Packaged FAU model number. Each digit in the model number has a corresponding code that identifies specific unit options.

F A D A 040 6 G A,0 0,8,4 0 1 A 0 1 A 0,5,7 0,7 A 0 0 0 E F 0 1 0,0,0 0,0 A A A A

1 2 3 4 5,6,7 8 9 10,11 12,13,141516171819 20 21,22,23 24,25 26 27 28 29 30 31 32 33 34,35,36 37,38 39 40 41 42

Digit 1 – Unit model

F = fresh air unit

Digit 2 – Unit configuration

A = air cooled

Digit 3 – Unit discharge direction

D = downflow

H = horizontal

Digit 4 – Development sequence

A = development sequence ‘A’

Digits 5, 6, 7 – Unit size

031 = 3100 cfm

040 = 4000 cfm

051 = 5100 cfm

066 = 6600 cfm

Digit 8 – Unit voltage

3 = 230 volt/60 hz/3 ph

4 = 460 volt/60 hz/3 ph

6 = 208 volt/60 hz/3 ph

Digit 9 – Heating system

0 = none

A = gas low rise, single bank, 2-stage

B = gas low rise, single bank, 2:1 modulate

C = gas high rise, single bank, 2-stage

D = gas high rise, single banks, 2:1 modulate

E = gas dual bank, 4-stage

F = gas dual bank 4:1 modulate

G= electric heat, 3-stage

H = electric heat, 7-stage

K = hydronic interface only

Digits 10, 11 – Design sequence

** = factory assigned

Digits 12, 13, 14 – Heat input

000 = none

020 = 20 kW

026 = 26 kW

032 = 32 kW

042 = 42 kW

056 = 56 kW

070 = 70 kW

084 = 84 kW

100 = 100 kW

122 = 122 kW

125 = 125 MBh

14

150 = 150 MBh

200 = 200 MBh

250 = 250 MBh

300 = 300 MBh

350 = 350 MBh

400 = 400 MBh

500 = 500 MBh

600 = 600 MBh

700 = 700 MBh

800= 800 MBh

Digit 15 – Heat exchanger material

0 = none

1 = 409 stainless steel, 409 stainless

Burner

2 = 321 stainless steel, 409 stainless burner

Digit 16 – Condenser reheat coil

0 = none

1 = condenser hot gas reheat coil

Digit 17 – Ventilation damper type

0 = parallel blade damper

1 = TRAQ™ damper with air flow measurement

Digit 18 – Energy recovery

0 = none

1 = total energy wheel w/occupancy control

2 = total energy wheel w/dry bulb control

Digit 19 – Return air damper

0 = none

1 = bottom return/reference enthalpy

2 = bottom return/comparative enthalpy

Digit 20 – Supply fan type 1

A = 12 - 9 centrifugal fan

B = 15 - 11 centrifugal fan

C = 18 - 13 centrifugal fan

Digits 21, 22, 23 – Supply fan rpm

037 = 375

040 = 400

065 = 650

067 = 675

042 = 425

045 = 450

047 = 475

050 = 500

052 = 525

055 = 550

057 = 575

060 = 600

062 = 625

070 = 700

072 = 725

075 = 750

077 = 775

080 = 800

082 = 825

085 = 850

087 = 875

090 = 900

Note 1 : The first number in this description indicates the fan wheel diameter (in.). The second number indicates the fan wheel width.

092 = 925

095 = 950

097 = 975

100 = 1000

102 = 1025

105 = 1050

107 = 1075

110 = 1100

112 = 1125

115 = 1150

117 = 1175

120 = 1200

122 = 1225

125 = 1250

127 = 1275

130 = 1300

132 = 1325

135 = 1350

137 = 1375

140 = 1400

142 = 1425

145 = 1450

147 = 1475

150 = 1500

152 = 1525

155 = 1550

157 = 1575

160 = 1600

162 = 1625

165 = 1650

167 = 1675

170 = 1700

172 = 1725

175 = 1750

177 = 1775

180 = 1800

182 = 1825

185 = 1850

187 = 1875

190 = 1900

192 = 1925

195 = 1950

197 = 1975

200 = 2000

202 = 2025

205 = 2050

207 = 2075

210 = 2100

Digits 24, 25 – Supply fan horsepower

01 = 1

02 = 2

03 = 3

05 = 5

07 = 7.5

10 = 10

15 = 15

Digit 26 – Fan motor type

A = standard efficiency ODP fan motor

B = high efficiency ODP fan motor

Digit 27 – Coil protection

0 = none

A = corrosion inhibiting coating

Digit 28 – Unit cabinet protection

0 = standard prepainted steel finish

A = corrosion inhibiting coating

Digit 29 – Filter type

0 = field-provided filter

1 = dirty filter switch (DFS) with fieldprovided filter

2 = 2” pleated media filters

3 = 2” pleated media filters & DFS

Digit 30 – System control

A = supply air dehumidification

B = supply air dehimidification with zone

RH reference

MUA-PRC004-EN

MUA-PRC004-EN

Selection

Procedure

Model Number

Description

E = zone dehumidification

F = zone dehumidification with OA RH reference

G= supply air temperature control (no dehumidification)

J = zone temperature control (no dehumidification)

Digit 31 – Control interface options

0 = none

A = LonTalk ® communications interface

(LCI ) (comm5)

B = LCI (comm5) & generic building automation system (GBAS) (0-5 VDC)

C = LCI (comm5) & GBAS (0-5 VDC) & ventilation override module (VOM)

D = LCI (comm5) & VOM

E = GBAS (0-5 VDC)

F = GBAS (0-5 VDC) & VOM

G= VOM

Digit 32 – Miscellaneous system control options

0 = none

1 = interface for remote human interface

Digit 33 – Exhaust option

0 = none

1 = exhaust interface

Digits 34, 35, 36 – Exhaust air fan rpm

000 = none 127 = 1275

045 = 450 130 = 1300

047 = 475 132 = 1325

050 = 500 135 = 1350

052 = 525 137 = 1375

055 = 550 140 = 1400

057 = 575 142 = 1425

060 = 600 145 = 1450

062 = 625 147 = 1475

065 = 650 150 = 1500

067 = 675 152 = 1525

070 = 700 155 = 1550

072 = 725 157 = 1575

075 = 750 160 = 1600

077 = 775 162 = 1625

080 = 800 165 = 1650

082 = 825 167 = 1675

085 = 850 170 = 1700

087 = 875 172 = 1725

090 = 900 175 = 1750

092 = 925 177 = 1775

095 = 950 180 = 1800

097 = 975 182 = 1825

100 = 1000 185 = 1850

102 = 1025 187 = 1875

105 = 1050 190 = 1900

107 = 1075 192 = 1925

110 = 1100 195 = 1950

112 = 1125 197 = 1975

115 = 1150 200 = 2000

117 = 1175 202 = 2025

120 = 1200 205 = 2050

122 = 1225 207 = 2075

125 = 1250 210 = 2100

Digits 37, 38 – Exhaust air fan horsepower

00 = none

01 = 1

02 = 2

03 = 3

05 = 5

07 = 7.5

10 = 10

Digit 39 – Unit connection type

A = terminal block

B = non-fused disconnect switch

Digit 40 – Convenience outlet

0 = none

A = 115V, factory wired

B = 115V, field wired

Digit 41 – Extended grease lines

0 = none

A= extended grease lines

Digit 42 – Agency approval

0 = no agency approval

A = UL approval

Digit 43 – Roof curb

A = 14” curb

B = 24” curb

15

Selection

Procedure

Model Number

Description

Packaged Fresh Air unit Accessory Model Number Description

Following is a complete description of the Packaged FAU accessory model number. Each digit in the model number has a corresponding code that identifies specific accessory options.

P F

1 2

K

3

A

4

031

5, 6, 7

3

8

A A0 B C 0 A A 0 A 0 A 0 A 0 A

9 10,11 12 13 14 15 16 17 18 19 20 21 22 23 24

Digit 1 – Parts/accessories

P = parts/accessories

Digit 2 – Unit type

F = fresh air unit

Digit 3 – Field installed kits

K = field installed kits

Digit 4 – Development sequence

A = development sequence

Digits 5, 6, 7 – Nominal size

031 = 3100 cfm

040 = 4000 cfm

051 = 5100 cfm

066 = 6600 cfm

Digit 8 – Unit voltage

3 = 230/60/3

4 = 460/60/3

6 = 208/60/3

Digit 9 – Roof curb

0 = none

A = 14”

B = 24”

C = acoustical

D = 14” curb for unit w/ERV

E = 24” extended for unit w/ERV

F = 24” extended, acoustical for unit w/

ERV

Digits 10, 11 – Design sequence

A0 = design sequence

Digit 12 – Filter type

0 = none

A = 2” pleated media

B = 2” cleanable

C = 2” pleated media total energy wheel only

D = 2” cleanable total energy wheel only

E = 2” pleated media unit & total energy wheel

F = 2” cleanable unit & total energy wheel

Digit 13 – Control interface kits

0 = none

A = LonTalk ® communications interface

(LCI) (comm5)

B = LCI (comm5) & generic building automation system (GBAS) (0-5 VDC)

C = LCI (comm5) & GBAS (0-5 VDC) & ventilation override module (VOM)

D = LCI (comm5) & VOM

E = GBAS (0-5 VDC)

F = GBAS (0-5 VDC) & VOM

G= VOM

Digit 14 – Time clock

0 = none

A = time clock

Digit 15 – Remote mounted human interface

0 = none

A = remote mounted human interface

B = remote mounted human interface with interprocessor communication bridge module board kit

C = interprocessor communication bridge module board kit

Digit 16 – Zone sensor

0 = none

A = zone temperature sensor

BAYSENS017*

Digit 17 – Zone sensor with timed override

0 = none

A = zone temperature densor with timed override BAYSENS013*

Digit 18 – Zone sensor with timed override and local setpoint adjustment

0 = none

A = zone temperature sensor with timed override buttons and local setpoint adjustment BAYSENS014*

Digit 19 – Remote minimum position potentiometer control

0 = none

A = remote minimum position potentiomenter control BAYSTAT023*

Digit 20 – Dual setpoint sensor

0 = none

A = dual setpoint sensor

Digit 21 – Dual setpoint sensor with system function lights

0 = none

A = dual setpoint sensor with system function lights

Digits 22 – Space relative humidity kit

0 = none

A = space relative humidity kit

Digit 23 – Carbon dioxide sensor

0 = none

A = carbon dioxide sensor

Digit 24 – Dry-bulb duct sensor

0 = none

A = dry-bulb duct sensor

16 MUA-PRC004-EN

MUA-PRC004-EN

Selection

Procedure

FAU Selection Procedure

Prior to selecting the fresh air unit (FAU) for a given application, give careful consideration to determining the design latent conditions (as described in the

Applications Considerations section of this catalog). Use Tables AC-1, AC-2, and AC-3 on pages 9 and 10 to identify the appropriate supply air dew point for specific design conditions. See SYS-

APG001-EN or SYS-APM-004 for more detailed information.

Selection of Trane Packaged Fresh Air units is divided into five basic areas:

1. cooling/dehumidification capacity

2. air delivery

3. heating capacity

4. unit electrical requirements

5. unit designation

Factors used in unit cooling/dehumidification (drying) selection:

Example

Example unit options include:

• parallel blade OA damper

• 2” pleated media filters

• gas heat – hi rise, single bank, 2-stage

• fan type 12-9

Given conditions:

• airflow required for proper ventilation

(per ASHRAE 62) = 2300 cfm

• outside air summer design conditions

= 95°db/78°wb, 95°F entering air to condenser

• supply air design dew point requirement = 53°F dew point

• total peak cooling load = 198 MBh (16.5

tons)

• total peak dehumidification load = 90

MBh (7.5 tons)

• condenser reheat provided (yes or no)

= for this example, reheat is installed

• external static pressure = 0.5 inches

• desired supply air db temp. = 75°F

Step 1 – Determine unit size.

To determine which unit size will meet your capacity requirements, first review the airflow ranges found in Table GD-1 on page 21. The specified airflow in this example of 2300 cfm falls in both the size 031 and 040 unit airflow ranges.

Step 2 – Determine SA dew point capability.

Check the smaller unit size first to determine if it has the capacity to meet the supply air dew point and cooling/ dehumidification requirements. See

Table PD-31 to review the supply air dew point vs. airflow range that the size

031 unit can provide. At 95°db/78°wb, the size 031 produces 53°F dew point supply air at 2301 cfm (value found by interpolating between the 52°F and

54°F dew point data provided in the table). Therefore, the size 031 unit meets the supply air dew point requirement.

Step 3 – Determine unit capacity.

Now check that the size 031 unit meets the cooling and dehumidification capacity requirements by reviewing

Table PD-28. At 2300 cfm and 95°F db/

78°F wb, the size 031 unit produces

201.42 MBh total and 92.68 MBh latent capacity. This meets our requirement.

Also note that Table PD-27 provides information very similar to that in Table

PD-28. Use Table PD-27 (and tables like it for all other units sizes) only when condenser reheat is not provided. For this example, we will include condenser reheat.

Step 4 – Determine supply air fan data.

First calculate size 031 unit total static pressure (tsp) at design supply cfm using the appropriate air pressure drop tables. See calculation below: external static pressure = 0.50‘’ parallel blade OA damper = 0.01’’

2” pleated media filter = 0.08’’ main evap coil (wet) = 0.37’’ reheat evap coil (wet) = condenser reheat coil = gas heat exchanger =

0.19’’

0.15’’

0.37’’ unit total static pressure = 1.67’’

Using 2300 cfm and tsp of 1.67 inches, refer to Table PD-1, which shows 1017 rpm and 1.06 bhp at 1.6 tsp. Interpolate the values from the table (between 1.60

and 1.80 tsp), and calculate 1058 rpm and 1.077 bhp at 1.67 tsp.

Step 5 – Determine supply air temperature.

If the unit does not have condenser reheat, the supply air db is equal to the supply air dew point (53°F). However, for this example, condenser reheat is required, and a supply air db temperature of 75°F is desired. Go to Table PD-

30 on page 49 to determine the supply air db temperature produced by the size

031 unit. At 2300 cfm and 95°F db/78°F

17

Selection

Procedure db, the size 031 unit produces condenser reheat max temp rise of 24.9°F.

Now calculate the fan motor heat temp rise for this selection. Go to Figure SP-1 to determine that 1.077 bhp = 3.269

MBh. Supply fan motor heat temp rise =

3269 btu/(1.085 x 2300 cfm) = 1.3°F.

Calculate supply air db temp by summing the off-coil supply air db with the condenser reheat maximum temperature rise and the motor heat temperature rise at the design condition:

Supply air db temperature:

53°F + 24.9°F + 1.3°F = 79.2°F

Thus, the size 031 unit has the capability to meet and slightly exceed the supply air db temperature requirement of 75°F.

So, for this example, the size 031 unit meets all requirements with a supply air temperature of 79.2°F db/63.1°F wb with a 53°F supply air dew point.

However, if the supply air temp setpoint at the unit controller is set to 75°F, the unit will modulate the condenser reheat to meet that supply air condition versus exceed it. Also note that Table PD-30 provides reheat max temp rise data for typical design and part load conditions.

This enables you to determine if the condenser reheat is sufficient to maintain comfort during typical part load conditions.

Heating Capacity Selection

Example

Given conditions:

• winter outdoor design conditions = 0°F

• heat type = gas

• max temp rise or heating kW/MBh requirement = 80°F temperature rise

To select a single bank gas heater as specified, go to Table PD-73 for the size

031 unit. At 2300 cfm, a 250 MBh gas heater will produce an 80°F temperature rise. Select this heater.

If your application requires electric heat, use the electric heat tables on pages 73 through 74.

Air Delivery Procedure

Supply Air Fan Selection

Unit supply air fan performance tables include pressure drops for internal cabinet static losses. Add static pressure drops of optional components such as heat and filters to the external duct static pressure to determine the total static pressure.

The supply requirements determined in

Step 4 of the cooling/dehumidification capacity example was 1.077 bhp at

1058 rpm. Thus, the supply fan motor size required is two hp at 1075 rpm.

Unit Electrical Requirements

To determine electrical requirements for wire sizing amps and maximum over-current protection, see in the

Electrical Data section on pages 86–89.

Unit Designation

After determining specific unit capacity requirements and considering specific job requirements, determine the complete unit model number by referencing pages 14–16.

STANDARD MOTOR

HIGH EFFICIENCY MOTOR

90

80

70

60

50

40

30

20

120

110

100

10

0

0 5 10 15 20 25 motor brake horsepower

Note: Fan motor heat (MBh) includes 1.1 correction factor for motor efficiency.

30

Figure SP-1. Fan motor heat

35 40

18 MUA-PRC004-EN

Selection

Procedure

Fresh Air Unit with Total

Energy Wheel

Common Terms

Following are definitions of common terms used when selecting a fresh air unit with a total energy wheel.For more information on this subject, reference

Trane application manual, Air-to-Air

Energy Recovery in HVAC Systems,

SYS-APM003-EN.

EATR - exhaust air transfer rate expressed as a percentage, is the tracer gas concentration difference between the outdoor airflow entering the total energy wheel and the supply airflow leaving the wheel divided by the tracer gas concentration difference between the exhaust airflow entering the total energy wheel and the outdoor airflow entering the wheel.

OACF - The outside air correction factor is defined as the supply-side airflow upstream of the wheel divided by the supply-side airflow downstream of the wheel. This value is important for sizing the fans. Also, if the system includes an airflow monitoring station or flowmeasuring damper, it allows for the set point of this device to compensate and assure that the proper amount of outdoor air flows into the wheel so that the required amount of outdoor air leaves the wheel. The OACF is typically small unless the pressure difference between the air streams is greater then

3.0 in H2O.

The term effectiveness is used to describe the heat transfer efficiency of an air-to-air heat exchanger. Effectiveness is defined as the actual energy

(sensible, latent, or total) transferred by

Table SP-1. OACF values

2P3 031 unit size

040 051 066

-2

-1.5

-1

-0.5

0

0.5

1

1.5

2

2.5

3

0.98

0.98

0.99

0.99

1.00

0.99

1.00

1.00

1.01

1.01

1.02

1.01

1.03

1.02

1.03

1.02

1.05

1.04

1.04

1.03

1.06

1.05

1.05

1.04

1.08

1.07

1.06

1.05

1.10

1.08

1.07

1.06

1.12

1.10

1.09

1.07

1.13

1.11

1.10

1.08

1.15

1.13

1.11

1.09

Note: EATR and OACF values are for wheels without purge. EATR for all units = 4%.

MUA-PRC004-EN the device, divided by the maximum possible energy transfer between the two air streams. If the effectiveness of the device were 100% the condition of the air leaving the supply-side of the device would be the same as the condition of the air entering the exhaust-side of the device.

In addition to understanding the wheel performance terms, consideration should be given to airflow performance in applications with a total energy wheel. The terms below explain the air paths through the total energy wheel and should all be considered when selecting an energy recovery device.

Entering exhaust airflow represents the exhaust airflow exiting the building prior to passing through the total energy wheel.

Leaving exhaust airflow represents the exhaust airflow after passing through the total energy wheel.

Net exhaust airflow represents the portion of leaving exhaust airflow that originated as entering exhaust airflow.

Leaving supply airflow represents the sum of the net supply airflow and the additional air picked up in the airstream while passing through the total energy wheel (difference between entering and net exhaust airflow).

Outdoor airflow represents the amount of outdoor air entering the unit.

Net supply airflow represents that portion of the leaving supply airflow that originated as outdoor airflow

(equal to 1 - EATR.

Note:

EA/OA is the ratio of net exhaust airflow to net supply airflow (expressed as a percentage).

Selection Example

Given:

4000 cfm, 100% EA/OA, 95/78°F OA conditions, 72/60°F (52 dewpoint) SA conditions, 1” WC supply ESP, 1” WC exhaust ESP, 75/63°F summer RA conditions, 70F/30% RH winter RA conditions

Step 1 - Determine unit size.

To determine which unit size will meet your capacity requirements, first review the airflow ranges found in Table GD-1.

The specified airflow in this example of

4000 falls into unit sizes 040, 051, and

066 airflow ranges.

Step 2 - Determine SA dewpoint capability.

Check the smaller unit size first to determine if it has the capacity to meet the supply air dewpoint requirements.

See Table PD-56 on page 63 to review the supply air dewpoint vs. airflow range that the size 040 unit can provide.

At 95/78°F, the size 040 unit has the capacity at 4000 cfm to provide a 51 DP or higher. Therefore, the size 040 unit meets the supply air dewpoint requirement.

Step 3 - Determine unit and wheel capacity.

The 040 unit with a total energy wheel data can be pulled directly of the unit capacity Tables PD-53 and PD- 54 on pages 62-63:

The 040 unit with a total energy wheel produces 391 MBh total capacity and

155 MBh latent capacity.

The 040 wheel only capacity is 152 MBh total and 92 MBh latent.

Step 4 - Determine exhaust airflow and actual amount of OA supplied to the space.

Use the APD lookup tables to find P2 and P3 below for the 040 unit at 4000 cfm:

Find P2 = energy module OA filters + energy wheel and module (use Table

PD-13)

P2 = 0.23 + 1.34 = 1.57

Find P3 = energy module EA filters + return ESP, using Table PD-13 on page

34:

P3 = 0.23 + 1 = 1.23

2P3 = 1.57 - 1.23 = 0.34

Find EATR and OACF using 2P3 from

Table SP-1:

EATR = 4.0%

OACF = 1.05

Calculate net OA: netOA = SA(1-EATR) netOA = 4000*(1- 0.04) = 3840 cfm

19

Selection

Procedure

Step 5 - Determine supply fan data.

First calculate unit total static pressure at design cfm of 4000 using the appropriate air pressure drop tables. See calculation below: external static pressure = 1.00” energy wheel OA filters = 0.23” energy wheel & module = 1.34”

OA dampers (Traq) = 0.28” reheat evap coil (wet) = 0.31” main evap coil (wet) = 0.62” condenser reheat coil = 0.24” unit total static pressure = 4.02”

Use SA and TSP with the fan curve/ table to determine the supply fan’s operating point.

12-9 FC, 1686 rpm, 5.19 hp

15-11 FC, 1330 rpm, 4.39 hp

Select 15-11 FC, 1350 rpm and 5 hp motor.

Step 6 - Determine exhaust fan data.

EA = SA[OACF + EATR -1 + (1 -

EATR)[net EA/net OA]] net EA = net OA [net EA/net OA]

EA = 4000*(1.05 + 0.04 - 1 + (1 -

0.04)*1.0) = 4200 cfm

NetEA = 3840*0.8 = 3072 cfm

Use EA and P3 with the 040 exhaust fan curve/tables, Chart PD-6 and Table PD-6 on page 27, to determine the exhaust fan’s operating point.

1763 rpm, 5.07 hp

Select 1775 rpm, 7.5 hp

Step 7 - Determine supply air temperature.

The 040 unit with evap coils plus the total energy wheel produce a supply air db of 51°F.

The 040 unit plus wheel produces a reheat rise of 19.8°F. See the size 040 unit/wheel reheat temp rise Table PD-55 on page 63.

Motor temp rise is X (for instructions on calculating motor heat temp rise, review step 5 under FAU selection procedure for unit without total energy wheel).

Supply air temp = 51 + 19.8 + X = 70.8 +

X

Step 8 - Determine wheel frost setpoint.

Find the point on the frost threshold curve (Table SP-2) that intersects with your RA winter relative humidity. Then read the associated OA dry-bulb temperature. The frost threshold chart assumes winter RA dry-bulb or 70°F.

For other conditions, use the TOPSS selection program.

20 outdoor temperature °F

Figure SP-2. Frost threshold based on 70°F return air

MUA-PRC004-EN

General

Data

Table GD-1. Packaged fresh air unit general data

Unit size nominal cfm maximum design cfm minimum design cfm

Compressor data reheat circuit (nom. tons R134a) main circuit (nom. tons R134a) unit cooling capacity steps %

Supply fan data, FC fan 1/FC fan 2 quantity size (diameter-width), in.

maximum hp maximum rpm

Condenser fan data quantity/fan diameter, in.-type cfm (reheat, main) number of motors/hp each

031

3100

3100

1800

3.0T

6.2T + 9.3T

100-66-50-16

1/1

12-9/15-11

7.5/15

2115/1760

1/24;2/26-prop

2900, 8500

3/1.0

Evaporator coil - main size, ft 2 rows/fin s series tube diameter, in./surface

Evaporator coil - reheat size, ft 2 rows/fin series tube diameter, in./surface

Condenser coil - main size, ft 2 rows/fin series tube diameter, in./surface

Condenser coil - reheat outdoor size, ft 2 rows/fin series tube diameter, in./surface

6.67

4/168

0.5/enhanced

6.67

2/168

0.5/enhanced

15.62

2/168

0.5/enhanced

5.35

2/168

0.5/enhanced

Condenser coil - reheat indoor size, ft 2 rows/fin series tube diameter, in./surface

6.67

2/168

0.5/enhanced

Heating data gas heat input, MBh elec. heat input, kW

125-350

20-56

Refrigerant operating charge, lbs., R-134a circuit (circuit 2) reheat circuit (circuit 1) cooling only (circuit 1)

25

29

9

Compressor oil data

main circuit POE oil type

reheat circuit POE oil type

main circuit, # pints

reheat circuit, # pints

Filters number-size, in.

face area, ft 2

Total energy (TE) wheel

wheel diameter (in)

wheel drive motor hp

exhaust fan

quantity

size (dia-width in.)

maximum hp

maximum rpm

outdoor air filters

number/size (in.)

face area (ft 2 )

return air filters

number/size (in.)

face area (ft 2 )

OIL00078

Mobil Artic EAL22CC

7/11.5

4.13

4 - 16x20x2

8.4

1

42

/

1

2

12-9

7.5

2115

4 - 16x20x2

8.4

4 - 16x20x2

8.4

MUA-PRC004-EN

040

4000

4000

2200

4.5T

6.7T + 10.0T

100-69-53-21

1/1

12-9/15-11

7.5/15

2115/1760

3/26-prop

4000, 10500

3/1.0

8.33

4/168

0.5/enhanced

8.33

2/168

0.5/enhanced

17.71

2/168

0.5/enhanced

7.29

2/168

0.5/enhanced

8.33

2/168

0.5/enhanced

125-400

26-84

28

32

13

OIL00078

Mobil Artic EAL22CC

7/11.5

3.75

4 - 16x20x2

8.4

1

48

/

2

1

12-9

7.5

2115

4 - 16x20x2

8.4

4 - 16x20x2

8.4

066

6600

6600

3600

6.2T

10.0T + 10.0T + 10.0T

100-72-45-17

1/1

15-11/18-13

15/13.76

1760/1515

3/26-prop

5500, 13000

3/1.0

14.06

4/168

0.5/enhanced

14.06

2/168

0.5/enhanced

28.13

2/168

0.5/enhanced

9.38

2/168

0.5/enhanced

14.06

2/168

0.5/enhanced

150-800

42-122

48

52

20 main

OIL00078

OIL0007

11.5/11.5/11.5

7

4 - 24x24x2

15.2

3

60

/

4

1

15-11

15

1760

4 - 20x25x2

13.3

4 - 16x25x2

10.5

21

051

5100

5100

2900

6.2T

6.2T + 6.2T + 9.3T

100-67-45-22

1/1

15-11/18-13

15/13.76

1760/1515

3/26-prop

5500, 12000

3/1.0

11.11

4/168

0.5/enhanced

11.11

2/168

0.5/enhanced

23.43

2/168

0.5/enhanced

9.38

2/168

0.5/enhanced

11.11

2/168

0.5/enhanced

125-600

32-100

34

50

18

OIL00078

OIL00078

7/7/11.5

7

4 - 24x24x2

15.2

3

54

/

4

1

15-11

15

1760

4 - 20x25x2

13.3

4 - 16x25x2

10.5

Performance

Data fan data

Chart PD-1. Size 12-9 supply fan, unit size 031

8

50% WO

60% WO

7 25% WO

6

5

2115 rpm

2100 rpm

2000 rpm

1900 rpm

1800 rpm

70% WO

80% WO

4

3

2

1

1700 rpm

1600 rpm

1500 rpm

1400 rpm

1300 rpm

1200 rpm

1100 rpm

1000 rpm

900 rpm

800 rpm

700 rpm

600 rpm

90% WO

0

0 2000 4000 6000 8000 10000

airflow, cfm

Note: Fan curves include internal cabinet static losses. To determine total static pressure to be used with these curves, add filter, damper, gas or electric heat, evaporator and reheat coils, and TE wheel pressure drops to external duct static pressure.

Table PD-1. Size 12-9 supply fan, unit size 031

0.0

0.5

1.0

1.5

2.0

total static pressure, in. wg.

3.0

3.5

4.0

5.0

5.5

6.0

7.0

7.5

8.0

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

1800 401 0.18 609 0.34 802 0.52 976 0.71 1148 0.95 1438 1.46 1565 1.73 1677 2.01

-

2200 490 0.33 658 0.51 827 0.72 982 0.95 1126 1.18 1405 1.73 1532 2.03 1654 2.35 1866 3.01 1965 3.35

-

2600 578 0.55 721 0.75 867 1.02 1005 1.24 1138 1.51 1377 2.06 1499 2.38 1618 2.72 1836 3.44 1935 3.81 2031 4.20

-

-

3100 690 0.93 802 1.14 929 1.42 1052 1.76 1169 2.02 1390 2.66 1493 2.98 1590 3.31 1792 4.05 1893 4.46 1989 4.88 2169 5.73

-

-

-

-

-

-

-

outside 25%WO limit outside rpm limit

22

MUA-PRC004-EN

Performance

Data fan data

Table PD-2. Size 15-11 supply fan, unit size 031

8

50% WO

25% WO

7 1760 rpm

1700 rpm

60% WO

6

1600 rpm 70% WO

5 1500 rpm

1400 rpm

4 80% WO

1300 rpm

1200 rpm

3

2

1

0

1100 rpm

1000 rpm

900 rpm

800 rpm

700 rpm

600 rpm

500 rpm

400 rpm

0

90% WO

2500 5000 7500 10000 12500 15000

airflow, cfm

Note: Fan curves include internal cabinet static losses. To determine total static pressure to be used with these curves, add filter, damper, gas or electric heat, evaporator and reheat coils, and TE wheel pressure drops to external duct static pressure.

Table PD-2. Supply fan size 15-11, unit size 031

0.0

0.5

1.0

1.5

2.0

3.0

total static pressure, in. wg.

3.5

4.0

5.0

5.5

6.0

7.0

7.5

8.0

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

1800 227 0.09 463 0.26 664 0.49 832 0.77 968 1.07

-

2200 277 0.16 479 0.37 648 0.59 813 0.89 956 1.23 1185 1.96

-

-

-

-

-

-

-

-

-

-

2600 327 0.26 501 0.50 657 0.76 798 1.04 936 1.40 1174 2.20 1275 2.62 1366 3.06

-

3100 390 0.44 534 0.69 677 1.03 801 1.33 918 1.66 1150 2.51 1254 2.97 1352 3.47 1523 4.47

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

outside 25%WO limit

MUA-PRC004-EN 23

Performance

Data fan data

Chart PD-3. Size 12-9 exhaust fan, unit size 031

8

7

2115 rpm

2100 rpm

2000 rpm

6

1900 rpm

30% WO

1800 rpm

50% WO

5

4

3

2

1

0

1700 rpm

1600 rpm

1500 rpm

1400 rpm

1300 rpm

1200 rpm

1100 rpm

1000 rpm

900 rpm

800 rpm

700 rpm

600 rpm

0

60% WO

70% WO

1000 2000 3000 4000 airflow, cfm

Note: Fan curves include internal energy module cabinet and wheel losses. Curves represent fan performance with an air density of 0.075 lbm/ft 3 .

80% WO

5000

90% WO

Table PD-3. Exhaust fan size 12-9, unit size 031

0.0

cfm rpm bhp

1800 692 0.37

2200 845 0.68

2600 999 1.13

3100 1191 1.91

0.5

rpm bhp

1.0

rpm bhp total static pressure, in.wg.

1.5

rpm bhp

2.0

rpm bhp

2.5

rpm bhp

895 0.55

1066 0.72

1229 0.94

1013 0.89

1169 1.11

1305 1.33

1143 1.37

1282 1.63

1406 1.87

1314 2.21

1430 2.50

1546 2.81

3.0

rpm bhp

1386 1.16

1536 1.39

1670 1.61

1438 1.58

1568 1.84

1697 2.12

1521 2.13

1634 2.43

1745 2.73

1650 3.10

1747 3.38

1842 3.72

outside 25%WO limit outside rpm limit

3.5

rpm bhp

4.0

rpm bhp

1788 1.83

1893 2.03

1822 2.40

1936 2.67

1856 3.05

1967 3.38

1937 4.08

2032 4.44

4.5

rpm bhp

-

2046 2.95

-

2075 3.71

2124 4.81

24

MUA-PRC004-EN

Performance

Data fan data

Chart PD-4. Unit size 040 with 12-9 supply fan

50% WO

8

25% WO 60% WO

7

2115 rpm

2100 rpm

2000 rpm

70% WO

6

1900 rpm

5 1800 rpm 80% WO

1700 rpm

4

1600 rpm

3

1500 rpm

1400 rpm

1300 rpm

90% WO

2

1

0

1200 rpm

1100 rpm

1000 rpm

900 rpm

800 rpm

700 rpm

600 rpm

0 2000 4000 6000

airflow, cfm

8000

Note: Fan curves include internal cabinet static losses. To determine total static pressure to be used with these curves, add filter, damper, gas or electric heat, evaporator and reheat coils, and TE wheel pressure drops to external duct static pressure.

Chart PD-4. Supply fan size 12-9, unit size 040

0.0

0.5

1.0

1.5

2.0

3.0

total static pressure, in. wg.

3.5

4.0

5.0

5.5

6.0

7.0

7.5

8.0

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

2200 490 0.33 658 0.51 827 0.72 982 0.95 1126 1.18 1405 1.73 1532 2.03 1654 2.35 1866 3.01 1965 3.35

-

2600 578 0.55 721 0.75 867 1.02 1005 1.24 1138 1.51 1377 2.06 1499 2.38 1618 2.72 1836 3.44 1935 3.81 2031 4.20

-

-

3000 667 0.84 786 1.05 915 1.33 1041 1.64 1162 1.91 1386 2.53 1490 2.84 1591 3.17 1800 3.92 1900 4.32 1998 4.74 2179 5.59

3400 756 1.23 853 1.44 975 1.77 1086 2.13 1195 2.41 1405 3.08 1504 3.44 1597 3.78 1780 4.52 1870 4.91 1965 5.35 2145 6.24

-

-

-

-

-

-

3800 845 1.71 929 1.93 1039 2.30 1138 2.61 1240 3.09 1430 3.71 1524 4.10 1615 4.51 1786 5.29 1869 5.69 1949 6.09 2111 6.97 2196 7.46

4000 890 2.00 968 2.23 1072 2.58 1168 2.95 1263 3.38 1448 4.09 1539 4.48 1627 4.89 1793 5.72 1874 6.14 1951 6.54 2104 7.41 2185 7.89

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

outside 25% WO limit outside rpm limit

MUA-PRC004-EN 25

26

Performance

Data fan data

Chart PD-5. Unit size 040 with 15-11 supply fan

50% WO

26% WO

8

1760 rpm

1700 rpm

60% WO

7

1600 rpm

70% WO

6

1500 rpm

5

1400 rpm

80% WO

4

1300 rpm

1200 rpm

3

1100 rpm

2

1

1000 rpm

900 rpm

800 rpm

700 rpm

600 rpm

500 rpm

400 rpm

90% WO

0

0 2500 5000 7500

airflow, cfm

10000 12500 15000

Note: Fan curves include internal cabinet static losses. To determine total static pressure to be used with these curves, add filter, damper, gas or electric heat, evaporator and reheat coils, and TE wheel pressure drops to external duct static pressure.

Table PD-5. Supply fan size 15-11, unit size 040

0.0

0.5

1.0

1.5

2.0

total static pressure, in. wg.

3.0

3.5

4.0

5.0

5.5

6.0

7.0

7.5

8.0

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

2200 277 0.16 479 0.37 648 0.59 813 0.89 956 1.23

-

2600 327 0.26 501 0.50 657 0.76 798 1.04 936 1.40 1174 2.20 1275 2.62

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

3000 377 0.40 526 0.65 672 0.97 800 1.27 920 1.60 1155 2.44 1261 2.91 1354 3.38 1526 4.37

-

3400 428 0.58 560 0.85 692 1.22 812 1.55 922 1.90 1135 2.72 1240 3.20 1337 3.71 1514 4.78 1594 5.33 1670 5.89

-

-

-

-

-

-

3800 478 0.82 593 1.11 713 1.49 829 1.89 933 2.26 1123 3.05 1221 3.54 1317 4.06 1495 5.18 1577 5.77 1654 6.37 1798 7.59

4000 503 0.95 611 1.26 725 1.64 839 2.07 939 2.46 1125 3.28 1215 3.74 1308 4.26 1487 5.41 1568 6.01 1646 6.62 1793 7.89

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

outside 25% WO limit outside rpm limit

MUA-PRC004-EN

Performance

Data fan data

Chart PD-6. Unit size 040 with 12-9 exhaust fan

8

7

2115 rpm

2100 rpm

2000 rpm

6

1900 rpm

5

4

3

2

1

0

1800 rpm

1700 rpm

1600 rpm

1500 rpm

1400 rpm

1300 rpm

1200 rpm

1100 rpm

1000 rpm

900 rpm

800 rpm

700 rpm

600 rpm

37% WO

50% WO

60% WO

70% WO

80% WO

90% WO

0 1000 2000 3000 4000 5000

airflow, cfm

Note: Fan curves include internal energy module cabinet and wheel losses. Curves represent fan performance with an air density of 0.075 ft 3 /lbm.

Table PD-6. Exhaust fan 12-9, unit size 040 cfm

2200

2600

3000

3400

3800

4000

0.00

0.50

rpm bhp rpm

845 0.68

1021

999 1.13

1149

1152 1.73

1284

1306 2.52

1424

1460 3.52

1566

1537 4.11

1638

1.00

1.50

total static pressure, in. wg.

2.00

2.50

3.00

3.50

4.00

4.50

rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp bhp

0.90

1179 1.12

1319 1.35

1457 1.62

1594 1.90

1727 2.18

1853 2.47

1969 2.76 2075 3.03

1.38

1291 1.65

1419 1.90

1538 2.18

1655 2.49

1769 2.80

1884 3.13

1998 3.47 2109 3.82

2.03

1409 2.33

1529 2.63

1639 2.92

1741 3.23

1842 3.58

1944 3.94

2045 4.32 2142 4.68

2.86

1534 3.19

1644 3.54

1748 3.89

1845 4.21

1936 4.54

2025 4.93

2113 5.33 2203 5.74

3.90

1665 4.27

1764 4.64

1861 5.04

1954 5.43

2039 5.78

2123 6.15

2205 6.56

4.50

1733 4.89

1825 5.28

1920 5.70

2010 6.11

2095 6.51

2176 6.89

2254 7.27

-

-

-

-

outside rpm limit

MUA-PRC004-EN 27

Performance

Data fan data

Chart PD-7. Unit size 051 with 15-11 supply fan

9 50% WO

25% WO

60% WO

8

1760 rpm

70% WO

7 1700 rpm

6

1600 rpm 80% WO

1500 rpm

5

1400 rpm

90% WO

4 1300 rpm

1200 rpm

3

1100 rpm

1

0

1000 rpm

2

900 rpm

800 rpm

700 rpm

600 rpm

500 rpm

400 rpm

0 2500 5000 7500

airflow, cfm

10000 12500

Note: Fan curves include internal cabinet static losses. To determine total static pressure to be used with these curves, add filter, damper, gas or electric heat, evaporator and reheat coils, and TE wheel pressure drops to external duct static pressure.

Table PD-7. Supply fan size 15-11, unit size 051

0.0

0.5

1.0

1.5

2.0

3.0

total static pressure, in. wg.

3.5

4.0

5.0

5.5

6.0

7.0

7.5

8.0

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

2900 353 0.35 498 0.56 646 0.87 776 1.15 900 1.48 1138 2.29 1243 2.74 1340 3.20

-

3300 402 0.51 525 0.75 662 1.09 784 1.41 896 1.74 1116 2.54 1220 3.01 1317 3.49 1494 4.52 1574 5.06 1650 5.60

-

-

-

-

-

-

3700 451 0.72 555 0.97 678 1.32 797 1.71 903 2.07 1096 2.83 1196 3.30 1293 3.81 1472 4.89 1554 5.46 1631 6.03 1775 7.22

-

4100 500 0.98 588 1.23 704 1.59 812 2.04 913 2.45 1098 3.26 1184 3.69 1272 4.17 1449 5.29 1531 5.88 1608 6.47 1758 7.74 1827 8.39

-

-

4500 548 1.29 620 1.53 731 1.94 829 2.40 928 2.88 1105 3.76 1187 4.21 1264 4.66 1427 5.73 1507 6.33 1586 6.96 1733 8.25 1805 8.95

4900 597 1.67 653 1.88 759 2.37 853 2.78 945 3.34 1115 4.31 1194 4.79 1271 5.29 1415 6.30 1487 6.86 1563 7.49 1712 8.84 1782 9.54

5100 621 1.88 673 2.09 775 2.59 867 3.00 952 3.57 1122 4.62 1198 5.10 1272 5.61 1415 6.65 1483 7.18 1555 7.80 1701 9.15 1767 9.82

-

-

-

-

-

-

outside 25%WO limit outside rpm limit

28

MUA-PRC004-EN

Performance

Data fan data

Chart PD-8. Unit size 051 with 18-13 supply fan

9

50% WO

1515 rpm

1500 rpm

29% WO

60% WO

8

1400 rpm

70% WO

7

1300 rpm

6

1200 rpm

5

1100 rpm

4

1000 rpm

900 rpm

3

800 rpm

2

1

0

700 rpm

600 rpm

500 rpm

400 rpm

300 rpm

80% WO

90% WO

0 5000 10000

airflow, cfm

15000 20000

Note: Fan curves include internal cabinet static losses. To determine total static pressure to be used with these curves, add filter, damper, gas or electric heat, evaporator and reheat coils, and TE wheel pressure drops to external duct static pressure.

Table PD-8. Supply fan size 18-13, unit size 051

0.00

0.50

1.00

1.50

2.00

3.00

total static pressure, in. wg.

3.50

4.00

5.00

5.50

6.00

7.00

7.50

8.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

2900 217 0.16 411 0.41 573 0.73 707 1.10 827 1.54

3300 246 0.24 419 0.51 573 0.86 701 1.23 817 1.67

-

-

-

-

-

-

-

-

-

-

3700 276 0.34 430 0.63 576 1.00 702 1.41 811 1.84 1008 2.90

-

4100 306 0.46 445 0.77 581 1.16 703 1.61 810 2.06 999 3.10 1086 3.70 1169 4.37

-

-

-

-

-

-

-

-

-

-

-

-

-

-

4500 336 0.61 461 0.94 589 1.35 705 1.81 811 2.31 995 3.36 1080 3.96 1160 4.62

-

4900 366 0.79 478 1.13 598 1.57 709 2.05 813 2.59 992 3.66 1074 4.26 1152 4.91 1298 6.32

-

-

5100 380 0.89 486 1.23 604 1.69 714 2.19 814 2.73 993 3.85 1072 4.43 1148 5.06 1295 6.50 1363 7.27

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

outside 25% WO limit

MUA-PRC004-EN 29

Performance

Data fan data

Chart PD-9. Unit size 051 with 15-11 exhaust fan

8

1760 rpm

1700 rpm

7

1600 rpm

6

1500 rpm

33% WO 50% WO

60% WO

5

1400 rpm

70% WO

1300 rpm

4

3

1200 rpm

1100 rpm

1000 rpm

2

900 rpm

1

800 rpm

700 rpm

600 rpm

500 rpm

400 rpm

0

0 2000 4000 6000

airflow, cfm

8000

Note: Fan curves include internal energy module cabinet and wheel losses. Curves represent fan performance with an air density of 0.075 lbm/ft 3 .

80% WO

90% WO

10000 cfm

2900

3300

3700

4100

4500

4900

5100

Table PD-9. Exhaust fan size 15-11, unit size 051

0.00

0.50

1.00

1.50

total static pressure, in. wg.

2.00

2.50

3.00

3.50

4.00

4.50

rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

537 0.63

700 0.94

612 0.92

759 1.28

686 1.30

820 1.70

760 1.77

883 2.21

840 1.28

979 1.69

1151 2.32

1290 2.93

1393 3.44

1483 3.93

1565 4.41

1640 4.88

885 1.66

1005 2.06

1130 2.56

1283 3.28

1420 4.03

1518 4.63

1606 5.20

1683 5.75

935 2.12

1045 2.55

1153 3.03

1263 3.58

1399 4.37

1533 5.26

1633 5.98

1719 6.66

990 2.66

1091 3.14

1189 3.63

1286 4.17

1384 4.78

1505 5.61

1628 6.56

1740 7.52

834 2.34

947 2.82

1048 3.32

1142 3.83

1232 4.35

1320 4.89

1409 5.50

1498 6.15

1605 7.01

1715 7.99

908 3.02

1013 3.54

1108 4.08

1195 4.63

1281 5.19

1363 5.77

1444 6.37

1524 7.01

1606 7.71

1697 8.55

945 3.41

1046 3.95

1138 4.51

1223 5.07

1306 5.66

1385 6.25

1464 6.86

1541 7.51

1618 8.20

1699 8.97

outside 25%WO limit

30

MUA-PRC004-EN

Performance

Data fan data

Chart PD-10. Unit size 066 with 15-11 supply fan

50% WO

9

60% WO

25% WO

8

1760 rpm

1700 rpm

7

6

1600 rpm

1500 rpm

5

1400 rpm

70% WO

80% WO

90% WO

4 1300 rpm

1200 rpm

3

1100 rpm

1000 rpm

2

1

0

900 rpm

800 rpm

700 rpm

600 rpm

500 rpm

0 2500 5000 7500

airflow, cfm

10000 12500

Note: Fan curves include internal cabinet static losses. To determine total static pressure to be used with these curves, add filter, damper, gas or electric heat, evaporator and reheat coils, and TE wheel pressure drops to external duct static pressure.

Table PD-10. Supply fan size 15-11, unit size 066

0.0

0.5

1.0

1.5

2.0

3.0

total static pressure, in. wg.

3.5

4.0

5.0

5.5

6.0

7.0

7.5

8.0

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

3600 439 0.66 548 0.91 673 1.26 793 1.63 900 1.98 1101 2.75 1201 3.22 1298 3.72 1477 4.79 1559 5.35 1639 5.94 1782 7.11

4000 487 0.91 580 1.16 696 1.51 809 1.96 911 2.35 1097 3.15 1185 3.58 1276 4.07 1455 5.19 1535 5.76 1615 6.36 1763 7.62

-

-

4400 536 1.21 613 1.45 725 1.84 824 2.31 924 2.77 1102 3.62 1185 4.07 1265 4.52 1431 5.61 1512 6.21 1591 6.83 1742 8.15 1811 8.81

4800 585 1.57 644 1.78 752 2.26 846 2.68 941 3.23 1113 4.17 1193 4.64 1269 5.12 1416 6.13 1493 6.73 1567 7.34 1716 8.67 1787 9.38

-

-

-

-

-

-

5200 634 1.99 683 2.20 782 2.71 875 3.12 957 3.69 1126 4.79 1201 5.27 1276 5.79 1416 6.84 1484 7.38 1552 7.96 1694 9.29 1763 9.99

-

5600 682 2.49 726 2.71 815 3.20 901 3.69 981 4.21 1141 5.45 1215 5.99 1286 6.53 1423 7.64 1486 8.19 1549 8.75 1675 9.98 1742 10.68 1810 11.44

6000 731 3.06 772 3.30 848 3.76 930 4.35 1010 4.80 1157 6.14 1230 6.77 1299 7.35 1431 8.51 1494 9.10 1556 9.71 1674 10.93 1733 11.56 1791 12.22

6400 780 3.71 818 3.98 879 4.38 961 5.02 1037 5.55 1174 6.84 1247 7.58 1315 8.24 1441 9.45 1504 10.08 1562 10.71 1677 11.98 1736 12.66 1790 13.31

6600 804 4.07 842 4.35 895 4.71 977 5.39 1050 5.97 1185 7.22 1255 7.98 1322 8.68 1449 9.99 1508 10.59 1568 11.26 1680 12.54 1737 13.23 1790 13.88

-

-

-

outside 25% WO limit outside rpm limit but may be used for interpolation purposes

MUA-PRC004-EN 31

Performance

Data fan data

Chart PD-11. Unit size 066 with 18-13 supply fan

8

1515 rpm

1500 rpm

7

1400 rpm

6

1300 rpm

5

1200 rpm

4

1100 rpm

3

1000 rpm

900 rpm

2

1

0

800 rpm

700 rpm

600 rpm

500 rpm

400 rpm

29% WO

50% WO

60% WO

70% WO

80% WO

90% WO

0 5000 10000 15000 20000

airflow, cfm

Note: Fan curves include internal cabinet static losses. To determine total static pressure to be used with these curves, add filter, damper, gas or electric heat, evaporator and reheat coils, and TE wheel pressure drops to external duct static pressure.

Table PD-11. Supply fan size 18-13, unit size 066

0.00

0.50

1.00

1.50

2.00

3.00

total static pressure, in. wg.

3.50

4.00

5.00

5.50

6.00

7.00

7.50

8.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

3600 269 0.31 427 0.60 576 0.96 702 1.36 813 1.79 1012 2.86

-

4000 298 0.43 441 0.73 580 1.12 702 1.55 809 1.99 1002 3.05 1090 3.66

-

-

-

-

-

-

-

4400 328 0.57 457 0.90 587 1.30 704 1.76 811 2.25 996 3.29 1081 3.90 1162 4.54

-

4800 358 0.74 474 1.08 595 1.51 708 1.99 812 2.52 992 3.58 1074 4.17 1153 4.83 1303 6.28

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

5200 388 0.94 490 1.29 608 1.76 715 2.26 815 2.80 992 3.94 1072 4.53 1147 5.15 1292 6.59 1361 7.36

-

5600 418 1.18 507 1.52 621 2.03 723 2.55 818 3.11 994 4.34 1071 4.95 1145 5.58 1287 6.99 1352 7.74 1419 8.58

-

-

6000 447 1.45 527 1.79 637 2.35 732 2.88 826 3.48 995 4.75 1072 5.40 1144 6.06 1282 7.45 1346 8.20 1411 9.01 1531 10.71

6400 477 1.76 549 2.10 654 2.69 744 3.25 833 3.86 997 5.17 1073 5.88 1146 6.59 1282 8.01 1343 8.73 1405 9.53

-

6600 492 1.93 560 2.28 662 2.88 752 3.46 838 4.07 999 5.39 1076 6.13 1147 6.86 1281 8.32 1343 9.04 1403 9.80

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

outside 25% WO limit outside rpm or hp limit

32

MUA-PRC004-EN

Performance

Data fan data

Chart PD-12. Unit size 066 with 15-11 exhaust fan

8

1760 rpm

1700 rpm

7

1600 rpm

6

1500 rpm

5

1400 rpm

1300 rpm

4

3

1200 rpm

1100 rpm

1000 rpm

2

900 rpm

800 rpm

1

700 rpm

600 rpm

500 rpm

0

400 rpm

0

31% WO

50% WO

60% WO

70% WO

2000 4000

airflow, cfm

6000 8000

Note: Fan curves include internal energy module cabinet and wheel losses. Curves represent fan performance with an air density of 0.075 lbm/ft 3 .

80% WO

90% WO

3600

4000

4400

4800

5200

5600

6000

6400

6600

Table PD-12. Exhaust fan size 15-11, unit size 066 cfm

0.00

0.50

rpm bhp rpm bhp

1.00

rpm bhp

1.50

rpm total static pressure, in. wg.

bhp

2.00

2.50

3.00

rpm bhp rpm bhp rpm

3.50

4.00

4.50

bhp rpm bhp rpm bhp rpm bhp

608 1.05

755 1.44

675 1.44

810 1.87

879 1.84

992 2.25

1103 2.71 1215 3.23 1353 3.98

1489 4.82

1595 5.56 1682 6.20

927 2.31

1032 2.76

1132 3.23 1232 3.75 1332 4.32

1452 5.10

1578 6.02 1694 6.95

743 1.92

867 2.39

977 2.87

1076 3.36

1169 3.87 1260 4.39 1351 4.96

1440 5.57

1543 6.34 1657 7.29

810 2.50

925 3.00

1029 3.53

1123 4.06

1210 4.60 1296 5.16 1378 5.72

1461 6.34

1545 7.01 1630 7.75

878 3.17

985 3.72

1083 4.29

1173 4.86

1255 5.43 1335 6.03 1413 6.63

1490 7.26

1566 7.91 1643 8.62

945 3.96 1046 4.56

1137 5.15

1224 5.77

1303 6.38 1379 7.02 1453 7.66

1525 8.31

1597 8.98 1667 9.68

1013 4.88 1108 5.52

1194 6.14

1276 6.81

1354 7.47 1425 8.13 1496 8.82

1564 9.50

1633 10.21 1699 10.91

1080 5.92 1171 6.61

1252 7.26

1330 7.97

1405 8.67 1474 9.37 1541 10.09

1607 10.82

1671 11.55 1734 12.29

1114 6.49 1202 7.20

1281 7.88

1358 8.60

1430 9.32 1499 10.05 1565 10.78

1628 11.53

1692 12.29 1754 13.05

MUA-PRC004-EN 33

34

Performance

Data airside pressure drop

Table PD-13. Air pressure drop, in. wg.

coils filters unit main evaps RH evaps size cfm wet dry wet dry

RH

cond dry unit

OA

ER

OA

031 1800 0.26

1900 0.28

2000 0.30

2100 0.33

2200 0.35

2300 0.37

2400 0.40

2500 0.42

2600 0.45

2700 0.48

2800 0.50

2900 0.53

3000 0.56

3100 0.59

ER dampers

RA std.

Traq

100%

RA

TE wheel

& module

0.20

0.13

0.10

0.10

0.05

0.05

0.05

0.01

0.06

0.02

0.77

0.22

0.14

0.11

0.11

0.05

0.05

0.05

0.01

0.06

0.03

0.81

0.23

0.15

0.12

0.12

0.06

0.06

0.06

0.01

0.07

0.03

0.86

0.25

0.16

0.13

0.13

0.06

0.06

0.06

0.01

0.08

0.03

0.91

0.27

0.17

0.14

0.14

0.07

0.07

0.07

0.01

0.08

0.04

0.95

0.29

0.19

0.15

0.15

0.08

0.08

0.08

0.01

0.09

0.04

1.00

0.31

0.20

0.16

0.16

0.08

0.08

0.08

0.01

0.10

0.04

1.05

0.33

0.21

0.17

0.17

0.09

0.09

0.09

0.02

0.11

0.05

1.09

0.35

0.23

0.18

0.18

0.10

0.10

0.10

0.02

0.12

0.05

1.14

0.37

0.24

0.19

0.19

0.11

0.11

0.11

0.02

0.13

0.05

1.19

0.40

0.25

0.20

0.20

0.11

0.11

0.11

0.02

0.13

0.06

1.24

0.42

0.27

0.21

0.21

0.12

0.12

0.12

0.02

0.14

0.06

1.29

0.44

0.28

0.22

0.22

0.13

0.13

0.13

0.02

0.15

0.07

1.34

0.46

0.29

0.23

0.23

0.14

0.14

0.14

0.02

0.17

0.07

1.38

040 2200 0.25

2300 0.27

2400 0.28

2500 0.30

2600 0.32

2700 0.34

2800 0.36

2900 0.38

3000 0.40

3100 0.42

3200 0.44

3300 0.46

3400 0.48

3500 0.50

3600 0.53

3700 0.55

3800 0.57

3900 0.59

4000 0.62

0.19

0.12

0.10

0.10

0.07

0.07

0.07

0.01

0.08

0.04

0.60

0.20

0.13

0.10

0.10

0.08

0.08

0.08

0.01

0.09

0.04

0.64

0.22

0.14

0.11

0.11

0.08

0.08

0.08

0.01

0.10

0.04

0.68

0.23

0.15

0.12

0.12

0.09

0.09

0.09

0.02

0.11

0.05

0.71

0.25

0.16

0.12

0.12

0.10

0.10

0.10

0.02

0.12

0.05

0.75

0.26

0.17

0.13

0.13

0.11

0.11

0.11

0.02

0.13

0.05

0.79

0.28

0.18

0.14

0.14

0.11

0.11

0.11

0.02

0.13

0.06

0.83

0.29

0.19

0.15

0.15

0.12

0.12

0.12

0.02

0.14

0.06

0.87

0.31

0.20

0.16

0.16

0.13

0.13

0.13

0.02

0.15

0.07

0.91

0.33

0.21

0.16

0.16

0.14

0.14

0.14

0.02

0.17

0.07

0.95

0.34

0.22

0.17

0.17

0.15

0.15

0.15

0.03

0.18

0.07

0.99

0.36

0.23

0.18

0.18

0.16

0.16

0.16

0.03

0.19

0.08

1.03

0.38

0.24

0.19

0.19

0.17

0.17

0.17

0.03

0.20

0.08

1.07

0.40

0.25

0.20

0.20

0.18

0.18

0.18

0.03

0.21

0.09

1.12

0.41

0.26

0.21

0.21

0.19

0.19

0.19

0.03

0.22

0.09

1.16

0.43

0.27

0.22

0.22

0.20

0.20

0.20

0.04

0.24

0.10

1.21

0.45

0.29

0.22

0.22

0.21

0.21

0.21

0.04

0.25

0.10

1.25

0.47

0.30

0.23

0.23

0.22

0.22

0.22

0.04

0.26

0.11

1.30

0.49

0.31

0.24

0.24

0.23

0.23

0.23

0.04

0.28

0.12

1.34

MUA-PRC004-EN

MUA-PRC004-EN

Performance

Data airside pressure drop

Table PD-14. Air pressure drop, in. wg.

unit coils

main evaps RH evaps size cfm wet dry wet dry

filters

RH

cond dry unit

OA

ER

OA

5100 0.58

066 3600 0.24

3700 0.25

3800 0.26

3900 0.27

4000 0.28

4100 0.29

4200 0.30

4300 0.31

4400 0.32

4500 0.33

4600 0.35

4700 0.36

4800 0.37

4900 0.38

5000 0.39

5100 0.40

5200 0.42

5300 0.43

5400 0.44

5500 0.45

5600 0.46

5700 0.48

5800 0.49

5900 0.50

6000 0.52

6100 0.53

6200 0.54

6300 0.56

6400 0.57

6500 0.58

6600 0.60

051 2900 0.25

3000 0.26

3100 0.27

3200 0.28

3300 0.30

3400 0.31

3500 0.33

3600 0.34

3700 0.35

3800 0.37

3900 0.38

4000 0.40

4100 0.41

4200 0.43

4300 0.45

4400 0.46

4500 0.48

4600 0.49

4700 0.51

4800 0.53

4900 0.54

5000 0.56

0.27

0.28

0.29

0.29

0.30

0.31

0.32

0.33

0.34

0.35

0.36

0.37

0.38

0.39

0.41

0.42

0.43

0.44

0.45

0.46

0.47

0.45

0.18

0.19

0.20

0.21

0.21

0.22

0.23

0.24

0.25

0.26

0.31

0.32

0.34

0.35

0.36

0.37

0.39

0.40

0.41

0.43

0.44

0.19

0.20

0.21

0.22

0.23

0.24

0.25

0.26

0.27

0.29

0.30

0.12

0.09

0.09

0.04

0.05

0.08

0.01

0.07

0.03

0.13

0.10

0.10

0.04

0.05

0.08

0.01

0.08

0.03

0.14

0.10

0.10

0.04

0.06

0.09

0.01

0.08

0.03

0.14

0.11

0.11

0.04

0.06

0.09

0.01

0.09

0.03

0.15

0.11

0.11

0.05

0.06

0.10

0.01

0.09

0.04

0.16

0.12

0.12

0.05

0.07

0.10

0.01

0.10

0.04

0.16

0.13

0.13

0.05

0.07

0.11

0.01

0.10

0.04

0.17

0.13

0.13

0.06

0.07

0.12

0.01

0.11

0.04

0.18

0.14

0.14

0.06

0.08

0.12

0.01

0.12

0.05

0.18

0.14

0.14

0.06

0.08

0.13

0.01

0.12

0.05

0.19

0.15

0.15

0.07

0.09

0.14

0.01

0.13

0.05

0.20

0.16

0.16

0.07

0.09

0.14

0.01

0.14

0.05

0.21

0.16

0.16

0.07

0.10

0.15

0.01

0.14

0.06

0.21

0.17

0.17

0.08

0.10

0.16

0.01

0.15

0.06

0.22

0.17

0.17

0.08

0.11

0.17

0.02

0.16

0.06

0.23

0.18

0.18

0.08

0.11

0.18

0.02

0.16

0.06

0.24

0.19

0.19

0.09

0.12

0.18

0.02

0.17

0.07

0.25

0.19

0.19

0.09

0.12

0.19

0.02

0.18

0.07

0.25

0.20

0.20

0.10

0.13

0.20

0.02

0.19

0.07

0.26

0.21

0.21

0.10

0.13

0.21

0.02

0.20

0.08

0.27

0.21

0.21

0.11

0.14

0.22

0.02

0.20

0.08

0.28

0.22

0.22

0.11

0.14

0.23

0.02

0.21

0.08

0.29

0.23

0.23

0.11

0.15

0.24

0.02

0.22

0.09

0.12

0.09

0.09

0.06

0.07

0.12

0.01

0.11

0.04

0.12

0.09

0.09

0.06

0.08

0.12

0.01

0.12

0.05

0.13

0.10

0.10

0.06

0.08

0.13

0.01

0.12

0.05

0.13

0.10

0.10

0.07

0.09

0.14

0.01

0.13

0.05

0.14

0.11

0.11

0.07

0.09

0.14

0.01

0.14

0.05

0.15

0.11

0.11

0.07

0.10

0.15

0.01

0.14

0.06

0.15

0.12

0.12

0.08

0.10

0.16

0.01

0.15

0.06

0.16

0.12

0.12

0.08

0.11

0.17

0.02

0.16

0.06

0.16

0.12

0.12

0.08

0.11

0.18

0.02

0.16

0.06

0.17

0.13

0.13

0.09

0.12

0.18

0.02

0.17

0.07

0.17

0.13

0.13

0.09

0.12

0.19

0.02

0.18

0.07

0.18

0.14

0.14

0.10

0.13

0.20

0.02

0.19

0.07

0.18

0.14

0.14

0.10

0.13

0.21

0.02

0.20

0.08

0.19

0.15

0.15

0.11

0.14

0.22

0.02

0.20

0.08

0.20

0.15

0.15

0.11

0.14

0.23

0.02

0.21

0.08

0.20

0.16

0.16

0.11

0.15

0.24

0.02

0.22

0.09

0.21

0.16

0.16

0.12

0.16

0.24

0.02

0.23

0.09

0.21

0.17

0.17

0.12

0.16

0.25

0.02

0.24

0.09

0.22

0.17

0.17

0.13

0.17

0.26

0.02

0.25

0.10

0.23

0.18

0.18

0.13

0.17

0.27

0.02

0.26

0.10

0.23

0.18

0.18

0.14

0.18

0.28

0.03

0.27

0.11

0.24

0.19

0.19

0.14

0.19

0.29

0.03

0.28

0.11

0.25

0.19

0.19

0.15

0.19

0.30

0.03

0.29

0.11

0.25

0.20

0.20

0.15

0.20

0.32

0.03

0.30

0.12

0.26

0.20

0.20

0.16

0.21

0.33

0.03

0.31

0.12

0.26

0.21

0.21

0.16

0.22

0.34

0.03

0.32

0.12

0.27

0.21

0.21

0.17

0.22

0.35

0.03

0.33

0.13

0.28

0.22

0.22

0.17

0.23

0.36

0.03

0.34

0.13

0.28

0.22

0.22

0.18

0.24

0.37

0.03

0.35

0.14

0.29

0.23

0.23

0.18

0.24

0.38

0.03

0.36

0.14

0.30

0.24

0.24

0.19

0.25

0.39

0.04

0.37

0.15

TE wheel

ER dampers

RA

100% & std.

Traq RA module

0.87

0.89

0.92

0.94

0.97

1.00

1.03

1.05

1.08

1.11

1.14

1.17

1.19

1.22

1.25

1.28

1.31

1.34

1.38

1.41

1.44

1.32

0.62

0.65

0.67

0.69

0.72

0.74

0.77

0.79

0.82

0.84

1.00

1.03

1.06

1.09

1.11

1.14

1.17

1.20

1.23

1.26

1.29

0.70

0.73

0.76

0.78

0.81

0.84

0.86

0.89

0.92

0.95

0.97

35

Performance

Data airside pressure drop

Table PD-15. Single gas duct furnace with 12-9 fan, unit sizes 031 & 040, in. wg.

unit size

031

040 cfm

1800

1900

2000

2100

2200

2300

2400

2500

2600

2700

2800

2900

3000

3100

2200

2300

2400

2500

2600

2700

2800

2900

3000

3100

3200

3300

3400

3500

3600

3700

3800

3900

4000

150/120

0.15

0.17

0.18

0.20

0.22

0.24

0.26

0.29

0.31

0.33

0.36

0.39

0.41

0.44

0.22

0.24

0.26

0.29

0.31

0.33

0.36

0.39

0.41

0.44

0.47

0.50

0.53

0.56

0.60

125/100

0.22

0.25

0.28

0.30

0.33

0.36

0.40

0.43

0.47

0.50

0.54

0.58

0.62

0.33

0.36

0.40

0.43

0.47

0.50

0.54

0.58

0.62

0.19

0.21

0.22

0.24

0.26

0.28

0.31

0.33

0.35

0.37

0.40

0.42

0.45

0.48

0.51

0.53

0.56

0.59

0.62

200/160 gas heat input/output (MBh)

250/200 300/240

0.22

0.25

0.16

0.17

0.19

0.21

0.22

0.24

0.26

0.28

0.31

0.33

0.35

0.37

0.29

0.33

0.37

0.41

0.33

0.37

0.40

0.44

0.47

0.51

0.55

0.45

0.50

0.54

0.58

0.63

0.51

0.54

0.33

0.37

0.41

0.33

0.37

0.40

0.44

0.47

0.51

0.55

0.59

0.63

0.67

0.71

0.75

0.80

0.84

0.89

0.94

0.45

0.50

0.54

0.58

0.63

0.51

0.54

0.58

0.62

0.66

0.71

0.75

0.79

0.84

0.88

0.93

400/320

350/280

0.54

0.57

0.61

0.54

0.57

0.61

0.66

0.70

0.74

0.58

0.61

0.65

0.69

0.72

0.76

36 MUA-PRC004-EN

Performance

Data airside pressure drop

Table PD-16. Single gas duct furnace with 15-11 fan, unit sizes 031 & 040, in. wg.

unit size

031

040

2700

2800

2900

3000

3100

3200

3300

3400

3500

3600

2800

2900

3000

3100

2200

2300

2400

2500

2600

3700

3800

3900

4000 cfm

1800

1900

2000

2100

2200

2300

2400

2500

2600

2700

0.25

0.27

0.29

0.31

0.33

0.36

0.38

0.40

0.43

0.45

0.27

0.29

0.31

0.33

0.17

0.18

0.20

0.22

0.24

150/120

0.11

0.13

0.14

0.15

0.17

0.18

0.20

0.22

0.24

0.25

0.43

0.47

0.50

0.54

0.47

0.50

0.54

0.29

0.32

0.34

0.37

0.40

125/100

0.19

0.22

0.24

0.26

0.29

0.32

0.34

0.37

0.40

0.43

0.19

0.20

0.21

0.23

0.24

0.26

0.28

0.29

0.31

0.33

0.20

0.21

0.23

0.24

0.12

0.13

0.15

0.16

0.17

0.35

0.37

0.39

0.41

200/160 gas heat input/output MBh)

250/200 300/240

0.21

0.24

0.10

0.11

0.12

0.13

0.15

0.16

0.17

0.19

0.26

0.29

0.31

0.34

0.25

0.27

0.29

0.37

0.40

0.43

0.32

0.34

0.36

0.39

0.29

0.31

0.34

0.25

0.27

0.29

0.32

0.34

0.36

0.39

0.41

0.44

0.46

0.49

0.52

0.55

0.58

0.61

0.64

0.43

0.46

0.50

0.36

0.38

0.41

0.43

0.46

0.49

0.52

0.46

0.50

0.36

0.38

0.37

0.40

0.54

0.57

0.60

0.64

400/320

0.62

0.66

0.71

0.75

0.80

0.85

0.69

0.72

0.62

0.66

0.71

0.76

0.80

0.83

0.87

350/280

MUA-PRC004-EN 37

Performance

Data airside pressure drop

Table PD-17. Dual gas duct furnace with 12-9 fan, unit sizes 031 & 040, in. wg.

unit size

031

040

2700

2800

2900

3000

3100

3200

3300

3400

3500

3600

2800

2900

3000

3100

2200

2300

2400

2500

2600

3700

3800

3900

4000 cfm

1800

1900

2000

2100

2200

2300

2400

2500

2600

2700

0.91

0.98

1.05

1.13

1.20

1.28

1.36

1.45

1.53

1.62

0.98

1.05

1.13

1.20

0.61

0.66

0.72

0.78

0.85

1.71

1.81

1.90

2.00

250/200

0.55

0.61

0.66

0.72

0.78

0.85

0.91

0.54

0.59

0.63

0.67

0.72

0.76

0.81

0.86

0.91

0.97

0.59

0.63

0.67

0.72

0.47

0.50

1.02

1.08

1.14

1.19

300/240

0.47

0.50

0.54

— gas heat input/output (MBh)

350/280

0.48

0.52

0.55

0.59

0.63

0.67

0.71

0.75

0.48

0.52

0.55

0.79

0.83

0.88

0.92

0.63

0.67

0.71

0.75

0.79

0.83

0.88

0.92

400/320

38 MUA-PRC004-EN

Performance

Data airside pressure drop

Table PD-18. Dual gas duct furnace with 15-11 fan, unit sizes 031 & 040, in. wg.

gas heat input/output (MBh) unit size

031

040 cfm

1800

1900

2000

2100

2200

2300

2400

2500

2600

2700

2800

2900

3000

3100

2200

2300

2400

2500

2600

2700

2800

2900

3000

3100

3200

3300

3400

3500

3600

3700

3800

3900

4000

250/200

0.51

0.56

0.61

0.67

0.72

0.78

0.84

0.91

0.97

1.04

1.11

0.56

0.61

0.67

0.72

0.78

0.84

0.91

0.97

1.04

1.11

1.19

1.26

1.34

1.42

1.50

1.59

1.67

1.76

1.85

300/240

0.40

0.43

0.46

0.50

0.53

0.57

0.61

0.40

0.43

0.46

0.50

0.53

0.57

0.61

0.65

0.69

0.73

0.78

0.82

0.87

0.92

0.97

1.02

350/280

0.37

0.40

0.42

0.37

0.40

0.42

0.45

0.48

0.51

0.54

0.57

0.60

0.64

0.67

0.70

400/320

0.48

0.51

0.54

0.57

0.60

0.64

0.67

0.70

MUA-PRC004-EN 39

Performance

Data airside pressure drop

Table PD-19. Electric heat with 12-9 fan, unit sizes 031 & 040, in. wg.

unit size

031

040 cfm

1800

1900

2000

2100

2200

2300

2400

2500

2600

2700

2800

2900

3000

3100

2200

2300

2400

2500

2600

2700

2800

2900

3000

3100

3200

3300

3400

3500

3600

3700

3800

3900

4000 electric heat

0.07

0.08

0.09

0.10

0.11

0.12

0.13

0.14

0.15

0.17

0.18

0.19

0.21

0.22

0.11

0.12

0.13

0.14

0.15

0.17

0.18

0.19

0.21

0.22

0.23

0.25

0.26

0.28

0.30

0.31

0.33

0.35

0.37

no heat

0.07

0.07

0.08

0.09

0.10

0.11

0.12

0.13

0.14

0.15

0.16

0.17

0.19

0.20

0.10

0.11

0.12

0.13

0.14

0.15

0.16

0.17

0.19

0.20

0.21

0.22

0.24

0.25

0.27

0.28

0.30

0.31

0.33

40 MUA-PRC004-EN

Performance

Data airside pressure drop

Table PD-20. Electric heat with 15-11 fan, unit sizes 031 & 040, in. wg.

unit size

031

040 cfm

1800

1900

2000

2100

2200

2300

2400

2500

2600

2700

2800

2900

3000

3100

2200

2300

2400

2500

2600

2700

2800

2900

3000

3100

3200

3300

3400

3500

3600

3700

3800

3900

4000 electric heat

0.04

0.04

0.05

0.05

0.06

0.06

0.07

0.08

0.08

0.09

0.10

0.10

0.11

0.12

0.06

0.06

0.07

0.08

0.08

0.09

0.10

0.10

0.11

0.12

0.13

0.13

0.14

0.15

0.16

0.17

0.18

0.19

0.20

no heat

0.03

0.04

0.04

0.04

0.05

0.05

0.06

0.06

0.07

0.07

0.08

0.08

0.09

0.10

0.05

0.05

0.06

0.06

0.07

0.07

0.08

0.08

0.09

0.10

0.10

0.11

0.12

0.12

0.13

0.14

0.14

0.15

0.16

MUA-PRC004-EN 41

Performance

Data airside pressure drop

Table PD-21. Single gas duct furnace with 15-11 fan, unit sizes 051 & 066, in. wg.

unit size

051

066 cfm

2900

3000

3100

3200

3300

3400

3500

3600

3700

3800

3900

4000

4100

4200

4300

4400

4500

4600

4700

4800

4900

5000

5100

3600

3700

3800

3900

4000

4100

4200

4300

4400

4500

4600

4700

4800

4900

5000

5100

5200

5300

5400

5500

5600

5700

5800

5900

6000

6100

6200

6300

6400

6500

6600

125/100

0.50

0.54

150/120

0.29

0.31

0.33

0.36

0.38

0.40

0.43

0.45

0.45

200/160

0.21

0.23

0.24

0.26

0.28

gas heat input/output (MBh)

250/200

0.34

0.36

0.39

0.41

0.44

300/240

0.50

0.36

0.38

0.41

0.43

0.59

0.61

0.33

0.35

0.37

0.39

0.41

0.43

0.45

0.47

0.49

0.51

0.29

0.31

0.33

0.35

0.37

0.39

0.41

0.43

0.45

0.47

0.49

0.51

0.54

0.56

0.54

0.56

0.59

0.61

0.46

0.49

0.52

0.55

0.58

0.61

0.64

0.67

0.71

0.74

0.78

0.81

0.85

0.89

0.93

0.96

1.00

1.05

0.52

0.55

0.58

0.61

0.64

0.67

0.71

0.74

0.78

0.81

0.85

0.89

0.93

0.96

1.00

1.05

1.09

1.13

1.17

1.22

1.26

1.31

1.35

1.40

1.45

1.50

0.84

0.88

0.92

0.96

0.99

1.04

1.08

1.12

1.16

1.20

1.25

1.29

1.34

1.39

1.43

1.48

1.53

1.58

1.63

1.68

1.74

0.92

0.96

0.99

1.04

0.52

0.54

0.57

0.60

0.64

0.67

0.70

0.74

0.77

0.81

0.46

0.49

0.52

0.54

0.57

0.60

0.64

0.67

0.70

0.74

0.77

0.81

0.84

0.88

400/320

0.64

0.67

0.71

0.75

0.79

0.83

0.88

0.71

0.74

0.78

0.82

0.85

0.89

0.94

0.98

1.02

1.06

1.11

1.16

0.86

0.90

0.95

0.99

0.71

0.74

0.78

0.82

0.85

0.89

0.94

0.98

1.02

1.06

1.11

1.16

1.20

1.25

1.30

1.35

1.41

1.46

1.51

1.57

1.63

1.68

1.74

1.80

1.86

1.92

1.99

350/280

0.48

0.52

0.56

0.60

0.64

0.68

0.52

0.55

0.59

0.62

0.65

0.69

0.72

0.75

0.79

0.82

0.86

0.90

0.93

0.97

1.00

1.04

1.08

0.55

0.59

0.62

0.65

0.69

0.72

0.75

0.79

0.82

0.86

0.90

0.93

0.97

1.00

1.04

1.08

1.12

1.16

1.19

1.23

1.27

1.31

1.35

1.39

1.43

1.47

1.52

1.56

1.60

1.64

1.69

MUA-PRC004-EN 42

Performance

Data airside pressure drop

Table PD-22. Single gas duct furnace with 18-13 fan, unit sizes 051 & 066, in. wg.

gas heat input/output (MBh) unit size

051

066

3600

3700

3800

3900

4000

4100

4200

4300

4400

4500

4600

4700

4800

4900

5000

5100

5200

5300

5400

5500

5600

5700

5800

5900

6000

6100

6200

6300

6400

6500

6600 cfm

2900

3000

3100

3200

3300

3400

3500

3600

3700

3800

3900

4000

4100

4200

4300

4400

4500

4600

4700

4800

4900

5000

5100

125/100

0.49

0.52

0.39

150/120

0.25

0.27

0.29

0.31

0.33

0.35

0.37

0.39

0.28

0.29

0.31

0.33

0.34

0.36

0.38

0.40

0.42

0.44

0.46

0.48

0.50

0.52

200/160

0.18

0.19

0.21

0.22

0.23

0.25

0.26

0.28

0.29

0.31

0.33

0.34

0.36

0.38

0.40

0.42

0.44

0.46

0.48

0.50

0.52

0.40

0.42

0.44

0.47

0.49

0.52

0.54

0.57

0.59

0.62

0.65

0.68

0.71

0.74

0.77

0.80

0.83

0.87

0.90

0.93

0.97

1.00

1.04

1.08

1.12

1.15

250/200

0.26

0.28

0.30

0.32

0.34

0.36

0.38

0.40

0.42

0.44

0.47

0.49

0.52

0.54

0.57

0.59

0.62

0.65

0.68

0.71

0.74

0.77

0.80

0.39

0.42

0.44

0.46

0.48

0.51

0.53

0.56

0.59

0.61

0.64

0.67

0.70

0.73

0.76

0.79

0.82

0.85

0.89

0.92

0.96

0.99

1.03

1.06

1.10

1.14

1.18

1.22

1.26

1.30

1.34

300/240

0.42

0.28

0.30

0.31

0.33

0.35

0.37

0.39

0.42

0.44

0.46

0.48

0.51

0.53

0.56

0.59

0.61

0.64

0.67

0.70

0.73

0.76

0.79

0.77

0.81

0.86

0.90

0.73

0.76

0.80

0.83

0.87

0.90

0.94

0.97

1.01

1.05

1.08

1.12

1.15

1.19

1.23

1.26

1.30

1.34

1.38

1.42

1.45

1.49

1.53

1.57

1.61

1.65

1.69

400/320

0.71

0.76

0.80

0.85

0.89

0.94

0.99

0.82

0.85

0.89

0.93

0.96

1.00

1.04

1.07

1.11

1.15

1.19

1.22

0.39

0.41

0.43

0.45

0.47

0.50

0.52

0.55

0.57

0.60

0.63

0.65

0.68

0.71

0.74

0.77

0.80

0.83

0.86

0.90

0.93

0.96

1.00

1.03

1.07

1.11

1.14

1.18

1.22

1.26

1.30

350/280

0.40

0.42

0.45

0.48

0.51

0.54

0.37

0.39

0.41

0.43

0.45

0.47

0.50

0.52

0.55

0.57

0.60

0.63

0.65

0.68

0.71

0.74

0.77

MUA-PRC004-EN 43

Performance

Data airside pressure drop

Table PD-23. Dual gas duct furnace with 15-11 fan, unit sizes 051 & 066, in. wg.

unit size cfm

051

2900

3000

3100

3200

3300

3400

3500

3600

3700

3800

3900

4000

4100

4200

4300

4400

4500

4600

4700

4800

4900

5000

5100

061

3600

3700

3800

3900

4000

4100

4200

4300

4400

4500

4600

4700

4800

4900

5000

5100

5200

5300

5400

5500

5600

5700

5800

5900

6000

6100

6200

6300

6400

6500

6600

0.57

0.60

0.64

0.67

0.70

0.74

0.78

0.81

0.85

0.89

0.93

0.97

1.01

1.06

1.10

1.15

1.19

1.24

1.28

1.33

1.38

1.43

1.48

1.53

1.59

1.64

1.69

1.75

1.80

350/280

0.37

0.40

0.42

0.45

0.48

0.51

0.54

0.57

0.60

0.64

0.67

0.70

0.74

0.78

0.81

0.85

0.89

0.93

0.97

1.01

1.06

1.10

1.15

1.50

1.59

1.67

1.76

1.85

1.95

2.04

2.14

2.24

2.35

2.45

250/200

0.97

1.04

1.11

1.19

1.26

1.34

1.42

1.50

1.59

1.67

1.76

1.85

1.95

2.04

2.14

2.24

2.35

2.45

0.82

0.87

0.92

0.97

1.02

1.07

1.12

1.18

1.23

1.29

1.35

1.40

1.46

1.53

1.59

1.65

1.72

1.79

1.85

1.92

300/240

0.53

0.57

0.61

0.65

0.69

0.73

0.78

0.82

0.87

0.92

0.97

1.02

1.07

1.12

1.18

1.23

1.29

1.35

1.40

1.46

1.53

1.59

1.65

0.57

0.60

0.64

0.67

0.70

0.74

0.78

0.81

0.85

0.89

0.93

0.97

1.01

1.06

1.10

1.15

1.19

1.24

1.28

1.33

1.38

1.43

1.48

1.53

1.59

1.64

1.69

1.75

1.80

1.86

1.92

400/320 gas heat input/output (MBh)

500/400 600/480

0.48

0.51

0.54

0.57

0.60

0.64

0.67

0.70

0.74

0.78

0.81

0.85

0.89

0.93

0.97

1.01

1.06

1.10

1.15

0.86

0.90

0.94

0.99

1.03

1.08

1.13

1.18

1.23

1.28

1.33

1.26

1.31

0.86

0.90

0.94

0.99

1.03

1.08

1.13

1.18

1.23

1.28

1.33

1.38

1.43

1.49

1.54

1.60

1.66

1.72

1.78

1.84

1.90

1.96

2.03

2.09

2.16

2.23

1.26

1.31

1.36

1.41

1.47

1.52

1.58

1.63

1.69

1.75

1.81

1.87

1.93

2.00

2.06

2.13

2.19

2.24

800/640

1.61

1.66

1.71

1.76

1.81

1.86

1.91

1.96

2.02

700/560

MUA-PRC004-EN 44

Performance

Data airside pressure drop

Table PD-24. Dual gas duct furnace with 18-13 fan, unit sizes 051 & 066, in. wg.

unit size

051

066 cfm

2900

3000

3100

3200

3300

3400

3500

3600

3700

3800

3900

4000

4100

4200

4300

4400

4500

4600

4700

4800

4900

5000

5100

3600

3700

3800

3900

4000

4100

4200

4300

4400

4500

4600

4700

4800

4900

5000

5100

5200

5300

5400

5500

5600

5700

5800

5900

6000

6100

6200

6300

6400

6500

6600

350/280

0.34

0.36

0.39

0.41

0.44

0.46

0.49

0.52

0.55

0.58

0.61

0.64

0.67

0.71

0.74

0.78

0.81

0.85

0.89

0.92

0.96

1.00

1.04

0.52

0.55

0.58

0.61

0.64

0.67

0.71

0.74

0.78

0.81

0.85

0.89

0.92

0.96

1.00

1.04

1.09

1.13

1.17

1.21

1.26

1.30

1.35

1.40

1.44

1.49

1.54

1.59

1.64

250/200

0.96

1.03

1.10

1.17

1.24

1.32

1.40

1.48

1.56

1.65

1.74

1.83

1.92

2.01

2.11

2.21

2.31

2.42

1.48

1.56

1.65

1.74

1.83

1.92

2.01

2.11

2.21

2.31

2.42

300/240

0.50

0.53

0.57

0.60

0.64

0.68

0.72

0.76

0.81

0.85

0.90

0.94

0.99

1.04

1.09

1.14

1.19

1.25

1.30

1.36

1.42

1.47

1.53

0.76

0.81

0.85

0.90

0.94

0.99

1.04

1.09

1.14

1.19

1.25

1.30

1.36

1.42

1.47

1.53

1.59

1.66

1.72

1.78

400/320

0.44

gas heat input/output (MBh)

500/400

600/480

0.92

0.96

1.00

1.04

0.52

0.55

0.58

0.61

0.64

0.67

0.71

0.74

0.78

0.81

0.46

0.49

0.52

0.55

0.58

0.61

0.64

0.67

0.71

0.74

0.78

0.81

0.85

0.89

0.85

0.89

0.92

0.96

1.00

1.04

1.09

1.13

1.17

1.21

1.26

1.30

1.35

1.40

1.44

1.49

1.54

1.59

1.64

1.70

1.75

0.70

0.73

0.77

0.80

0.84

0.88

0.92

0.96

1.00

1.04

1.08

0.70

0.73

0.77

0.80

0.84

0.88

0.92

0.96

1.00

1.04

1.08

1.13

1.17

1.22

1.26

1.31

1.36

1.41

1.46

1.51

1.56

1.61

1.66

1.72

1.77

1.83

1.02

1.06

1.11

1.15

1.19

1.24

1.29

1.33

1.38

1.43

1.48

1.53

1.58

1.63

1.69

1.74

1.80

1.02

1.06

700/560

1.25

1.30

1.34

1.39

1.43

1.48

1.53

1.58

1.63

800/640

1.94

MUA-PRC004-EN 45

46

Performance

Data airside pressure drop

Table PD-25. Electric heat with 15-11 fan, unit sizes 051 & 066, in. wg.

unit size

051

066

4800

4900

5000

5100

3600

3700

3800

3900

4000

3900

4000

4100

4200

4300

4400

4500

4600

4700

4100

4200

4300

4400

4500

4600

4700

4800

4900

5000 cfm

2900

3000

3100

3200

3300

3400

3500

3600

3700

3800

5100

5200

5300

5400

5500

5600

5700

5800

5900

6000

6100

6200

6300

6400

6500

6600

0.28

0.29

0.31

0.32

0.16

0.17

0.18

0.19

0.20

0.19

0.20

0.21

0.22

0.23

0.24

0.25

0.26

0.27

0.21

0.22

0.23

0.24

0.25

0.26

0.27

0.28

0.29

0.31

electric heat

0.10

0.11

0.12

0.13

0.13

0.14

0.15

0.16

0.17

0.18

0.32

0.33

0.34

0.36

0.37

0.38

0.40

0.41

0.43

0.44

0.46

0.47

0.49

0.50

0.52

0.53

0.23

0.24

0.25

0.26

0.13

0.14

0.14

0.15

0.16

0.15

0.16

0.17

0.18

0.19

0.19

0.20

0.21

0.22

0.17

0.18

0.19

0.19

0.20

0.21

0.22

0.23

0.24

0.25

no heat

0.08

0.09

0.10

0.10

0.11

0.12

0.12

0.13

0.14

0.14

0.26

0.27

0.28

0.29

0.30

0.31

0.33

0.34

0.35

0.36

0.37

0.39

0.40

0.41

0.42

0.44

MUA-PRC004-EN

Performance

Data airside pressure drop

Table PD-26. Electric heat with 18-13 fan, unit sizes 051 & 066, in. wg.

unit size

051

066 cfm

2900

3000

3100

3200

3300

3400

3500

3600

3700

3800

3900

4000

4100

4200

4300

4400

4500

4600

4700

4800

4900

5000

5100

3600

3700

3800

3900

4000

4100

4200

4300

4400

4500

4600

4700

4800

4900

5000

5100

5200

5300

5400

5500

5600

5700

5800

5900

6000

6100

6200

6300

6400

6500

6600 electric heat

0.06

0.07

0.07

0.07

0.08

0.08

0.09

0.09

0.10

0.11

0.11

0.12

0.12

0.13

0.13

0.14

0.15

0.15

0.16

0.17

0.17

0.18

0.19

0.09

0.10

0.11

0.11

0.12

0.12

0.13

0.13

0.14

0.15

0.15

0.16

0.17

0.17

0.18

0.19

0.20

0.20

0.21

0.22

0.23

0.24

0.24

0.25

0.26

0.27

0.28

0.29

0.30

0.31

0.32

no heat

0.04

0.05

0.05

0.05

0.05

0.06

0.06

0.07

0.07

0.07

0.08

0.08

0.08

0.09

0.09

0.10

0.10

0.11

0.11

0.12

0.12

0.13

0.13

0.07

0.07

0.07

0.08

0.08

0.08

0.09

0.09

0.10

0.10

0.11

0.11

0.12

0.12

0.13

0.13

0.14

0.14

0.15

0.15

0.16

0.16

0.17

0.17

0.18

0.19

0.19

0.20

0.21

0.21

0.22

MUA-PRC004-EN 47

Performance

Data unit capacity total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent

Table PD-27. Size 031 cooling capacity without reheat installed, MBh cfm

1800

1900

2000

2100

2200

2300

2400

2500

2600

2700

2800

2900

3000

3100

189.76

79.00

192.46

79.57

195.01

80.04

197.42

80.41

199.70

80.70

95/76

173.48

74.21

177.18

75.45

180.63

76.51

183.86

77.46

186.90

78.30

201.88

80.91

203.96

81.05

205.96

81.14

207.87

81.18

212.29

132.38

215.31

134.60

218.15

136.67

220.81

138.59

223.32

140.39

85/80

193.74

118.48

197.98

121.69

201.93

124.66

205.62

127.43

209.06

129.99

225.69

142.06

227.93

143.63

230.05

145.09

232.05

146.46

204.41

119.24

207.35

121.17

210.12

122.94

212.73

124.59

215.18

126.11

85/78

186.37

107.02

190.49

109.87

194.33

112.49

197.91

114.92

201.26

117.17

217.50

127.53

219.69

128.83

221.77

130.05

223.74

131.17

196.79

106.47

199.66

108.09

202.36

109.58

204.90

110.94

207.30

112.20

85/76

179.28

95.94

183.27

98.41

187.00

100.69

190.48

102.78

193.74

104.70

209.57

113.34

211.71

114.39

213.74

115.35

215.67

116.23

196.97

91.11

199.69

91.86

202.24

92.48

204.66

93.03

206.94

93.51

dry-bulb / wet-bulb temperature (°F)

95/78 95/80 105/76 105/78

180.28

84.98

187.35

96.11

168.58

53.76

174.16

63.66

184.10

86.58

187.65

87.97

190.97

89.18

194.07

90.22

191.29

98.05

194.95

99.78

198.36

101.31

201.55

102.66

172.35

54.21

175.87

54.49

179.16

54.63

182.24

54.63

177.98

64.34

181.58

64.44

184.95

64.84

188.10

65.10

209.10

93.90

211.15

94.20

213.09

94.42

214.94

94.58

204.52

103.85

207.31

104.88

209.92

105.77

212.38

106.54

214.69

107.20

216.88

107.75

218.93

108.20

220.88

108.57

222.72

108.85

185.14

54.51

187.86

54.27

190.42

53.94

192.84

53.51

195.12

53.01

197.28

52.43

199.33

51.77

201.27

51.07

203.11

50.30

203.42

64.22

205.50

63.77

207.47

63.25

209.33

62.67

191.05

65.22

193.83

65.22

196.45

65.11

198.91

64.90

201.23

64.60

180.46

30.99

183.02

29.81

185.43

28.55

187.71

27.21

189.85

25.80

115/76

164.83

35.19

168.39

34.62

171.71

33.90

174.82

33.04

177.73

32.07

191.88

24.33

193.80

22.80

195.61

21.23

197.37

19.85

197.21

76.63

200.02

76.43

202.68

76.54

205.18

76.54

207.54

76.46

105/80

180.52

73.84

184.24

74.69

187.74

75.36

191.03

75.88

194.17

76.29

209.77

76.28

211.88

76.02

213.87

75.69

215.76

75.29

191.97

52.05

194.64

51.32

197.14

50.49

199.49

49.56

201.71

48.56

115/80

175.65

53.70

179.38

53.69

182.86

53.50

186.11

53.15

189.14

52.66

203.80

47.48

205.78

46.34

207.65

45.14

209.43

43.89

186.10

41.39

188.72

40.44

191.17

39.39

193.49

38.26

195.67

37.05

115/78

170.12

44.31

173.77

44.02

177.17

43.57

180.35

42.97

183.32

42.24

197.73

35.78

199.68

34.45

201.53

33.06

203.28

31.63

Table PD-28. Size 031 cooling capacity with reheat installed, MBh cfm

1800

1900

2000

2100

2200

2300

2400

2500

2600

2700

2800

2900

3000

3100 total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent

95/76

177.53

75.51

181.40

76.86

185.03

78.03

188.43

79.02

191.63

79.86

194.64

80.56

197.49

81.14

200.18

81.60

202.75

81.97

205.20

82.24

207.54

82.45

209.80

82.79

211.92

82.98

213.94

83.10

85/80

196.07

119.54

200.41

122.81

204.44

125.83

208.21

128.64

211.72

131.24

215.01

133.66

218.08

135.91

220.97

138.00

223.69

139.94

226.25

141.76

228.66

143.44

230.93

145.02

233.08

146.48

235.12

147.85

85/78

188.99

108.09

193.20

110.98

197.12

113.65

200.78

116.11

204.20

118.39

207.41

120.49

210.41

122.43

213.23

124.22

215.89

125.88

218.39

127.41

220.75

128.83

222.98

130.13

225.09

131.34

227.08

132.45

85/76

182.16

96.98

186.24

99.50

190.05

101.81

193.60

103.93

196.93

105.88

200.05

107.66

202.98

109.29

205.73

110.78

208.32

112.15

210.76

113.40

213.07

114.54

215.25

115.57

217.31

116.52

219.27

117.38

dry-bulb / wet-bulb temperature (°F)

95/78 95/80 105/76 105/78

184.02

86.16

187.99

87.84

190.84

97.29

194.91

99.28

174.42

55.83

178.41

56.41

179.76

65.23

183.84

66.11

191.69

89.32

195.15

90.61

198.38

91.72

201.42

92.68

204.28

93.50

206.97

94.19

209.51

94.76

211.91

95.23

198.70

101.05

202.22

102.61

205.52

104.01

208.60

105.25

211.50

106.33

214.21

107.27

216.77

108.08

219.18

108.78

182.14

56.83

185.64

57.10

188.92

57.22

192.00

57.21

194.90

57.09

197.64

56.86

200.22

56.53

202.65

56.11

187.66

66.80

191.22

67.33

194.57

67.70

197.71

67.94

200.66

68.05

203.44

68.04

206.06

67.93

208.53

67.72

214.18

95.60

216.35

95.88

218.40

96.08

220.36

96.21

221.46

109.36

223.61

109.85

225.65

110.25

227.60

110.57

204.96

55.61

207.14

55.04

209.21

54.41

211.18

53.71

210.87

67.42

213.08

67.04

215.17

66.60

217.17

66.09

48

105/80

185.68

75.55

189.67

76.45

193.44

77.18

197.03

77.76

200.45

78.45

203.64

78.93

206.63

79.26

209.45

79.47

212.11

79.58

214.61

79.57

216.98

79.47

219.22

79.29

221.34

79.03

223.35

78.71

115/76

172.31

37.93

176.19

37.55

179.82

37.02

183.23

36.34

186.43

35.54

189.44

34.62

192.27

33.60

194.93

32.48

197.45

31.28

199.83

30.01

202.08

28.66

204.22

27.25

206.24

25.79

208.16

24.28

115/78

177.36

47.08

181.34

46.98

185.05

46.72

188.52

46.30

191.78

45.74

194.84

45.05

197.71

44.25

200.42

43.35

202.97

42.36

205.39

41.29

207.67

40.14

209.83

38.92

211.87

37.65

213.82

36.32

115/80

182.67

56.49

186.72

56.67

190.50

56.67

194.04

56.50

197.35

56.19

200.46

55.73

203.38

55.15

206.12

54.47

208.71

53.68

211.15

52.81

213.46

51.85

215.64

50.83

217.72

49.73

219.68

48.58

MUA-PRC004-EN

Performance

Data unit capacity

Table PD-29. Size 031 reheat data, MBh dry-bulb / wet-bulb temperature (°F) cfm 55/48 55/50 55/52 65/56 65/58 65/60 75/66 75/68 75/70 85/76 85/78 85/80 95/76 95/78 95/80 105/76 105/78 105/80 115/76 115/78 115/80

1800 39.3

40.9

42.4

45.4

46.9

48.4

52.8

54.2

55.7

60.0

61.4

62.8

59.9

61.2

62.6

62.9

62.8

63.2

68.1

67.9

67.8

1900 39.7

41.2

42.8

45.8

47.3

48.8

53.1

54.6

56.1

60.3

61.8

63.2

60.3

61.6

63.0

63.9

63.7

63.8

69.2

69.0

68.8

2000 40.0

41.6

43.1

46.1

47.6

49.1

53.5

54.9

56.4

60.7

62.1

63.6

60.7

61.9

63.3

64.8

64.6

64.5

70.2

70.0

69.8

2100 40.3

41.9

43.4

46.4

47.9

49.4

53.8

55.2

56.7

61.0

62.4

63.9

61.2

62.3

63.6

65.6

65.4

65.2

71.1

70.9

70.7

2200 40.6

42.1

43.7

46.7

48.2

49.7

54.0

55.5

57.0

61.2

62.7

64.1

61.5

62.6

63.9

66.3

66.2

66.0

71.9

71.7

71.5

2300 40.8

42.4

43.9

46.9

48.4

49.9

54.3

55.8

57.2

61.5

62.9

64.4

61.9

62.9

64.2

67.0

66.9

66.7

72.7

72.5

72.3

2400 41.1

42.6

44.1

47.2

48.6

50.1

54.5

56.0

57.5

61.7

63.2

64.6

62.3

63.2

64.4

67.7

67.5

67.3

73.5

73.2

73.0

2500 41.3

42.8

44.3

47.4

48.8

50.3

54.7

56.2

57.7

61.9

63.4

64.8

62.7

63.5

64.7

68.3

68.1

67.9

74.2

73.9

73.7

2600 41.5

43.0

44.5

47.6

49.0

50.5

54.9

56.4

57.9

62.1

63.6

65.0

63.1

63.8

64.9

68.9

68.7

68.5

74.8

74.6

74.3

2700 41.7

43.1

44.7

47.8

49.2

50.7

55.0

56.5

58.0

62.3

63.8

65.2

63.5

64.1

65.1

69.4

69.2

69.0

75.4

75.2

74.9

2800 41.9

43.3

44.9

48.0

49.3

50.9

55.2

56.7

58.2

62.4

63.9

65.4

63.9

64.3

65.3

70.0

69.8

69.5

76.0

75.8

75.5

2900 42.1

43.5

45.0

48.2

49.5

51.0

55.3

56.8

58.3

62.6

64.1

65.5

64.4

64.6

65.5

70.4

70.2

70.0

76.5

76.3

76.0

3000 42.2

43.6

45.2

48.3

49.6

51.1

55.5

57.0

58.5

62.7

64.2

65.7

64.8

64.9

65.7

70.9

70.7

70.5

77.1

76.8

76.6

3100 42.4

43.7

45.3

48.5

49.8

51.3

55.6

57.1

58.6

62.9

64.3

65.8

65.1

65.1

65.9

71.3

71.1

70.9

77.5

77.3

77.0

Table PD-30. Size 031 condenser reheat max temperature rise,°F dry-bulb / wet-bulb temperature (°F) cfm 55/48 55/50 55/52 65/56 65/58 65/60 75/66 75/68 75/70 85/76 85/78 85/80 95/76 95/78 95/80 105/76 105/78 105/80 115/76 115/78 115/80

1800 20.1

20.9

21.7

23.2

24.0

24.7

26.9

27.7

28.4

30.4

31.1

31.8

30.4

31.0

31.7

1900 19.2

20.0

20.7

22.2

22.9

23.6

25.7

26.4

27.1

29.0

29.7

30.3

29.0

29.6

30.2

2000 18.4

19.1

19.9

21.2

21.9

22.6

24.5

25.2

25.8

27.7

28.3

28.9

27.7

28.2

28.8

2100 17.7

18.4

19.0

20.3

21.0

21.6

23.5

24.1

24.7

26.5

27.1

27.7

26.6

27.0

27.6

2200 17.0

17.6

18.3

19.5

20.1

20.7

22.5

23.1

23.7

25.4

26.0

26.5

25.5

25.9

26.4

2300 16.3

17.0

17.6

18.8

19.3

19.9

21.6

22.2

22.8

24.4

24.9

25.5

24.5

24.9

25.4

2400 15.8

16.3

16.9

18.1

18.6

19.2

20.8

21.3

21.9

23.4

23.9

24.5

23.6

24.0

24.4

31.9

30.7

29.6

28.5

27.5

26.6

25.7

31.8

30.6

29.4

28.4

27.4

26.5

25.6

32.0

30.6

29.3

28.3

27.3

26.3

25.5

34.6

33.3

32.0

30.9

29.8

28.8

27.9

34.5

33.1

31.9

30.8

29.7

28.7

27.8

34.3

33.0

31.8

30.6

29.6

28.6

27.6

2500 15.2

15.8

16.3

17.4

17.9

18.5

20.0

20.6

21.1

22.6

23.1

23.5

22.8

23.1

23.5

2600 14.7

15.2

15.8

16.8

17.3

17.8

19.3

19.8

20.3

21.7

22.2

22.7

22.1

22.3

22.6

2700 14.2

14.7

15.2

16.3

16.7

17.2

18.7

19.1

19.6

21.0

21.5

21.9

21.4

21.6

21.9

2800 13.8

14.2

14.7

15.7

16.2

16.7

18.0

18.5

19.0

20.3

20.7

21.2

20.8

20.9

21.1

2900 13.4

13.8

14.3

15.3

15.7

16.1

17.5

17.9

18.4

19.6

20.1

20.5

20.2

20.2

20.5

3000 13.0

13.4

13.8

14.8

15.2

15.6

16.9

17.3

17.8

19.0

19.4

19.8

19.6

19.6

19.8

3100 12.6

13.0

13.4

14.4

14.7

15.2

16.4

16.8

17.2

18.4

18.8

19.2

19.1

19.0

19.2

24.9

24.8

24.7

27.0

26.9

26.8

24.1

24.0

23.9

26.2

26.1

26.0

23.4

23.3

23.2

25.4

25.3

25.2

22.7

22.6

22.5

24.7

24.6

24.5

22.1

22.0

21.9

24.0

23.9

23.8

21.5

21.4

21.3

23.4

23.3

23.1

20.9

20.8

20.7

22.8

22.6

22.5

Table PD-31. Size 031 design supply air dew point, cfm dry-bulb

(°F)

85

95

105

115 wet-bulb

(°F)

76

78

80

76

78

80

76

78

80

76

78

80

46

1896

1863

1898

1996

48

2069

1868

2037

1827

2098

1813

2211

1893

— design supply air dew point (°F)

50 52 54 56

2267

2038

1840

2497

2231

2005

2767

2455

2194

3090

2717

2412

2239

1995

2332

2003

2466

2093

1801

2476

2188

1957

2611

2223

1926

2779

2330

1989

2762

2414

2143

2952

2483

2122

2615

2210

2969

2474

2683

2360

2798

2369

58

3031

2668

3010

2617

2663

2797

60

2972

2928

3024

62

MUA-PRC004-EN 49

Performance

Data unit capacity

Table PD-32. Size 040 cooling capacity without reheat installed, MBh cfm 85/76 85/78 85/80 95/76 dry-bulb / wet-bulb temperature (°F)

95/78 95/80 105/76 105/78

2200

2300

2400

2500

2600

2700

2800

2900

3000

3100

3200

3300

3400

3500

3600

3700

3800

3900

4000 total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent

242.98

131.97

245.67

133.47

248.22

134.85

250.64

136.13

252.95

137.33

255.16

138.43

257.26

139.46

259.26

140.41

219.44

117.88

223.41

120.35

227.15

122.65

230.68

124.80

234.01

126.79

237.16

128.65

240.15

130.37

261.18

141.29

263.01

142.10

264.77

142.85

266.45

143.54

252.28

147.83

255.03

149.60

257.63

151.26

260.11

152.82

262.47

154.28

264.71

155.64

266.86

156.92

268.90

158.12

228.12

131.46

232.20

134.29

236.05

136.94

239.67

139.42

243.09

141.74

246.33

143.90

249.38

145.93

270.85

159.24

272.71

160.29

274.50

161.28

276.21

162.20

261.88

164.10

264.68

166.16

267.34

168.09

269.87

169.92

272.27

171.64

274.56

173.26

276.73

174.79

278.81

176.23

237.12

145.48

241.32

148.67

245.27

151.66

248.98

154.47

252.48

157.11

255.79

159.58

258.92

161.91

280.79

177.60

282.69

178.88

284.50

180.10

286.23

181.25

234.08

96.96

236.57

97.29

238.93

97.54

241.17

97.70

243.32

97.84

245.38

97.94

247.35

97.99

249.23

97.97

212.23

91.23

215.93

92.48

219.40

93.56

222.68

94.49

225.77

95.29

228.70

95.96

231.46

96.51

251.04

97.90

252.78

97.77

254.45

97.61

256.05

97.40

243.02

112.34

245.55

112.96

247.96

113.47

250.25

113.89

252.43

114.22

254.50

114.47

256.48

114.64

258.36

114.75

220.60

104.45

224.39

106.03

227.97

107.45

231.33

108.70

234.51

109.81

237.50

110.78

240.34

111.62

260.16

114.79

261.88

114.77

263.52

114.69

265.10

114.56

252.23

128.13

254.82

129.01

257.28

129.79

259.62

130.47

261.84

131.06

263.94

131.55

265.95

131.97

267.87

132.32

229.27

118.07

233.17

120.00

236.84

121.74

240.29

123.32

243.53

124.73

246.60

125.99

249.49

127.12

269.70

132.59

271.45

132.80

273.11

132.94

274.70

133.04

227.39

64.73

230.02

64.37

232.53

63.94

234.91

63.44

237.18

62.86

239.36

62.23

241.44

61.53

243.42

60.79

204.86

65.34

208.50

65.65

212.00

65.85

215.42

66.01

218.65

65.25

221.72

65.17

224.62

65.00

245.33

60.00

247.16

59.17

248.91

58.29

250.59

57.38

234.30

78.56

236.99

78.42

239.54

77.43

241.95

77.13

244.26

76.76

246.46

76.32

248.56

75.82

250.57

75.26

212.50

77.44

216.09

77.95

219.49

78.32

222.72

78.55

225.79

78.68

228.73

78.71

231.56

78.67

252.49

74.65

254.33

73.99

256.10

73.29

257.79

72.55

242.26

92.65

244.75

92.56

247.14

92.39

249.43

92.15

251.63

91.86

253.77

91.52

255.85

91.15

257.89

90.76

105/80

220.74

90.34

224.35

91.01

227.75

91.56

230.97

92.02

234.01

92.35

236.90

92.55

239.65

92.65

259.86

89.57

261.72

89.09

263.50

88.56

265.20

87.99

229.32

48.27

231.88

47.22

234.33

46.10

236.66

44.91

238.87

43.66

240.99

42.35

243.01

40.99

244.95

39.58

115/78

206.97

52.89

210.72

52.59

214.27

52.15

217.61

51.59

220.78

50.91

223.77

50.12

226.62

49.24

246.80

38.13

248.57

36.64

250.27

35.12

251.90

33.57

222.65

35.55

225.18

34.29

227.60

32.96

229.89

31.57

232.09

30.12

234.18

28.62

236.18

27.08

238.10

25.49

115/76

200.66

41.86

204.34

41.29

207.82

40.60

211.11

39.78

214.23

38.86

217.18

37.85

219.99

36.74

239.93

23.86

241.76

22.80

243.54

21.89

245.28

20.98

236.21

61.27

238.81

60.43

241.28

59.51

243.63

58.51

245.87

57.45

248.01

56.33

250.06

55.16

252.01

53.93

115/80

213.53

64.21

217.34

64.18

220.95

64.00

224.35

63.68

227.56

63.24

230.60

62.68

233.48

62.02

253.87

52.66

255.66

51.34

257.37

49.99

259.02

48.61

50 MUA-PRC004-EN

Performance

Data unit capacity

Table PD-33. Size 040 cooling capacity with reheat installed, MBh cfm 85/76 85/78 85/80 95/76 dry-bulb / wet-bulb temperature (°F)

95/78 95/80 105/76 105/78

2200

2300

2400

2500

2600

2700

2800

2900

3000

3100

3200

3300

3400

3500

3600

3700

3800

3900

4000 total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent

246.80

133.36

249.58

134.87

252.22

136.28

254.72

137.59

257.11

138.80

259.38

139.91

261.55

140.95

263.62

141.90

222.46

118.93

226.56

121.47

230.43

123.83

234.08

126.02

237.53

128.06

240.79

129.96

243.88

131.72

265.60

142.78

267.49

143.59

269.30

144.33

271.03

145.02

255.57

149.15

258.41

150.96

261.10

152.66

263.66

154.24

266.09

155.73

268.41

157.11

270.62

158.41

272.73

159.62

230.61

132.42

234.83

135.31

238.80

138.02

242.55

140.56

246.08

142.93

249.42

145.14

252.58

147.21

274.74

160.75

276.66

161.81

278.50

162.80

280.26

163.73

264.57

165.31

267.46

167.41

270.21

169.39

272.82

171.26

275.30

173.01

277.65

174.66

279.90

176.22

282.04

177.69

239.01

146.28

243.34

149.54

247.42

152.60

251.25

155.47

254.87

158.17

258.28

160.70

261.51

163.08

284.09

179.07

286.04

180.38

287.91

181.61

289.70

182.78

239.91

98.90

242.58

99.34

245.12

99.69

247.55

99.95

249.87

100.12

252.10

100.23

254.23

100.26

256.27

100.24

216.71

92.44

220.61

93.80

224.28

94.99

227.76

96.03

231.04

96.94

234.15

97.71

237.10

98.36

258.24

100.16

260.14

100.02

261.97

99.84

263.73

99.62

248.17

113.93

250.86

114.61

253.42

115.20

255.85

115.68

258.17

116.08

260.38

116.39

262.49

116.62

264.51

116.79

224.59

105.57

228.58

107.23

232.33

108.71

235.86

110.02

239.20

111.17

242.35

112.21

245.34

113.13

266.44

116.89

268.30

116.93

270.08

116.91

271.79

116.84

256.82

129.54

259.54

130.45

262.12

131.25

264.57

131.95

266.90

132.55

269.13

133.09

271.25

133.54

273.27

133.92

232.71

119.09

236.81

121.09

240.66

122.91

244.28

124.54

247.69

126.01

250.91

127.33

253.94

128.50

275.21

134.23

277.05

134.47

278.82

134.65

280.52

134.77

236.16

68.29

239.00

68.05

241.70

67.73

244.27

67.34

246.73

66.87

249.08

66.33

251.32

65.73

253.47

65.08

211.69

67.18

215.78

67.60

219.64

67.95

223.30

68.24

226.77

68.42

230.06

68.48

233.19

68.43

255.53

64.37

257.50

63.62

259.40

62.82

261.21

61.98

242.78

81.34

245.64

81.32

248.37

81.21

250.96

81.02

253.44

80.75

255.80

80.40

258.07

80.00

260.23

79.53

218.58

79.36

222.51

79.95

226.25

80.40

229.82

80.72

233.26

80.93

236.59

81.06

239.77

81.27

262.30

79.00

264.29

78.42

266.19

77.79

268.02

77.12

233.47

40.04

236.27

38.93

238.94

37.75

241.49

36.50

243.93

35.19

246.26

33.82

248.48

32.40

250.61

30.93

115/76

209.29

45.08

213.32

44.71

217.14

44.21

220.75

43.58

224.18

42.84

227.43

42.00

230.52

41.06

252.66

29.41

254.61

27.86

256.49

26.27

258.29

24.64

249.74

95.09

252.53

95.06

255.23

94.96

257.86

94.81

260.37

94.89

262.75

94.74

265.02

94.51

267.20

94.22

105/80

226.08

92.13

230.02

92.99

233.75

93.68

237.27

94.21

240.62

94.61

243.80

94.88

246.83

95.04

269.28

93.88

271.28

93.47

273.19

93.01

275.02

92.51

239.76

52.76

242.59

51.86

245.28

50.89

247.85

49.83

250.31

48.71

252.65

47.53

254.89

46.30

257.04

45.00

115/78

215.28

56.13

219.37

56.02

223.24

55.78

226.90

55.40

230.37

54.90

233.66

54.29

236.79

53.57

259.09

43.67

261.06

42.28

262.94

40.86

264.76

39.41

246.27

65.74

249.12

65.05

251.84

64.28

254.43

63.42

256.90

62.49

259.25

61.49

261.51

60.44

263.66

59.32

115/80

221.52

67.45

225.66

67.61

229.58

67.62

233.28

67.49

236.79

67.22

240.12

66.84

243.27

66.34

265.72

58.16

267.70

56.95

269.60

55.69

271.42

54.40

MUA-PRC004-EN 51

Performance

Data unit capacity cfm

2200

2300

2400

2500

2600

2700

2800

2900

3000

3100

3200

3300

3400

3500

3600

3700

3800

3900

4000

Table PD-34. Size 040 reheat data, MBh dry-bulb / wet-bulb temperature (°F)

55/48 55/50 55/52 65/56 65/58 65/60 75/66 75/68 75/70 85/76 85/78 85/80 95/76 95/78 95/80 105/76 105/78 105/80 115/76 115/78 115/80

58.8

60.8

62.7

66.7

68.8

71.0

77.4

79.7

82.0

88.5

90.7

92.9

88.2

90.5

92.7

90.2

91.2

92.8

97.6

97.5

59.3

61.2

63.2

67.2

69.3

71.5

78.0

80.2

82.5

89.0

91.3

93.5

88.8

91.0

93.2

91.4

92.0

93.5

98.9

98.8

97.4

98.7

59.7

61.7

63.7

67.7

69.8

72.0

78.5

80.7

83.0

89.5

91.8

94.0

89.3

91.5

93.7

92.6

92.8

94.1

100.2

100.1

100.0

60.1

62.1

64.1

68.1

70.2

72.4

78.9

81.2

83.5

90.0

92.3

94.5

89.9

92.0

94.2

93.6

93.7

94.8

101.4

101.3

101.2

60.5

62.4

64.4

68.5

70.6

72.8

79.3

81.6

83.9

90.4

92.7

94.9

90.3

92.4

94.6

94.7

94.5

95.4

102.6

102.4

102.3

60.8

62.8

64.8

68.9

71.0

73.2

79.7

82.0

84.3

90.8

93.1

95.3

90.8

92.8

95.0

95.6

95.5

96.1

103.6

103.5

103.4

61.1

63.1

65.1

69.2

71.4

73.6

80.1

82.4

84.6

91.2

93.5

95.7

91.2

93.2

95.4

96.6

96.4

96.7

104.7

104.5

104.4

61.4

63.4

65.4

69.5

71.7

73.9

80.4

82.7

85.0

91.6

93.8

96.1

91.7

93.6

95.8

97.4

97.3

97.4

105.6

105.5

105.3

61.7

63.7

65.7

69.8

72.0

74.2

80.8

83.0

85.3

91.9

94.2

96.4

92.1

94.0

96.1

98.3

98.1

98.0

106.6

106.4

106.2

61.9

64.0

66.0

70.1

72.3

74.5

81.1

83.3

85.6

92.2

94.5

96.7

92.5

94.3

96.4

99.1

98.9

98.7

107.5

107.3

107.1

62.2

64.2

66.3

70.4

72.6

74.8

81.3

83.6

85.9

92.5

94.8

97.0

92.9

94.7

96.7

99.8

99.7

99.5

108.3

108.1

107.9

62.4

64.4

66.5

70.6

72.8

75.0

81.6

83.9

86.2

92.8

95.0

97.3

93.3

95.0

97.0

100.5

100.4

100.2

109.1

108.9

108.7

62.6

64.7

66.7

70.9

73.1

75.3

81.9

84.1

86.4

93.0

95.3

97.6

93.6

95.3

97.3

101.2

101.1

100.9

109.9

109.7

109.5

62.9

64.9

67.0

71.1

73.3

75.5

82.1

84.4

86.7

93.3

95.6

97.8

94.0

95.6

97.5

101.9

101.7

101.5

110.6

110.4

110.2

63.1

65.1

67.2

71.3

73.5

75.7

82.3

84.6

86.9

93.5

95.8

98.0

94.4

95.9

97.8

102.5

102.3

102.2

111.3

111.1

110.9

63.3

65.3

67.4

71.6

73.7

75.9

82.5

84.8

87.1

93.7

96.0

98.3

94.8

96.1

98.0

103.1

102.9

102.8

112.0

111.8

111.6

63.5

65.5

67.5

71.8

73.9

76.1

82.7

85.0

87.3

93.9

96.2

98.5

95.1

96.4

98.3

103.7

103.5

103.3

112.7

112.4

112.2

63.6

65.6

67.7

72.0

74.1

76.3

82.9

85.2

87.5

94.1

96.4

98.7

95.5

96.7

98.5

104.3

104.1

103.9

113.3

113.1

112.8

63.8

65.8

67.9

72.2

74.3

76.5

83.1

85.4

87.7

94.3

96.6

98.9

95.9

97.0

98.7

104.8

104.6

104.4

113.9

113.7

113.4

Table PD-35. Size 040 condenser reheat max temperature rise, °F dry-bulb / wet-bulbtemperature (°F) cfm 55/48 55/50 55/52 65/56 65/58 65/60 75/66 75/68 75/70 85/76 85/78 85/80 95/76 95/78 95/80 105/76 105/78 105/80 115/76 115/78 115/80

2200 24.7

25.5

26.3

27.9

28.8 29.7

32.3

33.2

34.2

36.8

37.6 38.5

36.7

37.5

38.4

37.5

37.8

38.4

2300 23.8

24.5

25.3

26.9

27.7 28.6

31.1

32.0

32.9

35.4

36.2 37.0

35.3

36.1

36.9

36.3

36.5

37.0

2400 22.9

23.7

24.4

26.0

26.8 27.6

30.0

30.8

31.7

34.1

34.9 35.7

34.0

34.8

35.6

35.2

35.3

35.7

2500 22.2

22.9

23.6

25.1

25.8 26.6

29.0

29.8

30.6

32.9

33.6 34.4

32.8

33.5

34.3

34.2

34.1

34.5

2600 21.4

22.1

22.8

24.2

25.0 25.7

28.0

28.8

29.5

31.7

32.5 33.2

31.7

32.4

33.1

33.2

33.1

33.4

40.5

39.3

38.1

37.0

36.0

40.4

39.2

38.0

36.9

35.9

40.4

39.1

37.9

36.8

35.8

2700 20.7

21.4

22.1

23.5

24.2 24.9

27.1

27.8

28.6

30.7

31.4 32.1

30.7

31.3

32.0

32.3

32.2

32.3

2800 20.1

20.8

21.4

22.7

23.4 24.1

26.2

26.9

27.7

29.7

30.4 31.1

29.7

30.3

31.0

31.4

31.3

31.4

2900 19.5

20.1

20.8

22.0

22.7 23.4

25.4

26.1

26.8

28.8

29.4 30.1

28.8

29.4

30.0

30.6

30.5

30.5

3000 18.9

19.5

20.2

21.4

22.1 22.7

24.7

25.3

26.0

27.9

28.5 29.2

28.0

28.5

29.1

29.8

29.7

29.7

3100 18.4

19.0

19.6

20.8

21.4 22.1

23.9

24.6

25.2

27.1

27.7 28.3

27.2

27.7

28.2

29.1

29.0

28.9

3200 17.9

18.5

19.1

20.2

20.8 21.4

23.3

23.9

24.5

26.3

26.9 27.5

26.4

26.9

27.4

28.4

28.3

28.2

3300 17.4

18.0

18.5

19.7

20.3 20.9

22.6

23.2

23.9

25.6

26.2 26.7

25.7

26.1

26.7

27.7

27.6

27.5

3400 17.0

17.5

18.1

19.2

19.7 20.3

22.0

22.6

23.2

24.9

25.5 26.0

25.0

25.4

25.9

27.1

27.0

26.9

3500 16.5

17.1

17.6

18.7

19.2 19.8

21.5

22.0

22.6

24.2

24.8 25.3

24.4

24.8

25.2

26.5

26.4

26.3

3600 16.1

16.6

17.2

18.2

18.7 19.3

20.9

21.5

22.0

23.6

24.1 24.7

23.8

24.2

24.6

25.9

25.8

25.7

3700 15.7

16.2

16.7

17.8

18.3 18.8

20.4

20.9

21.5

23.0

23.5 24.1

23.3

23.6

24.0

25.3

25.2

25.1

3800 15.4

15.8

16.3

17.3

17.8 18.4

19.9

20.4

21.0

22.5

23.0 23.5

22.7

23.0

23.4

24.8

24.7

24.6

3900 15.0

15.5

16.0

16.9

17.4 17.9

19.4

19.9

20.5

21.9

22.4 22.9

22.2

22.5

22.9

24.3

24.2

24.1

4000 14.7

15.1

15.6

16.6

17.0 17.5

19.0

19.5

20.0

21.4

21.9 22.4

21.8

22.0

22.3

23.8

23.7

23.6

35.0

34.1

33.2

32.4

31.6

30.8

30.1

29.4

28.8

28.1

27.5

27.0

26.4

25.9

34.9

34.0

33.1

32.3

31.5

30.7

30.0

29.3

28.7

28.0

27.4

26.9

26.3

25.8

34.8

33.9

33.0

32.2

31.4

30.6

29.9

29.2

28.5

27.9

27.3

26.7

26.2

25.7

Table PD-36. SIze 040 design supply air dew point, cfm drybulb

(°F)

85

95

105

115

76

78

80

76

78

80 wetbulb

(°F)

76

78

80

76

78

80

2271

2387

46

2329

2280

2509

2200

2648

2260

48

2539

2291

2491

2238

2792

2410

2958

2503

50

2780

2497

2252

2734

2441

3127

2658

2343

3334

2789

2375 design supply air dew point (°F)

52 54 56

3058

2731

2452

3018

2673

2395

3385

3002

2680

3358

2945

2620

3776

3319

2944

3772

3268

2881

3535

2969

2573

3804

3133

2641

3345

2845

3556

2958

3812

3174

3346

58

3698

3252

3658

3188

60

3620

3560

3609

3833

62

52 MUA-PRC004-EN

Performance

Data unit capacity total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent

314.81

170.17

317.15

171.42

319.39

172.60

321.56

173.72

323.65

174.78

325.67

175.78

327.61

176.72

329.49

177.62

331.31

178.46

333.07

179.26

334.77

180.01

292.38

157.29

295.62

159.22

298.72

161.06

301.69

162.79

304.55

164.44

307.24

165.98

309.87

167.45

312.39

168.85

85/76

278.02

148.46

281.82

150.83

285.49

153.09

289.01

155.25

Table PD-37. Size 051 cooling capacity without reheat installed, MBh cfm

2900

3000

3100

3200

3300

3400

3500

3600

3700

3800

3900

4000

4100

4200

4300

4400

4500

4600

4700

4800

4900

5000

5100

339.28

212.46

341.71

214.22

344.05

215.91

346.29

217.52

348.46

219.06

350.55

220.54

352.56

221.95

354.51

223.31

356.39

224.61

358.20

225.85

359.95

227.04

326.87

191.05

329.26

192.56

331.55

194.00

333.76

195.37

335.89

196.67

337.95

197.91

339.93

199.09

341.85

200.22

343.69

201.29

345.48

202.32

347.18

203.27

303.93

175.90

307.26

178.15

310.39

180.27

313.43

182.29

316.34

184.22

319.13

186.06

321.82

187.81

324.39

189.47

dry-bulb / wet-bulb temperature (°F)

85/78 85/80 95/76 95/78

289.08

165.70

300.62

183.52

268.58

114.49

279.28

131.30

293.05

168.44

296.84

171.05

300.46

173.54

304.71

186.62

308.61

189.57

312.29

192.37

272.15

115.70

275.56

116.80

278.81

117.79

282.96

132.84

286.47

134.27

289.83

135.57

315.84

195.04

319.23

197.59

322.47

200.03

325.58

202.35

328.55

204.56

331.41

206.68

334.12

208.68

336.75

210.61

281.93

118.67

284.92

119.46

287.77

120.16

290.48

120.75

293.09

121.27

295.60

121.71

298.01

122.09

300.33

122.39

292.99

136.74

296.04

137.82

298.96

138.80

301.76

139.69

304.43

140.48

307.00

141.20

309.47

141.83

311.83

142.40

302.56

122.62

304.70

122.80

306.76

122.92

308.75

122.98

310.66

122.99

312.52

123.05

314.33

123.10

316.08

123.11

317.77

123.08

319.41

123.01

321.00

122.92

314.11

142.89

316.29

143.31

318.40

143.67

320.43

143.98

322.38

144.23

324.26

144.42

326.08

144.57

327.81

144.65

329.49

144.70

331.13

144.72

332.70

144.69

326.00

163.64

328.22

164.31

330.36

164.91

332.43

165.45

334.41

165.93

336.32

166.35

338.17

166.72

339.94

167.04

341.66

167.31

343.32

167.54

344.92

167.73

304.44

155.33

307.56

156.71

310.55

157.98

313.39

159.13

316.13

160.20

318.75

161.18

321.26

162.08

323.68

162.90

95/80

290.40

148.63

294.15

150.50

297.74

152.24

301.17

153.85

301.95

97.61

304.19

97.32

306.39

97.00

308.54

96.67

310.66

96.32

312.76

95.97

314.79

94.01

316.71

93.60

318.57

93.16

320.37

92.69

322.12

92.20

281.37

98.19

284.27

98.34

287.05

98.41

289.75

98.42

292.35

98.36

294.86

98.25

297.29

98.07

299.65

97.86

105/78

268.53

96.68

271.96

97.21

275.21

97.63

278.35

97.95

293.51

79.62

295.85

79.29

298.10

78.92

300.28

78.50

302.39

78.05

304.42

77.56

306.39

77.03

308.30

76.47

310.14

75.88

311.93

75.26

313.67

74.62

271.67

82.27

274.64

82.28

277.56

82.24

280.41

82.17

283.21

82.08

285.99

81.97

288.60

80.13

291.09

79.89

105/76

258.64

81.51

262.07

81.82

265.38

82.04

268.58

82.19

288.48

43.37

290.76

42.28

292.95

41.16

295.07

40.00

297.12

38.81

299.10

37.59

301.02

36.34

302.88

35.07

304.68

33.78

306.42

32.46

308.11

31.15

266.94

50.35

270.01

49.68

272.96

48.95

275.80

48.15

278.53

47.29

281.16

46.38

283.69

45.42

286.13

44.42

115/76

253.32

52.28

256.95

51.93

260.43

51.49

263.77

50.97

312.18

115.76

314.31

115.56

316.37

115.31

318.36

115.02

320.30

114.69

322.18

114.33

324.01

113.93

325.79

113.50

327.53

113.05

329.22

112.57

330.87

112.08

292.01

115.12

294.88

115.46

297.65

115.73

300.31

115.91

302.86

116.01

305.32

116.04

307.69

116.01

309.97

115.91

105/80

279.12

113.21

282.58

113.86

285.87

114.38

289.01

114.79

304.51

74.74

306.82

73.99

309.05

73.20

311.20

72.36

313.28

71.49

315.29

70.58

317.23

69.64

319.11

68.67

320.93

67.67

322.70

66.64

324.41

65.59

282.50

78.69

285.64

78.44

288.67

78.10

291.57

77.70

294.36

77.22

297.04

76.69

299.62

76.09

302.11

75.44

115/80

268.53

80.43

272.18

80.42

275.80

80.39

279.22

78.86

296.37

58.91

298.67

57.99

300.88

57.03

303.02

56.04

305.08

55.01

307.08

53.94

309.01

52.85

310.88

51.73

312.69

50.58

314.45

49.41

316.15

48.22

274.59

64.36

277.70

63.90

280.68

63.37

283.55

62.76

286.31

62.10

288.97

61.38

291.53

60.60

294.00

59.78

115/78

260.79

65.40

264.45

65.27

267.97

65.05

271.35

64.75

MUA-PRC004-EN 53

Performance

Data unit capacity

Table PD-38. Size 051 cooling capacity with reheat installed, MBh cfm

2900

3000

3100

3200

3300

3400

3500

3600

3700

3800

3900

4000

4100

4200

4300

4400

4500

4600

4700

4800

4900

5000

5100

85/76 total 281.82

latent 149.66

total 285.78

latent 152.10

total 289.58

latent 154.41

total 293.26

latent 156.62

total 296.78

latent 158.72

total 300.15

latent 160.70

total 303.38

latent 162.58

total 306.48

latent 164.36

total 309.46

latent 166.05

total 312.32

latent 167.64

total 315.02

latent 169.13

total 317.64

latent 170.55

total 320.17

latent 171.89

total 322.60

latent 173.16

total 324.94

latent 174.36

total 327.19

latent 175.49

total 329.37

latent 176.56

total 331.46

latent 177.57

total 333.49

latent 178.52

total 335.44

latent 179.42

total 337.33

latent 180.26

total 339.15

latent 181.06

total 340.91

latent 181.80

297.94

122.62

300.71

123.24

303.41

123.79

306.00

124.26

308.50

124.67

310.90

125.00

313.22

125.28

315.46

125.50

95/76

274.57

115.78

278.37

117.06

281.99

118.21

285.45

119.25

288.77

120.20

291.95

121.10

295.00

121.91

317.62

125.66

319.71

125.78

321.73

125.84

323.69

125.86

325.58

125.83

327.41

125.77

329.19

125.67

330.92

125.53

317.34

183.72

320.37

185.70

323.29

187.58

326.08

189.37

328.75

191.06

331.32

192.67

333.80

194.21

336.19

195.68

85/78

291.93

166.68

296.07

169.50

300.03

172.18

303.81

174.73

307.43

177.16

310.90

179.47

314.18

181.64

338.49

197.07

340.70

198.39

342.84

199.65

344.90

200.85

346.89

201.99

348.81

203.07

350.66

204.10

352.46

205.08

328.46

203.52

331.56

205.79

334.53

207.96

337.38

210.03

340.12

212.01

342.75

213.90

345.28

215.71

347.72

217.43

85/80

302.45

184.21

306.71

187.38

310.78

190.41

314.62

193.28

318.31

196.03

321.84

198.64

325.22

201.14

350.06

219.08

352.31

220.66

354.49

222.17

356.58

223.61

358.61

225.00

360.56

226.32

362.44

227.58

364.27

228.80

328.17

145.84

330.26

146.15

332.28

146.41

334.22

146.61

336.10

146.77

337.92

146.88

339.68

146.95

341.38

146.97

308.33

141.22

311.17

142.05

313.90

142.79

316.52

143.44

319.01

144.00

321.44

144.56

323.77

145.05

326.01

145.48

dry-bulb / wet-bulb temperature – °F

95/78 95/80 105/76 105/78

284.42

132.42

294.57

149.51

267.62

83.56

276.50

98.93

288.33

134.05

292.06

135.54

298.58

151.47

302.37

153.28

271.41

83.91

275.08

84.17

280.29

99.52

283.92

99.99

295.63

136.90

299.04

138.15

302.25

139.27

305.36

140.29

306.02

154.96

309.49

156.51

312.81

157.95

315.99

159.27

278.63

84.35

282.07

84.46

285.44

84.52

288.75

84.53

287.40

100.37

290.71

100.63

293.93

100.81

297.02

100.91

319.02

160.48

321.93

161.60

324.72

162.62

327.40

163.54

329.96

164.39

332.42

165.15

334.79

165.84

337.07

166.45

291.93

84.23

294.96

84.29

297.88

84.28

300.69

84.22

303.40

84.09

306.01

83.91

308.54

83.67

310.97

83.39

300.01

100.93

302.91

100.89

305.72

100.80

308.45

100.64

311.12

100.45

313.74

100.22

316.31

99.96

318.83

99.71

339.25

167.00

341.36

167.48

343.39

167.90

345.34

168.26

347.23

168.57

349.05

168.83

350.81

169.03

352.51

169.22

313.33

83.06

315.60

82.69

317.81

82.28

319.94

81.83

322.00

81.34

323.99

80.82

325.93

80.27

327.80

79.68

321.20

99.55

323.49

99.34

325.70

99.09

327.85

98.79

329.92

98.46

331.92

98.09

333.86

97.69

335.75

97.25

309.43

118.56

312.27

118.69

315.00

118.75

317.63

118.73

320.18

118.65

322.64

118.51

325.03

118.31

327.34

118.07

105/80

285.98

114.97

289.76

115.81

293.40

116.54

296.89

117.15

300.22

117.65

303.41

118.05

306.48

118.35

329.58

117.77

331.76

117.44

333.89

117.07

335.96

116.66

337.99

116.23

339.99

115.78

341.95

115.31

343.89

114.83

289.68

52.85

292.69

52.13

295.60

51.36

298.40

50.54

301.10

49.66

303.71

48.73

306.22

47.76

308.65

46.75

115/76

264.92

55.86

268.90

55.67

272.72

55.40

276.39

55.04

279.92

54.61

283.31

54.10

286.58

53.51

311.00

45.70

313.28

44.62

315.47

43.50

317.60

42.35

319.66

41.17

321.65

39.96

323.58

38.73

325.46

37.48

304.47

82.42

307.53

82.09

310.48

81.68

313.32

81.22

316.06

80.69

318.69

80.11

321.24

79.48

323.70

78.80

115/80

279.17

82.74

283.28

82.72

287.18

82.90

290.93

82.98

294.52

82.97

297.97

82.86

301.28

82.68

326.07

78.07

328.36

77.30

330.58

76.49

332.72

75.64

334.80

74.76

336.80

73.84

338.75

72.90

340.63

71.93

296.95

67.49

299.99

66.96

302.92

66.38

305.74

65.73

308.46

65.03

311.08

64.28

313.62

63.48

316.06

62.64

115/78

271.94

68.99

275.97

69.05

279.85

69.01

283.53

68.86

287.09

68.63

290.50

68.32

293.79

67.94

318.42

61.75

320.71

60.83

322.91

59.86

325.05

58.86

327.12

57.83

329.12

56.78

331.06

55.69

332.94

54.58

54 MUA-PRC004-EN

Performance

Data unit capacity

Table PD-39. Size 051 reheat data, MBh cfm dry-bulb / wet-bulb temperature (°F)

55/48 55/50 55/52 65/56 65/58 65/60 75/66 75/68 75/70 85/76 85/78 85/80 95/76 95/78 95/80 105/76 105/78 105/80 115/76115/78115/80

2900 82.8

85.5

88.4

94.1

97.2

100.3 109.7 113.0 116.4 126.4 129.9

133.4 126.0 129.5 133.0 127.3 129.8

132.8 137.0 137.0 137.0

3000 83.3

86.1

89.0

94.7

97.8

100.9 110.3 113.7 117.0 127.1 130.6

134.1 126.7 130.2 133.7 128.3 130.6

133.5 138.5 138.5 138.6

3100 83.8

86.6

89.5

95.3

98.4

101.5 110.9 114.3 117.7 127.7 131.2

134.7 127.3 130.8 134.3 129.3 131.4

134.3 140.0 140.0 140.0

3200 84.3

87.1

90.0

95.8

98.9

102.1 111.5 114.9 118.3 128.3 131.8

135.3 127.9 131.4 134.9 130.3 132.3

135.0 141.4 141.4 141.4

3300 84.8

87.6

90.5

96.3

99.4

102.6 112.1 115.4 118.8 128.9 132.4

135.9 128.5 132.0 135.5 131.4 133.0

135.6 142.7 142.7 142.7

3400 85.2

88.1

91.0

96.8

99.9

103.1 112.6 115.9 119.4 129.4 132.9

136.5 129.0 132.5 136.0 132.5 133.8

136.3 144.1 144.0 144.0

3500 85.6

88.5

91.5

97.3

100.4 103.6 113.1 116.4 119.9 129.9 133.5

137.0 129.5 133.0 136.5 133.6 134.6

137.0 145.3 145.3 145.2

3600 86.0

88.9

91.9

97.7

100.8 104.0 113.6 116.9 120.3 130.4 133.9

137.5 130.0 133.5 137.0 134.8 135.4

137.6 146.5 146.5 146.4

3700 86.4

89.3

92.3

98.1

101.3 104.4 114.0 117.4 120.8 130.9 134.4

137.9 130.5 134.0 137.5 135.9 136.2

138.2 147.7 147.6 147.6

3800 86.8

89.7

92.7

98.5

101.7 104.9 114.4 117.8 121.2 131.3 134.9

138.4 131.0 134.4 137.9 136.9 137.0

138.8 148.8 148.8 148.7

3900 87.1

90.0

93.0

98.9

102.0 105.2 114.8 118.2 121.6 131.7 135.3

138.8 131.5 134.8 138.3 137.8 137.8

139.4 149.9 149.8 149.8

4000 87.5

90.4

93.4

99.3

102.4 105.6 115.2 118.6 122.0 132.1 135.6

139.2 131.9 135.2 138.7 138.8 138.6

140.0 151.0 150.9 150.8

4100 87.8

90.7

93.7

99.6

102.8 106.0 115.6 119.0 122.4 132.5 136.0

139.6 132.4 135.6 139.1 139.7 139.5

140.6 152.0 151.9 151.8

4200 88.1

91.0

94.0

99.9

103.1 106.3 115.9 119.3 122.7 132.9 136.4

140.0 132.8 136.0 139.5 140.6 140.4

141.2 153.0 152.9 152.8

4300 88.4

91.3

94.3

100.2 103.4 106.6 116.2 119.6 123.1 133.2 136.7

140.3 133.2 136.3 139.8 141.4 141.3

141.8 153.9 153.8 153.7

4400 88.6

91.6

94.6

100.5 103.7 106.9 116.6 120.0 123.4 133.5 137.1

140.6 133.6 136.7 140.2 142.2 142.1

142.4 154.9 154.7 154.6

4500 88.9

91.9

94.9

100.8 104.0 107.2 116.9 120.3 123.7 133.9 137.4

141.0 134.0 137.0 140.5 143.0 142.9

143.0 155.7 155.6 155.5

4600 89.2

92.1

95.2

101.1 104.3 107.5 117.2 120.6 124.0 134.2 137.7

141.3 134.4 137.3 140.8 143.8 143.7

143.7 156.6 156.5 156.4

4700 89.4

92.4

95.4

101.4 104.6 107.8 117.4 120.9 124.3 134.5 138.0

141.6 134.8 137.7 141.1 144.5 144.4

144.3 157.4 157.3 157.2

4800 89.6

92.6

95.7

101.6 104.8 108.1 117.7 121.1 124.6 134.7 138.3

141.9 135.1 138.0 141.4 145.3 145.1

144.9 158.3 158.1 158.0

4900 89.9

92.8

95.9

101.9 105.1 108.3 118.0 121.4 124.8 135.0 138.6

142.1 135.5 138.3 141.6 146.0 145.8

145.6 159.0 158.9 158.8

5000 90.1

93.1

96.1

102.1 105.3 108.5 118.2 121.6 125.1 135.3 138.8

142.4 135.9 138.6 141.9 146.6 146.5

146.2 159.8 159.6 159.5

5100 90.3

93.3

96.3

102.3 105.5 108.8 118.4 121.9 125.3 135.5 139.1

142.7 136.2 138.9 142.1 147.3 147.1

147.0 160.5 160.4 160.2

Table PD-40. Size 051 condenser reheat max temperature rise, °F dry-bulb / wet-bulb temperature – °F cfm 55/48 55/50 55/52 65/56 65/58 65/60 75/66 75/68 75/70 85/76 85/78 85/80 95/76 95/78 95/80 105/76 105/78 105/80 115/76 115/78 115/80

2900 26.3

27.2

28.1

29.9

30.8

31.8

34.7

35.7

36.8

39.8

40.8

41.9

39.7

40.7

41.8

40.1

40.8

41.7

43.1

3000 25.6

26.5

27.3

29.1

30.0

30.9

33.7

34.7

35.7

38.7

39.7

40.7

38.5

39.6

40.6

39.0

39.7

40.5

42.2

3100 24.9

25.7

26.6

28.3

29.2

30.1

32.8

33.8

34.7

37.6

38.6

39.5

37.5

38.4

39.4

38.1

38.6

39.4

41.2

3200 24.3

25.1

25.9

27.5

28.4

29.3

32.0

32.9

33.8

36.6

37.5

38.5

36.5

37.4

38.3

37.2

37.6

38.4

40.3

3300 23.7

24.5

25.3

26.9

27.7

28.6

31.1

32.0

32.9

35.6

36.5

37.4

35.5

36.4

37.3

36.3

36.7

37.4

39.5

3400 23.1

23.9

24.6

26.2

27.0

27.8

30.3

31.2

32.1

34.7

35.6

36.5

34.6

35.5

36.4

35.5

35.8

36.4

38.7

3500 22.5

23.3

24.0

25.6

26.4

27.2

29.6

30.5

31.3

33.8

34.7

35.6

33.7

34.6

35.4

34.8

35.0

35.5

37.9

3600 22.0

22.7

23.5

25.0

25.7

26.5

28.9

29.7

30.6

33.0

33.8

34.7

32.9

33.7

34.6

34.1

34.2

34.7

37.1

3700 21.5

22.2

22.9

24.4

25.1

25.9

28.2

29.0

29.8

32.2

33.0

33.8

32.1

32.9

33.7

33.4

33.5

33.9

36.4

3800 21.0

21.7

22.4

23.8

24.6

25.3

27.6

28.4

29.2

31.5

32.3

33.1

31.4

32.2

32.9

32.8

32.8

33.2

35.7

3900 20.6

21.2

21.9

23.3

24.0

24.8

27.0

27.7

28.5

30.7

31.5

32.3

30.7

31.4

32.2

32.2

32.1

32.4

35.0

4000 20.1

20.8

21.5

22.8

23.5

24.2

26.4

27.1

27.9

30.1

30.8

31.6

30.0

30.7

31.5

31.6

31.5

31.8

34.4

4100 19.7

20.4

21.0

22.3

23.0

23.7

25.8

26.5

27.3

29.4

30.1

30.9

29.4

30.0

30.8

31.0

30.9

31.1

33.8

4200 19.3

19.9

20.6

21.9

22.5

23.2

25.3

26.0

26.7

28.8

29.5

30.2

28.8

29.4

30.1

30.5

30.4

30.5

33.2

4300 18.9

19.5

20.2

21.4

22.1

22.7

24.7

25.4

26.1

28.2

28.9

29.6

28.2

28.8

29.5

29.9

29.8

29.9

32.6

4400 18.5

19.1

19.8

21.0

21.6

22.3

24.2

24.9

25.6

27.6

28.3

29.0

27.6

28.2

28.9

29.4

29.3

29.3

32.0

4500 18.2

18.8

19.4

20.6

21.2

21.8

23.8

24.4

25.1

27.0

27.7

28.4

27.1

27.6

28.3

28.9

28.8

28.8

31.5

4600 17.8

18.4

19.0

20.2

20.8

21.4

23.3

23.9

24.6

26.5

27.2

27.8

26.5

27.1

27.7

28.4

28.3

28.3

31.0

4700 17.5

18.1

18.7

19.8

20.4

21.0

22.8

23.5

24.1

26.0

26.6

27.3

26.0

26.6

27.2

28.0

27.9

27.8

30.5

4800 17.2

17.7

18.3

19.4

20.0

20.6

22.4

23.0

23.7

25.5

26.1

26.7

25.6

26.1

26.6

27.5

27.4

27.3

30.0

4900 16.9

17.4

18.0

19.1

19.7

20.3

22.0

22.6

23.2

25.0

25.6

26.2

25.1

25.6

26.1

27.1

27.0

26.9

29.5

5000 16.6

17.1

17.7

18.7

19.3

19.9

21.6

22.2

22.8

24.6

25.2

25.8

24.7

25.1

25.7

26.6

26.6

26.5

29.1

5100 16.3

16.8

17.4

18.4

19.0

19.5

21.2

21.8

22.4

24.1

24.7

25.3

24.2

24.7

25.2

26.2

26.2

26.1

28.6

30.4

29.9

29.4

29.0

28.5

30.3

29.8

29.3

28.9

28.4

43.1

43.0

42.1

42.0

41.2

41.1

40.3

40.2

39.4

39.3

38.6

38.5

37.8

37.7

37.0

37.0

36.3

36.2

35.6

35.5

34.9

34.9

34.3

34.2

33.7

33.6

33.1

33.0

32.5

32.4

32.0

31.9

31.4

31.3

30.9

30.8

Table PD-41. Size 051 design supply air dew point, cfm drybulb

(°F)

85

95

105

115

76

78

80

76

78

80

76

78

80 wetbulb

(°F)

76

78

80

46

3000

48

3083

3054

3091

3380

50

3399

3023

3372

2989

3447

2975

3833

3117

— design supply air dew point – °F

52 54 56

3764

3332

2962

4190

3685

3262

4700

4098

3606

3748

3296

2923

3894

3298

4393

3525

2905

4195

3649

3220

4468

3681

3185

4020

3267

4741

4067

3563

4153

3541

4639

3713

58

4590

4006

4579

3966

4791

3969

4262

60

4482

4448

4497

4964

62

5058

5041

MUA-PRC004-EN 55

Performance

Data unit capacity total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent

391.97

210.58

393.78

211.42

395.54

212.22

397.24

212.98

398.91

213.70

400.52

214.38

402.10

215.03

403.63

215.65

405.12

216.24

406.57

216.79

375.37

202.19

377.67

203.42

379.91

204.60

382.07

205.72

384.17

206.79

386.21

207.81

388.19

208.78

390.11

209.70

85/76

337.10

179.72

340.68

181.95

344.13

184.08

347.50

186.13

350.75

188.09

353.88

189.96

356.90

191.75

359.81

193.46

362.63

195.09

365.35

196.64

367.98

198.13

370.52

199.55

372.98

200.90

406.39

237.36

408.24

238.43

410.02

239.46

411.76

240.44

413.45

241.38

415.09

242.29

416.69

243.16

418.25

243.99

419.76

244.79

421.23

245.55

389.47

227.01

391.83

228.50

394.11

229.93

396.32

231.30

398.46

232.62

400.53

233.88

402.55

235.09

404.50

236.25

85/78

350.17

200.65

353.90

203.23

357.49

205.71

360.94

208.08

364.27

210.35

367.48

212.53

370.58

214.62

373.57

216.62

376.45

218.54

379.23

220.38

381.92

222.14

384.52

223.83

387.04

225.45

421.23

264.74

423.10

266.04

424.92

267.29

426.68

268.50

428.39

269.66

430.06

270.78

431.68

271.86

433.26

272.91

434.79

273.92

436.28

274.89

404.02

252.45

406.41

254.19

408.74

255.88

410.98

257.49

413.16

259.05

415.27

260.56

417.32

262.00

419.31

263.40

85/80

363.81

222.26

367.64

225.18

371.32

227.99

374.86

230.68

378.27

233.26

381.56

235.75

384.73

238.13

387.78

240.43

390.73

242.63

393.57

244.75

396.32

246.79

398.97

248.75

401.54

250.63

Table PD-42. Size 066 cooling capacity without reheat installed, MBh cfm

3600

3700

3800

3900

4000

4100

4200

4300

4400

4500

4600

4700

4800

4900

5000

5100

5200

5300

5400

5500

5600

5700

5800

5900

6000

6100

6200

6300

6400

6500

6600

373.65

387.56

168.93

193.57

375.80

389.75

169.32

194.20

377.88

391.86

169.65

194.78

379.89

393.91

169.94

195.30

381.84

395.90

170.17

195.77

383.73

397.82

170.36

196.19

385.56

399.68

170.50

196.57

387.34

401.49

170.61

196.90

389.06

403.24

170.67

197.18

390.74

404.94

170.70

197.43

392.38

406.59

170.77

197.64

393.98

408.20

170.84

197.81

395.54

409.75

170.87

197.94

397.05

411.27

170.88

198.05

398.53

412.74

170.87

198.11

399.97

414.17

170.83

198.15

401.37

415.56

170.76

198.16

402.74

416.91

170.68

198.14

dry-bulb / wet-bulb temperature (°F)

95/78 95/80 105/76 105/78

337.61

350.70

157.65

178.63

313.71

98.17

324.30

115.68

341.04

354.22

159.02

180.33

344.35

357.61

160.30

181.92

317.21

96.85

320.58

97.19

327.59

116.13

330.78

116.50

347.52

360.87

161.48

183.40

350.58

364.00

162.57

184.79

353.53

367.02

163.57

186.08

356.37

369.92

164.49

187.29

323.84

97.45

326.98

97.64

330.02

97.77

332.96

97.83

333.88

116.81

336.90

117.07

339.85

117.28

342.75

117.46

359.11

372.72

165.34

188.41

361.75

375.42

166.10

189.45

364.30

378.02

166.80

190.41

366.76

380.53

167.43

191.30

369.13

382.95

167.99

192.12

371.44

385.30

168.49

192.88

335.80

97.83

338.54

97.78

341.20

97.66

343.78

97.50

346.27

97.29

348.70

97.04

345.61

117.61

348.46

117.78

351.12

116.22

353.73

116.26

356.25

116.23

358.69

116.16

367.47

92.98

369.27

92.38

371.03

91.74

372.73

91.09

374.40

90.41

376.02

89.70

377.60

88.98

379.14

88.24

380.64

87.48

382.10

86.70

351.03

96.73

353.30

96.39

355.51

96.01

357.65

95.59

359.73

95.13

361.75

94.64

363.71

94.12

365.61

93.57

377.64

113.64

379.46

113.19

381.22

112.71

382.94

112.21

384.62

111.68

386.25

111.12

387.83

110.54

389.38

109.94

390.89

109.32

392.36

108.69

361.06

116.04

363.35

115.88

365.58

115.67

367.74

115.42

369.84

115.14

371.87

114.81

373.85

114.46

375.77

114.07

375.79

146.45

377.50

146.45

379.18

146.42

380.82

146.36

382.41

146.28

383.98

146.18

385.50

146.05

387.00

145.91

388.46

145.75

389.90

145.58

360.24

145.27

362.38

145.56

364.46

145.80

366.48

146.00

368.45

146.16

370.36

146.29

372.21

146.38

374.02

146.43

95/76

324.98

137.28

328.32

138.34

331.53

139.30

334.63

140.17

337.61

140.96

340.49

141.67

343.26

142.31

345.93

142.87

348.51

143.36

351.01

143.78

353.41

144.15

355.76

144.55

358.03

144.94

56

359.33

43.26

361.15

42.72

362.93

42.15

364.68

41.56

366.40

40.96

368.09

40.35

369.75

39.73

371.39

39.09

373.00

38.45

374.58

37.80

343.43

52.33

345.62

51.19

347.74

50.02

349.80

48.83

351.81

47.60

353.75

46.34

355.64

45.07

357.48

43.79

115/76

307.48

63.01

310.85

62.53

314.10

61.99

317.24

61.37

320.27

60.70

323.19

59.96

326.02

59.17

328.76

58.33

331.40

57.44

333.96

56.50

336.44

55.52

338.84

54.49

341.17

53.43

388.09

134.67

389.92

134.37

391.69

134.04

393.42

133.68

395.11

133.30

396.74

132.89

398.34

132.45

399.89

131.99

401.40

131.51

402.88

131.01

371.46

137.55

373.69

137.44

375.89

137.32

378.06

137.19

380.23

137.06

382.29

135.36

384.28

135.16

386.21

134.93

105/80

336.34

134.66

339.60

135.30

342.75

135.86

345.79

136.32

348.72

136.71

351.55

137.03

354.30

137.28

356.96

137.47

359.54

137.60

362.05

137.67

364.49

137.70

366.86

137.69

369.19

137.64

378.80

82.84

380.56

81.80

382.27

80.73

383.93

79.64

385.55

78.53

387.13

77.40

388.66

76.25

390.16

75.08

391.61

73.90

393.03

72.71

362.74

90.15

364.97

89.35

367.12

88.52

369.22

87.65

371.25

86.75

373.22

85.82

375.13

84.85

376.99

83.86

115/80

325.94

95.64

329.41

95.62

332.75

95.53

335.98

95.35

339.09

95.10

342.09

94.78

344.98

94.39

347.78

93.95

350.48

93.44

353.10

92.88

355.63

92.27

358.08

91.61

360.45

90.90

MUA-PRC004-EN

368.90

62.47

370.65

61.28

372.35

60.06

374.01

58.83

375.62

57.58

377.19

56.30

378.72

55.02

380.21

53.71

381.72

52.97

383.21

52.30

352.94

71.06

355.15

70.09

357.29

69.10

359.37

68.07

361.39

67.00

363.35

65.91

365.25

64.79

367.10

63.64

115/78

316.54

79.12

319.96

78.88

323.26

78.56

326.45

78.17

329.52

77.70

332.48

77.18

335.35

76.59

338.11

75.95

340.79

75.25

343.38

74.50

345.89

73.71

348.31

72.87

350.66

71.98

Performance

Data unit capacity

Table PD-43. Size 066 cooling cpacity with reheat installed, MBh cfm 85/76 85/78 85/80 95/76 dry-bulb / wet-bulb temperature (°F)

95/78 95/80 105/76 105/78

3600 total latent

343.28

181.96

355.54

202.82

368.32

224.32

333.64

139.62

345.54

159.91

357.84

180.84

325.90

100.12

335.63

118.67

3700

3800

3900

4000

4100

4200

4300

4400

4500

4600

4700

4800

4900

5000

5100

5200

5300

5400

5500

5600

5700

5800

5900

6000

6100

6200

6300

6400

6500

6600 total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent

407.21

216.43

408.88

217.10

410.50

217.74

412.07

218.34

413.61

218.91

415.10

219.44

392.01

209.54

394.11

210.57

396.15

211.54

398.13

212.46

400.05

213.34

401.92

214.18

403.73

214.97

405.50

215.72

372.53

199.26

375.25

200.77

377.89

202.21

380.43

203.59

382.90

204.90

385.29

206.15

387.60

207.34

389.83

208.47

346.99

184.24

350.57

186.42

354.02

188.51

357.39

190.52

360.64

192.43

363.77

194.26

366.79

196.01

369.71

197.67

421.03

244.35

422.72

245.25

424.37

246.12

425.97

246.95

427.53

247.74

429.05

248.50

405.55

235.50

407.70

236.78

409.78

238.01

411.79

239.18

413.75

240.30

415.65

241.38

417.49

242.41

419.29

243.40

385.67

223.04

388.45

224.84

391.14

226.57

393.75

228.22

396.26

229.80

398.70

231.32

401.06

232.77

403.34

234.17

359.41

205.47

363.13

208.01

366.71

210.45

370.17

212.78

373.49

215.01

376.70

217.15

379.80

219.20

382.78

221.16

435.16

272.78

436.88

273.91

438.55

275.01

440.17

276.06

441.76

277.08

443.30

278.06

419.43

262.00

421.61

263.53

423.73

265.00

425.78

266.42

427.77

267.79

429.70

269.11

431.57

270.38

433.39

271.60

399.16

247.38

402.01

249.46

404.75

251.47

407.41

253.40

409.97

255.25

412.45

257.04

414.86

258.75

417.18

260.41

372.29

227.32

376.11

230.19

379.78

232.95

383.32

235.61

386.73

238.15

390.00

240.60

393.17

242.95

396.22

245.20

395.14

149.36

396.84

149.21

398.51

149.04

400.14

148.85

401.75

148.64

403.34

148.42

380.07

149.59

382.12

149.68

384.12

149.73

386.06

149.74

387.96

149.73

389.82

149.68

391.63

149.60

393.40

149.49

361.37

147.23

363.96

147.71

366.47

148.13

368.91

148.50

371.27

148.81

373.56

149.07

375.79

149.29

377.96

149.46

337.16

140.79

340.57

141.88

343.86

142.88

347.04

143.80

350.10

144.63

353.06

145.38

355.92

146.07

358.69

146.68

407.08

174.60

408.70

174.57

410.29

174.51

411.83

174.43

413.34

174.31

414.82

174.18

392.37

173.59

394.39

173.85

396.36

174.08

398.27

174.26

400.14

174.40

401.94

174.50

403.70

174.57

405.41

174.60

373.69

169.57

376.30

170.28

378.82

170.92

381.26

171.51

383.63

172.03

385.92

172.50

388.13

172.91

390.28

173.27

349.16

161.35

352.65

162.68

356.00

163.91

359.22

165.04

362.33

166.08

365.32

167.04

368.20

167.93

371.00

168.78

420.09

201.00

421.70

201.14

423.26

201.24

424.78

201.32

426.26

201.36

427.70

201.38

405.44

198.51

407.47

198.96

409.43

199.38

411.34

199.75

413.19

200.08

414.99

200.37

416.74

200.62

418.43

200.82

386.63

193.06

389.28

193.98

391.83

194.82

394.29

195.59

396.67

196.30

398.98

196.94

401.20

197.52

403.36

198.04

361.56

182.60

365.13

184.25

368.56

185.80

371.86

187.24

375.04

188.58

378.10

189.83

381.04

190.99

383.89

192.07

391.12

96.48

392.87

95.84

394.57

95.17

396.22

94.48

397.84

93.78

399.41

93.05

375.33

100.64

377.50

100.23

379.61

99.78

381.66

99.31

383.66

98.80

385.60

98.26

387.49

97.69

389.33

97.10

355.39

102.43

358.16

102.37

360.85

102.26

363.44

102.10

365.97

101.89

368.41

101.64

370.79

101.35

373.09

101.02

329.64

100.67

333.26

101.13

336.75

101.52

340.12

101.84

343.38

102.08

346.53

102.26

349.59

102.38

352.54

102.43

400.82

117.76

402.57

117.26

404.27

116.74

405.93

116.20

407.55

115.63

409.13

115.04

384.94

120.67

387.13

120.43

389.25

120.14

391.32

119.83

393.32

119.47

395.27

119.09

397.17

118.68

399.02

118.23

364.86

121.02

367.65

121.16

370.35

121.24

372.98

121.26

375.52

121.24

377.98

121.16

380.37

121.04

382.69

120.88

339.22

119.14

342.71

119.54

346.10

119.86

349.42

120.12

352.66

120.34

355.87

120.52

358.99

120.57

361.97

120.83

MUA-PRC004-EN

386.56

44.95

388.31

44.38

390.04

43.79

391.74

43.19

393.41

42.58

395.05

41.95

370.93

54.54

373.08

53.39

375.16

52.20

377.19

51.00

379.17

49.76

381.09

48.51

382.96

47.23

384.77

45.93

351.25

62.49

353.98

61.64

356.63

60.74

359.20

59.80

361.69

58.82

364.10

57.80

366.44

56.75

368.72

55.66

115/76

322.18

67.63

325.87

67.32

329.43

66.94

332.87

66.49

336.19

65.97

339.41

65.39

342.51

64.74

345.52

64.04

348.43

63.29

410.77

139.38

412.53

139.02

414.23

138.64

415.90

138.23

417.52

137.80

419.10

137.35

394.84

141.06

397.04

140.98

399.17

140.85

401.24

140.69

403.25

140.49

405.21

140.26

407.12

140.00

408.97

139.70

374.87

141.24

377.56

141.27

380.19

141.26

382.76

141.20

385.30

141.12

387.81

141.02

390.25

141.10

392.58

141.10

105/80

346.72

138.02

350.28

138.71

353.72

139.30

357.04

139.80

360.24

140.22

363.35

140.56

366.36

140.83

369.28

141.03

372.11

141.16

404.99

86.24

406.72

85.18

408.41

84.10

410.05

83.00

411.65

81.89

413.21

80.76

389.27

93.76

391.44

92.93

393.54

92.06

395.58

91.16

397.57

90.23

399.50

89.27

401.38

88.28

403.21

87.27

369.36

98.96

372.13

98.48

374.82

97.94

377.42

97.36

379.93

96.72

382.38

96.04

384.74

95.32

387.04

94.56

115/80

339.71

100.36

343.49

100.51

347.13

100.58

350.65

100.56

354.04

100.47

357.32

100.30

360.48

100.06

363.54

99.76

366.50

99.39

395.64

65.27

397.37

64.08

399.06

62.86

400.70

61.63

402.30

60.38

403.86

59.11

379.97

73.99

382.12

72.99

384.22

71.97

386.26

70.92

388.24

69.84

390.17

68.73

392.04

67.60

393.87

66.45

360.16

80.55

362.91

79.88

365.58

79.17

368.16

78.41

370.67

77.60

373.10

76.76

375.46

75.87

377.74

74.95

115/78

330.78

83.80

334.52

83.72

338.12

83.57

341.60

83.34

344.96

83.03

348.21

82.66

351.35

82.22

354.38

81.72

357.32

81.16

57

Performance

Data unit capacity

Table PD-44. Size 066 reheat data, MBh dry-bulb / wet-bulb temperature – °F cfm 55/48 55/50 55/52 65/56 65/58 65/60 75/66 75/68 75/70 85/76 85/78 85/80 95/76 95/78 95/80 105/76 105/78 105/80 115/76 115/78 115/80

3600 88.1

91.0

94.1 100.1 103.3 106.5 116.3 119.7 123.2 133.5 137.1 140.8

133.1 136.7 140.3

137.1

138.0

140.5

149.0

149.0

148.9

3700 88.5

91.5

94.5 100.5 103.7 107.0 116.8 120.2 123.7 134.0 137.7 141.3

133.6 137.2 140.8

138.2

138.8

141.2

150.3

150.3

150.2

3800 88.9

91.9

94.9 100.9 104.2 107.4 117.2 120.7 124.2 134.5 138.1 141.8

134.1 137.6 141.3

139.3

139.6

141.8

151.6

151.5

151.4

3900 89.3

92.2

95.3 101.3 104.6 107.9 117.7 121.1 124.7 135.0 138.6 142.3

134.6 138.1 141.8

140.4

140.5

142.5

152.8

152.7

152.6

4000 89.6

92.6

95.7 101.7 105.0 108.3 118.1 121.6 125.1 135.4 139.1 142.7

135.1 138.5 142.2

141.5

141.4

143.1

154.0

153.9

153.8

4100 89.9

93.0

96.0 102.1 105.3 108.6 118.5 122.0 125.5 135.8 139.5 143.2

135.5 139.0 142.6

142.5

142.3

143.7

155.1

155.0

154.9

4200 90.3

93.3

96.4 102.5 105.7 109.0 118.9 122.4 125.9 136.2 139.9 143.6

136.0 139.4 143.0

143.5

143.3

144.4

156.3

156.1

156.0

4300 90.6

93.6

96.7 102.8 106.1 109.4 119.2 122.7 126.3 136.6 140.3 143.9

136.4 139.7 143.4

144.4

144.3

145.0

157.3

157.2

157.0

4400 90.9

93.9

97.0 103.1 106.4 109.7 119.6 123.1 126.6 137.0 140.6 144.3

136.8 140.1 143.8

145.3

145.2

145.6

158.4

158.2

158.1

4500 91.2

94.2

97.3 103.4 106.7 110.0 119.9 123.4 127.0 137.3 141.0 144.7

137.3 140.5 144.1

146.2

146.1

146.3

159.4

159.2

159.1

4600 91.4

94.5

97.6 103.7 107.0 110.3 120.2 123.7 127.3 137.6 141.3 145.0

137.7 140.8 144.5

147.1

146.9

147.0

160.3

160.2

160.0

4700 91.7

94.8

97.9 104.0 107.3 110.6 120.5 124.0 127.6 138.0 141.6 145.3

138.1 141.2 144.8

147.9

147.8

147.6

161.3

161.1

160.9

4800 92.0

95.0

98.2 104.3 107.6 110.9 120.8 124.3 127.9 138.3 141.9 145.7

138.5 141.5 145.1

148.7

148.6

148.3

162.2

162.0

161.9

4900 92.2

95.3

98.4 104.5 107.8 111.2 121.1 124.6 128.2 138.6 142.2 146.0

138.9 141.9 145.4

149.5

149.3

149.1

163.1

162.9

162.7

5000 92.4

95.5

98.6 104.8 108.1 111.4 121.4 124.9 128.4 138.8 142.5 146.2

139.2 142.2 145.7

150.3

150.1

149.9

164.0

163.8

163.6

5100 92.6

95.7

98.9 105.0 108.3 111.7 121.6 125.1 128.7 139.1 142.8 146.5

139.6 142.5 146.0

151.0

150.8

150.6

164.8

164.6

164.4

5200 92.9

96.0

99.1 105.3 108.6 111.9 121.9 125.4 129.0 139.4 143.1 146.8

140.0 142.8 146.2

151.7

151.5

151.4

165.6

165.4

165.2

5300 93.1

96.2

99.3 105.5 108.8 112.2 122.1 125.6 129.2 139.6 143.3 147.0

140.4 143.1 146.5

152.4

152.2

152.0

166.4

166.2

166.0

5400 93.3

96.4

99.5 105.7 109.0 112.4 122.3 125.9 129.4 139.9 143.6 147.3

140.7 143.4 146.7

153.1

152.9

152.7

167.2

167.0

166.8

5500 93.5

96.6

99.7 105.9 109.2 112.6 122.6 126.1 129.7 140.1 143.8 147.5

141.1 143.7 147.0

153.8

153.6

153.4

167.9

167.7

167.5

5600 93.7

96.8

99.9 106.2 109.4 112.8 122.8 126.3 129.9 140.3 144.0 147.8

141.5 144.0 147.2

154.4

154.2

154.0

168.7

168.4

168.2

5700 93.9

96.9 100.1 106.4 109.6 113.0 123.0 126.5 130.1 140.5 144.2 148.0

141.8 144.3 147.5

155.0

154.8

154.6

169.4

169.1

168.9

5800 94.1

97.1 100.3 106.6 109.8 113.2 123.2 126.7 130.3 140.7 144.5 148.2

142.2 144.5 147.7

155.7

155.4

155.2

170.1

169.8

169.6

5900 94.2

97.3 100.5 106.8 110.0 113.4 123.4 126.9 130.5 140.9 144.7 148.4

142.6 144.8 147.9

156.2

156.0

155.8

170.7

170.5

170.3

6000 94.4

97.5 100.6 107.0 110.2 113.6 123.5 127.1 130.7 141.1 144.9 148.6

143.0 145.1 148.1

156.8

156.6

156.4

171.4

171.1

170.9

6100 94.6

97.6 100.8 107.1 110.3 113.7 123.7 127.3 130.9 141.3 145.0 148.8

143.3 145.3 148.4

157.4

157.1

156.9

172.0

171.8

171.5

6200 94.8

97.8 101.0 107.3 110.5 113.9 123.9 127.4 131.0 141.5 145.2 149.0

143.7 145.6 148.6

157.9

157.7

157.5

172.6

172.4

172.2

6300 94.9

97.9 101.1 107.5 110.7 114.1 124.1 127.6 131.2 141.7 145.4 149.2

144.1 145.8 148.8

158.5

158.2

158.0

173.2

173.0

172.8

6400 95.1

98.1 101.3 107.7 110.8 114.2 124.2 127.8 131.4 141.8 145.6 149.3

144.5 146.1 149.0

159.0

158.7

158.5

173.8

173.6

173.3

6500 95.2

98.2 101.4 107.9 111.0 114.4 124.4 127.9 131.5 142.0 145.7 149.5

144.9 146.4 149.2

159.5

159.2

159.0

174.3

174.2

173.9

6600 95.4

98.3 101.5 108.0 111.1 114.5 124.5 128.1 131.7 142.2 145.9 149.7

145.3 146.6 149.4

160.0

159.7

159.5

174.9

174.7

174.5

Table PD-45. Size 066 condenser reheat max temperature rise, °F dry-bulb / wet-bulb temperature – °F cfm 55/48 55/50 55/52 65/56 65/58 65/60 75/66 75/68 75/70 85/76 85/78 85/80 95/76 95/78 95/80 105/76 105/78 105/80 115/76 115/78 115/80

3600 22.5

23.3

24.1

25.6

26.4

27.2

29.6

30.5

31.3

33.9

34.7

35.6

33.7

34.6

35.5

34.7

3700 22.0

22.8

23.6

25.0

25.8

26.6

28.9

29.8

30.6

33.1

33.9

34.8

32.9

33.8

34.6

34.1

3800 21.6

22.3

23.0

24.4

25.2

26.0

28.3

29.1

29.9

32.3

33.1

34.0

32.2

33.0

33.8

33.5

3900 21.1

21.8

22.5

23.9

24.6

25.4

27.7

28.5

29.3

31.6

32.4

33.2

31.5

32.2

33.1

32.8

4000 20.6

21.3

22.0

23.4

24.1

24.9

27.1

27.8

28.6

30.9

31.7

32.4

30.8

31.5

32.3

32.3

4100 20.2

20.9

21.6

22.9

23.6

24.3

26.5

27.2

28.0

30.2

31.0

31.7

30.1

30.8

31.6

31.7

4200 19.8

20.5

21.1

22.4

23.1

23.8

25.9

26.7

27.4

29.6

30.3

31.1

29.5

30.2

30.9

31.1

4300 19.4

20.0

20.7

22.0

22.7

23.4

25.4

26.1

26.8

28.9

29.7

30.4

28.9

29.6

30.3

30.6

4400 19.0

19.6

20.3

21.5

22.2

22.9

24.9

25.6

26.3

28.3

29.1

29.8

28.3

29.0

29.7

30.1

4500 18.7

19.3

19.9

21.1

21.8

22.4

24.4

25.1

25.8

27.8

28.5

29.2

27.8

28.4

29.1

29.6

34.9

32.8

32.2

31.6

31.0

30.5

30.0

29.5

35.5

34.2

34.7

37.1

37.0

33.5

33.9

36.4

36.3

33.2

32.5

31.9

31.2

30.6

30.0

29.5

37.8

35.8

35.1

34.5

33.9

33.4

32.8

32.3

37.7

35.7

35.0

34.4

33.8

33.3

32.7

32.2

37.6

36.9

36.2

35.6

35.0

34.3

33.8

33.2

32.6

32.1

4600 18.3

18.9

19.5

20.7

21.4

22.0

23.9

24.6

25.3

27.2

27.9

28.6

27.2

27.8

28.5

29.1

4700 18.0

18.6

19.2

20.3

21.0

21.6

23.5

24.1

24.8

26.7

27.4

28.1

26.7

27.3

27.9

28.7

4800 17.6

18.2

18.8

20.0

20.6

21.2

23.0

23.7

24.3

26.2

26.9

27.5

26.2

26.8

27.4

28.2

4900 17.3

17.9

18.5

19.6

20.2

20.8

22.6

23.3

23.9

25.7

26.4

27.0

25.8

26.3

26.9

27.8

5000 17.0

17.6

18.1

19.3

19.8

20.4

22.2

22.8

23.5

25.3

25.9

26.5

25.3

25.8

26.4

27.4

5100 16.7

17.3

17.8

18.9

19.5

20.1

21.8

22.4

23.0

24.8

25.4

26.0

24.9

25.4

25.9

26.9

5200 16.4

17.0

17.5

18.6

19.2

19.7

21.4

22.0

22.6

24.4

25.0

25.6

24.5

24.9

25.5

26.5

5300 16.2

16.7

17.2

18.3

18.8

19.4

21.1

21.7

22.2

23.9

24.5

25.1

24.1

24.5

25.0

26.2

5400 15.9

16.4

16.9

18.0

18.5

19.1

20.7

21.3

21.9

23.5

24.1

24.7

23.7

24.1

24.6

25.8

5500 15.6

16.1

16.7

17.7

18.2

18.8

20.4

20.9

21.5

23.1

23.7

24.3

23.3

23.7

24.2

25.4

5600 15.4

15.9

16.4

17.4

17.9

18.5

20.0

20.6

21.2

22.8

23.3

23.9

23.0

23.3

23.8

25.1

5700 15.2

15.6

16.1

17.1

17.6

18.2

19.7

20.3

20.8

22.4

22.9

23.5

22.6

22.9

23.4

24.7

5800 14.9

15.4

15.9

16.9

17.4

17.9

19.4

19.9

20.5

22.0

22.6

23.1

22.3

22.6

23.0

24.4

5900 14.7

15.2

15.6

16.6

17.1

17.6

19.1

19.6

20.2

21.7

22.2

22.8

21.9

22.2

22.7

24.1

6000 14.5

14.9

15.4

16.4

16.8

17.3

18.8

19.3

19.9

21.4

21.9

22.4

21.6

21.9

22.3

23.7

6100 14.3

14.7

15.2

16.1

16.6

17.1

18.5

19.0

19.6

21.0

21.5

22.1

21.3

21.6

22.0

23.4

6200 14.1

14.5

15.0

15.9

16.3

16.8

18.3

18.8

19.3

20.7

21.2

21.7

21.0

21.3

21.7

23.1

6300 13.9

14.3

14.7

15.7

16.1

16.6

18.0

18.5

19.0

20.4

20.9

21.4

20.8

21.0

21.3

22.8

6400 13.7

14.1

14.5

15.4

15.9

16.3

17.7

18.2

18.7

20.1

20.6

21.1

20.5

20.7

21.0

22.6

6500 13.5

13.9

14.3

15.2

15.6

16.1

17.5

18.0

18.4

19.8

20.3

20.8

20.2

20.4

20.7

22.3

6600 13.3

13.7

14.1

15.0

15.4

15.9

17.2

17.7

18.2

19.5

20.0

20.5

20.0

20.1

20.4

22.0

29.0

28.6

28.1

27.7

27.3

29.0

28.5

28.0

27.6

27.2

31.8

31.3

30.8

30.3

29.9

31.7

31.2

30.7

30.2

29.8

26.9

26.8

29.4

29.3

26.5

26.4

29.0

28.9

26.1

26.0

28.6

28.5

25.7

25.6

28.2

28.1

25.3

25.3

27.8

27.7

25.0

24.9

27.4

27.3

24.6

24.6

27.0

26.9

24.3

24.2

26.7

26.6

24.0

23.9

26.3

26.2

23.7

23.6

26.0

25.9

23.4

23.3

25.6

25.6

23.1

23.0

25.3

25.2

22.8

22.7

25.0

24.9

22.5

22.4

24.7

24.6

22.2

22.1

24.4

24.3

21.9

21.8

24.1

24.0

27.2

26.8

26.5

26.1

25.8

25.5

25.1

24.8

24.5

24.2

23.9

31.6

31.1

30.6

30.1

29.7

29.2

28.8

28.4

28.0

27.6

58 MUA-PRC004-EN

Performance

Data unit capacity

Table PD-46. Size 066 design supply air dew point, cfm dry-bulb

°F

85

95

105

115 wet-bulb

°F

76

78

80

76

78

80

76

78

80

76

78

80

46

3638

48

3680

3636

3700

4083

— design supply air dew point, °F

50 52 54

4054

3610

4485

3975

4990

4395

3896

4018

4169

4614

3777

4463

3918

4725

3933

5267

4257

6128

4837

3956

4994

4337

3833

5405

4410

3790

56

5593

4884

4304

5643

4838

4238

6267

5026

4213

5562

4482

58

6328

5467

4779

6468

5444

4712

5793

4725

6508

5126

60

6175

5342

6198

5279

5399

5948

62

6025

5986

6285

MUA-PRC004-EN 59

Performance

Data unit w/TE wheel capacity

Table PD-47. Size 031 cooling capacity without reheat, MBh cfm

2200

2300

2400

2500

2600

2700

2800

2900

3000

3100 total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent

85/76

332.54

142.54

-

-

334.92

143.45

337.20

144.36

339.37

145.75

342.53

141.73

344.56

142.46

-

-

-

-

-

-

85/78

334.18

145.91

-

-

336.62

147.03

338.95

148.09

341.18

149.64

344.39

145.78

346.48

146.66

-

-

-

-

-

-

85/80

330.52

146.41

-

-

-

-

334.11

143.45

335.82

149.28

338.32

150.60

340.71

151.82

342.99

153.53

346.26

149.82

348.40

150.87

95/76 entering dry-bulb/wet-bulb °F

95/78 95/80 105/76

327.29

134.30

-

-

329.56

134.82

331.73

135.35

333.81

136.11

336.87

131.71

338.81

132.04

-

-

-

-

-

-

-

-

-

-

-

-

-

328.93

137.67

331.26

138.40

333.49

139.08

335.62

140.00

338.73

135.75

340.73

136.24

-

-

-

-

325.51

138.96

328.99

135.57

330.57

141.04

332.96

141.97

335.24

142.81

337.43

143.89

340.60

139.80

342.65

140.45

322.05

126.05

-

-

324.20

126.19

326.26

126.34

328.24

126.47

331.21

121.68

333.06

121.62

-

-

-

-

-

-

105/78

323.69

129.42

-

-

325.90

129.77

328.02

130.07

330.05

130.36

333.07

125.73

334.98

125.82

-

-

-

-

-

-

105/80

320.50

131.50

-

-

-

-

323.88

127.70

325.33

132.79

327.60

133.34

329.78

133.80

331.86

134.25

334.94

129.77

336.90

130.03

115/76

316.81

117.81

-

-

318.84

117.56

320.80

117.33

322.67

116.84

325.54

111.65

327.31

111.20

-

-

-

-

-

-

115/78

318.45

121.18

-

-

320.54

121.13

322.55

121.06

324.48

120.72

327.41

115.70

329.23

115.40

-

-

-

-

-

-

115/80

315.50

124.04

-

-

-

-

318.76

119.83

320.09

124.55

322.24

124.71

324.31

124.79

326.29

124.61

329.27

119.75

331.15

119.61

Note: Capacities are with all compressors runnning, balanced supply and exhaust airflow, and ARI 1060 return air conditions of 75/63°F. Dashed fields indicate that the unit will cycle compressor to maintain the DP setpoint above 45°F.

Table PD-48. Size 031 cooling capacity with reheat, MBh cfm

2200

2300

2400

2500

2600

2700

2800

2900

3000

3100 total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent

85/76

342.40

142.16

344.68

143.04

-

-

-

-

-

-

-

-

-

-

-

-

346.86

143.85

348.95

144.61

85/78

341.72

144.94

-

-

344.16

146.03

346.50

147.05

-

-

-

-

-

-

-

-

348.73

148.02

350.88

148.94

85/80

338.10

146.01

-

-

-

-

-

-

340.81

147.29

343.44

148.66

345.93

149.90

348.32

151.07

350.60

152.19

352.80

153.26

95/76 entering dry-bulb/wet-bulb °F

95/78 95/80 105/76

338.19

133.28

340.40

133.76

-

-

-

-

-

-

-

-

-

-

-

-

342.52

134.19

344.55

134.56

337.60

136.44

-

-

339.96

137.14

342.22

137.78

-

-

-

-

-

-

-

-

344.39

138.35

346.48

138.88

334.16

138.29

-

-

-

-

-

-

336.78

139.19

339.32

140.16

341.73

141.01

344.04

141.79

346.26

142.52

348.40

143.20

336.12

124.48

-

-

-

-

-

-

-

-

-

-

-

-

-

-

338.18

124.52

340.15

124.50

105/78

333.48

127.94

-

-

335.75

128.26

337.94

128.50

-

-

-

-

-

-

-

-

340.05

128.69

342.08

128.83

105/80

332.75

131.09

335.19

131.66

337.52

132.12

339.76

132.52

-

-

-

-

-

-

-

-

341.92

132.85

344.00

133.15

115/76

331.84

115.21

-

-

-

-

-

-

-

-

-

-

-

-

-

-

333.83

114.85

335.75

114.45

115/78

329.35

119.44

-

-

331.55

119.37

333.66

119.22

-

-

-

-

-

-

-

-

335.70

119.02

337.68

118.77

115/80

328.72

122.99

331.07

123.16

333.32

123.24

335.48

123.24

-

-

-

-

-

-

-

-

337.57

123.19

339.60

123.09

Note: Capacities are with all compressors runnning, balanced supply and exhaust airflow, and ARI 1060 return air conditions of 75/63°F. Dashed fields indicate that the unit will cycle compressor to maintain the DP setpoint above 45°F.

60 MUA-PRC004-EN

Performance

Data unit w/TE wheel capacity

Table PD-49. Size 031 reheat, MBh cfm

1800

2200

2600

3100 entering dry-bulb/wet-bulb °F

55/48 55/50 55/52 65/56 65/58 65/60 75/66 75/68 75/70 85/76 85/78 85/80 95/76 95/78 95/80 105/76 105/78 105/80 115/76 115/78 115/80

46.5

46.8

47.0

47.8

48.0

48.3

49.3

49.5

49.8

50.8

51.0

51.2

51.1

51.3

51.5

51.4

51.6

51.8

51.6

47.9

48.1

48.3

49.2

49.4

49.6

50.8

51.0

51.2

52.3

52.5

52.7

52.9

53.1

53.3

53.5

53.7

53.9

54.1

49.2

49.4

49.5

50.6

50.8

50.9

52.2

52.3

52.5

53.7

53.9

54.0

54.6

54.8

54.9

55.5

55.6

55.8

56.4

49.8

49.9

50.0

51.5

51.6

51.7

53.4

53.5

53.6

55.2

55.3

55.5

56.5

56.6

56.7

57.7

57.8

57.9

58.9

51.9

54.3

56.5

59.1

52.1

54.4

56.7

59.2

Note: Capacities are for balanced supply and exhaust airflow with ARI 1060 return air conditions (75/63°F).

Table PD-50. Size 031 condenser reheat max temperature rise, °F cfm entering dry-bulb/wet-bulb °F

55/48 55/50 55/52 65/56 65/58 65/60 75/66 75/68 75/70 85/76 85/78 85/80 95/76 95/78 95/80 105/76 105/78 105/80 115/76 115/78 115/80

1800 24.4

24.5

24.7

25.0

25.1

25.3

25.8

25.9

26.0

26.5

26.6

26.7

26.6

26.7

26.9

26.8

26.9

2200 20.6

20.7

20.7

21.1

21.2

21.3

21.7

21.8

21.9

22.3

22.4

22.5

22.6

22.6

22.7

22.8

22.9

2600 17.9

18.0

18.0

18.4

18.4

18.5

18.9

18.9

19.0

19.4

19.4

19.5

19.7

19.7

19.8

20.0

20.1

3100 15.2

15.3

15.3

15.7

15.7

15.8

16.2

16.2

16.3

16.7

16.7

16.8

17.1

17.1

17.1

17.4

17.5

27.0

23.0

20.1

17.5

26.9

23.0

20.3

17.8

27.0

23.1

20.4

17.8

27.1

23.2

20.4

17.9

Note: Temperature rises are for balanced supply and exhaust airflow with ARI 1060 return air conditions (75/63°F).

Table PD-51. Size 031 design supply air dew point, cfm dry-bulb

(°F)

85

95

105

115 wet-bulb

(°F)

76

78

80

76

78

80

76

78

80

76

78

80

46

2781

2656

2531

2742

2617

2492

2704

2579

2453

2665

2540

2415

48

3043

2918

2792

3004

2879

2754

2965

2840

2715

2927

2802

2677

2977

3063

2938 design supply air dew point (°F)

50 52 54 56

3054

58

Note: Dew point temps are with all compressors running, balanced supply and exhaust airflow and ARI 1060 return air conditions of 75/63°F.

60

62

MUA-PRC004-EN 61

Performance

Data unit w/TE wheel capacity

Table PD-52. Size 040 cooling capacity without reheat, MBh cfm

2900

3000

3100

3200

3300

3400

3500

3600

3700

3800

3900

4000 total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent

85/80

378.18

169.32

380.27

170.30

382.40

171.33

384.46

172.32

387.96

167.30

389.92

168.20

342.99

153.53

368.38

163.79

368.38

163.79

370.95

165.08

373.41

166.87

377.11

162.29

85/78

376.20

165.05

378.19

165.84

380.28

166.73

382.29

167.57

385.75

162.40

387.66

163.15

341.18

149.64

366.53

160.06

366.53

160.06

369.05

161.20

371.47

162.85

375.13

158.12

85/76

374.21

160.79

376.12

161.38

378.16

162.12

380.13

162.81

383.53

157.50

385.41

158.11

369.53

158.83

373.14

153.96

-

-

-

-

-

-

-

-

369.32

154.07

371.32

154.57

373.34

155.10

375.29

155.58

378.68

150.04

380.54

150.42

335.62

140.00

360.07

150.84

360.07

150.84

362.50

151.63

364.83

152.67

368.41

147.58

95/76 entering dry-bulb/wet-bulb °F

95/78 95/80 105/76

367.33

149.81

369.25

150.11

371.22

150.50

373.12

150.83

376.47

145.14

378.28

145.38

362.89

148.65

366.42

143.42

-

-

-

-

-

-

-

-

371.31

158.34

373.40

159.03

375.46

159.71

377.46

160.33

380.89

154.94

382.80

155.46

337.43

143.89

361.92

154.56

361.92

154.56

364.39

155.50

366.77

156.69

370.39

151.75

360.46

138.82

362.38

138.85

364.28

138.87

366.12

138.84

369.40

132.78

371.16

132.64

356.25

138.48

359.70

132.87

-

-

-

-

-

-

-

-

105/78 105/80

330.05

331.86

130.36

134.25

353.61

355.45

141.61

145.34

353.61

355.45

141.61

145.34

355.94

357.84

142.05

145.92

358.19

360.13

142.50

146.52

361.68

363.67

137.04

141.20

362.44

364.43

143.09

147.35

364.45

366.53

143.31

147.77

366.40

368.52

143.48

148.09

368.28

370.45

143.59

148.35

371.61

373.83

137.68

142.58

373.41

375.67

137.68

142.72

115/76

353.58

127.84

355.50

127.59

357.34

127.25

359.11

126.85

362.34

120.42

364.03

119.90

349.61

128.30

352.98

122.33

-

-

-

-

-

-

-

-

115/78

355.57

132.11

357.58

132.05

359.46

131.86

361.28

131.61

364.55

125.32

366.29

124.94

324.48

120.72

347.15

132.38

347.15

132.38

349.39

132.47

351.55

132.32

354.96

126.50

115/80

357.55

136.37

359.66

136.51

361.58

136.46

363.45

136.36

366.76

130.22

368.55

129.99

326.29

124.61

348.99

136.11

348.99

136.11

351.28

136.34

353.49

136.34

356.95

130.66

Note: Capacities are with all compressors runnning, balanced supply and exhaust airflow, and ARI 1060 return air conditions of 75/63°F. Dashed fields indicate that the unit will cycle compressor to maintain the DP setpoint above 45°F.

Table PD-53. Size 040 cooling capacity with reheat, MBh cfm

2900

3000

3100

3200

3300

3400

3500

3600

3700

3800

3900

4000 total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent

85/76

381.56

158.11

-

-

383.66

158.77

385.82

159.51

-

-

-

-

-

-

-

-

387.89

160.67

389.91

161.33

391.86

161.98

393.75

162.60

85/78

381.13

161.45

383.60

162.56

385.78

163.40

387.98

164.29

-

-

-

-

-

-

-

-

390.09

165.61

392.15

166.43

394.14

167.22

396.07

167.99

85/80

378.05

163.33

380.66

164.59

-

-

-

-

383.17

165.80

385.64

167.01

387.90

168.04

390.14

169.08

392.29

170.54

394.39

171.53

396.42

172.47

398.39

173.38

95/76 entering dry-bulb/wet-bulb °F

95/78 95/80 105/76

376.22

147.54

-

-

378.35

147.90

380.47

148.28

-

-

-

-

-

-

-

-

382.51

148.80

384.51

149.10

386.43

149.37

388.30

149.61

375.91

151.31

378.26

151.99

380.47

152.53

382.63

153.06

-

-

-

-

-

-

-

-

384.71

153.74

386.75

154.19

388.71

154.61

390.62

155.00

372.95

153.96

375.50

154.84

-

-

-

-

377.95

155.66

380.30

156.44

382.59

157.17

384.79

157.85

386.91

158.68

388.98

159.29

390.99

159.86

392.94

160.39

373.03

137.03

375.12

137.05

-

-

-

-

-

-

-

-

-

-

-

-

377.14

136.94

379.10

136.86

381.00

136.76

382.85

136.63

105/78 105/80

-

-

-

-

-

-

-

-

367.86

144.59

370.33

145.10

-

-

-

-

370.69

372.73

141.18

145.53

372.93

374.97

141.41

145.87

375.15

377.27

141.66

146.30

377.28

379.44

141.84

146.62

379.34

381.54

141.88

146.81

381.34

383.58

141.96

147.06

383.28

385.56

142.00

147.25

385.17

387.49

142.01

147.40

115/76

367.72

126.16

369.77

125.82

-

-

-

-

-

-

-

-

-

-

-

-

371.77

125.07

373.70

124.63

375.57

124.15

377.39

123.64

115/80

362.76

135.22

365.17

135.35

-

-

-

-

367.51

135.39

369.63

135.29

371.96

135.43

374.09

135.39

376.17

134.95

378.18

134.82

380.13

134.64

382.03

134.41

115/78

365.47

131.04

367.59

130.84

369.84

130.79

371.93

130.61

-

-

-

-

-

-

-

-

373.97

130.01

375.94

129.73

377.85

129.39

379.71

129.03

Note: Capacities are with all compressors runnning, balanced supply and exhaust airflow, and ARI 1060 return air conditions of 75/63°F. Dashed fields indicate that the unit will cycle compressor to maintain the DP setpoint above 45°F.

62 MUA-PRC004-EN

Performance

Data unit w/TE wheel capacity

Table PD-54. Size 040 reheat, MBh cfm entering dry-bulb/wet-bulb °F

55/48 55/50 55/52 65/56 65/58 65/60 75/66 75/68 75/70 85/76 85/78 85/80 95/76 95/78 95/80 105/76 105/78 105/80 115/76 115/78 115/80

2200

2600

3000

3400

3800

4000

68.6 69.0

69.4

70.4

70.8

71.2

72.7

73.1

73.5

75.0

75.4

75.8

75.2

75.6

76.0

75.5

75.9

70.1 70.5

70.9

72.1

72.5

72.9

74.5

74.9

75.3

77.0

77.3

77.7

77.4

77.8

78.2

77.9

78.3

71.3 71.7

72.0

73.5

73.9

74.2

76.1

76.4

76.8

78.6

79.0

79.4

79.4

79.7

80.1

80.1

80.5

72.6 72.9

73.2

74.9

75.2

75.6

77.6

77.9

78.2

80.2

80.5

80.8

81.2

81.6

81.9

82.3

82.6

73.3 73.6

74.0

75.9

76.2

76.4

78.7

79.0

79.3

81.5

81.8

82.1

82.9

83.2

83.5

84.3

84.6

73.7 74.0

74.2

76.3

76.6

76.9

79.3

79.5

79.8

82.2

82.5

82.8

83.7

84.0

84.3

85.3

85.6

76.3

75.8

78.7

78.3

80.8

80.9

82.9

83.3

84.9

85.7

85.8

86.8

76.2

78.7

81.2

83.6

86.0

87.1

76.6

79.1

81.6

84.0

86.3

87.4

Note: Capacities are for balanced supply and exhaust airflow with ARI 1060 return air conditions (75/63°F).

cfm

2200

2600

3000

3400

3800

4000

Table PD-55. Size 040 condenser reheat max temperature rise, °F entering dry-bulb/wet-bulb °F

55/48 55/50 55/52 65/56 65/58 65/60 75/66 75/68 75/70 85/76 85/78 85/80 95/76 95/78 95/80 105/76 105/78 105/80 115/76 115/78 115/80

29.3 29.4

29.6

30.0

30.2

30.3

30.9

31.1

31.2

31.8

32.0

32.1

31.9

32.1

32.2

32.0

32.2

32.4

32.1

25.4 25.5

25.6

26.0

26.2

26.3

26.8

27.0

27.1

27.6

27.8

27.9

27.8

27.9

28.1

27.9

28.1

28.2

28.1

22.4 22.5

22.6

23.0

23.1

23.2

23.7

23.8

23.9

24.5

24.6

24.7

24.7

24.8

24.9

24.9

25.0

25.1

25.1

20.1 20.2

20.3

20.7

20.8

20.9

21.4

21.4

21.5

22.0

22.1

22.2

22.3

22.4

22.4

22.6

22.6

22.7

22.8

18.2 18.3

18.3

18.8

18.8

18.9

19.4

19.4

19.5

20.0

20.1

20.1

20.3

20.4

20.5

20.7

20.7

20.8

21.0

17.4 17.4

17.5

17.9

18.0

18.0

18.6

18.6

18.7

19.2

19.2

19.3

19.5

19.6

19.6

19.9

19.9

20.0

20.2

32.3

28.2

25.2

22.9

21.1

20.3

32.5

28.4

25.3

23.0

21.1

20.3

Note: Capacities are for balanced supply and exhaust airflow with ARI 1060 return air conditions (75/63°F).

Table PD-56. Size 040 design supply air dewpoint, cfm dry-bulb

(°F)

85

95

105

115 wet-bulb

(°F)

76

78

80

76

78

80

76

78

80

76

78

80

46

3422

3271

3121

3368

3218

3067

3315

3164

3014

3261

3111

2960

48

3754

3603

3453

3700

3550

3399

3647

3496

3346

3593

3443

3292

3979

3828

3678

3925

3775

3624 design supply air dew point (°F)

50 52 54 56

3936

3785

3882

3731

3956

58

Note: Dew point temps are with all compressors running, balanced supply and exhaust airflow and ARI 1060 return air conditions of 75/63°F.

60

62

MUA-PRC004-EN 63

Performance

Data unit w/TE wheel capacity

Table PD-57. Size 051 cooling capacity without reheat, MBh cfm

3200

3300

3400

3500

3600

3700

3800

3900

4000

4100

4200

4300

4400

4500

4600

4700

4800

4900

5000

5100 total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent

85/76

422.97

181.48

425.27

182.39

427.50

183.23

429.68

183.99

433.68

177.91

433.86

185.50

435.87

186.20

437.82

186.87

439.72

187.55

418.18

179.55

420.61

180.55

-

-

-

-

-

-

-

-

-

-

-

-

-

-

443.61

181.25

445.43

181.86

85/78

425.46

186.53

427.81

187.56

430.09

188.53

432.31

189.44

436.35

183.50

436.57

191.23

438.63

192.08

440.62

192.89

442.56

193.71

415.39

182.04

418.02

183.20

420.58

184.35

423.06

185.47

-

-

-

-

-

-

-

-

-

-

446.49

187.54

448.36

188.28

85/80

427.96

191.58

430.35

192.73

432.67

193.83

434.93

194.89

439.02

189.09

439.29

196.97

441.38

197.96

443.42

198.92

445.40

199.87

414.93

185.25

-

-

-

-

-

-

-

-

417.69

186.60

420.38

187.88

422.98

189.15

425.50

190.39

449.38

193.82

451.28

194.69

95/76 entering dry-bulb/wet-bulb °F

95/78 95/80 105/76

414.30

168.92

416.51

169.47

418.66

169.98

420.75

170.41

424.68

164.00

424.79

171.26

426.73

171.64

428.63

171.97

430.46

172.32

409.70

167.66

412.03

168.32

-

-

-

-

-

-

-

-

-

-

-

-

-

-

434.30

165.68

436.07

165.96

416.79

173.97

419.05

174.65

421.24

175.28

423.38

175.86

427.35

169.59

427.50

176.99

429.49

177.51

431.43

178.00

433.31

178.48

407.12

170.86

409.65

171.66

412.10

172.47

414.48

173.24

-

-

-

-

-

-

-

-

-

-

437.19

171.97

439.00

172.37

419.29

179.02

421.59

179.82

423.82

180.58

426.01

181.31

430.02

175.19

430.22

182.73

432.25

183.39

434.23

184.02

436.15

184.64

406.78

174.41

-

-

-

-

-

-

-

-

409.43

175.42

412.00

176.34

414.50

177.27

416.93

178.17

440.07

178.25

441.93

178.79

405.63

156.35

407.75

156.56

409.81

156.73

411.83

156.83

415.68

150.09

415.72

157.02

417.60

157.07

419.43

157.07

421.21

157.09

401.22

155.78

403.45

156.09

-

-

-

-

-

-

-

-

-

-

-

-

-

-

425.00

150.11

426.72

150.05

105/78 105/80

-

-

-

-

-

-

-

-

-

-

396.03

162.87

-

-

398.63

163.58

-

-

-

-

398.86

401.16

159.67

164.23

401.28

403.63

160.12

164.80

403.62

406.02

160.58

165.38

405.90

408.35

161.02

165.94

408.12

410.62

161.40

166.45

410.29

412.83

161.74

166.91

412.40

414.98

162.03

167.33

414.46

417.08

162.28

167.73

418.35

421.02

155.68

161.28

418.44

421.15

162.75

168.49

420.36

423.11

162.95

168.82

422.23

425.03

163.10

169.12

424.05

426.90

163.25

169.41

427.88

430.77

156.39

162.68

429.64

432.57

156.47

162.89

115/76 115/78

-

-

-

-

-

-

-

-

-

-

-

-

-

390.59

148.49

392.90

148.58

392.74

395.14

143.89

148.70

394.88

397.33

143.86

148.79

-

-

-

-

-

-

-

-

-

-

396.96

399.45

143.78

148.83

398.99

401.53

143.65

148.82

400.97

403.55

143.49

148.78

402.90

405.53

143.25

148.70

406.68

409.35

136.18

141.77

406.65

409.37

142.78

148.51

408.46

411.22

142.50

148.38

410.23

413.03

142.18

148.20

411.96

414.80

141.87

148.02

415.69

418.58

134.54

140.82

417.36

420.28

134.15

140.57

115/80

401.95

153.88

404.07

154.00

406.13

154.08

408.16

154.15

412.03

147.37

412.08

154.25

413.98

154.26

415.83

154.23

417.64

154.18

388.00

152.38

-

-

390.48

152.74

-

-

-

-

392.89

153.05

395.25

153.26

397.54

153.50

399.77

153.71

421.46

147.11

423.21

146.99

Note: Capacities are with all compressors runnning, balanced supply and exhaust airflow, and ARI 1060 return air conditions of 75/63°F. Dashed fields indicate that the unit will cycle compressor to maintain the DP setpoint above 45°F.

64 MUA-PRC004-EN

Performance

Data unit w/TE wheel capacity

Table PD-58. Size 051 cooling capacity with reheat installed, MBh cfm

3200

3300

3400

3500

3600

3700

3800

3900

4000

4100

4200

4300

4400

4500

4600

4700

4800

4900

5000

5100 total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent

85/80

431.84

187.47

434.52

188.73

437.08

189.86

439.63

191.15

-

-

-

-

-

-

-

-

-

-

-

-

-

-

442.07

192.29

444.45

193.39

446.77

194.45

449.01

195.49

451.20

196.50

453.33

197.48

455.65

198.80

457.43

199.39

459.40

200.31

85/76

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

436.78

180.99

439.07

181.83

441.30

182.63

443.47

183.41

445.57

184.15

447.63

184.86

449.87

185.91

451.58

186.24

453.48

186.91

85/78

434.55

184.56

437.02

185.62

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

439.43

186.64

441.76

187.61

444.03

188.54

446.24

189.45

448.38

190.33

450.48

191.17

452.76

192.36

454.50

192.82

456.44

193.61

95/76 entering dry-bulb/wet-bulb °F

95/78 95/80 105/76

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

430.29

168.11

432.51

168.60

434.68

169.05

436.80

169.48

438.86

169.87

440.87

170.23

443.21

171.07

444.75

170.84

446.61

171.15

428.20

172.43

430.60

173.10

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

432.93

173.76

435.20

174.38

437.42

174.96

439.57

175.52

441.67

176.04

443.72

176.54

446.10

177.51

447.67

177.42

449.57

177.85

425.64

176.06

428.24

176.96

430.72

177.74

433.20

178.62

-

-

-

-

-

-

-

-

-

-

-

-

-

-

435.58

179.42

437.89

180.16

440.15

180.87

442.35

181.56

444.48

182.22

446.57

182.84

448.99

183.96

450.60

183.99

452.53

184.56

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

425.96

155.38

-

-

428.07

155.47

430.13

155.54

432.14

155.58

434.11

155.59

436.56

156.23

437.92

155.44

439.75

155.39

105/78 105/80

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

419.45

164.64

421.95

165.18

421.84

424.37

160.31

165.62

424.17

426.77

160.58

166.10

-

-

-

-

-

-

-

-

-

-

-

-

-

-

426.44

429.09

160.89

166.54

428.65

431.34

161.16

166.94

430.80

433.53

161.38

167.29

432.90

435.68

161.58

167.62

434.95

437.77

161.76

167.93

436.96

439.81

161.90

168.21

439.44

442.33

162.67

169.11

440.84

443.76

162.01

168.59

442.71

445.67

162.10

168.80

115/76 115/78

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

419.95

148.02

422.09

147.93

421.45

424.18

141.89

147.80

423.46

426.24

141.61

147.65

425.43

428.24

141.30

147.47

427.35

430.20

140.96

147.26

429.90

432.78

141.38

147.83

431.09

434.01

140.04

146.61

432.88

435.84

139.64

146.34

417.75

148.06

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

115/80

413.25

153.23

415.67

153.40

418.02

153.49

420.35

153.58

-

-

-

-

-

-

-

-

-

-

-

-

-

-

422.59

153.67

424.78

153.71

426.92

153.71

429.01

153.69

431.05

153.65

433.05

153.57

435.67

154.27

436.93

153.19

438.80

153.04

Note: Capacities are with all compressors runnning, balanced supply and exhaust airflow, and ARI 1060 return air conditions of 75/63°F. Dashed fields indicate that the unit will cycle compressor to maintain the DP setpoint above 45°F.

MUA-PRC004-EN 65

Performance

Data unit w/TE wheel capacity

Table PD-59. Size 051 reheat data, MBh cfm entering dry-bulb/wet-bulb °F

55/48 55/50 55/52 65/56 65/58 65/60 75/66 75/68 75/70 85/76 85/78 85/80 95/76 95/78 95/80 105/76 105/78 105/80 115/76 115/78 115/80

2900 96.9

97.5

98.2

99.7

100.4 101.0 103.2 103.8 104.4 106.6 107.2 107.9 106.9 107.6

108.2 107.3 107.9

108.5

107.6

108.2

108.8

3300 98.5

99.1

99.8 101.6 102.2 102.9 105.3 106.0 106.6 109.1 109.7 110.4 109.5 110.2

110.8 110.0 110.6

111.3

110.4

111.1

111.8

3700 100.0 100.6 101.3 103.2 103.9 104.5 107.2 107.8 108.5 111.1 111.8 112.4 111.8 112.4

113.1 112.5 113.1

113.8

113.2

113.8

114.5

4100 102.1 102.6 103.2 105.3 105.9 106.5 109.2 109.8 110.3 113.0 113.6 114.2 114.0 114.6

115.1 115.0 115.5

116.1

115.9

116.5

117.1

4500 102.5 103.1 103.7 106.1 106.7 107.3 110.4 111.0 111.6 114.6 115.2 115.8 115.9 116.5

117.1 117.2 117.7

118.3

118.4

119.0

119.6

4900 103.5 104.0 104.6 107.3 107.9 108.5 111.8 112.3 112.9 116.2 116.8 117.3 117.8 118.4

119.0 119.5 120.0

120.6

121.1

121.7

122.2

5100 103.9 104.5 105.0 107.9 108.4 109.0 112.4 113.0 113.5 116.9 117.5 118.0 118.7 119.2

119.8 120.5 121.0

121.6

122.2

122.8

123.3

Note: Capacities are for balanced supply and exhaust airflow with ARI 1060 return air conditions (75/63°F).

Table PD-60. Size 051 condenser reheat max temperature rise, °F cfm entering dry-bulb/wet-bulb °F

55/48 55/50 55/52 65/56 65/58 65/60 75/66 75/68 75/70 85/76 85/78 85/80 95/76 95/78 95/80 105/76 105/78 105/80 115/76 115/78 115/80

2900 32.1

32.3

32.5

32.9

33.1

33.3

34.0

34.2

34.3

35.0

35.2

35.4

35.1

35.3

35.5

35.2

35.4

3300 28.7

28.9

29.1

29.5

29.7

29.9

30.5

30.7

30.9

31.5

31.7

31.8

31.6

31.8

32.0

31.8

31.9

3700 26.0

26.2

26.3

26.8

27.0

27.1

27.7

27.9

28.0

28.7

28.8

29.0

28.8

29.0

29.1

29.0

29.1

4100 24.0

24.2

24.3

24.7

24.8

25.0

25.5

25.6

25.8

26.3

26.4

26.6

26.5

26.7

26.8

26.7

26.9

4500 22.0

22.1

22.2

22.7

22.8

22.9

23.5

23.6

23.7

24.3

24.4

24.6

24.6

24.7

24.8

24.8

25.0

4900 20.5

20.5

20.6

21.1

21.2

21.3

21.9

22.0

22.1

22.7

22.8

22.9

23.0

23.1

23.2

23.3

23.4

5100 19.8

19.8

19.9

20.4

20.5

20.6

21.2

21.3

21.3

21.9

22.0

22.1

22.2

22.3

22.4

22.6

22.6

35.6

32.1

29.3

27.0

25.1

23.5

22.7

35.3

31.9

29.1

27.0

25.1

23.6

22.9

35.5

32.0

29.3

27.1

25.2

23.7

23.0

35.7

32.2

29.5

27.2

25.3

23.8

23.0

Note: Capacities are for balanced supply and exhaust airflow with ARI 1060 return air conditions (75/63°F).

Table PD-61. Size 051 design supply air dew point, cfm dry-bulb

(°F)

85

95

105

115 wet-bulb

(°F)

76

78

80

76

78

80

76

78

80

76

78

80

46

4263

4063

3863

4211

4011

3811

4159

3959

3759

4107

3907

3707

48

4701

4501

4301

4649

4449

4249

4597

4397

4197

4545

4345

4145 design supply air dew point (°F)

50 52 54 56

4939

4739

5087

4887

4687

5035

4835

4635

4983

4783

4583

5073

5021

58

Note: Dew point temps are with all compressors running, balanced supply and exhaust airflow and ARI 1060 return air conditions of 75/63°F.

60

62

66 MUA-PRC004-EN

Performance

Data unit w/TE wheel capacity

Table PD-62. Size 066 cooling capacity without reheat, MBh cfm

4000

4100

4200

4300

4400

4500

4600

4700

4800

4900

5000

5100

5200

5300

5400

5500

5600

5700

5800

5900

6000

6100

6200

6300

6400

6500

6600 total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent

85/76

482.61

206.50

484.68

207.27

486.71

208.03

488.68

208.75

490.62

209.44

492.52

210.11

494.37

210.78

498.61

203.15

497.95

212.01

499.67

212.60

501.37

213.17

503.01

213.72

507.23

207.00

508.85

207.49

471.48

202.20

473.82

203.13

476.10

204.03

478.31

204.89

480.49

205.71

469.07

201.28

-

-

-

-

-

-

-

-

-

-

-

-

-

-

85/78

485.61

212.85

487.72

213.77

489.79

214.66

491.81

215.52

493.79

216.35

495.72

217.16

497.62

217.96

501.90

210.46

501.27

219.46

503.04

220.18

504.77

220.88

506.46

221.56

510.71

214.96

512.37

215.58

474.25

207.90

476.63

208.96

478.96

209.99

481.23

210.98

483.44

211.93

466.71

204.62

-

-

469.29

205.74

471.80

206.84

-

-

-

-

-

-

-

-

85/80

488.61

219.20

490.76

220.26

492.87

221.29

494.94

222.29

496.95

223.26

498.93

224.21

500.87

225.14

505.19

217.77

504.60

226.90

506.41

227.75

508.18

228.59

509.90

229.40

514.19

222.93

515.89

223.68

477.02

213.59

479.45

214.79

481.83

215.95

484.14

217.07

486.40

218.16

463.88

207.28

-

-

-

-

-

-

466.64

208.62

469.34

209.93

471.97

211.17

474.52

212.41

95/76 entering dry-bulb/wet-bulb °F

95/78 95/80 105/76

471.56

190.66

473.55

191.12

475.49

191.55

477.39

191.95

479.25

192.31

481.07

192.66

482.86

193.00

487.03

185.04

486.30

193.57

487.97

193.83

489.60

194.06

491.20

194.27

495.36

186.58

496.92

186.73

460.90

187.95

463.14

188.56

465.32

189.15

467.45

189.68

469.53

190.19

458.59

187.36

-

-

-

-

-

-

-

-

-

-

-

-

-

-

474.56

197.02

476.59

197.61

478.58

198.18

480.52

198.72

482.42

199.23

484.28

199.71

486.11

200.18

490.32

192.35

489.63

201.02

491.34

201.41

493.01

201.77

494.64

202.11

498.84

194.54

500.45

194.82

463.67

193.64

465.96

194.39

468.19

195.11

470.36

195.78

472.48

196.41

453.92

190.48

456.45

191.34

458.92

192.14

461.32

192.92

-

-

-

-

-

-

-

-

477.56

203.37

479.64

204.10

481.66

204.81

483.65

205.49

485.59

206.14

487.49

206.76

489.36

207.36

493.61

199.66

492.96

208.46

494.70

208.98

496.42

209.48

498.09

209.95

502.32

202.51

503.97

202.91

466.44

199.33

468.77

200.22

471.05

201.06

473.27

201.87

475.44

202.64

451.16

193.59

453.86

194.64

-

-

-

-

456.50

195.67

459.08

196.65

461.60

197.57

464.05

198.48

460.52

174.83

462.42

174.96

464.28

175.07

466.10

175.15

467.89

175.19

469.63

175.22

471.35

175.23

475.46

166.93

474.66

175.13

476.27

175.06

477.84

174.95

479.38

174.82

483.49

166.16

485.00

165.97

450.32

173.69

452.46

173.99

454.55

174.26

456.58

174.48

458.57

174.67

448.12

173.43

-

-

-

-

-

-

-

-

-

-

-

-

-

-

105/80

466.52

187.54

468.51

187.95

470.45

188.34

472.36

188.69

474.22

189.02

476.05

189.31

477.85

189.58

482.03

181.55

481.32

190.02

483.00

190.21

484.65

190.37

486.27

190.50

490.45

182.09

492.04

182.15

455.86

185.07

458.09

185.65

460.28

186.18

462.40

186.67

464.48

187.12

441.27

181.30

443.84

182.01

-

-

-

-

446.35

182.71

448.82

183.37

451.23

183.96

453.57

184.56

115/76

449.48

158.99

451.30

158.81

453.07

158.60

454.81

158.35

456.52

158.07

458.19

157.77

459.84

157.45

463.88

148.82

463.02

156.69

464.56

156.29

466.08

155.85

467.56

155.37

471.61

145.74

473.07

145.20

439.74

159.43

441.78

159.42

443.77

159.38

445.71

159.28

447.62

159.15

437.64

159.51

-

-

-

-

-

-

-

-

-

-

-

-

-

-

115/78

452.47

165.35

454.34

165.30

456.16

165.23

457.94

165.12

459.69

164.99

461.40

164.82

463.09

164.63

467.17

156.13

466.35

164.13

467.93

163.86

469.49

163.55

471.01

163.21

475.10

153.71

476.59

153.30

442.51

165.12

444.60

165.25

446.63

165.34

448.62

165.37

450.57

165.38

433.63

164.57

435.93

164.78

438.18

164.92

440.37

165.07

-

-

-

-

-

-

-

-

105/78

463.52

181.18

465.47

181.46

467.37

181.71

469.23

181.92

471.05

182.11

472.84

182.26

474.60

182.40

478.74

174.24

477.99

182.58

479.63

182.63

481.25

182.66

482.82

182.66

486.97

174.13

488.52

174.06

453.09

179.38

455.28

179.82

457.41

180.22

459.49

180.57

461.53

180.89

443.77

177.52

446.19

178.06

448.55

178.53

450.84

179.00

-

-

-

-

-

-

-

-

115/80

455.47

171.70

457.38

171.79

459.24

171.86

461.07

171.89

462.85

171.90

464.61

171.86

466.33

171.81

470.45

163.44

469.68

171.58

471.30

171.44

472.89

171.26

474.45

171.05

478.58

161.67

480.11

161.39

445.28

170.82

447.42

171.08

449.50

171.30

451.53

171.46

453.53

171.60

431.38

169.00

433.82

169.37

-

-

-

-

436.21

169.75

438.56

170.09

440.86

170.36

443.10

170.63

Note: Capacities are with all compressors runnning, balanced supply and exhaust airflow, and ARI 1060 return air conditions of 75/63°F. Dashed fields indicate that the unit will cycle compressor to maintain the DP setpoint above 45°F.

MUA-PRC004-EN 67

Performance

Data unit w/TE wheel capacity

Table PD-63. Size 066 cooling capacity with reheat, MBh cfm

4400

4500

4600

4700

4800

4900

5000

5100

5200

5300

5400

5500

5600

5700

5800

5900

6000

6100

6200

6300

6400

6500

6600 total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent

85/76

491.74

203.14

493.97

203.93

496.14

204.68

498.27

205.41

500.35

206.12

489.47

202.30

-

-

-

-

-

-

-

-

-

-

-

-

-

-

502.39

206.81

504.38

207.46

506.34

208.05

508.24

208.71

510.11

209.35

511.93

209.95

513.71

210.55

515.46

211.12

517.16

211.67

518.83

212.20

85/78

494.76

209.65

497.02

210.58

499.24

211.47

501.41

212.32

503.52

213.17

485.14

205.61

487.63

206.66

490.07

207.72

492.45

208.69

-

-

-

-

-

-

-

-

505.60

214.00

507.62

214.82

509.61

215.56

511.56

216.35

513.46

217.12

515.32

217.84

517.13

218.58

518.91

219.28

520.65

219.96

522.35

220.62

85/80

497.78

216.17

500.08

217.22

502.34

218.25

504.54

219.24

506.70

220.22

486.89

212.09

-

-

-

-

-

-

487.99

211.63

490.52

212.79

493.00

213.98

495.42

215.08

508.80

221.19

510.87

222.18

512.89

223.07

514.87

223.99

516.81

224.89

518.70

225.74

520.55

226.61

522.36

227.44

524.14

228.25

525.87

229.05

95/76 entering dry-bulb/wet-bulb °F

95/78 95/80 105/76

483.29

187.71

485.45

188.18

487.56

188.61

489.63

189.01

491.66

189.39

481.08

187.21

-

-

-

-

-

-

-

-

-

-

-

-

-

-

493.64

189.76

495.58

190.07

497.49

190.34

499.35

190.65

501.17

190.96

502.96

191.22

504.71

191.48

506.41

191.72

508.09

191.94

509.73

192.13

486.31

194.23

488.51

194.83

490.66

195.39

492.77

195.92

494.83

196.44

479.39

192.31

-

-

481.75

192.98

484.06

193.60

-

-

-

-

-

-

-

-

496.85

196.95

498.83

197.43

500.77

197.84

502.66

198.30

504.52

198.73

506.35

199.11

508.13

199.51

509.87

199.88

511.58

200.23

513.25

200.55

489.33

200.74

491.57

201.47

493.76

202.17

495.90

202.84

498.00

203.49

478.28

197.87

-

-

-

-

-

-

479.82

197.63

482.28

198.45

484.68

199.25

487.04

199.98

500.06

204.14

502.07

204.79

504.04

205.35

505.98

205.94

507.87

206.50

509.73

207.01

511.55

207.54

513.32

208.04

515.07

208.52

516.77

208.98

474.84

172.28

476.93

172.43

478.98

172.53

480.99

172.61

482.96

172.66

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

484.89

172.70

486.78

172.69

488.64

172.62

490.46

172.60

492.24

172.57

493.99

172.48

495.70

172.42

497.37

172.32

499.02

172.20

500.63

172.06

105/80

491.31

187.08

493.27

187.40

495.19

187.63

497.08

187.88

498.93

188.11

500.76

188.28

502.54

188.48

504.28

188.65

505.99

188.79

507.67

188.91

115/76

468.41

156.68

-

-

470.40

156.46

472.35

156.21

474.27

155.93

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

476.14

155.65

477.98

155.30

479.79

154.91

481.56

154.55

483.30

154.18

485.02

153.75

486.69

153.35

488.33

152.93

489.95

152.47

491.53

151.99

105/78

477.86

178.80

479.99

179.08

482.08

179.32

484.13

179.52

486.13

179.71

471.14

177.97

-

-

473.43

178.25

475.68

178.50

-

-

-

-

-

-

-

-

488.10

179.89

490.03

180.04

491.92

180.13

493.77

180.24

495.59

180.34

497.37

180.38

499.12

180.45

500.83

180.49

502.51

180.50

504.15

180.48

480.87

185.31

483.05

185.72

485.18

186.10

487.26

186.44

489.30

186.76

469.67

183.66

-

-

-

-

-

-

471.65

183.64

474.03

184.11

476.37

184.51

478.65

184.89

115/78

469.40

163.37

471.47

163.33

473.50

163.24

475.49

163.12

477.44

162.98

462.90

163.62

-

-

465.12

163.51

467.29

163.41

-

-

-

-

-

-

-

-

479.35

162.84

481.23

162.66

483.07

162.41

484.88

162.19

486.65

161.95

488.40

161.65

490.11

161.38

491.79

161.09

493.43

160.76

495.05

160.42

115/80

472.42

169.89

474.53

169.97

476.60

170.02

478.62

170.04

480.61

170.04

461.07

169.45

-

-

-

-

-

-

463.49

169.64

465.79

169.76

468.05

169.77

470.27

169.80

482.56

170.03

484.47

170.01

486.35

169.92

488.19

169.83

490.00

169.73

491.79

169.55

493.53

169.41

495.24

169.25

496.92

169.06

498.58

168.84

Note: Capacities are with all compressors runnning, balanced supply and exhaust airflow, and ARI 1060 return air conditions of 75/63°F. Dashed fields indicate that the unit will cycle compressor to maintain the DP setpoint above 45°F.

68 MUA-PRC004-EN

Performance

Data unit w/TE wheel capacity

Table PD-64. Size 066 reheat data, MBh cfm entering dry-bulb/wet-bulb °F

55/48 55/50 55/52 65/56 65/58 65/60 75/66 75/68 75/70 85/76 85/78 85/80 95/76 95/78 95/80 105/76 105/78 105/80 115/76 115/78 115/80

3600 102.6 103.2 103.8 105.4 106.1 106.7 108.9 109.5 110.1 112.3 112.9 113.5 112.8 113.4 114.0 113.2

113.8

114.4

113.6

114.2

114.8

4000 104.0 104.6 105.2 107.0 107.6 108.2 110.6 111.2 111.8 114.2 114.8 115.4 114.9 115.5 116.1 115.5

116.1

116.7

116.1

116.7

117.3

4400 105.4 106.0 106.5 108.5 109.1 109.7 112.2 112.8 113.3 115.9 116.5 117.0 116.8 117.4 117.9 117.7

118.3

118.8

118.6

119.2

119.7

4800 106.6 107.1 107.6 109.9 110.4 110.9 113.7 114.2 114.7 117.5 118.0 118.5 118.7 119.2 119.7 119.9

120.4

120.9

121.1

121.6

122.1

5200 107.6 108.1 108.6 111.1 111.5 112.0 115.0 115.5 116.0 119.0 119.5 119.9 120.5 121.0 121.5 122.0

122.5

123.0

123.6

124.0

124.5

5600 108.6 109.0 109.5 112.2 112.7 113.1 116.3 116.8 117.2 120.4 120.8 121.3 122.2 122.7 123.1 124.1

124.5

125.0

125.9

126.4

126.8

6000 109.5 109.9 110.3 113.3 113.7 114.1 117.5 118.0 118.4 121.8 122.2 122.6 123.9 124.3 124.7 126.1

126.5

126.9

128.2

128.6

129.1

6400 110.1 110.5 110.9 114.2 114.6 115.0 118.6 119.0 119.4 123.0 123.4 123.8 125.5 125.9 126.3 128.0

128.4

128.8

130.5

130.8

131.2

6600 110.4 110.8 111.2 114.6 114.9 115.3 119.1 119.5 119.9 123.6 124.0 124.4 126.3 126.6 127.0 128.9

129.3

129.7

131.5

131.9

132.3

Note: Capacities are for balanced supply and exhaust airflow with ARI 1060 return air conditions (75/63°F).

cfm

3600

4000

4400

4800

5200

5600

6000

6400

6600

Table PD-65. Size 066 condenser reheat max temperature rise, °F entering dry-bulb/wet-bulb °F

55/48 55/50 55/52 65/56 65/58 65/60 75/66 75/68 75/70 85/76 85/78 85/80 95/76 95/78 95/80 105/76 105/78 105/80 115/76 115/78 115/80

27.3

27.4

27.5

27.9

28.1

28.2

28.8

28.9

29.1

29.6

29.7

29.9

29.7

29.8

30.0

29.8

29.9

30.1

29.9

24.9

25.0

25.2

25.6

25.7

25.8

26.3

26.5

26.6

27.1

27.2

27.4

27.2

27.4

27.5

27.4

27.5

27.6

27.5

23.0

23.1

23.2

23.6

23.7

23.8

24.3

24.4

24.5

25.0

25.1

25.2

25.2

25.3

25.4

25.4

25.5

25.6

25.6

21.3

21.4

21.5

21.9

22.0

22.1

22.6

22.7

22.8

23.3

23.3

23.4

23.5

23.6

23.7

23.7

23.8

23.9

23.9

19.9

20.0

20.0

20.5

20.5

20.6

21.1

21.2

21.3

21.7

21.8

21.9

22.0

22.1

22.2

22.3

22.4

22.4

22.6

18.7

18.7

18.8

19.2

19.3

19.3

19.8

19.9

20.0

20.4

20.5

20.6

20.7

20.8

20.9

21.0

21.1

21.2

21.3

17.6

17.6

17.7

18.1

18.2

18.2

18.7

18.8

18.8

19.3

19.4

19.4

19.6

19.7

19.7

20.0

20.0

20.1

20.3

16.6

16.6

16.7

17.1

17.2

17.2

17.7

17.8

17.8

18.3

18.3

18.4

18.6

18.7

18.7

19.0

19.0

19.1

19.4

16.1

16.2

16.2

16.7

16.7

16.8

17.2

17.3

17.3

17.8

17.9

17.9

18.2

18.2

18.3

18.6

18.6

18.6

18.9

30.0

27.7

25.7

24.0

22.6

21.4

20.3

19.4

19.0

30.2

27.8

25.8

24.1

22.7

21.5

20.4

19.4

19.0

Note: Capacities are for balanced supply and exhaust airflow with ARI 1060 return air conditions (75/63°F).

Table PD-66. Size 066 design supply air dew point, cfm dry-bulb

(°F)

85

95

105

115 wet-bulb

(°F)

76

78

80

76

78

80

76

78

80

76

78

80

46

5079

4809

4538

5031

4760

4489

4982

4711

4440

4933

4662

4392

48

5652

5381

5111

5603

5333

5062

5554

5284

5013

5505

5235

4964 design supply air dew point (°F)

50 52 54 56

6225

5954

5683

6527

6256

6176

5905

5635

6127

5856

5586

6078

5807

5537

6478

6207

6429

6158

6380

6109

58

Note: Dew point temps are with all compressors running, balanced supply and exhaust airflow and ARI 1060 return air conditions of 75/63°F.

60

62

MUA-PRC004-EN 69

Performance

Data

TE wheel capacity

Table PD-67. Total energy wheel (only) cooling capacity unit size cfm 85/76 85/78 85/80 95/76 entering dry-bulb/wet-bulb °F

95/78 95/80 105/76 105/78 105/80 115/76 115/78 115/80

031 1800

040

051

066

2200

2600

3100

2200

2600

3000

3400

3800

4000

2900

3300

3700

4100

4500

4900

5100

3600

4000

4400

4800

5200

5600

6000

6400

6600 total latent total latent

67.21

51.67

78.71

60.35

79.25

63.73

91.82

66.16

76.33

35.71

92.78

107.46

77.61

74.45

89.16

41.72

78.03

47.62

90.42

65.02

60.05

20.22

91.50

105.98

76.38

55.63

70.15

23.62

76.74

31.97

88.96

44.24

90.09

104.39

37.35

51.68

total latent

89.13

105.02

121.61

68.17

84.09

100.71

88.04

47.12

103.74

62.83

120.11

79.23

86.75

26.68

102.28

42.18

118.45

58.37

total 100.74

118.66

137.36

99.73

117.45

135.91

98.43

115.97

134.23

latent 76.81

94.75

113.47

53.09

70.79

89.27

30.06

47.53

65.77

total latent

83.14

63.95

98.04

113.59

81.79

78.89

94.48

44.21

96.49

111.81

80.36

58.94

74.33

25.03

94.86

109.98

39.57

54.76

63.84

5.16

75.06

6.03

75.41

16.76

88.62

19.58

87.47

28.88

102.74

33.73

85.34

100.70

116.69

6.81

78.88

6.39

22.12

93.19

20.75

38.10

96.95

114.31

132.38

7.67

24.92

42.93

108.11

35.74

total latent

95.08

112.09

129.85

73.00

90.05

107.85

93.67

50.46

110.46

67.28

127.96

84.84

92.12

28.57

108.70

45.17

125.97

62.51

90.49

106.86

123.92

7.29

23.68

40.80

total 106.16

125.13

144.92

104.73

123.46

142.98

103.10

121.60

140.88

101.35

119.64

138.69

latent 81.36

100.36

120.19

56.24

74.99

94.56

31.84

50.34

69.66

8.13

26.40

45.47

total 116.44

137.21

158.87

115.02

135.54

156.92

113.34

133.63

154.75

111.51

131.57

152.45

latent 89.06

109.86

131.57

61.56

82.08

103.51

34.85

55.11

76.26

8.90

28.89

49.77

total 125.94

148.37

171.76

124.58

146.74

169.84

122.88

144.81

167.64

120.98

142.68

165.27

latent 96.14

118.59

142.03

66.45

88.61

111.73

37.62

59.49

82.32

9.60

31.19

53.73

total 130.42

153.62

177.82

129.09

152.03

175.94

127.39

150.10

173.74

125.47

147.95

171.33

latent 99.46

122.68

146.93

68.75

91.67

115.59

38.92

61.54

85.16

9.93

32.27

55.59

total 108.90

128.41

148.77

107.17

126.41

146.48

105.30

124.30

144.10

103.38

122.13

141.67

latent 83.74

103.30

123.71

57.88

77.18

97.32

32.77

51.82

71.70

8.36

27.17

46.80

total 120.76

142.38

164.93

118.97

140.29

162.53

117.00

138.05

159.99

114.93

135.72

157.39

latent 92.73

114.38

136.98

64.10

85.46

107.77

36.29

57.38

79.40

9.26

30.08

51.82

total 131.96

155.54

180.15

130.13

153.41

177.68

128.08

151.07

175.04

125.88

148.61

172.29

latent 101.17

124.79

149.46

69.93

93.24

117.58

39.59

62.60

86.62

10.11

32.82

56.54

total 142.50

167.94

194.48

140.69

165.80

191.99

138.57

163.40

189.26

136.28

160.83

186.39

latent 109.09

134.57

161.16

75.41

100.54

126.79

42.69

67.50

93.41

10.90

35.39

60.97

total 152.43

179.60

207.95

150.65

177.49

205.47

148.49

175.04

202.69

146.12

172.39

199.73

latent 116.51

143.72

172.12

80.54

107.39

135.41

45.60

72.10

99.76

11.64

37.80

65.12

total 161.76

190.56

220.61

160.04

188.50

218.17

157.87

186.04

215.37

155.44

183.33

212.33

latent 123.45

152.29

182.38

85.34

113.79

143.48

48.31

76.39

105.71

12.33

40.05

69.00

total 166.21

195.79

226.64

164.53

193.77

224.23

162.36

191.30

221.43

159.91

188.56

218.37

latent 126.75

156.36

187.25

87.62

116.83

147.32

49.61

78.43

108.53

12.66

41.12

70.84

total 135.14

159.35

184.62

132.99

156.87

181.78

130.68

154.25

178.82

128.29

151.57

175.81

latent 103.92

128.19

153.52

71.83

95.78

120.77

40.67

64.30

88.98

10.38

33.71

58.08

total 147.06

173.39

200.85

144.85

170.82

197.90

142.43

168.07

194.79

139.89

165.22

191.60

latent 112.95

139.33

166.86

78.07

104.10

131.27

44.20

69.89

96.71

11.28

36.64

63.13

total 158.44

186.77

216.33

156.19

184.15

213.30

153.67

181.29

210.07

151.01

178.30

206.72

latent 121.54

149.92

179.55

84.01

112.02

141.26

47.56

75.21

104.07

12.14

39.43

67.93

total 169.29

199.53

231.08

167.03

196.88

228.00

164.44

193.94

224.68

161.67

190.83

221.20

latent 129.70

159.99

191.61

89.66

119.54

150.75

50.76

80.26

111.06

12.96

42.08

72.49

total 179.62

211.67

245.11

177.38

209.03

242.03

174.74

206.03

238.63

171.87

202.82

235.04

latent 137.45

169.55

203.06

95.01

126.69

159.75

53.79

85.06

117.69

13.73

44.59

76.82

total 189.46

223.23

258.47

187.25

220.62

255.40

184.58

217.58

251.95

181.64

214.29

248.27

latent 144.80

178.62

213.92

100.09

133.46

168.30

56.67

89.60

123.99

14.46

46.98

80.93

total 198.82

234.23

271.16

196.67

231.66

268.13

193.99

228.61

264.66

190.99

225.26

260.91

latent 151.77

187.22

224.21

104.91

139.88

176.39

59.40

93.91

129.95

15.16

49.24

84.82

total 207.72

244.67

283.21

205.65

242.18

280.25

202.97

239.13

276.78

199.92

235.73

272.98

latent 158.37

195.35

233.95

109.47

145.96

184.06

61.98

98.00

135.60

15.82

51.38

88.51

total 212.00

249.69

289.01

209.98

247.25

286.09

207.30

244.21

282.62

204.24

240.79

278.80

latent 161.53

199.25

238.63

111.65

148.88

187.73

63.21

99.95

138.31

16.13

52.41

90.28

70 MUA-PRC004-EN

Performance

Data

TE wheel capacity

Table PD-68. Total energy wheel (only) heating capacity, MBh

031

040

051

066

4900

5100

3600

4000

4400

4800

5200

5600

6000

6400

6600

3400

3800

4000

2900

3300

3700

4100

4500 cfm

1800

2200

2600

3100

2200

2600

3000

189.89

195.36

156.58

170.76

184.36

197.40

209.89

221.85

233.30

244.25

249.54

25

77.92

91.65

104.23

118.44

96.27

110.46

123.75

136.18

147.78

153.28

126.17

140.29

153.70

166.41

178.47

213.19

219.33

175.80

191.72

206.98

221.62

235.65

249.08

261.93

274.22

280.16

20

87.48

102.89

117.01

132.97

108.08

124.02

138.94

152.89

165.91

172.09

141.66

157.51

172.56

186.83

200.37

236.98

243.81

195.42

213.11

230.08

246.35

261.94

276.87

291.16

304.82

311.42

15

97.24

114.37

130.07

147.81

120.14

137.86

154.44

169.95

184.43

191.29

157.46

175.08

191.81

207.68

222.73

261.27

268.81

215.45

234.96

253.67

271.61

288.80

305.26

321.01

336.07

343.35

10

107.21

126.10

143.41

162.97

132.46

151.99

170.28

187.37

203.33

210.90

173.61

193.03

211.48

228.98

245.56

157.02

167.06

171.88

137.76

150.24

162.20

173.67

184.66

195.19

205.26

214.89

219.55

30 winter outdoor dry-bulb, °F

35 40

68.55

80.63

59.38

69.84

50.39

59.26

91.70

104.21

84.69

97.19

79.42

90.26

73.36

84.18

67.40

76.59

62.25

71.43

108.88

119.81

130.02

134.86

111.01

123.43

135.22

146.41

94.31

103.77

112.61

116.81

96.15

106.91

117.12

126.81

80.02

88.06

95.56

99.12

81.59

90.72

99.39

107.61

136.00

144.70

148.87

119.32

130.13

140.49

150.43

159.95

169.06

177.78

186.13

190.16

115.40

122.79

126.33

101.25

110.42

119.21

127.65

135.72

143.46

150.86

157.94

161.36

101.31

104.23

83.54

91.10

98.36

105.32

111.98

118.36

124.47

130.31

133.13

72.65

78.84

81.78

67.32

74.85

82.00

88.78

95.22

45

41.57

48.89

55.61

63.19

51.36

58.93

66.02

80.25

82.56

66.18

72.17

77.91

83.42

88.70

93.76

98.60

103.22

105.46

57.55

62.45

64.78

53.32

59.29

64.95

70.33

75.42

50

32.93

38.73

44.05

50.06

40.68

46.68

52.30

55

24.46

28.77

32.71

37.18

30.22

34.67

38.84

42.74

46.38

48.11

39.60

44.03

48.24

52.23

56.02

59.60

61.32

49.15

53.60

57.87

61.96

65.88

69.63

73.23

76.66

78.32

39.35

40.49

32.45

35.39

38.21

40.91

43.50

45.98

48.35

50.62

51.71

28.22

30.62

31.76

26.15

29.07

31.85

34.49

36.99

60

16.15

18.99

21.60

24.55

19.95

22.89

25.65

Note: Capacities based on ARI 1060 return air conditions, 70/58°F. Outdoor air is assumed to have a relative humidity of 80%. The supply and exhaust airflow are equal.

19.49

20.05

16.07

17.52

18.92

20.26

21.54

22.77

23.94

25.07

25.61

13.98

15.17

15.73

12.95

14.40

15.77

17.08

18.32

65

8.00

9.41

10.70

12.16

9.88

11.34

12.70

MUA-PRC004-EN 71

72

Performance

Data

TE wheel capacity cfm

031 1800

2200

2600

3100

040 2200

2600

3000

3400

3800

4000

051 2900

3300

3700

4100

4500

4900

5100

066 3600

4000

4400

4800

5200

5600

6000

6400

6600

Table PD-69. Total energy wheel performance data

74.8%

73.0%

72.2%

82.0%

80.5%

79.0%

77.5%

76.1%

74.7%

73.3%

71.9%

71.3%

effectiveness sensible latent

81.6%

78.6%

79.2%

75.7%

75.6%

72.1%

82.5%

80.1%

72.3%

68.4%

80.1%

77.4%

77.8%

75.5%

73.3%

72.3%

82.0%

80.1%

78.3%

76.5%

74.8%

72.2%

69.8%

68.6%

79.6%

77.5%

75.4%

73.3%

71.4%

69.5%

68.5%

79.6%

77.8%

76.1%

74.5%

72.9%

71.3%

69.7%

68.2%

67.5%

71.3%

70.5%

80.8%

79.2%

77.6%

76.1%

74.6%

73.1%

71.6%

70.2%

69.5% total

80.5%

77.2%

74.1%

70.3%

81.4%

78.8%

76.3%

74.0%

71.6%

70.5%

80.9%

78.9%

76.9%

75.0%

73.1%

Note: Performance based on ARI 1060 test conditions.

3800

4000

2900

3300

3700

4100

4500

4900

1800

2200

2600

3100

2200

2600

3000

3400

5100

3600

4000

4400

4800

5200

5600

6000

6400

6600

Table PD-70. Total energy wheel temperature rise unit size cfm 10 15 winter outdoor dry-bulb, °F

20 25 30 35 40

031

040

051

066

45 50 55 60 65

48.96 44.88 40.80 36.72 32.64 28.56 24.48 20.40 16.32 12.24

8.16

4.08

47.11 43.19 39.26 35.33 31.41 27.48 23.56 19.63 15.70 11.78

7.85

3.93

45.34 41.56 37.78 34.00 30.22 26.45 22.67 18.89 15.11 11.33

7.56

3.78

43.21 39.61 36.01 32.41 28.81 25.21 21.61 18.00 14.40 10.80

7.20

3.60

49.49 45.36 41.24 37.12 32.99 28.87 24.74 20.62 16.50 12.37

8.25

4.12

48.05 44.05 40.04 36.04 32.03 28.03 24.02 20.02 16.02 12.01

8.01

4.00

46.65 42.77 38.88 34.99 31.10 27.21 23.33 19.44 15.55 11.66

7.78

3.89

45.30 41.52 37.75 33.97 30.20 26.42 22.65 18.87 15.10 11.32

7.55

3.77

43.98 40.32 36.65 32.99 29.32 25.66 21.99 18.33 14.66 11.00

7.33

3.67

43.34 39.73 36.12 32.50 28.89 25.28 21.67 18.06 14.45 10.83

7.22

3.61

49.21 45.11 41.01 36.90 32.80 28.70 24.60 20.50 16.40 12.30

8.20

4.10

48.08 44.07 40.07 36.06 32.05 28.05 24.04 20.03 16.03 12.02

8.01

4.01

46.98 43.07 39.15 35.24 31.32 27.41 23.49 19.58 15.66 11.75

7.83

3.92

45.90 42.08 38.25 34.43 30.60 26.78 22.95 19.13 15.30 11.48

7.65

3.83

44.85 41.12 37.38 33.64 29.90 26.16 22.43 18.69 14.95 11.21

7.48

3.74

43.83 40.18 36.52 32.87 29.22 25.57 21.91 18.26 14.61 10.96

7.30

3.65

43.32 39.71 36.10 32.49 28.88 25.27 21.66 18.05 14.44 10.83

7.22

3.61

49.19 45.09 40.99 36.89 32.79 28.70 24.60 20.50 16.40 12.30

8.20

4.10

48.28 44.26 40.23 36.21 32.19 28.16 24.14 20.12 16.09 12.07

8.05

4.02

47.39 43.44 39.49 35.54 31.59 27.64 23.69 19.75 15.80 11.85

7.90

3.95

46.51 42.64 38.76 34.88 31.01 27.13 23.26 19.38 15.50 11.63

7.75

3.88

45.65 41.85 38.04 34.24 30.43 26.63 22.83 19.02 15.22 11.41

7.61

3.80

44.81 41.07 37.34 33.60 29.87 26.14 22.40 18.67 14.94 11.20

7.47

3.73

43.98 40.31 36.65 32.98 29.32 25.65 21.99 18.32 14.66 10.99

7.33

3.66

43.16 39.57 35.97 32.37 28.77 25.18 21.58 17.98 14.39 10.79

7.19

3.60

42.76 39.20 35.63 32.07 28.51 24.94 21.38 17.82 14.25 10.69

7.13

3.56

Note: Temperature rises based on ARI 1060 return air conditions, 70/58°F. Outdoor air is assumed to have a relative humidity of 80%. The supply and exhaust airflow are equal.

MUA-PRC004-EN

Performance

Data electric heat

Table PD-71. Electric heat temperature rise,°F, sizes 031 & 040 unit size cfm 20 26 32 42

3-stage [33,66,100%]

56 heat input (kW)

70 84 100

7-stage [14,27,41,59,68,86,100%]

031

040

68

65

63

61

59

57

65

63

61

59

57

48

46

45

44

55

53

52

50

49

68

60

57

55

53

51

49

47

46

44

43

49

47

46

44

43

36

35

34

33

41

40

39

38

37

60

57

55

53

51

70

66

63

46

44

42

40

39

37

36

35

34

32

37

36

35

34

32

31

30

46

44

42

40

39

59

56

53

50

48

37

36

34

33

31

30

30

37

36

34

33

31

48

45

43

41

39

37

35

33

31

2700

2800

2900

3000

3100

2200

2300

2400

2500

2600

2700

2800

2900

3000

3100

3200

3300

3400

3500

3600

3700

3800

3900

4000

1700

1800

1900

2000

2100

2200

2300

2400

2500

2600

59

58

56

55

69

67

65

63

61

70

68

66

Notes: entries with ‘’—‘’ have temperature rises less than 30°F or greater than 70°F low rise = 30 – 40ºF intermediate rise = 40 – 60ºF medium rise = 60 – 70ºF

122

MUA-PRC004-EN 73

74

Performance

Data electric heat

Table PD-72. Electric heat temperature rise, °F, sizes 051 & 066 unit size cfm 20 26 32 42 heat input (kW)

56

3-stage [33, 66, 100%]

051

066

4800

4900

5000

5100

3600

3700

3800

3900

4000

4100

4200

4300

4400

4500

4600

4700

4800

4900

5000

2800

2900

3000

3100

3200

3300

3400

3500

3600

3700

3800

3900

4000

4100

4200

4300

4400

4500

4600

4700

5100

5200

5300

5400

5500

5600

5700

5800

5900

6000

6100

6200

6300

6400

6500

6600

Notes: entries with ‘’—‘’ have temperature rises less than 30°F or greater than 70° F

low rise = 30 – 40°F

intermediate rise = 40 – 60°F

medium rise = 60 – 70°F

49

48

46

45

44

37

36

35

35

38

37

37

36

35

43

42

41

40

39

53

52

50

49

48

63

61

59

57

55

41

40

39

38

37

46

45

44

43

42

31

31

30

35

34

33

33

32

37

36

35

34

33

32

31

31

30

40

39

38

37

36

47

46

44

43

41

31

30

35

34

33

32

31

30

36

35

34

32

31

70 84 100 122

39

39

38

37

37

43

42

42

41

40

36

36

35

34

34

33

61

59

58

56

55

46

45

44

43

48

47

46

45

44

54

52

51

50

49

7-stage [14, 27, 41, 59, 68, 86, 100%]

69

51

50

49

48

47

58

56

55

54

52

67

65

63

61

59

70

68

66

64

63

61

60

59

57

56

70

68

67

47

46

46

45

44

52

51

50

49

48

43

43

42

41

41

40

70

68

66

55

54

53

52

57

56

55

54

53

64

63

61

60

59

56

55

54

53

52

62

60

59

58

57

52

51

50

49

48

48

66

64

63

62

68

67

66

64

63

70

69

67

66

65

64

70

63

62

61

60

59

58

MUA-PRC004-EN

Performance

Data gas heat

Table PD-73. Gas heat temperature rise, °F, sizes 031 & 040 unit size cfm

1700

1800

1900

2000

2100 input (MBh) output (MBh)

031

2200

2300

2400

2500

2600

2700

2800

2900

3000

3100

2200

2300

2400

2500

2600

040

2700

2800

2900

3000

3100

3200

3300

3400

3500

3600

3700

3800

3900

4000

125

100

150

120

34

33

32

31

34

33

32

31

42

40

38

37

35

42

40

38

37

35

54

51

49

46

44

35

34

33

32

31

41

39

38

37

36

41

39

38

37

36

50

48

46

44

43

50

48

46

44

43

65

61

58

55

53

200

160

46

45

43

42

41

55

53

51

49

48

40

39

38

37

55

53

51

49

48

67

64

61

59

57

67

64

61

59

57

87

82

78

74

70

250

200

58*

56*

54*

53*

51*

68*

66*

64*

61*

59*

50*

49*

47*

46*

68*

66*

64*

61*

59*

84*

80*

77*

74*

71*

84*

80*

77*

74*

71*

87*

300

240

69*

67*

65*

63*

61*

82*

79*

76*

74*

71*

60*

58*

57*

55*

82*

79*

76*

74*

71*

88*

85*

88*

85*

400

320

89*

87*

84*

82*

80*

78*

76*

74*

350

280

81*

78*

76*

74*

72*

89*

86*

83*

70*

68*

66*

65*

89*

86*

83*

500 600 700 800

400 480 560

(dual heaters only)

640

Notes: entries with ‘’—’’ have temperature rises less than 30°F or greater than 90°F

250/300/350/400 MBh inputs have option for dual or single heaters, except there is no 400 MBh single heater in small cabinet

* = dual (lo-rise) = 40 – 90°F

single lo-rise = 30 – 75°F

single hi-rise = 75 – 90°F

MUA-PRC004-EN 75

Performance

Data gas heat

Table PD-74. Gas heat temperature rise °F, sizes 051 & 066 input (MBh) output (MBh) unit size cfm

051

3800

3900

4000

4100

4200

4300

4400

4500

4600

4700

2800

2900

3000

3100

3200

3300

3400

3500

3600

3700

4800

4900

5000

5100

3600

3700

3800

3900

4000

066

4100

4200

4300

4400

4500

4600

4700

4800

4900

5000

5100

5200

5300

5400

5500

5600

5700

5800

5900

6000

6100

6200

6300

6400

6500

6600

125

100

33

32

31

150

120

34

33

32

31

39

38

37

36

35

31

200

160

32

31

31

30

36

35

34

34

33

34

34

33

32

31

39

38

37

36

35

45

43

42

41

40

53

51

49

48

46

41

40

39

38

37

31

30

250

200

300

240

350

280

40*

39

38

38

37

45*

44*

43*

42*

41*

33

32

32

31

31

36

35

35

34

34

30

43*

42*

41*

40*

39

49*

47*

46*

45*

44*

64*

61*

59*

58*

56*

54*

53*

51*

50*

38

38

37

36

51*

50*

49*

47*

46*

Notes: entries with ‘’—’’ have temperature rises less than 30°F or greater than 90°F

250/300/350/400 MBh inputs have option for dual or single heaters, except there is no 400 MBh single heater in small cabinet

* = dual (lo-rise) = 40 – 90°F

single lo-rise = 30 – 75°F

single hi-rise = 75 – 90°F

48*

47*

46*

45*

44*

54*

53*

51*

50*

49*

39

39

38

37

37

43*

43*

42*

41*

40*

36

36

35

35

34

34

51*

50*

49*

48*

47*

58*

57*

55*

54*

53*

67*

65*

63*

61*

60*

66*

76*

74*

71*

69*

46*

45*

44*

43*

61*

60*

58*

57*

55*

56*

55*

54*

53*

52*

63*

61*

60*

59*

57*

46*

45*

44*

44*

43*

51*

50*

49*

48*

47*

42*

42*

41*

40*

40*

39

60*

59*

57*

56*

55*

68*

66*

65*

63*

61*

78*

76*

74*

72*

70*

79*

89*

86*

83*

81*

54*

53*

52*

51*

72*

70*

68*

66*

65*

64*

63*

61*

60*

59*

72*

70*

69*

67*

66*

53*

52*

51*

50*

49*

58*

57*

56*

55*

54*

48*

48*

47*

46*

45*

45*

80*

78*

77*

75*

74*

90*

88*

86*

84*

82*

66*

65*

64*

62*

61*

72*

71*

70*

68*

67*

60*

59*

59*

58*

57*

56*

86*

84*

82*

80*

78*

90*

88*

77*

75*

74*

72*

400

320

500

400

600

480

700

560

(dual heaters only)

800

640

69*

67*

66*

64*

63*

78*

76*

74*

72*

70*

89*

87*

84*

82*

80*

61*

60*

59*

58*

82*

80*

78*

76*

74*

88*

87*

— —

88*

79*

78*

76*

75*

74*

87*

85*

83*

82*

80*

73*

71*

70*

69*

68*

67*

89*

87*

86*

85*

83*

82*

81*

79*

78*

89*

76 MUA-PRC004-EN

Controls

Packaged Fresh Air Unit

with

Controls

The Intelligent Air-Cooled Chillers

We have designed the Trane Packaged

Fresh Air unit with the latest control technology. Modular DDC controls with human interface (HI) panel make

Packaged Fresh Air units flexible and easy to operate.

Controls are Trane-designed to work with Trane equipment for optimum efficiency. The factory installs and commissions each control component to ensure simple and reliable operation.

Furthermore, the DDC control’s modular design allows greater application flexibility using up to twelve different modules, dependent upon unit options.

You can order exactly what the job requires as options, instead of one large control package. And since unit features are distributed among multiple printed circuit boards, field replacement is easy.

Depending on unit options, IntelliPak™ units can operate as:

1) stand-alone

2) interface with Trane’s Tracer Summit™ building management system

3) interface with a generic (non-Trane) building management system (via

LCI-I using LonTalk ® DAC profile).

4) interface with a generic hard-wired

(non-Trane) building management system via analog input and binary output interface board (GBAS)

Available Input and Output Points Base

Unit (RTM module on all units)

Binary inputs

• emergency stop

• external auto/stop

• unoccupied/occupied

• dirty filter

• exhaust fan air proving

Binary outputs

• unoccupied mode indicator

• alarm

• exhaust fan enable

Analog input

• OA damper minimum position heating option

• analog output (hydronic heat interface)

LonTalk ® communication interface

(LCI-I ) option

MUA-PRC004-EN

Binary input

• enthalpy enable unoccupied economizer

Binary outputs

• compressor on/off status

• ventilation status

• heat status

Analog outputs

• supply air pressure

• supply air temperature

• suction temperature of each circuit

• zone temperature

• supply air temperature reset signal

• morning warmup sensor temperature

• entering air temperature

Analog inputs

• cooling and heating setpoints

• VAV discharge air temperature setpoints

• supply air pressure setpoint

• cooling and heating enable/disable

• unoccupied economizer enable/disable

• economizer minimum position

• unit priority shutdown

Generic BAS Option (GBAS)

Binary inputs

• demand limit contacts

Binary outputs

• dirty filter relay

• refrigeration fail relay

• heat fail relay

• supply fan fail relay

• active diagnostics

Analog inputs

• occupied zone cooling setpoint

• occupied zone heating setpoint

• unoccupied zone cooling setpoint

• unoccupied zone heating setpoint or minimum outside air flow setpoint

• supply air cooling setpoint

• supply air heating setpoint

• supply air static pressure setpoint

Zone Humidity Options (ECEM)

Analog inputs

• zone relative humidity

Traq™ Damper Option (VCM)

Analog inputs

• ventilation airflow

Ventilation Override Module (VOM)

Option

Binary inputs

• VOM mode A, unit off

• VOM mode B, pressurize

• VOM mode C, exhaust

• VOM mode D, purge

• VOM mode E, purge

Binary output

• V.O. relay

Standard IntelliPak Unit Control

Features

All set-up parameters are preset from the factory, requiring less startup time during installation.

The human interface panel is easy to read and requires less time for building maintenance personnel to learn to interact with the unit. It features a clear language display (in English, Spanish, or

French) that shows all of the Packaged

Fresh Air unit control parameters, including system on/off, demand limiting type, night setback setpoints, and many other setpoints. All adjustments are done through the human interface keypad. Also, the human interface panel allows you to monitor diagnostic points such as sensor failures, supply airflow loss, and inoperative refrigerant circuit.

No special tools are required for servicing the unit. Diagnostics are held in memory, even during power loss.

This allows the operator/servicer to diagnose the failure root cause.

IntelliPak Unit Features

• Unit mounted human interface panel with a two line x 40 character display in English, Spanish, or French language and a 16-function keypad that includes CUSTOM, DIAGNOSTICS, and SERVICE TEST MODE menu keys

• Frostat™ coil frost protection on all units

• Supply air or zone dehumidification control

• Supply air or zone temperature control

• Efficient condenser hot gas reheat with modulating capacity (optional)

• Morning warmup operation

• unoccupied airside economizer

77

Controls

(optional) when unit has return air damper option

• supply airflow proving

• supply air tempering control with heating option

• mappable sensors and setpoint sources

• occupied/unoccupied switching

• timed override activation

Human Interface Panel (HI)

The human interface panel provides a

16-button keypad for monitoring, setting, editing and controlling. The HI panel is mounted in the unit’s main control panel, accessible through the unit’s control panel door.

The optional remote-mount version of the human interface (RHI) panel has all the functions of the unit-mounted version, except for the service mode. To use a RHI, the unit must be equipped with the remote HI interface option, which includes an interprocessor communications bridge (IPCB). The RHI can be located up to 1,000 feet (304.8

m) from the unit. A single RHI can be used to monitor and control up to four fresh air units, that have each been supplied with a RHI interface option

(IPCB module).

The main menus of the human interface panels are:

• STATUS monitors temperature, pressure, humidity, setpoints, and input and output status.

• CUSTOM key allows the user to customize a status report - consisting of up to four screens of the data available in the main Status menu.

• SETPOINT allows the user to edit all factory preset default setpoints.

• DIAGNOSTICS allows the user to review active and historical lists of diagnostic conditions. A total of 49 different diagnostics can be read at the human interface (HI) panel and the last 20 diagnostics can be held in an active history buffer log at the HI panel.

• SETUP allows the user to edit control parameters, sensor selections, setpoint source selections, output definitions, and numerous other points in this menu. All points have factory preset values to keep unnecessary editing to a minimum.

• CONFIGURATION allows changing of factory-preset unit configuration

78

Figure C-1. The human interface panel on the Trane Packaged Fresh Air unit information. This information can be edited only if certain options are fieldinstalled or deleted from the unit. For example, if a communication interface

(LCI-I) module or ventilation override module (VOM) were field-installed, the unit configuration will require editing to reflect those options for proper unit operation.

• SERVICE allows servicing or troubleshooting the unit by selecting component control outputs such as compressors, fans, damper position, etc. This menu is accessible only at the unitmounted human interface panel.

Supply Air

Dehumidification Unit

1

Occupied Sequence

During occupied mode, the primary function of the unit is to provide ventilation air to the space. Upon entering the occupied mode, the outside air damper is opened and the supply air fan will start.

Drying Mode

The unit will enter the drying mode when the OA dew point exceeds the SA drying setpoint (dew point). The SA drying setpoint can be reset down based on OA dew point conditions.

Drying functions will have priority over cooling mode. Upon entering drying mode, the first compressor will stage up. While in drying mode, the first compressor stage will always remain active. This allows condenser reheat

(when ordered) to be available as required during drying operation.

Additional compressors will be sequenced to match unit capacity to the latent load.

Reheat will be controlled to meet a supply air reheat setpoint that is a minimum of 3°F greater than the supply air drying setpoint. The supply air reheat setpoint can be reset up based on OA or zone temperature conditions. When available, condenser reheat will be cycled to achieve a time-weighted average of the reheat setpoint. If primary heat reheat is user-enabled, additional reheat capacity will be made available to match sensible load.

Cooling Sequence

When not in drying mode, the unit will stage cooling capacity to maintain the supply air cooling setpoint. The supply air cooling setpoint can be reset down based on HI selectable parameters (OA sensor, zone sensor if installed).

MUA-PRC004-EN

Controls

Sequence of

Operation

Heating Sequence

When not in drying mode, the unit will stage heating capacity to maintain the supply air heating setpoint. The supply air heating setpoint can be reset up based on HI selectable parameters (OA sensor, zone sensor if installed). The supply air heating setpoint must be lower than the supply air cooling setpoint.

2

Unoccupied Sequence

In unoccupied mode, the fan is stopped and the OA damper is closed.

Supply Air

Dehumidification with Zone

RH Reference Unit

1

Occupied Sequence

During occupied mode, the primary function of the unit is to provide ventilation air to the space. Upon entering the occupied mode, the outside air damper is opened and the supply air fan will start.

Drying Mode

The unit will enter the drying mode when the OA dew point exceeds the SA drying setpoint (dew point). The SA drying setpoint can be reset down based on zone relative humidity conditions or OA dew point conditions.

Drying functions will have priority over cooling mode. Upon entering drying mode, the first compressor will stage up. While in drying mode, the first compressor stage will always remain active. This allows condenser reheat

(when ordered) to be available as required during drying operation.

Additional compressors will be sequenced to match unit capacity to the latent load.

Reheat will be controlled to meet a supply air reheat setpoint that is a minimum of 3°F greater than the supply air drying setpoint. The supply air reheat setpoint can be reset up based on OA or zone temperature conditions. When available, condenser reheat will be cycled to achieve a time-weighted average of the reheat setpoint. If primary heat reheat is user-enabled,

MUA-PRC004-EN additional reheat capacity will be made available to match sensible load.

Cooling Sequence

When not in drying mode, the unit will stage cooling capacity to maintain the supply air cooling setpoint. The supply air cooling setpoint can be reset down based on HI selectable parameters (OA sensor, Zone sensor if installed).

Heating Sequence

When not in drying mode, the unit will stage heating capacity to maintain the supply air heating setpoint. The supply air heating setpoint can be reset up based on HI selectable parameters (OA sensor, zone sensor if installed). The supply air heating setpoint must be lower than the supply air cooling setpoint.

2

Unoccupied Sequence

When the return air damper option is installed and a request for unoccupied operation is received, the fan, cooling, and heating capacity will be cycled in a recirculating mode to maintain zone requirements. See below for a detailed description of the operating modes.

If no return air damper is installed, the fan is stopped and the OA damper is closed in unoccupied mode.

Drying Mode

During unoccupied mode (with return air damper option installed), the unit will enter the drying mode when the zone

RH exceeds the unoccupied zone RH setpoint. In the drying mode, capacity will be cycled to maintain the supply air drying (dew point) setpoint. The SA drying setpoint can be reset down based on zone relative humidity conditions and will be based on the unoccupied zone RH setpoint.

Supply air reheat functions will be active to maintain the supply air reheat setpoint. Supply air reheat reset functions will be active and reset based on unoccupied zone setpoints. Exhaust fan operation control will be cycled off during unoccupied modes unless unoccupied economizer operations are active.

Cooling Mode

During unoccupied cooling mode, the fan, economizer and mechanical cooling cycle to control zone temperature.

Economizer functions will be enabled when the difference in the enthalpy of the OA and zone is adequate. Mechanical cooling will supplement economizer capacity as required.

Heating Mode

During unoccupied heating mode, fan and heating capacity are cycled to maintain the unoccupied zone heating setpoint.

Zone Dehumidification Unit

Sequence of Operation

1

Occupied Sequence

During occupied mode, the primary function of the unit is to provide ventilation air to the space. Upon entering the occupied mode, the outside air damper is opened and the supply air fan will start.

Drying Mode

The unit enters the drying mode when the zone relative humidity exceeds the zone relative humidity setpoint (%RH).

In the drying mode, the capacity is controlled to meet the default supply air drying setpoint (dewpoint). The SA drying setpoint can be reset down based on zone relative humidity conditions. Drying functions have priority over cooling mode. Upon entering drying mode, the first compressor stages up. While in drying mode, the first compressor stage always remains active. This allows condenser reheat option (if ordered) to be available as required during the drying operation.

Additional compressors will sequence to match unit capacity to the latent load.

Reheat is controlled to meet a supply air reheat setpoint that is a minimum of 3°F greater than the supply air drying setpoint. The supply air reheat setpoint can be reset up based on OA or zone temperature conditions. When available, condenser reheat will cycle to achieve a time-weighted average of the reheat setpoint. If primary heat reheat is user-enabled, additional reheat capacity is made available to match the sensible load.

79

Controls

Sequence of

Operation

Drying mode stops when the zone relative humidity falls below the operator adjustable setpoint for leaving drying mode.

Cooling Sequence

When not in drying mode, the unit stages cooling capacity to maintain the supply air cooling setpoint. The supply air cooling setpoint can be reset down based on HI selectable parameters (OA sensor, zone sensor if installed).

Heating Sequence

When not in drying mode, the unit will stage heating capacity to maintain the supply air heating setpoint. The supply air heating setpoint can be reset up based on HI selectable parameters (OA sensor, zone sensor if installed). The supply air heating setpoint must be lower than the supply air cooling setpoint.

2

Unoccupied Sequence

In unoccupied mode, the fan is stopped and the OA damper is closed.

Drying Mode

During unoccupied mode (with return air damper option installed), the unit enters the drying mode when the zone

RH exceeds the unoccupied zone RH setpoint. In the drying mode, capacity cycles to maintain the supply air drying

(dew point) setpoint. The SA drying setpoint can be reset down based on zone relative humidity conditions and will be based on the unoccupied zone

RH setpoint.

Supply air reheat functions are active to maintain the supply air reheat setpoint.

Supply air reheat reset functions are active and reset based on unoccupied zone setpoints. Exhaust fan operation control cycles off during unoccupied modes unless unoccupied economizer operations are active.

Cooling Mode

During unoccupied cooling mode, the fan, economizer, and mechanical cooling cycle to control zone temperature.

Economizer functions enable when the difference in the enthalpy of the OA and zone is adequate. Mechanical cooling supplements economizer capacity as required.

Heating Mode

During unoccupied heating mode, fan and heating capacity cycle to maintain the unoccupied zone heating setpoint.

Zone Dehumidification with

Outside Air RH Reference

Unit

1

Occupied Sequence

During occupied mode, the primary function of the unit is to provide ventilation air to the space. Upon entering the occupied mode, the outside air damper opens and the supply air fan starts.

Drying Mode

The unit enters the drying mode when the zone relatiave humidity exceeds the zone relative humidity setpoint (%RH).

In the drying mode, capacity is controlled to meet the default supply air drying setpoint (dew point). The SA drying setpoint can be reset down based on zone relative humidity conditions or OA dew point conditions.

Drying functions will have priority over cooling mode. Upon entering drying mode, the first compressor stages up.

While in drying mode, the first compressor stage always remains active. This allows condenser reheat (when ordered) to be available as required during drying operation. Additional compressors will sequence to match unit capacity to the latent load.

Reheat is controlled to meet a supply air reheat setpoint that is a minimum of 3°F greater than the supply air drying setpoint. The supply air reheat setpoint can be reset up based on OA or zone temperature conditions. When available, condenser reheat will cycle to achieve a time-weighted average of the reheat setpoint. If primary heat reheat is user-enabled, additional reheat capacity is made available to match sensible load.

Drying mode stops when the zone relative humidity falls below the operator-adjustable setpoint for leaving drying mode.

Cooling Sequence

When not in drying mode, the unit stages cooling capacity to maintain the supply air cooling setpoint. The supply air cooling setpoint can be reset down based on HI selectable parameters (OA sensor, zone sensor if installed).

Heating Sequence

When not in drying mode, the unit stages heating capacity to maintain the supply air heating setpoint. The supply air heating setpoint can be reset up based on HI selectable parameters (OA sensor, zone sensor if installed). The supply air heating setpoint must be lower than the supply air cooling setpoint.

2

Unoccupied Sequence

When the return air damper option is installed and a request for unoccupied operation is received, the fan and cooling/heating capacity cycle in a recirculating mode to maintain zone requirements. See below for a detailed description of the operating modes.

If no return air damper is installed, the fan stops and the OA damper closes in unoccupied mode.

Drying Mode

During unoccupied mode (with return air damper option installed), the unit enters the drying mode when the zone

RH exceeds the unoccupied zone RH setpoint. In the drying mode, capacity cycles to maintain the supply air drying

(dew point) setpoint. The SA drying setpoint can be reset down based on zone relative humidity conditions and will be based on the unoccupied zone

RH setpoint.

Supply air reheat functions are active to maintain the supply air reheat setpoint.

Supply air reheat reset functions are active and reset based on unoccupied zone setpoints. Exhaust fan operation control will cycle off during unoccupied modes unless unoccupied economizer operations are active.

Cooling Mode

During unoccupied cooling mode, the fan, economizer, and mechanical cooling cycle to control zone temperature.

Economizer functions will enable when the difference in the enthalpy of the OA

80 MUA-PRC004-EN

Controls

Sequence of

Operation and zone is adequate. Mechanical cooling supplements economizer capacity as required.

Heating Mode

During unoccupied heating mode, fan and heating capacity cycle to maintain the unoccupied zone heating setpoint.

Supply Air Temp Control

(No Dehumidification) Unit

1

Occupied Sequence

During occupied mode, the primary function of the unit is to provide ventilation air to the space. Upon entering the occupied mode, the outside air damper opens and the supply air fan starts.

Cooling Sequence

The unit stages cooling capacity to maintain the supply air cooling setpoint.

The supply air cooling setpoint can be reset down based on HI selectable parameters (OA sensor, zone sensor if installed).

Heating Sequence

The unit stages heating capacity to maintain the supply air heating setpoint.

The supply air heating setpoint can be reset up based on HI selectable parameters (OA sensor, zone sensor if installed). The supply air heating setpoint must be lower than the supply air cooling setpoint.

2

Unoccupied Sequence

In unoccupied mode, the fan stops and the OA damper closes.

Zone Temp Control (No

Dehumidification) Unit

1

Occupied Sequence

During occupied mode, the primary function of the unit is to provide ventilation air to the space. Upon entering the occupied mode, the outside air damper opens and the supply air fan starts.

Cooling Sequence

The unit stages cooling capacity to maintain the supply air cooling setpoint.

MUA-PRC004-EN

The supply air cooling setpoint can be reset down based on HI selectable parameters (OA sensor, zone sensor if installed).

Heating Sequence

The unit stages heating capacity to maintain the supply air heating setpoint.

The supply air heating setpoint can be reset up based on HI selectable parameters (OA sensor, zone sensor if installed). The supply air heating setpoint must be lower than the supply air cooling setpoint.

2

Unoccupied Sequence

In unoccupied mode, the fan stops and the OA damper closes.

Control Sequences of

Operation

Morning Warmup

This feature is available on all types of factory-installed heat units and on units with no heat. This function may still be selected to support systems with heat sources not provided by the fresh air unit. At the conclusion of unoccupied mode, the selected zone is heated to the user-defined morning warmup setpoint.

The unit is then released to occupied mode. There are two types of morning warmup: full capacity or cycling capacity.

• Full capacity morning warmup (MWU)

Full capacity morning warmup uses full heating capacity to heat the zone as quickly as possible. Full heating capacity is provided until the morning warmup setpoint is met. At this point, the unit is released to daytime mode.

• Cycling capacity morning warmup

(MWU)

Cycling capacity morning warmup provides gradual heating to overcome

“building sink” as the zone is heated.

Normal zone temperature control with varying capacity raises the zone temperature to the MWU zone temperature setpoint. Cycling capacity

MWU will operate until MWU setpoint is reached or for 60 minutes. Then the unit switches to occupied mode. Cooling will suspend until building load conditions exceed the MWU setpoint of 3°F (1.7°C), which is field adjustable.

Ventilation Override (VOM) Option

The user can customize up to five different override sequences for purposes of ventilation override control.

If more than one VOM sequence is requested, the sequence with the highest priority initiates first. Priority schedule is that sequence “A” (unit off) is first, with sequence “E” (purge sequence) last.

• UNIT OFF sequence “A”

When complete system shut down is required, the following sequence is used.

• supply fan – off

• outside air dampers – closed

• heat – all stages – off, modulating heat output at 0 vdc

• occupied/unoccupied output – deenergized

• VO relay –energized

• exhaust fan (field-installed) – off

• exhaust damper (field-installed) – closed

• PRESSURIZE sequence “B”

This override sequence is for use when a positively pressured space is desired instead of a negatively pressurized space.

• supply fan – on

• outside air dampers – open

• heat – all stages – off, modulating heat output at 0 vdc

• occupied/ unoccupied output – energized

• VO relay – energized

• exhaust fan (field-installed) – Off

• exhaust damper (field-installed) – closed

• EXHAUST sequence “C”

With the building’s exhaust fans running and the unit’s supply fan off, the conditioned space becomes negatively pressurized. This is desirable for clearing the area of smoke when necessary (i.e., from an extinguished fire, to keep smoke out of areas that were not damaged).

• supply fan – off

• outside air dampers – closed

81

Controls

Sequence of

Operation

• heat – all stages – off, modulating heat output at 0 vdc

• occupied/unoccupied output – deenergized

• VO relay – energized

• exhaust fan (field-installed) – on

• exhaust damper (field-installed) – open

• PURGE sequence “D”

This sequence is for purging air out of a building before coming out of unoccupied mode of operation. Also, it can purge smoke or stale air.

• supply fan on

• outside air damper – open

• heat: all stages off, modulating heat output at 0 vdc

• occupied/unoccupied output energized

• VO relay energized

• exhaust fan (field-installed) on

• exhaust damper (field-installed) open

• PURGE sequence “E”

This sequence uses supply air control for smoke control.

• supply fan on

• outside air dampers open

• heat: all stages off, modulating heat output at 0 vdc

• occupied/unoccupied output energized

• VO relay energized

• exhaust fan (field-installed) on

• exhaust damper (field-installed) open

Note: Each system (cooling, exhaust, supply air, etc.) within the unit can be redefined in the field for each of the five sequences, if required. Also the definitions of any or all of the five sequences may be locked into the software by simple key strokes at the human interface panel.

Generic Building Automation System

Module (GBAS) Option

The generic building automation system module (GBAS) provides broad control capabilities for building automation systems other than a Tracer Summit system. Use a field provided potentiometer or a 0-5 vdc signal to any of the

GBAS inputs, to access the following inputs and outputs listed in the paragraphs below.

• GBAS analog inputs

These four analog inputs can be configured to any of the following:

(1) occupied zone cooling

(2) unoccupied zone cooling

(3) uccupied zone heating

(4) unoccupied zone heating

(5) SA cooling setpoint

(6) SA heating setpoint

(7) space static pressure setpoint

(8) SA static pressure setpoint

• GBAS binary outputs

Each of the five (5) relay outputs can be mapped to any/all of the available diagnostics.

• Demand limiting binary input

This function is operational on units with a GBAS and reduces electrical consumption at peak load times. There are two types of demand limiting, 50% and

100%. When demand limiting is needed, mechanical cooling and heating operation are either partially (50%), or completely disabled (100%) to save energy. The demand limit definition is user definable at the human interface panel. Demand limit binary input accepts a field supplied switch or contact closure. When the need for demand limiting discontinues, the unit’s cooling/heating functions will (again) fully enable.

Evaporator Coil Frost Protection

Frostat™

A temperature sensor on the evaporator determines if the coil is getting close to a freezing condition. Mechanical cooling capacity is shed as necessary to prevent icing.

The Frostat™ system eliminates the need for hot gas bypass and adds a suction line surface temperature sensor mounted near the TXV bulb location to shut off cooling when coil frosting conditions occur. The supply fan does not shut off and will de-ice the coil.

Timers prevent the compressors from rapid cycling.

Occupied/Unoccupied Switching

There are four ways to switch occupied/ unoccupied:

(1) programmable night setback sensor

(2) field-supplied contact closure

(hardwired binary input to RTM)

(3) Tracer Summit or other BAS (via LCI with LonTalk DAC profile)

(4) factory-mounted time clock

• Field supplied occupied/unoccupied input on the RTM

This input accepts a field supplied switch or contacts closure such as a time clock.

• Tracer system

The Tracer system can control the occupied/unoccupied status of the fresh air unit.

• Factory mounted time cock

A time clock can control the occupied/unoccupied status of the fresh air unit.

Timed Override Activation - ICS

This function is operational whenever the unit’s RTM module board is used as the zone temperature sensor source, which can be set at the human interface panel. Initiate this function by pressing the override button on the zone sensor, to switch the unit to the occupied mode.

Unit operation (occupied mode) during timed override will terminate by a signal from Tracer.

Timed Override Activation - Non-ICS

This function is active whenever the user selects the unit’s RTM module board as the zone temperature source

(can be set at the human interface panel). Initiate this function by pressing the override button on the zone sensor, which will switch the unit to the occupied mode. Automatic cancellation of the timed override mode occurs after three hours of operation.

Low Ambient Compressor Lockout

This function will lock out the compressor if the outdoor air temperature is below the low ambient compressor lock-out temperature setpoint when using a field-installed outside air sensor.

This setpoint is adjustable at the human interface panel. Compressors will lock

82 MUA-PRC004-EN

MUA-PRC004-EN

Controls

Sequence of

Operation out when outdoor air temperature falls below that selected temperature and will start again when the temperature rises 5°F above the setpoint.

Comparative Enthalpy Control of

Unoccupied Economizer Operation

An optional comparative enthalpy system controls the economizer operation and measures the temperature and humidity of both return air and outside air to determine which source has lower enthalpy. This system allows true comparison of outdoor air and return air enthalpy by measurement of outdoor and return air temperature and humidity. The comparative enthalpy option should always be ordered with a return air damper.

Note: If the unit does not have comparative enthalpy, the Packaged Fresh Air unit compares outdoor air enthalpy with a fixed reference enthalpy, set through the human interface panel. If ordering the reference enthalpy option, you should also order a return air damper.

Also, either supply air dehumidification with zone RH reference or zone dehumidification with OA RH reference must be ordered to utilize either comparative enthalpy or reference enthalpy control.

Emergency Stop Input

A binary input is provided on the unit’s

RTM module board for installation of a field-provided switch or contacts to immediately shutdown all unit functions.

Total Energy Wheel with Occupancy

Control

The optional total energy wheel recovers energy from the exhaust airstream and preconditions the outdoor air. The total energy wheel enables when the unit is in occupied mode and the exhaust fan is running.

The wheel disables during unoccupied mode or any time that the exhaust fan is not running. This includes the unoccupied economizer mode when the wheel disables, but the exhaust fan enables.

The wheel also disables via a factoryinstalled thermostat at any time a frost condition occurs (default setpoint 12°F).

This frost protection thermostat utilizes a setpoint range of -30 to 100°F.

Total Energy Wheel with Dry-Bulb

Control

The optional total energy wheel recovers energy from the exhaust airstream and preconditions the outdoor air. The total energy wheel enables when all of the following are true:

• unit is in occupied mode

• exhaust fan is enabled

• outside air temperature is above the upper limit setpoint (default setpoint

80°F) or below the lower limit setpoint

(default setpoint 45°F)

• outside air temperature is above the frost protection setpoint (default setpoint 12°F)

Always set the upper limit setpoint to the anticipated return air dry-bulb temperature. Set the lower limit setpoint to 10°F less than the unit supply air dry-bulb setpoint. The wheel will disable during unoccupied mode or when the exhaust fan is not running.

This includes the unoccupied economizer mode when the wheel will disable, but the exhaust fan will enable.

The wheel also disables via a factory installed thermostat when a frost condition occurs. This frost protection thermostat utilizes a setpoint range of

-30 to 100°F.

83

Controls

Zone Sensor

Options

Standard With All Units Optional Zone Sensors

Zone temperature sensor, accessory model number digit 16 = A, BAYSENS017

Dual setpoint, manual/automatic changeover sensor, accessory model number digit 20 = A

This wall-mounted zone sensor ships with every Packaged Fresh Air unit.

Additional sensors are also available for order using the accessory model number. This zone sensor includes an internal thermistor and should be mounted in the zone. This sensor is available for use with all zone sensor options to provide remote sensing capabilities.

Standard with All Units if Supply Air

Dehumidification w/Zone Reference or

Zone Dehumidification

This zone sensor module is for use with cooling/heating applications. It provides the following features and system control functions:

• System control switch (auto/off):

Allows you to automatically select heating or cooling as required, or turn the system off.

• Dual temperature setpoint levers allow you to set different cooling (blue lever) and heating setpoints (red lever).

• Thermometer to indicate temperature in the zone.

• System control switch to select AUTO mode for automatic selection of heating or cooling as required, or OFF to turn the system off.

• Dual temperature setpoint levers for setting cooling (blue lever) or heating

(red lever).

• Thermometer to indicate temperature in the zone.

• Function status indicator lights:

SYS ON glows continuously during normal operation, or blinks if system is in test mode.

COOL glows continuously during cooling cycles or blinks to indicate a cooling system failure.

HEAT glows continuously during heating cycles or blinks to indicate a heating system failure.

SERVICE blinks or glows to indicate a problem. These signals vary depending on the particular equipment used.

Carbon dioxide zone sensor, accessory model number digit 23 = A

This zone sensor is for use with Packaged Fresh Air units to monitor CO

2 levels in the space.

Zone relative humidity sensor

This wall-mounted zone sensor ships with every Packaged Fresh Air unit when the system control options above are ordered. Additional sensors are also available for order using the accessory model number and ordering the space relative humidity kit.

Dual setpoint, manual/automatic changeover sensor with system function lights, accessory model number digit 21 = A

This zone sensor is for use with cooling/ heating applications. It provides the following features and system control functions:

84 MUA-PRC004-EN

MUA-PRC004-EN

Controls

Integrated Comfort™

Systems Sensors for FAU

Applications

Zone Sensor

Options

Zone temperature sensor w/timed override buttons and local setpoint adjustment, accessory model number digit 18 = A, BAYSENS014

Zone temperature sensor w/timed override buttons, accessory model number digit 17 = A, BAYSENS013

This zone sensor is for use with cooling/ heating ICS™. It provides the following features and system control functions:

• Remote temperature sensing in the zone

• A timed override button to move an

Integrated Comfort ™ System or a building management system from unoccupied to occupied mode.

• Setpoint thumbwheel for local setpoint adjustment

• Cancel button to cancel the unoccupied override command.

This zone sensor is for use with cooling/ heating Integrated Comfort™ Systems

(ICS). It provides the following features and system control functions:

• Remote temperature sensing in the zone

• A timed override button to move an

ICS or building management system from it unoccupied to occupied mode.

• Cancel button to cancel the unoccupied override command.

85

Electrical

Data

Power Wire Sizing and

Protection Device

Equations

Each type of unit has its own set of calculations for MCA (minimum circuit ampacity) and MOP (maximum overcurrent protection. For units with multiple modes of operation, you must consider each individual field-wired hazardous voltage circuit. Use the load that provides the highest value in the applicable circuit. To correctly size the unit’s electrical service wiring, read the load definitions that follow and then find the appropriate set of calculations based on your unit type.

Load Definitions

Load 1 = current of the largest motor

(compressor or fan motor)

Load 2 = sum of the currents of all remaining motors

Load 3 = current of electric heaters

Load 4 = control power transformer

= any other load rated at one amp or more (gas heat, factory-wired convenience outlet)

Set #1: Cooling Only Units and Cooling with Gas Heat, All Single Source Power

MCA = (1.25 x load 1) + load 2 + load 4

MOP = (2.25 x load 1) + load 2 + load 4

Select an overcurrent protective device rating equal to the MOP value. If the

MOP value does not equal a standard device size as listed in NEC 240-6, select the next lower standard device rating. If the selected MOP is less than the MCA, then reselect the lowest standard maximum overcurrent protective device size that is equal to or larger than the MCA, provided the reselected device size does not exceed 800 amps.

Disconnect Switch Sizing (DSS) – if field provided and installed

If the unit has a factory-installed, nonfused disconnect switch, this sizing equation is not necessary. If the disconnect is field-provided and installed, use the following equation to determine its rating:

DSS = 1.15 x (load 1 + load 2 + load 4)

Select a disconnect switch (DSS) size equal to or larger than the DSS value calculated.

86

Set #2: Units with Electric Heat, Single

Source Power, Non-Concurrent Load

To arrive at the correct MCA and MOP values, you must perform two sets of calculations: one for cooling only (set #1) and one for electric heat only (set #2).

Calculate the MCA and MOP values as if the unit were in the cooling mode (use the equations given in set #1). Then repeat the calculations for MCA and

MOP for the unit in the heating mode using set #2. When determining loads, keep in mind that the compressors and condenser fans do not run while the unit is in the heating mode.

For units using heaters:

• less than 50 kW, use the formula,

MCA = 1.25 x (load 1 + load 2 + load 4)

+ (1.25 x load 3)

• equal to or greater than 50 kW, use

the formula, MCA = 1.25 x (load 1 + load 2 + load 4) + load 3

Select the nameplate MCA value that is the larger of the cooling (set #1) or the heating mode MCA calculated above.

MOP = (2.25 x load 1) + load 2 + load 3 + load 4

Select an overcurrent protective device rating equal to the MOP value. If the

MOP value does not equal a standard device size as listed in NEC 240-6, select the next lower standard device rating. If the next lower standard rating is less than 125% of the current rating of the electric heater load, select the next higher standard device rating. If the selected MOP is less than the MCA, then reselect the lowest standard device size which is equal to or larger than the

MCA, provided the reselected device size does not exceed 800 amps.

Select the MOP value that is the larger of the cooling (set #1) mode MOP value or the heating MOP value calculated above.

Disconnect Switch Sizing (DSS) – if field provided and installed

If the unit is ordered with a factoryinstalled non-fused disconnect switch, this sizing equation is not necessary. If the disconnect is to be field-provided and installed, use the following equation to determine its rating:

DSS = 1.15 x (load 1 + load 2 + load 3 + load 4)

Select the DSS value that is the larger of the cooling (set #1) mode DSS or the heating mode DSS value calculated above. Select a disconnect switch size equal to or greater than the DSS value calculated.

Set #3: Units with Electric Heat, Single

Source Power, Concurrent Load

Concurrent load = 2 compressors and first stage electric heat

Primary Heat Reheat Selection

You may enable primary heat reheat to take advantage of the primary heat source as supplemental reheat for the condenser reheat. Although in most cases, the MCA and MOP values are unaffected by the concurrent loads of compressors, condenser fans, and first stage of electric heat, there are a few circumstances where the MCA and

MOP are increased when this sequence is employed.

You must perform three sets of calculations to obtain the correct MCA and

MOP values: one for cooling (set #1) only, one for electric heat (set #2) only, and one for when the unit is in the cooling mode with compressors and electric heat on concurrently (set #3).

For size 031 and 040 units, compressors

A (1K1) and B (1K2) can run concurrently with 1 /

3

of three-stage electric heat or 1 /

7

of seven-stage electric heat.

For size 051 and 066 size units, compressors A (1K1) and D (1K4) can run concurrently with 1 /

3

of three-stage electric heat or 1 /

7

of seven-stage electric heat.

For units using heaters less than 50 kW:

MCA = (1.25 x load 1) + load 2 + load 4 +

(1.25 x load 3)

For unit using heaters equal to or greater than 50 kW:

MCA = (1.25 X load 1) + load 2 + load 3 + load 4

Select the nameplate MCA value that is the largest of the three sets of MCA calculations.

MOP = (2.25 x load 1) + load 2 + load 3 + load 4

Select an overcurrent protective device rating equal to the MOP value. If the

MOP value does not equal a standard device size as listed in NEC 240-6, select

MUA-PRC004-EN

Electrical

Data the next lower standard device rating. If the next lower standard rating is less than 125% of the current rating of the electric heater load, select the next higher standard device rating. If the selected MOP is less than the MCA, then reselect the lowest standard device size which is equal to or larger than the

MCA, provided the reselected device size does not exceed 800 amps.

The MOP value selected should be the largest of the three sets of MOP value calculations.

Disconnect Switch Sizing (DSS) – if field provided and installed

If the unit is ordered with a factoryinstalled non-fused disconnect switch, this sizing equation is not necessary. If the disconnect is to be field-provided and installed, use the following equation to determine its rating:

DSS = 1.15 x (load 1 + load 2 + load 3 + load 4)

Select the DSS that is the largest of the three sets of DSS calculations. Select a disconnect switch size equal to or greater than the DSS value calculated.

Set #4: Units with Electric Heat, Dual

Source Power

Dual source power is required only on some 208V and 230V units when provided with electric heat. Those units are: size voltage elec ht kW

031

040

051

066

208V or 230V

208V or 230V

208V or 230V

208V or 230V

42 kW or larger

42 kW or larger

70 kW or larger

70 kW or larger

Dual Source Power

For units with dual source power, use two different sets or MCA and MOP calculations, one for each power connection. MCA1 and MOP1 represent the values calculated for the operation of the compressors and condenser fans.

For the calculations of MCA1 and MOP1, use the instructions from set #1 previously in this section.

MCA2 and MOP2 represent the values calculated for the operation of the unit in heating mode:

MCA2 = (1.25 x load 3) if heater kW is less than 50kW or

(1.0 x load 3) if heater kW is 50kW or greater, MOP2 = (1.25 x load 3)

Select an overcurrent protective device rating for the heating circuit equal to the

MOP2 value. If the MOP2 value does not equal a standard device size as listed in

NEC 240-6, select the next lower standard device rating. If the selected

MOP2 is less than the MCA2, then reselect the lowest standard device size that is equal to or larger than the MCA2, provided the reselected device size does not exceed 800 amps.

Disconnect Switch Sizing (DSS) – if field provided and installed:

If the unit is ordered with a factoryinstalled non-fused disconnect switch, this sizing equation is not necessary. If the disconnect is to be field-provided and installed, use the following equation to determine its rating:

DSS2 = 1.15 x (load 3)

Select the DSS2 value that is the largest of the three sets of DSS2 calculations.

Select a disconnect switch size equal to or greater than the DSS2 value calculated.

Load Definitions

Load 1

Supply Fan Exhaust Fan

Reheat Comp (A) Condenser Fan 1 (A)

Main Comp 1 (B) Condenser Fan 2 (B)

Main Comp 2 (C) Condenser Fan 3 (C)

Main Comp 3 (D) [5100/6600] total Energy Wheel

Load 3

Electric Heat kW < 50 kW > 50

Load 4

Control Power Transformer (Loads > 1

Amp [1T1 - 208/230])

Gas Heat

Factory-Wired Convenience Outlet

MUA-PRC004-EN 87

88

Electrical

Data

Table ED-1. Electrical Service Sizing Data unit size

031

040

056

066 reheat comp (A) main comp 1 (B) main comp 2 (C) main comp 3 (D) voltage tons* rla lra tons* rla lra tons* rla lra tons* rla lra

208/60/3 4.5

15 124

230/60/3 4.5

15 124

9.0

9.0

460/60/3 4.5

8 59.6

9.0

208/60/3 6.75

23 164 10.0

230/60/3 6.75

23 164 10.0

460/60/3 6.75

11 100 10.0

208/60/3 9.0

35 222 14.0

230/60/3 9.0

31 251 14.0

460/60/3 9.0

16 117 14.0

208/60/3 9.0

35 222 15.0

230/60/3 9.0

31 251 15.0

460/60/3 9.0

16 117 15.0

35

31

16

35

31

16

48

43

23

51

46

23

222

251

117

222

251

117

337

376

178

337

376

178

14.0

14.0

14.0

15.0

15.0

15.0

9.0

9.0

9.0

15.0

15.0

15.0

48

43

23

51

46

23

35

31

16

51

46

23

337

376

178

337

376

178

222

251

117

337

376

178

9.0

9.0

9.0

15.0

15.0

15.0

35

31

222

251

16 117

51 337

46 376

23 178

*tons refers to nominal R22 tons electric heat FLA is determined at 208, 240, & 480 volts

Table ED-2. Supply fan motor fla standard efficiency high efficiency

Voltage 1 hp 2 hp 3 hp 5 hp 7.5 hp 10 hp 15 hp 1 hp 2 hp 3 hp 5 hp 7.5 hp 10 hp 15 hp

208/60/3 3.1

5.9

8.7

14.0

22.2

28.2

40.7

230/60/3 2.8

5.6

8.0

13.2

21.6

28.0

40.6

460/60/3 1.4

2.8

4.0

6.6

10.8

14.0

20.3

3.1

2.8

1.4

6.1

5.4

2.7

9.3

8.2

4.1

14.9

12.8

6.4

21.3

20.0

10.0

29.0

25.8

12.9

40.7

35.4

17.7

Table ED-3. Exhaust fan motor fla standard efficiency high efficiency

Voltage 1 hp 2 hp 3 hp 5 hp 7.5 hp 10 hp 15 hp 1 hp 2 hp 3 hp 5 hp 7.5 hp 10 hp 15 hp

208/60/3 3.1

5.9

8.7

14.0

22.2

28.2

40.7

230/60/3 2.8

5.6

8.0

13.2

21.6

28.0

460/60/3 1.4

2.8

4.0

6.6

10.8

14.0

3.1

6.1

9.3

14.9

21.3

29.0

2.8

5.4

8.2

12.8

20.0

25.8

1.4

2.7

4.1

6.4

10.0

12.9

Table ED-4. Energy wheel motor fla unit size voltage

208/60/3

230/60/3

460/60/3

031 040

1/2 hp 1/2

2.7

2.7

2.4

1.2

2.4

1.2

051

3/4

3.6

3.0

1.5

066

3/4

3.6

3.0

1.5

Table ED-5. Condenser fan motors voltage

208/60/3

230/60/3

460/60/3

Table ED-6. Factory-wired convenience outlet voltage

208/60/3

230/60/3

460/60/3 amps

7.21

6.52

3.26

Table ED-7. total gas heat amps with combustion blower voltage

208/60/3

230/60/3

460/60/3 amps

2.54

2.30

1.15

fla

3.8

3.6

1.8

Table ED-8. Control power transformer (loads greater than 1 amp) voltage

208/60/3

230/60/3 amps

1.20

1.09

MUA-PRC004-EN

MUA-PRC004-EN

Electrical

Data

Table ED-9. Electric heat FLA unit size

031

040

051

066 voltage

208/60/3

230/60/3

460/60/3

208/60/3

230/60/3

460/60/3

208/60/3

230/60/3

460/60/3

208/60/3

230/60/3

460/60/3 kW kW kW

20 26 32 kW

42 kW kW

56 70

55.5

72.2

88.8

116.6

155.4

48.1

62.5

77.0

101.0

134.7

24.1

31.3

38.5

50.5

67.4

— kW kW kW

84 100 122

— 72.2

88.8

116.6

155.4 194.3 233.2

— 62.5

77.0

101.0

134.7 168.4 202.1

— 31.3

38.5

50.5

67.4

84.2 101.0

88.8

77.0

38.5

116.6

101.0

50.5

155.4 194.3 233.2 277.6

134.7 168.4 202.1 240.6

67.4

84.2 101.0 120.3

— 116.6

155.4 194.3 233.2 277.6 338.6

— 101.0

134.7 168.4 202.1 240.6 293.5

— 50.5

67.4

84.2 101.0 120.3 146.7

Note: Electric heat FLA is determined at 208, 240 & 480 volts.

Table ED-10. Dual source electric heat - customer wire gauge, AWG unit size

031

040 voltage

208/60/3

230/60/3

208/60/3

230/60/3 kW kW kW

42 56 70

1/0 2/0

1 1/0

1/0 2/0

1 1/0 kW

84

3/0 250

2/0 4/0 kW

100

— kW

122

051

066

208/60/3

230/60/3

208/60/3

230/60/3

— —

— —

— —

— —

3/0 250 300

2/0 4/0 250

3/0 250 300 500

2/0 4/0 250 350

Table ED-11. Voltage utilization range voltage

208/60/3

230/60/3

460/60/3 utilization range

187-220

208-254

416-508

89

Dimensions &

Weights

Typical exterior dimensions

outdoor side view, unit without total energy wheel

OUTDOOR SIDE VIEW

LIFTING HOLE

DETAIL A outdoor side view, unit with total energy wheel

DETAIL B detail B lifting hole detail A

INLET HOOD

END VIEW

CONTROL PANEL

END VIEW inlet hood end view control panel end view

90 unit size A B C without TE wheel

031, 041 18' - 10" 2' - 7" 4' - 2"

051, 066 19' - 3" 3' 5' - 10" with TE wheel

031, 041

051, 066

24' - 2"

24' - 7"

2' - 7"

3'

4' - 2"

5' - 10"

D

3' - 10"

4' - 1"

E

— dimensions (ft and in)

F

3' - 2"

3' - 6"

G

10"

1' - 3"

H

9"

10 1’4"

J

1' - 11 1/2"

2' - 4 1/2"

K

1 1/4"

1 1/4"

L

1' - 6 1’4"

3' - 6 3/4"

M

ø 2 1/2"

ø 3"

N

P

3' - 10" 9 1/4" 3' - 2"

4' - 1" 8" 3' - 6"

10"

1' - 3"

9"

10 - 1’4"

1' - 11 1/2"

2' - 4 1/2"

1' 6"

1' 8"

1' - 6 1’4"

3' - 6 3/4"

ø 2 1/2"

ø 3"

7"

7"

1' - 3/4"

11"

MUA-PRC004-EN

Dimensions &

Weights

Typical exterior dimensions

unit without TE wheel - indoor side view (electric heat version shown) unit with TE wheel - indoor side view (electric heat version shown) single & dual gas heater options

MUA-PRC004-EN 91

Dimensions &

Weights unit without TE wheel

Unit base plan view, duct openings and thru-base power openings, unit sizes 031 & 040

unit without TE wheel unit with TE wheel

92 MUA-PRC004-EN

Dimensions &

Weights

Unit base plan view, duct openings and thru-base power openings, unit sizes 051 &066

unit without TE wheel unit with TE wheel

MUA-PRC004-EN 93

94

Dimensions &

Weights

Fresh air unit control panel detail, all unit sizes

detail A

3x

THRU-BASE MAIN POWER WIRING ENTRANCE

HOLE Ø3.000’’

NOTE: DRILL OR PUNCH HOLE IN COVER PLATE FOR

SMALLER CONDUIT CONNECTION

MUA-PRC004-EN

Dimensions &

Weights

Exterior features for unit sizes 031 & 040, without TE wheel

CONDENSER FANS

CONVENIENCE OUTLET (OPTION)

LIFTING HOLES

MAIN COMPRESSOR ACCESS PANEL

(40x35)

REHEAT COMPRESSOR/COIL ACCESS PANEL

(34x36)

MAIN CONDENSER

COIL ACCESS PANEL

(68x36)

MAIN POWER WIRING ENTRANCE

(CAN ALSO BE RUN THRU-BASE)

HORIZONTAL DISCHARGE

(OPTION)

HUMAN INTERFACE

ACCESS DOOR

UNIT CONTROL PANEL

24 VOLT CONTROL CIRCUIT WIRING ENTRANCE

(CAN ALSO BE RUN THRU-BASE)

DUAL GAS HEAT ACCESS PANEL

(EACH HEATER HAS SEPARATE PANEL)

(16x23)

GAS CONNECTION–DUAL GAS HEAT

(EACH HEATER HAS SEPARATE GAS CONNECTIONS)

NATURAL GAS 250–400 MBH:

.500 NPT INTERNAL

ELECTRIC HEAT POWER WIRING ENTRANCE

(ALSO CAN BE RUN THRU-BASE)

ELECTRIC HEATER ELECTRICAL PANEL (24x30)

-OR-

GAS HEAT PANEL (16x23)

-OR-

FIXED PANEL FOR NO-HEAT OPTION

OR HYDRONIC HEAT INTERFACE OPTION (24x47)

SUPPLY FAN ACCESS DOOR

(33X34)

MUA-PRC004-EN

CONDENSATE

DRAIN CONNECTION

INLET HOOD

FILTER AND DAMPER ACCESS DOOR

(25x39)

EVAP COIL AND

CONDENSATE DRAIN PAN

ACCESS DOOR (18x34)

95

Dimensions &

Weights

Exterior features, unit sizes 031 & 040 with TE wheel

96 MUA-PRC004-EN

Dimensions &

Weights

Exterior features for unit sizes 051 & 066, without TE wheel

CONDENSER FANS

LIFTING HOLES

REHEAT COMPRESSOR/

COIL ACCESS PANEL (40x52)

MAIN COMPRESSOR/

COIL ACCESS PANEL (34x52)

CONVENIENCE OUTLET

(OPTION)

MAIN COMPRESSOR/

COIL ACCESS PANEL

(68x52)

MAIN POWER WIRING ENTRANCE

(CAN ALSO BE RUN THRU-BASE)

HORIZONTAL DISCHARGE

(OPTION)

HUMAN INTERFACE

ACCESS DOOR

UNIT CONTROL PANEL

24 VOLT CONTROL CIRCUIT WIRING ENTRANCE

(CAN ALSO BE RUN THRU-BASE)

DUAL GAS HEAT ACCESS PANEL

(EACH HEATER HAS SEPARATE PANEL)

(16x23)

GAS CONNECTION–DUAL GAS HEAT

(EACH HEATER HAS SEPARATE GAS CONNECTIONS)

ELECTRIC HEAT POWER WIRING ENTRANCE

FOR 208/230 V: 70, 84, 100, 122 kW

(CAN ALSO BE RUN THRU-BASE)

ELECTRIC HEATER ELECTRICAL PANEL (24x49)

-OR-

SINGLE GAS HEAT ACCESS PANEL (16x23)

-OR-

FIXED PANEL FOR NO-HEAT OPTION

OR HYDRONIC HEAT INTERFACE OPTION (24x67)

GAS CONNECTION–SINGLE GAS HEATER

MUA-PRC004-EN

CONDENSATE DRAIN

CONNECTION

SUPPLY FAN ACCESS DOOR

(33x54)

INLET HOOD

FILTER AND DAMPER ACCESS DOOR

(25x59)

97

Dimensions &

Weights

Exterior features for unit sizes 051 & 066 with TE wheel

98 MUA-PRC004-EN

Dimensions &

Weights

Standard curb, unit sizes 031 & 040 without TE wheel

MUA-PRC004-EN

6’’ WOOD NAILER

99

Dimensions &

Weights

Standard roof curb, unit sizes 031 & 040 with TE wheel

100

6" WOOD NAILER

MUA-PRC004-EN

Dimensions &

Weights

Standard curb, unit sizes 051 & 66 without TE wheel

MUA-PRC004-EN

6’’ WOOD NAILER

101

Dimensions &

Weights

Standard roof curb, unit sizes 051 & 066 with total energy wheel

102

6" WOOD NAILER

MUA-PRC004-EN

Dimensions &

Weights

Extended height curb, unit sizes 031 & 040 without TE wheel

6’’ WOOD NAILER

MUA-PRC004-EN 103

Dimensions &

Weights

Extended height roof curb , unit sizes 031 & 040 with TE wheel

104

6" WOOD NAILER

MUA-PRC004-EN

Dimensions &

Weights

Extended height curb, unit sizes 051 & 066 without TE wheel

6’’ WOOD NAILER

MUA-PRC004-EN 105

Dimensions &

Weights

Extended height roof curb, unit sizes 051 & 066 with TE wheel

106

6" WOOD NAILER

MUA-PRC004-EN

Dimensions &

Weights

Unit and accessory weights

Table I-DW-1. Typical unit, unit with total energy wheel, and roof curb weights unit size

031

040

051

066 base unit total energy wheel unit roof curb for unit w/o TE wheel roof curb for unit with TE wheel weight 1 base weight 1 low high acoustic low high

4600

4700

5600

6000

1460

1520

1920

1970

282

282

282

282

613

613

613

613

1500

1500

1500

1500

350

350

350

350

766

766

766

766

1. Base unit operating weight is for units with the condenser hot gas reheat option, return air, and no heat. Subtract condenser hot gas reheat weight for cooling only units. See Table

I-DW-2 for weight.

Table I-DW-2. Typical component weights unit size

031

040

051

066 single gas (MBh)

125 150 200

201 217 247

201 217 247

201 217 247

201 217 247

250 300 350

295 295 333

295 295 333

400

250 300 dual gas (MBh)

400

402 434 —

402 434 494

500

600

700

electric heaters

800

295 295 333 361 402 434 494 590 590 — —

295 295 333 361 402 434 494 590 590 666 722

20-84 kW

60

60

60

60

100,122 kW

100

100 condenser hot gas reheat 2

150

150

270

270

D E F

C

Figure I-DW-1. Fresh air unit weight and center of gravity unit size center of gravity

X (in) Y (in) units without total energy wheel

031 90 50

040

051

066

90

100

100

50

51

51 units with total energy wheel

031 123 50

040

051

066

123

130

130

50

51

51 max operational weight (lbs)

4934

5194

6190

6722

6394

6718

8081

8663

A

16

16

13

13

16

16

19

19

B typical point loading—% of unit weight

B C D E

16

16

15

15

18

18

18

18

19

19

17

17

17

16

17

17

18

18

15

15

18

17

20

21

17

17

18

18

16

16

15

15

F

16

17

16

16

14

14

16

16

MUA-PRC004-EN

A

107

Component arrangement unit size 031 & 040

Dimensions &

Weights unit without TE wheel unit sizes 031 & 040 unit with TE wheel

108 MUA-PRC004-EN

Component arrangement unit size 051 & 066

Dimensions &

Weights unit withouth TE wheel unit with TE wheel

MUA-PRC004-EN 109

Dimensions &

Weights

Total energy wheel cassette locations, typical indoor side views

unit size 031 unit size 040 unit size 051 unit size 066

110 MUA-PRC004-EN

Minimum operating & service clearances

Dimensions &

Weights unit without TE wheel unit without TE wheel

TOP: CLEAR OF ALL OBSTACLES OR OVERHANGS unit with TE wheel

MUA-PRC004-EN

TOP: CLEAR OF ALL OBSTACLES OR OVERHANGS

111

Mechanical

Specifications

Fan Motors

The supply and exhast fan motors are either standard-efficiency open dripproof or high-efficiency open drip-proof.

All supply fan motors meet the U.S.

Energy Policy Act of 1992 (EPACT).

Exhaust Backdraft Damper

A backdraft damper prevents outside air entry into the building through the exhaust fan. Damper frame is extruded aluminum with mitered corners. Blades are formed aluminum with extruded vinyl edge seals that mechanically lock into the blade edge. Bearings are corrosion resistant synthetic and the linkage is concealed in frame for low pressure drop and noise.

Condenser Fan and Motors

The unit condenser fans are vertical discharge, direct-drive fans. They are statically and dynamically balanced. The blades and spider are constructed of zinc-plated steel. Condenser fan motors are three-phase motors with permanently lubricated ball bearings, built-in current and thermal overload protection, and weather-tight slingers over the motor bearings.

Filters

The filter racks (see Figure MS-4) accommodate 2” filter media and are field convertible to allow 4” filter media.

Figure MS-4. Filter racks

112

Dampers – Low Leak

The outside air damper has a unitcontrolled actuator with parallel-blades.

The blade construction is a 14-gage galvanized steel, roll-formed airfoil-type.

Figure MS-5. Traq ™ Damper

Figure MS-6. Return air damper building comfort. A centralized microprocessor provides anti-short cycle timing and time delay between compressors to provide a higher level of machine protection. The unit controls can function as a stand-alone controller ling. The character font is 5 x 7 dot matrix plus cursor. The display is a supertwist liquid crystal display (LCD) with blue characters on a gray/green background, which provides high visibility and interface ease. Meaningful diagnostics are also reported and displayed at the HI panel display.

The HI keypad is equipped with 16 individual touch-sensitive membrane key switches. The switches are divided into four separate sections and password protected to prevent tampering by unauthorized personnel. The six main menus are STATUS, SETPOINTS,

DIAGNOSTICS, SETUP, CONFIGURA-

TION, and SERVICE MODE.

Options

Electric Heating Option

High nickel chrome alloy resistance wire is mechanically staked and welded to corrosion-resistant terminals. Heaters are provided with both manual and automatic temperature control devices.

See Figure MS-4.

3-Stage Electric Heat

These electric heaters have three balanced stages with heating steps of

33, 66, and 100%.

7-Stage Electric Heat

These heaters have three unbalanced stages, resulting in seven steps of 14,

27, 41, 59, 68, 86, and 100%.

Electrical and Controls

Controls

The Trane Packaged Fresh Air unit is completely factory-wired with necessary controls and terminal block for power wiring. Microprocessor controls are provided for all 24-volt and 115-volt control functions. The resident control algorithms make all heating, cooling, drying, and/or ventilating decisions in response to electronic signals from sensors measuring indoor temperature, outdoor temperature, and humidity.

The control algorithm maintains accurate temperature, dew point, and/ or humidity control. It also minimizes setpoint drift and provides better Figure MS-7. Electric heat option

MUA-PRC004-EN

Mechanical

Specifications

Gas-Fired Heating Option

The Packaged Fresh Air unit’s furnaces are certified for 80% thermal efficiency.

The heaters include an integral power vent system. All natural gas-fired units are completely assembled and wired at the factory. The burner and bottom pans are type 409 stainless steel.

409 Stainless Steel Heat Exchanger

Heat exchanger headers and tubing are type 409 stainless steel.

321 Stainless Steel Heat Exchanger

Heat exchanger headers and tubing are type 321 stainless steel.

Single Bank Staged

A single heater unit with a two-stage gas valve provides two steps of heat.

Single Bank Modulated

A single heater unit with solid state controls provides close temperature control through regulating manifold pressure. The controls modulate between 50 and 100%.

Dual Bank Staged

The heater bank contains a single-stage and a two-stage unit. This combination results in steps of 25, 50, 75, and 100%.

Dual Bank Modulated

The heater bank contains a single-stage and a modulating unit. The microprocessor sequences the single stage bank with the modulating bank to provide capacity control between 25-100% heating capacity. This combination results in 25 to 50% modulation, a 25% step, and 75 to 100% modulation.

Hydronic Heat Interface

A bulkhead and coil support is provided downstream of the fan to accept a fieldinstalled one or two-row hydronic heating coil. The unit controller provides a modulating output to control a fieldinstalled water valve and accepts a low temperature limit input signal. The coil supports accept a standard Trane

33X36” heating coil for the small cabinet and 33X48” coil for the large cabinet. Large cabinets may require field-provided blockoffs. Also, if fieldinstalling smaller coils than recommended, additional field modifications or blockoffs must be made. Openings in the unit side panels for piping must also be field constructed.

Condenser Hot Gas Reheat

An indoor reheat condenser is mounted downstream of the evaporator coils.

The indoor and outdoor reheat condenser has parallel circuits. A liquid solenoid valve controls where refrigerant condensation occurs.

Traq™ Damper

Traq outdoor air dampers with flow measurement rings and a ventilation control module are available for airflow measurement and verification. Each damper has a unit-controlled actuator.

See Figure MS-5.

Return Air/Reference Enthalpy

Air returns vertically through the unit base. Dampers are low-leak. Each damper has a unit-controlled actuator.

Inputs are provided for unoccupied economizer control, based upon a comparison of the outside air stream to a definable enthalpy reference point.

See Figure MS-6.

Return Air/Comparative Enthalpy

Air returns vertically through the unit base. Dampers are low-leak. Each damper has a unit-controlled actuator.

Inputs are provided for unoccupied economizer control, based upon a comparison of enthalpies of the return and outdoor air streams.

External Exhaust Interface

The exhaust plenum is internal to the unit cabinet and has one-inch, doublewall, foamed construction. The unit controller provides a binary exhaust fan signal and accepts a binary fan airflow proving input signal from a fieldinstalled exhaust fan.

Corrosion-Inhibiting Coil Coating

The indoor and outdoor coils have a four to six mil protective coating applied by a multiple dip and bake process.

Corrosion-Inhibiting Cabinet Coating

The unit’s interior and exterior surfaces have a four to six mil spray-on protective coating applied with an air-dry process.

Two-Inch Throwaway Filter

The Fresh Air Unit’s filters are UL class

2. Filters are 30% efficient based on

ASHRAE test standard 52-76 with an arrestance of 90-92%.

Dirty Filter Switch

This option indicates when there is a dirty filter. The dirty filter switch triggers an information-only diagnostic message on the human interface or lights the service LED on the zone sensor, and will allow continued unit operation.

Non-Fused Disconnect Switch

A through-the-door, non-fused disconnect switch with external handle is factory-installed. See Figure MS-7.

Figure MS-8. Non-fused disconnect switch

Convenience Outlet

A convenience outlet is provided on the condenser side of the unit. The GFI outlet is 115 volt, and capable of manual resetting.

Figure MS-9. Convenience outlet

Extended Grease Lines

Factory installed extended grease lines provide a common location for regreasing the supply and exhaust fan bearings. The grease fittings are easily accessible within the fan compartment.

MUA-PRC004-EN 113

114

Mechanical

Specifications

LonTalk ® Communications Interface

(LCI-I)

The LCI-I provides an interface to a

Tracer Summit system or other control system that supports LonTalk and the

DAC profile. The LCI-I is a factoryinstalled device and provides a Comm5 interface to a Trane Integrated Comfort

System (ICS). The LCI-I allows control and monitoring of the unit via a twowire communication link.

Generic Building Automation

System (GBAS)

The GBAS module is for use with a non-

Trane building management system.

The module provides a binary input for demand limiting, four analog inputs for setpoint adjustment, and five relay outputs for diagnostic reporting. Inputs can use a potentiometer or 0-5 VDC signal.

Ventilation Override Module (VOM)

The VOM allows programming of the unit with up to five ventilation sequences: smoke purge, evacuation, pressurization, purge, and purge with duct control. Typically a hard-wire short from a smoke detector or fire control panel will cause a binary input on the

VOM to close, thus causing the programmed sequence to occur. These points can be permanently locked to prevent tampering.

Interface for Remote Human

Interface (RHI)

This interface consists of an interprocesor communication board

(IPCB) and is factory-installed in the unit control panel. This component provides a communication bridge for the RHI to up to four units. This option must be installed in the unit to communicate with a remote HI.

Accessories

Roof Mounting Curb

The roof mounting curb is fabricated of

14-gage galvanized steel with a nominal two x two-inch nailer setup. The curb ships knocked down with a curb gasket.

Curb height options are 14 or 24-inches.

Acoustical Roof Curb

The acoustical roof curb ships fully assembled and has prefabricated, noncombustible construction with sealing gasket around perimeter members to ensure air/water tight integrity. The curb construction is a minimum 14 gage galvanized steel structural members with minimum 20 gage galvanized steel flashing with overlapping continuous rubber counter flashing. Curbs have a 2”x2” nailer strip for attaching roof felts. The base contains acoustically nonconductive floor pans with the supply and return openings framed for duct attachment.

The roof curb incorporates an integral spring-vibration isolation rail with adjustable 1” deflection isolators, and is properly sized and selected for unit point loading. Spring isolators have a minimum 90% isolation efficiency.

Permanent Filters

Permanent filters are provided with a

2” metal frame and permanent wire mesh media. The filter media is cleanable.

LonTalk Communications Interface

(LCI-I) Kit

A field-installed LCI-I kit is provided to interface with a Tracer Summit system or other control system that supports

LonTalk and the DAC (discharge air control) profile. The LCI-I kit provides a

Comm5 interface to control and monitor the unit via a two-wire communication link.

Generic BAS (GBAS) Interface Kit

A field-installed GBAS kit is provided for use with a non-Trane building management system. The GBAS module provides a binary input for demand limiting, four analog inputs for setpoint adjustment, and five relay outputs for diagnostic reporting. Inputs use a potentiometer or a 0-5VDC signal.

Ventilation Override Module (VOM)

Kit

This field kit allows ventilation override capability. The VOM module allows programming of the unit with up to five ventilation sequences: smoke purge, evacuation, pressurization, purge and purge with duct control. Typically a hard-wire short from a smoke detector or fire control panel will cause a binary input on the VOM to close, thus causing the programmed sequence to occur.

These points can be permanently locked to prevent tampering.

MUA-PRC004-EN

MUA-PRC004-EN

Mechanical

Specifications

Electronic Time Clock

The electronic time clock is fieldinstalled. It allows night setback and unoccupied functions when using a standard (dual setpoint) zone sensor module.

Remote Human Interface

The remote human interface (RHI) panel can perform all the same functions as the unit mounted human interface, except for the service mode. It uses the same two line x 40-character display and keypad as the HI. Also, the RHI can monitor up to four units.

Zone Temperature Sensor

A remote zone temperature sensor is available for use when using zone sensors for morning warmup (with all units or as a zone sensor with the Tracer

Integrated Comfort system).

Zone Sensor with Timed Override

A zone temperature sensor with timed override buttons is available for use with the Tracer Integrated Comfort system.

Zone Sensor with Local Setpoints

A zone temperature sensor with local temperature adjustment control and timed override buttons is available for use with the Tracer Integrated Comfort system or for use as a morning warmup setpoint and sensor.

Remote Minimum Position

Potentiometer Control

A remote minimum position potentiometer allows remote control of the minimum outside air damper position.

Dual Setpoint Sensor

The dual setpoint sensor is for use with zone heating and cooling setpoints, and supply air cooling and heating resets.

The zone sensor has two temperature setpoint levers and an auto-off system switch.

Dual Setpoint Sensor with System

Function Lights

The dual setpoint sensor is for use with zone heating and cooling setpoints, as well as supply air cooling and heating resets. The zone sensor has two temperature setpoint levers, an auto-off system switch, and status indication

LED lights for: system on, heat, cool, and service.

Space Relative Humidity Kit

The zone relative humidity sensor initiates the dehumidification mode for zone dehumidification units. It can also reset the supply air-drying or zone relative humidity setpoints.

Carbon Dioxide Sensor

The carbon dioxide sensor is fieldinstalled. It monitors carbon dioxide concentrations and displays on the human interface panel.

Dry-bulb Duct Sensor

This field-installed bullet-type sensor option is for use as a temperature input from a location such as a return air duct.

115

A business of American Standard Inc.

www.trane.com

Literature Order Number

File Number

Supersedes

Stocking Location

For more information contact your local Trane office or email comfort@trane.com

MUA-PRC004-EN

PL-AH-MUA-PRC004-EN 1202

MUA-PRC004-EN 0402

LaCrosse–Inland

Trane has a policy of continuous product improvement, and reserves the right to change designs and specifications without notice.