December 2002
Introduction
Unit mounted IntelliPak ™ microprocessor control with easy-to-read human interface
2’’ Pleated filter section with adjustable rack to 4’’
Horizontal or vertical discharge openings
Hi-rise electric
(or gas) heat
1’’ Solid double-wall panels of foamed-inplace construction
Quiet FC fan
© 2002 American Standard Inc.
Non-corrosive IAQ drain pan sloped in two directions
Optional condenser reheat coil with modulating control
Standard protective bird screen on inlet hood
Traq ® damper available for airflow measurement
Optional return air damper for unoccupied recirculation
MUA-PRC004-EN
MUA-PRC004-EN
Table of
Contents
3
Features and
Benefits
We designed the Packaged Fresh Air unit based on customer requirements from across the country. Thorough analysis of the performance requirements resulted in a robust design with the ability to effectively operate over an expansive performance envelope required for the year-round treatment of outdoor air.
Also, we took into account today’s HVAC market issues, such as indoor air quality
(IAQ). We equipped the Packaged Fresh
Air unit to meet your ventilation needs
— in direct response to the ventilation and humidity control requirements of
ASHRAE standard 62.1-1999.
Trane’s Packaged Fresh Air unit leads the industry in the key areas of:
• indoor air quality (IAQ)
• high quality and durability
• advanced, integrated controls
• flexibility
• enhanced serviceability
Indoor Air Quality (IAQ) Features
• Non-corrosive drain pan sloped in two directions to ensure proper drainage to reduce the potential for microbial growth
• Double-wall foamed panel construction throughout the indoor section of unit to provide, non-porous, cleanable interior surfaces
• High efficiency throwaway filter option with standard 2” or 4” adjustable filter rack
• Traq™ outdoor airflow measurement damper
• total energy wheel option for recovered energy from centralized building exhaust
• Easy filter access encourages frequent changing
High Quality and Durability
• Robust unit construction with 1” double-wall panels and access doors.
• High quality, long-lasting latches and hinges for all access doors.
• Protective standard prepainted finish on cabinet exterior with optional corrosion inhibiting coatings available for the unit exterior, interior and coils.
• Assured dehumidification performance and control with capability of providing low dew point supply air.
• Optional modulating recovered refrigerant reheat for unit supply air.
Advanced Controls
• All controls are factory-engineered, mounted, configured and tested to minimize field startup time.
• IntelliPak™ microprocessor control with easy-to-read human interface clear language display (English,
French, or Spanish).
• Human interface with 16-button keypad for monitoring, setting, editing and controlling.
• Capable of supply-air control or zone control of both temperature and relative humidity
• Occupied and unoccupied control sequences including unoccupied economizer logic.
• Additional control sequences including demand limit, exhaust control and
CO2 monitoring.
• Optional remote human interface for ease of control access without going outdoors.
• Optional LonTalk® communications interface (LCI-I) communication link with a Tracer Summit™ building management system or other control systems that support the LonTalk discharge air control (DAC) profile.
• Generic BAS and ventilation override capability for added control flexibility
Flexibility
• Modular Intellipak controller design…you only pay for what you need
• Vertical or horizontal discharge available
• Numerous heater options and temperature rise capabilities available.
• Standardized roof curb
Figure FB-1. Fan side view of the Trane Packaged fresh air unit
4 MUA-PRC004-EN
Features and
Benefits
Enhanced Serviceability
• Five hinged access doors with safety chains for ease of maintenance and service
• Easy-open door latches
• Human Interface (HI) door provides access without opening control panel door
• Modular control board design with ability to swing out HI during service
Standard Unit Features
• Four unit sizes (031, 040, 051, 066) with airflow range of 1800-6600 cfm
• Double-wall construction with 18g outer and 20g inner galvanized metal skin.
• Outdoor air inlet hood
• Prepainted exterior finish
• Air-cooled DX refrigeration system
• Completely factory-piped and leaktested refrigeration system
• Non-corrosive drain pans sloped in two planes
• Centrifugal double-width, double-inlet
FC fan with permanently lubricated bearings
• Scroll compressors
• Terminal block for power connection
• Single-point power connections for non-electric heat units
• Filter rack adjustable for two or four inch filters
• UL listing on all standard options
Standard Control Features
• Fully integrated, factory-installed and commissioned microelectronic controls
• Unit mounted human interface panel
• FROSTAT™ coil frost protection
• Supply airflow proving
• Emergency stop
• Mappable sensors and setpoint sources
• Occupied/unoccupied control modes
• Timed override for unoccupied mode
Optional Features
• Vertical or horizontal discharge
• Low or high rise gas heaters (single bank and dual bank)
• Staged or modulating gas heat control
(4:1 max turndown)
• 409 or 321 stainless steel gas burner
• Three or seven stage electric heat
• Hydronic heat interface (heat coil fieldprovided)
• Condenser reheat with modulating control
• Low-leak parallel blade or Traq™ outdoor airflow damper
• Return air damper with comparative or reference enthalpy
• Standard or high-efficiency fan motor
• total energy wheel
• Protective coatings for the unit and/or coils
• Two inch pleated media filters (30% efficiency)
• Dirty filter switch
• Supply air or zone control
• Larger, more efficient fan option available for high airflow, low external static pressure points
• LonTalk® Communications Interface module
• Generic BAS module
• Ventilation override from up to five external inputs
• Remote human interface
• Exhaust interface with exhaust opening integral to unit cabinet
• Through-the-door, non-fused disconnect switch
• Factory or field-wired convenience outlet
• Extended fan grease lines
Field-Installed Accessories
• Roof curb in 14” or 24” height
• Remote human interface controls up to four units
• 2” cleanable filters
• Time clock
• Zone sensors with a variety of different features and functions
• Field-installed module kits available for field upgrade of controls
• Remote minimum potentiometer control
• CO
2
sensor available with Traq™ only
• Duct-mounted temperature sensor
Figure FB-2. Compressor side view of the Trane Packaged fresh air unit
MUA-PRC004-EN 5
Application
Considerations
6
Fresh Air Unit Functions
The Packaged Fresh Air unit (FAU) provides conditioned outdoor air suitable for mechanical ventilation or make-up air. The FAU conditions outdoor air as necessary to meet system performance requirements by filtration, cooling, dehumidification, and/ or heating. The FAU may deliver ventilation air in a number of ways. See the System Configurations section and
Figures AC-1 through AC-3 for more information.
Filtration
Filtration is necessary for the FAU to maintain system operating efficiency, meet occupant comfort and health needs, and provide adequate building filtration to aid indoor air quality. The
Packaged FAU offers a variety of filter options to meet most application needs.
Cooling
When the outdoor air dry-bulb temperature is warmer than space conditions, the unit cools the outdoor air to the appropriate supply air dry-bulb temperature. The Packaged FAU provides cooling using an air-cooled, directexpansion (DX) refrigeration system with scroll compressors.
Dehumidification (Drying)
The Packaged FAU dehumidifies the outdoor air when it is more humid than the required space target conditions.
This helps prevent high relative humidity levels in the space. Occasionally, the outdoor air may require sub-cooling to remove excess moisture. When necessary, the FAU reheats discharge air to meet space comfort conditions.
The Packaged FAU recovers energy from the cooling process to reheat the sub-cooled air as necessary.
When the outdoor air dry-bulb temperature is colder than space conditions require, the FAU heats the outdoor air to meet space temperature requirements.
The Packaged FAU has electric or gas heat options available.
Dedicated outdoor air systems can deliver conditioned outdoor air in one of the following ways:
1. Directly to the occupied space, with the local terminal unit controlling the space dry-bulb temperature. See
Figure AC-1.
2. Directly to local terminal units, which deliver a mixture of the conditioned outdoor air and (conditioned) recirculated return air to the space. See
Figure AC-2.
3. Directly to a single space and control the space temperature directly. For example, this application will provide temperature control of a hotel hallway and ventilation of the adjacent rooms.
See Figure AC-3.
Supply Air Temperature
Give careful consideration when selecting the FAU supply air temperature. Many current system designs control the fresh air unit discharge air to a “space neutral” dry-bulb condition, typically about 75°F. At some operating conditions, reheating the FAU supply air will add cooling load to the space, thus requiring the local terminal units to “recool” the conditioned outdoor air to meet the space setpoint. Therefore, to help lower energy costs, use reheat only when required to maintain occupant comfort and space relative humidity. The Capacity Control section discusses this issue in more detail.
Airside Economizers
Often fresh air units are sized to deliver the minimum ventilation air required for the space it serves. However, ventilation air is typically only a portion of the space supply air. Airside economizing can provide up to 100% of the space supply air when outdoor air conditions are suitable for “free cooling” capability.
It’s important to remember that airside economizer capability can be lost if dedicated outdoor air systems are sized for minimum ventilation air only. To provide economizer capability on a dedicated outdoor air system, the terminal units must be able to introduce
100% outdoor air during the economizer-cooling mode. The terminal unit’s outdoor air damper should modulate between fully closed and fully open to allow the FAU to deliver the ventilation air design volume to the space. The terminal unit should enable economizing only if the outdoor dry-bulb and dew point conditions are sufficiently low to justify economizing.
Figure AC-1. Direct discharge to conditioned space
Figure AC-2. Indirect discharge to fan-coil units
Figure AC-3. Direct hall discharge with fancoil or PTAC units
MUA-PRC004-EN
Application
Considerations
The Packaged FAU can use either DX cooling, condenser reheat, electric or gas heat to condition the outdoor air.
The unit controls cooling and heating capacity in stages with the exception of the modulated heat options. Cooling and heating staging result in supply air temperature swings. The unit controls deliver the desired supply air conditions on a time-based, weighted average.
Figure AC-4 shows the FAU system with a DX refrigerant circuit design using reheat.
Dehumidification
Consider Chart AC-1. If the outdoor air dew point is above the drying setpoint
(or in the case of zone control, the zone
RH is above the RH setpoint), the FAU will:
• cool the outdoor air to remove required moisture and
• reheat to meet the discharge temperature setpoint.
At h1, 100% outdoor air enters the FAU.
The FAU filters, cools, and dehumidifies the air as it moves through the evaporator coil. Air leaves the evaporator coil saturated at the preset dew point condition (h3) and is reheated by the reheat condenser to the pre-set reheat temperature setpoint (h4). The reheat evaporator transfers energy to the reheat condenser. A liquid solenoid valve effectively modulates the reheat condenser capacity. The reheat outdoor condenser rejects surplus heat. The reheat evaporator circuit is first on and last off, so reheat energy is available at full and part load conditions. For those conditions where the reheat condenser capacity is insufficient to meet reheat demand, optional electric or gas heat can provide additional reheat capacity.
Since both the dew point setpoint and discharge temperature setpoint are fully adjustable, the desired supply air conditions are maintained at all load conditions.
Cooling or Heating
Consider Chart AC-2. If the outdoor air dew point or zone RH is equal to or below the drying setpoint, the FAU will heat or cool the outdoor air to separate and adjust cooling or heating setpoints.
At t1 or t3, 100% outdoor air enters the
FAU. The FAU filters, and cools or heats the air as it is drawn through the evaporators and heating section. The air leaves the FAU at the cooling or heating setpoint (t2 or t4) and equal to or below the dew point setpoint.
h3 h2 h4
W et Bulb T emperature t3 heating t4 t2 cooling t1
Dry Bulb Temperature h1
Chart AC-1. Psychrometric dhart with dehumidification and reheat
Chart AC-2. Psychrometric chart with cooling and heating only
Figure AC-4. Refrigeration system diagram with reheat
MUA-PRC004-EN
Subcooler
Receiver
7
Application
Considerations
Figure AC-5 shows the Packaged FAU
DX system, using a refrigerant circuit design without reheat.
Dehumidification (Drying)
Consider Chart AC-3. If the outdoor air dew point or zone RH is above the drying setpoint, the FAU will dehumidify the outdoor air. 100% outdoor air enters the FAU (h1). The unit filters, cools (h2) and dehumidifies the air as it is drawn through the evaporator coils. Air leaves the evaporator coils saturated at a preset dew point setpoint (h3). Since the dew point setpoint is fully adjustable, the desired dew point condition is maintained at all load conditions.
Cooling or Heating
Consider Chart AC-4. If the outdoor air dew point is equal to or below the dew point setpoint, the FAU will heat or cool the outdoor air to separate and adjust cooling or heating setpoints. 100% outdoor air enters the FAU (t1). The unit filters and cools or heats the air as it is drawn through the evaporators and heating section. The air leaves the FAU at the cooling or heating setpoint and equal to or below the dew point setpoint.
Wet Bulb Temperature
Dehumidification h3 h2
W et Bulb T em pe rature t3 heating t4 t2 h1
Dry Bulb Temperature
Chart AC-3. Psychrometric chart with dehumidification, no reheat cooling t1
Dry Bulb Temperature
Chart AC-4. Psychrometric chart with cooling and heating only
Evaporator 1
Circuit 2 Compressors
Circuit 1 Compressor
Condenser 1
Subcooler
Evaporator 2
Condenser 2
FIgure AC-5. Refrigeration system diagram without reheat
8
MUA-PRC004-EN
Application
Considerations
Determining the FAU capacity requirements requires careful thought. Airhandling equipment is typically selected based on design sensible conditions.
Since latent loads drive the need for the
FAU, base the selection on design latent conditions.
Evaporator Design Entering Conditions
For many climates the peak outdoor air enthalpy occurs at a time when the outdoor dry-bulb temperature is not the highest. Refer to the chapter on climatic design information in the ASHRAE
Handbook of Fundamentals. The cooling and dehumidification design condition data is provided three ways:
1. Design dry-bulb temperature with mean coincident wet bulb temperature
2. Design wet-bulb temperature with mean coincident dry-bulb temperature
3. Design dew point temperature with single bank option is 50% and the dual bank is 25%. Calculate the minimum temperature rise to determine the heating control capability. mean coincident dry-bulb temperature
The design wet-bulb condition typically represents a significantly higher outdoor air enthalpy than the design dry-bulb condition. Use the condition that represents the highest enthalpy as the entering evaporator selection condition.
Evaporator Design Leaving Conditions
Due to the uncertainty of the local terminal unit’s latent capacity at part load, it is usually most straightforward to size the FAU to handle the entire latent load on the system, both indoor and outdoor. With this design approach, the terminal units may do some latent cooling (dehumidification) during periods of higher sensible load. At these times, the space will run slightly drier than the design RH limit. This is why it makes sense to select the FAU to limit the space RH to a maximum allowable level for those conditions when the terminal units are providing no space latent cooling. ASHRAE standards 62.1
and 55 recommend using 60% RH design limit for comfort cooling. Using lower design limits may result in an unnecessary increase in system operating energy use.
Use Tables AC-1, AC-2, and AC-3, on pages 9 and 10, to identify the appropriate supply air dew point for specific design conditions. For a more detailed discussion on determining the selection criteria of a FAU, reference Trane publications SYS-EB-3 or SYS-APM-
004.
The Trane FAU utilizes recovered energy from the cooling process to reheat the air leaving the cooling coil as required to meet the discharge air setpoint. The reheat refrigerant circuit is adequate to deliver enough reheat to supply space temperature neutral air
(e.g. 75°F dry-bulb) under most operating conditions. On very low load days, the reheat circuit may not contain enough energy to meet the desired reheat setpoint. Under those operating conditions, the FAU can use supplemental heat provided in the heating section.
Because the heat section is sized for the design heating condition, larger than normal supply air temperature swings may occur when using it for incremental reheat energy.
Table AC-1. Supply air dew point temperature, 75°F at 60% RH space limit latent load
Btu/h per Person
100
120
140
160
180
10
54.6
53.3
52.0
50.6
49.2
400
420
440
460
480
500
300
320
340
360
380
200
220
240
260
280
47.7
46.1
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Note: Minimum dew point selectable is 45°F.
52.5
51.6
50.6
49.7
48.7
—
—
—
—
—
—
47.7
46.6
45.5
—
—
15
56.6
55.8
55.0
54.2
53.3
55.8
55.3
54.8
54.3
53.8
53.3
52.8
52.3
51.7
51.2
50.6
50.1
49.5
48.9
48.3
47.7
25
58.1
57.6
57.2
56.7
56.3
54.6
54.0
53.3
52.7
52.0
51.3
50.6
49.9
49.2
48.5
47.7
46.9
46.1
45.3
—
—
20
57.5
57.0
56.4
55.8
55.2
56.6
56.2
55.8
55.4
55.0
54.6
54.2
53.8
53.3
52.9
52.5
52.0
51.6
51.1
50.6
50.2
30
58.4
58.1
57.7
57.3
57.0
cfm per person
35
58.7
58.4
58.1
57.8
57.4
57.1
56.8
56.5
56.1
55.8
55.5
55.1
54.8
54.4
54.1
53.7
53.3
53.0
52.6
52.2
51.8
57.5
57.2
57.0
56.7
56.4
56.1
55.8
55.5
55.2
54.9
54.6
54.3
54.0
53.6
53.3
53.0
40
58.9
58.6
58.3
58.1
57.8
58.4
58.3
58.1
57.9
57.7
57.5
57.3
57.1
57.0
56.8
56.6
56.4
56.2
56.0
55.8
55.6
60
59.3
59.2
59.0
58.8
58.6
58.3
58.1
57.9
57.7
57.5
57.3
57.1
56.8
56.6
56.4
56.2
56.0
55.8
55.6
55.4
55.1
55
59.2
59.1
58.9
58.7
58.5
58.1
57.9
57.6
57.4
57.2
57.0
56.7
56.5
56.3
56.0
55.8
55.6
55.3
55.1
54.8
54.6
50
59.2
58.9
58.7
58.5
58.3
57.8
57.6
57.3
57.1
56.8
56.6
56.3
56.1
55.8
55.5
55.3
55.0
54.7
54.4
54.2
53.9
45
59.0
58.8
58.6
58.3
58.1
MUA-PRC004-EN 9
Application
Considerations
Table AC-2. Supply air dew point temperature, 75°F at 55% RH space limit latent Load
Btu/h per Person
200
220
240
260
280
100
120
140
160
180
400
420
440
460
480
500
300
320
340
360
380
25
55.5
55.0
54.5
54.0
53.5
53.0
52.4
51.9
51.4
50.8
50.2
49.7
49.1
48.5
47.9
47.2
46.6
46.0
45.3
—
—
20
54.9
54.2
53.6
53.0
52.3
51.6
50.9
50.2
49.5
48.8
—
—
—
—
—
—
48.0
47.2
46.4
45.6
—
15
53.8
53.0
52.1
51.2
50.2
49.3
48.3
47.2
46.2
45.1
—
—
—
—
—
—
—
—
—
—
—
10
—
—
—
—
—
51.6
50.2
48.8
47.2
45.6
—
—
—
—
—
—
—
—
—
—
—
30
55.9
55.5
55.1
54.6
54.2
53.8
53.4
53.0
52.5
52.1
51.6
51.2
50.7
50.2
49.8
49.3
48.8
48.3
47.8
47.2
46.7
cfm per person
35
56.1
55.8
55.5
55.1
54.8
54.4
54.1
53.7
53.3
53.0
52.6
52.2
51.8
51.4
51.0
50.6
50.2
49.8
49.4
49.0
48.6
40
56.3
56.1
55.8
55.5
55.2
54.9
54.5
54.2
53.9
53.6
53.3
53.0
52.6
52.3
52.0
51.6
51.3
50.9
50.6
50.2
49.9
Table AC-3. Supply air dew point temperature, 75° at 50% RH space limit latent Load
Btu/h per Person
200
220
240
260
280
100
120
140
160
180
10
—
—
—
—
—
48.4
46.8
45.2
—
—
300
320
340
360
380
—
—
—
—
—
400
420
440
460
480
500
—
—
—
—
—
—
Note: Minimum dew point selectable is 45°F.
—
—
—
—
—
—
—
—
—
—
—
15
50.8
49.8
48.9
47.9
46.8
45.7
—
—
—
—
30
53.0
52.6
52.2
51.7
51.3
50.8
50.3
49.8
49.4
48.9
48.4
47.9
47.3
46.8
46.3
45.7
45.2
—
—
—
—
25
52.6
52.1
51.5
51.0
50.4
49.8
49.3
48.7
48.1
47.4
—
—
—
—
—
—
46.8
46.2
45.5
—
—
20
51.9
51.3
50.6
49.8
49.1
48.4
47.6
46.8
46.0
45.2
—
—
—
—
—
—
—
—
—
—
— cfm per person
35
53.3
53.0
52.6
52.2
51.8
51.5
51.1
50.7
50.3
49.8
49.4
49.0
48.6
48.2
47.7
47.3
46.8
46.3
45.9
45.4
—
40
53.6
53.3
52.9
52.6
52.3
51.9
51.6
51.3
50.9
50.6
50.2
49.8
49.5
49.1
48.7
48.4
48.0
47.6
47.2
46.8
46.4
55
54.0
53.8
53.5
53.3
53.1
52.8
52.6
52.4
52.1
51.9
51.6
51.4
51.1
50.9
50.6
50.4
50.1
49.8
49.6
49.3
49.1
50
53.9
53.6
53.4
53.1
52.9
52.6
52.3
52.1
51.8
51.5
51.3
51.0
50.7
50.4
50.1
49.8
49.6
49.3
49.0
48.7
48.4
45
53.8
53.5
53.2
52.9
52.6
52.3
52.0
51.7
51.4
51.1
50.8
50.5
50.2
49.8
49.5
49.2
48.9
48.5
48.2
47.9
47.5
60
56.8
56.6
56.4
56.2
56.1
55.9
55.7
55.5
55.3
55.1
54.9
54.6
54.4
54.2
54.0
53.8
53.6
53.4
53.2
53.0
52.7
55
56.7
56.5
56.3
56.1
55.9
55.7
55.5
55.2
55.0
54.8
54.6
54.3
54.1
53.9
53.7
53.4
53.2
53.0
52.7
52.5
52.2
50
56.6
56.4
56.2
55.9
55.7
55.5
55.2
55.0
54.7
54.5
54.2
54.0
53.7
53.5
53.2
53.0
52.7
52.4
52.2
51.9
51.6
45
56.5
56.2
56.0
55.7
55.5
55.2
54.9
54.6
54.4
54.1
53.8
53.5
53.3
53.0
52.7
52.4
52.1
51.8
51.5
51.2
50.9
The FAU has electric or gas heat options. The electric heat option is available in 30-70°F temperature rise offerings with three to seven capacity control stages. This means that the lowest temperature rise provided using one stage depends on heater size, unit airflow, and the number of stages selected. Calculate the temperature rise to confirm that it provides acceptable control. The electric heat will cycle to maintain heating setpoint.
If using hot water heat, install it in the optional rack within the Packaged FAU or in the supply ductwork of the fresh air system. The unit controller will modulate a coil control valve. Provide an ethylene glycol and water mixture or other means of freeze protection for the hot water coil if the FAU will be subject to sub-freezing temperatures.
The capacity control system on the
Packaged Fresh Air unit is flexible enough to accommodate a variety of system applications. These applications include:
• treating outdoor air to supply a single space or multiple spaces or
• simultaneously meet building makeup air needs while controlling the temperature and relative humidity of a single space.
Each of these applications requires careful consideration to achieve the desired results.
60
54.1
53.9
53.7
53.5
53.3
53.0
52.8
52.6
52.4
52.2
51.9
51.7
51.5
51.3
51.0
50.8
50.6
50.3
50.1
49.8
49.6
10
MUA-PRC004-EN
Application
Considerations
Supply Air Control
For many multiple space systems, the
FAU will continuously supply outdoor air at a dry-bulb setpoint and a dew point that does not exceed its dew point setpoint. This control approach is simple because it allows the FAU to function independent of local terminal unit operation or actual space conditions. If the unit selection criteria is determined using the method suggested in the
Establishing Capacity Requirements section, the fresh air unit will limit the space relative humidity to the target level.
When space sensible loads are relatively high, the local terminal unit may perform some latent cooling and drive the space relative humidity level lower than the FAU selection limit. Resetting the supply air dew point from the FAU will offer system operating cost savings.
See the Dew Point Reset section for resetting strategies.
Many fresh air systems supply reheated air directly to terminal units or to spaces that have terminal units performing local sensible cooling. This results in the local terminal units recooling the previously re-heated outdoor air. Resetting the supply air drybulb temperature of the fresh air unit offers the opportunity to minimize the amount of time re-cooling occurs. See the Dry-Bulb Reset section for more information.
Dew Point Reset
The local terminal unit provides sensible control of the space and as a result may coincidentally provide latent cooling to the space. The latent loads in the space can vary, especially if occupant density changes. Since the FAU can provide latent cooling to the space as well, it may be beneficial to reset the FAU supply air dew point to prevent overdehumidifying the space and unnecessarily wasting cooling energy. One way to do this is to place a relative humidity sensor in the space served by the FAU or in a common relief air path (like a return corridor) if the FAU serves multiple spaces. This relative humidity sensor can reset the supply air dew point setpoint of the FAU by responding to actual space latent conditions. The
Packaged FAU offers this control capability.
An alternative dew point control strategy is to reset the leaving dew point of the fresh air unit based on the zone with the highest relative humidity.
The building automation system will determine the zone requiring the driest
(lowest dew point) air and reset the dew point of the air leaving on the FAU accordingly. With this approach, the control and setpoint selection of the fresh air system is dynamically optimized based on actual demand of the controlled space. Comfort and indoor air quality requirements are met while minimizing system energy consumption. A Trane Integrated Comfort TM system can provide this control capability.
Dry-Bulb Reset
Because the Trane FAU dehumidifies the outdoor air by cooling it, this cool outdoor air can reduce the sensible cooling load on the local terminal unit. At low space sensible loads, the cool outdoor air may sub-cool the space, causing the local terminal unit to add heat (new energy heat). Therefore, reset the dry-bulb temperature of the dehumidified outdoor air to minimize space sensible re-cooling so the terminal unit with the lowest sensible load is almost at zero cooling capacity
(within the limit of the dew point setpoint). For chilled water terminal units (such as fan-coils), determine this by monitoring the chilled water valve position. For DX terminal units (such as water-source heat pumps or packaged rooftops), determine by monitoring compressor operation. To take full advantage of space demand based drybulb reset, size the local terminal units based on neutral outdoor air temperature. This strategy will more effectively manage occupant comfort during seasonal changeover for two-pipe terminal unit systems. Because the FAU is not connected to the chiller or boiler plant, accomplish this by resetting the fresh air unit dry-bulb temperature to keep the critical zone at zero heating capacity when the boiler is off and zero cooling capacity when the chiller is off. A
Trane Integrated Comfort™ system can provide this control capability.
Unoccupied Space Humidity Control
The Packaged FAU provides conditioned outdoor air for the ventilation and/or make-up air needs of a building during occupied hours. It can also limit building relative humidity during unoccupied hours. To do this, provide a return air path to the FAU and place a relative humidity sensor in the space served by the FAU or in a common relief air path (like a return corridor) if the FAU serves multiple spaces. The unit will cycle as required to limit the space relative humidity to the unoccupied relative humidity setpoint. Reheat and return air damper options are required for this operation. For dedicated outdoor air systems ducted to terminal units, these units must cycle with the operation of the Packaged FAU.
A Trane Integrated™ Comfort system can provide this control capability.
For single space applications, the
Packaged FAU can control space temperature and limit space relative humidity. To do this, size the airflow to meet whichever is the highest: the space loads and ventilation and/or make-up air needs of the application.
Install a temperature sensor in the space to provide temperature control and reset the supply air temperature. If reset of the supply air dew point is desired, install a space relative humidity sensor in the space to provide relative humidity limit control.
Establish final unit airflow through a field air balancing procedure. Change the fan speed through replacement or fan sheave adjustment.
To simplify this procedure, optional
Traq TM outdoor airflow measuring dampers are available for continuous airflow sensing feedback. The dampers monitor the outdoor airflow intake and can help validate and troubleshoot system airflow issues. Do not use them for building pressure control.
MUA-PRC004-EN 11
Application
Considerations
Energy recovery can significantly reduce HVAC system first-cost and operating energy costs. You can use recovered energy for two purposes:
1. to temper or reheat supply air for independent control of sensible and latent capacity, or
2. to precondition outdoor air as it enters the building for ventilation.
The Packaged FAU offers refrigerant heat recovery for reheating the supply air. To precondition the outdoor air, use the total energy wheel option to recover energy from building exhaust.
Controlling an Energy Recovery
Ventilator
One way to control an energy recovery device is to turn it on and off with the
FAU system exhaust fan. In this case, the total energy wheel enables when the unit is in occupied mode and the exhaust fan is running. While this control method is certainly simple and effective in some applications, it may not provide the expected energy saving benefit, particularly when cold air (vs. neutral air) is supplied to the building.
Another more effective approach is to use the outdoor air dry-bulb to determine when to energize or de-energize the energy recovery device. See Figure
AC-7 for an example of this simplified version of energy recovery. In addition to being more effective from a control standpoint, it’s also a very simple control method because the total energy wheel (only) enables when all of the following are true:
• unit is in occupied mode
• exhaust fan is enabled
• outside air temperature is above the upper limit setpoint (default setpoint
80°F) or below the lower limit setpoint
(default setpoint 45°F)
• outside air temperature is above the frost protection setpoint (default setpoint 12°F).
Set the upper limit setpoint to the anticipated return air dry-bulb temperature. Set the lower limit setpoint to 10°F less than the supply air dry-bulb setpoint. This control strategy prevents the energy recovery device from potentially adding to the load seen by the cooling and/or heating system of the unit, but rather utilizing the device only at those times when it provides true operating energy savings.
If using the FAU to deliver cold, dry conditioned air to the building (outdoor air is cooled to a low dew point but not reheated), use the dry-bulb control option.
Cross Leakage
All energy wheels have some cross leakage. Therefore, do not use energy wheels in applications involving toxic or hazaradous air streams. The percentage of cross leakage depends on the pressure differentials across the wheel section. With Trane Packaged FAU energy wheels, the exhaust air transfer ratios are typically low (<4%).
Figure AC-6. Dry-bulb control in a cold DB/dry DP application Figure AC-7. Dry-bulb control in a neutral DB/dry DP application
12
MUA-PRC004-EN
Application
Considerations
FAU units are selected based on dehumidification capability. As such, condensate can form at an enormous rate. Therefore, the Packaged FAU drain pan and condensate line are sized and designed accordingly. However, an often-overlooked element of proper condensate drainage is trapping. An incorrectly designed and installed trap on the piping exiting the drain pan can restrict condensate flow or cause condensate to ‘‘spit’’ or “geyser.” This can dampen the air handler interior and/ or ductwork, creating an opportunity for mold infestation. Carefully install and trap the drain pan to ensure adequate condensate removal under all conditons. See Figure AC-8 for the proper p-trap design for the drain pan.
H = (1’’ for each 1’’ of maximum negative static pressure) + 1’’
J = half of H
L = H + J+ pipe diameter + insulation
Figure AC-8. P-trap design for drain pan
Proper unit placement is critical to reducing transmitted sound levels from the FAU to the building. Therefore, consider acoustic concerns during the design phase and place the unit accordingly. The most economical means of avoiding an acoustical problem is to place the unit(s) away from acoustically critical areas. If possible, do not locate units directly above areas such as: offices, conference rooms, executive office areas, and classrooms. Instead, ideal locations to consider are: over corridors, utility rooms, toilets, or other areas where higher sound levels directly below the unit(s) are acceptable.
Follow these basic guidelines for unit placement to minimize sound transmission through the building structure.
1. Never cantilever the compressor side of the unit. A structural cross member must support this side of the unit.
2. Locate the unit’s center of gravity close to or over column or main support beam.
3. If the roof structure is very light, replace roof joists by a structural shape in the critical areas described above.
4. If several units are to be placed on one span, stagger them to reduce deflection over that span.
It is impossible to totally quantify the building structure effect on sound transmission because it is dependent on how the roof and building members respond to the FAU ’s sound and vibration. However, following the guidelines listed above will help reduce sound transmissions.
Follow the recommended unit clearances to assure adequate serviceability, maximum capacity, and peak operating efficiency. Reducing unit clearances may result in condenser coil starvation or warm condenser air recirculation. If the recommended clearances are not possible on a particular job, consider the following:
• Do the clearances available allow for major service work, such as changing compressors or coils?
• Do the clearances available allow for proper outside air intake, exhaust air removal, and condenser airflow?
• If screening around the unit is used, is there a possibility of air recirculation from the exhaust to the outside air intake or from condenser exhaust to condenser intake.
Review any actual clearances that appear inadequate with your local
Trane sales engineer.
When two or more units are placed side by side, increase the distance between the units to 150% of the recommended single unit clearance. Stagger the units for these two reasons:
1.To reduce span deflection if more than one unit is placed on a single span.
Reducing deflection discourages sound transmission.
2.To assure proper exhaust air diffusion before contact with the adjacent unit’s outside air intake.
Duct Design
It is important to note that the rated capacities of the FAU can be met only if the unit is properly installed. A welldesigned duct system is essential to meet these capacities.
Satisfactory air distribution throughout the system requires an unrestricted and uniform airflow from the rooftop discharge duct.
However, when job conditions dictate installation of elbows near the FAU outlet, using guide vanes may reduce capacity and static pressure loss.
MUA-PRC004-EN 13
Selection
Procedure
Model Number
Description
Packaged Fresh Air unit Model Number Description
Following is a complete description of the Packaged FAU model number. Each digit in the model number has a corresponding code that identifies specific unit options.
F A D A 040 6 G A,0 0,8,4 0 1 A 0 1 A 0,5,7 0,7 A 0 0 0 E F 0 1 0,0,0 0,0 A A A A
1 2 3 4 5,6,7 8 9 10,11 12,13,141516171819 20 21,22,23 24,25 26 27 28 29 30 31 32 33 34,35,36 37,38 39 40 41 42
Digit 1 – Unit model
F = fresh air unit
Digit 2 – Unit configuration
A = air cooled
Digit 3 – Unit discharge direction
D = downflow
H = horizontal
Digit 4 – Development sequence
A = development sequence ‘A’
Digits 5, 6, 7 – Unit size
031 = 3100 cfm
040 = 4000 cfm
051 = 5100 cfm
066 = 6600 cfm
Digit 8 – Unit voltage
3 = 230 volt/60 hz/3 ph
4 = 460 volt/60 hz/3 ph
6 = 208 volt/60 hz/3 ph
Digit 9 – Heating system
0 = none
A = gas low rise, single bank, 2-stage
B = gas low rise, single bank, 2:1 modulate
C = gas high rise, single bank, 2-stage
D = gas high rise, single banks, 2:1 modulate
E = gas dual bank, 4-stage
F = gas dual bank 4:1 modulate
G= electric heat, 3-stage
H = electric heat, 7-stage
K = hydronic interface only
Digits 10, 11 – Design sequence
** = factory assigned
Digits 12, 13, 14 – Heat input
000 = none
020 = 20 kW
026 = 26 kW
032 = 32 kW
042 = 42 kW
056 = 56 kW
070 = 70 kW
084 = 84 kW
100 = 100 kW
122 = 122 kW
125 = 125 MBh
14
150 = 150 MBh
200 = 200 MBh
250 = 250 MBh
300 = 300 MBh
350 = 350 MBh
400 = 400 MBh
500 = 500 MBh
600 = 600 MBh
700 = 700 MBh
800= 800 MBh
Digit 15 – Heat exchanger material
0 = none
1 = 409 stainless steel, 409 stainless
Burner
2 = 321 stainless steel, 409 stainless burner
Digit 16 – Condenser reheat coil
0 = none
1 = condenser hot gas reheat coil
Digit 17 – Ventilation damper type
0 = parallel blade damper
1 = TRAQ™ damper with air flow measurement
Digit 18 – Energy recovery
0 = none
1 = total energy wheel w/occupancy control
2 = total energy wheel w/dry bulb control
Digit 19 – Return air damper
0 = none
1 = bottom return/reference enthalpy
2 = bottom return/comparative enthalpy
Digit 20 – Supply fan type 1
A = 12 - 9 centrifugal fan
B = 15 - 11 centrifugal fan
C = 18 - 13 centrifugal fan
Digits 21, 22, 23 – Supply fan rpm
037 = 375
040 = 400
065 = 650
067 = 675
042 = 425
045 = 450
047 = 475
050 = 500
052 = 525
055 = 550
057 = 575
060 = 600
062 = 625
070 = 700
072 = 725
075 = 750
077 = 775
080 = 800
082 = 825
085 = 850
087 = 875
090 = 900
Note 1 : The first number in this description indicates the fan wheel diameter (in.). The second number indicates the fan wheel width.
092 = 925
095 = 950
097 = 975
100 = 1000
102 = 1025
105 = 1050
107 = 1075
110 = 1100
112 = 1125
115 = 1150
117 = 1175
120 = 1200
122 = 1225
125 = 1250
127 = 1275
130 = 1300
132 = 1325
135 = 1350
137 = 1375
140 = 1400
142 = 1425
145 = 1450
147 = 1475
150 = 1500
152 = 1525
155 = 1550
157 = 1575
160 = 1600
162 = 1625
165 = 1650
167 = 1675
170 = 1700
172 = 1725
175 = 1750
177 = 1775
180 = 1800
182 = 1825
185 = 1850
187 = 1875
190 = 1900
192 = 1925
195 = 1950
197 = 1975
200 = 2000
202 = 2025
205 = 2050
207 = 2075
210 = 2100
Digits 24, 25 – Supply fan horsepower
01 = 1
02 = 2
03 = 3
05 = 5
07 = 7.5
10 = 10
15 = 15
Digit 26 – Fan motor type
A = standard efficiency ODP fan motor
B = high efficiency ODP fan motor
Digit 27 – Coil protection
0 = none
A = corrosion inhibiting coating
Digit 28 – Unit cabinet protection
0 = standard prepainted steel finish
A = corrosion inhibiting coating
Digit 29 – Filter type
0 = field-provided filter
1 = dirty filter switch (DFS) with fieldprovided filter
2 = 2” pleated media filters
3 = 2” pleated media filters & DFS
Digit 30 – System control
A = supply air dehumidification
B = supply air dehimidification with zone
RH reference
MUA-PRC004-EN
MUA-PRC004-EN
Selection
Procedure
Model Number
Description
E = zone dehumidification
F = zone dehumidification with OA RH reference
G= supply air temperature control (no dehumidification)
J = zone temperature control (no dehumidification)
Digit 31 – Control interface options
0 = none
A = LonTalk ® communications interface
(LCI ) (comm5)
B = LCI (comm5) & generic building automation system (GBAS) (0-5 VDC)
C = LCI (comm5) & GBAS (0-5 VDC) & ventilation override module (VOM)
D = LCI (comm5) & VOM
E = GBAS (0-5 VDC)
F = GBAS (0-5 VDC) & VOM
G= VOM
Digit 32 – Miscellaneous system control options
0 = none
1 = interface for remote human interface
Digit 33 – Exhaust option
0 = none
1 = exhaust interface
Digits 34, 35, 36 – Exhaust air fan rpm
000 = none 127 = 1275
045 = 450 130 = 1300
047 = 475 132 = 1325
050 = 500 135 = 1350
052 = 525 137 = 1375
055 = 550 140 = 1400
057 = 575 142 = 1425
060 = 600 145 = 1450
062 = 625 147 = 1475
065 = 650 150 = 1500
067 = 675 152 = 1525
070 = 700 155 = 1550
072 = 725 157 = 1575
075 = 750 160 = 1600
077 = 775 162 = 1625
080 = 800 165 = 1650
082 = 825 167 = 1675
085 = 850 170 = 1700
087 = 875 172 = 1725
090 = 900 175 = 1750
092 = 925 177 = 1775
095 = 950 180 = 1800
097 = 975 182 = 1825
100 = 1000 185 = 1850
102 = 1025 187 = 1875
105 = 1050 190 = 1900
107 = 1075 192 = 1925
110 = 1100 195 = 1950
112 = 1125 197 = 1975
115 = 1150 200 = 2000
117 = 1175 202 = 2025
120 = 1200 205 = 2050
122 = 1225 207 = 2075
125 = 1250 210 = 2100
Digits 37, 38 – Exhaust air fan horsepower
00 = none
01 = 1
02 = 2
03 = 3
05 = 5
07 = 7.5
10 = 10
Digit 39 – Unit connection type
A = terminal block
B = non-fused disconnect switch
Digit 40 – Convenience outlet
0 = none
A = 115V, factory wired
B = 115V, field wired
Digit 41 – Extended grease lines
0 = none
A= extended grease lines
Digit 42 – Agency approval
0 = no agency approval
A = UL approval
Digit 43 – Roof curb
A = 14” curb
B = 24” curb
15
Selection
Procedure
Model Number
Description
Packaged Fresh Air unit Accessory Model Number Description
Following is a complete description of the Packaged FAU accessory model number. Each digit in the model number has a corresponding code that identifies specific accessory options.
P F
1 2
K
3
A
4
031
5, 6, 7
3
8
A A0 B C 0 A A 0 A 0 A 0 A 0 A
9 10,11 12 13 14 15 16 17 18 19 20 21 22 23 24
Digit 1 – Parts/accessories
P = parts/accessories
Digit 2 – Unit type
F = fresh air unit
Digit 3 – Field installed kits
K = field installed kits
Digit 4 – Development sequence
A = development sequence
Digits 5, 6, 7 – Nominal size
031 = 3100 cfm
040 = 4000 cfm
051 = 5100 cfm
066 = 6600 cfm
Digit 8 – Unit voltage
3 = 230/60/3
4 = 460/60/3
6 = 208/60/3
Digit 9 – Roof curb
0 = none
A = 14”
B = 24”
C = acoustical
D = 14” curb for unit w/ERV
E = 24” extended for unit w/ERV
F = 24” extended, acoustical for unit w/
ERV
Digits 10, 11 – Design sequence
A0 = design sequence
Digit 12 – Filter type
0 = none
A = 2” pleated media
B = 2” cleanable
C = 2” pleated media total energy wheel only
D = 2” cleanable total energy wheel only
E = 2” pleated media unit & total energy wheel
F = 2” cleanable unit & total energy wheel
Digit 13 – Control interface kits
0 = none
A = LonTalk ® communications interface
(LCI) (comm5)
B = LCI (comm5) & generic building automation system (GBAS) (0-5 VDC)
C = LCI (comm5) & GBAS (0-5 VDC) & ventilation override module (VOM)
D = LCI (comm5) & VOM
E = GBAS (0-5 VDC)
F = GBAS (0-5 VDC) & VOM
G= VOM
Digit 14 – Time clock
0 = none
A = time clock
Digit 15 – Remote mounted human interface
0 = none
A = remote mounted human interface
B = remote mounted human interface with interprocessor communication bridge module board kit
C = interprocessor communication bridge module board kit
Digit 16 – Zone sensor
0 = none
A = zone temperature sensor
BAYSENS017*
Digit 17 – Zone sensor with timed override
0 = none
A = zone temperature densor with timed override BAYSENS013*
Digit 18 – Zone sensor with timed override and local setpoint adjustment
0 = none
A = zone temperature sensor with timed override buttons and local setpoint adjustment BAYSENS014*
Digit 19 – Remote minimum position potentiometer control
0 = none
A = remote minimum position potentiomenter control BAYSTAT023*
Digit 20 – Dual setpoint sensor
0 = none
A = dual setpoint sensor
Digit 21 – Dual setpoint sensor with system function lights
0 = none
A = dual setpoint sensor with system function lights
Digits 22 – Space relative humidity kit
0 = none
A = space relative humidity kit
Digit 23 – Carbon dioxide sensor
0 = none
A = carbon dioxide sensor
Digit 24 – Dry-bulb duct sensor
0 = none
A = dry-bulb duct sensor
16 MUA-PRC004-EN
MUA-PRC004-EN
Selection
Procedure
Prior to selecting the fresh air unit (FAU) for a given application, give careful consideration to determining the design latent conditions (as described in the
Applications Considerations section of this catalog). Use Tables AC-1, AC-2, and AC-3 on pages 9 and 10 to identify the appropriate supply air dew point for specific design conditions. See SYS-
APG001-EN or SYS-APM-004 for more detailed information.
Selection of Trane Packaged Fresh Air units is divided into five basic areas:
1. cooling/dehumidification capacity
2. air delivery
3. heating capacity
4. unit electrical requirements
5. unit designation
Factors used in unit cooling/dehumidification (drying) selection:
Example
Example unit options include:
• parallel blade OA damper
• 2” pleated media filters
• gas heat – hi rise, single bank, 2-stage
• fan type 12-9
Given conditions:
• airflow required for proper ventilation
(per ASHRAE 62) = 2300 cfm
• outside air summer design conditions
= 95°db/78°wb, 95°F entering air to condenser
• supply air design dew point requirement = 53°F dew point
• total peak cooling load = 198 MBh (16.5
tons)
• total peak dehumidification load = 90
MBh (7.5 tons)
• condenser reheat provided (yes or no)
= for this example, reheat is installed
• external static pressure = 0.5 inches
• desired supply air db temp. = 75°F
Step 1 – Determine unit size.
To determine which unit size will meet your capacity requirements, first review the airflow ranges found in Table GD-1 on page 21. The specified airflow in this example of 2300 cfm falls in both the size 031 and 040 unit airflow ranges.
Step 2 – Determine SA dew point capability.
Check the smaller unit size first to determine if it has the capacity to meet the supply air dew point and cooling/ dehumidification requirements. See
Table PD-31 to review the supply air dew point vs. airflow range that the size
031 unit can provide. At 95°db/78°wb, the size 031 produces 53°F dew point supply air at 2301 cfm (value found by interpolating between the 52°F and
54°F dew point data provided in the table). Therefore, the size 031 unit meets the supply air dew point requirement.
Step 3 – Determine unit capacity.
Now check that the size 031 unit meets the cooling and dehumidification capacity requirements by reviewing
Table PD-28. At 2300 cfm and 95°F db/
78°F wb, the size 031 unit produces
201.42 MBh total and 92.68 MBh latent capacity. This meets our requirement.
Also note that Table PD-27 provides information very similar to that in Table
PD-28. Use Table PD-27 (and tables like it for all other units sizes) only when condenser reheat is not provided. For this example, we will include condenser reheat.
Step 4 – Determine supply air fan data.
First calculate size 031 unit total static pressure (tsp) at design supply cfm using the appropriate air pressure drop tables. See calculation below: external static pressure = 0.50‘’ parallel blade OA damper = 0.01’’
2” pleated media filter = 0.08’’ main evap coil (wet) = 0.37’’ reheat evap coil (wet) = condenser reheat coil = gas heat exchanger =
0.19’’
0.15’’
0.37’’ unit total static pressure = 1.67’’
Using 2300 cfm and tsp of 1.67 inches, refer to Table PD-1, which shows 1017 rpm and 1.06 bhp at 1.6 tsp. Interpolate the values from the table (between 1.60
and 1.80 tsp), and calculate 1058 rpm and 1.077 bhp at 1.67 tsp.
Step 5 – Determine supply air temperature.
If the unit does not have condenser reheat, the supply air db is equal to the supply air dew point (53°F). However, for this example, condenser reheat is required, and a supply air db temperature of 75°F is desired. Go to Table PD-
30 on page 49 to determine the supply air db temperature produced by the size
031 unit. At 2300 cfm and 95°F db/78°F
17
Selection
Procedure db, the size 031 unit produces condenser reheat max temp rise of 24.9°F.
Now calculate the fan motor heat temp rise for this selection. Go to Figure SP-1 to determine that 1.077 bhp = 3.269
MBh. Supply fan motor heat temp rise =
3269 btu/(1.085 x 2300 cfm) = 1.3°F.
Calculate supply air db temp by summing the off-coil supply air db with the condenser reheat maximum temperature rise and the motor heat temperature rise at the design condition:
Supply air db temperature:
53°F + 24.9°F + 1.3°F = 79.2°F
Thus, the size 031 unit has the capability to meet and slightly exceed the supply air db temperature requirement of 75°F.
So, for this example, the size 031 unit meets all requirements with a supply air temperature of 79.2°F db/63.1°F wb with a 53°F supply air dew point.
However, if the supply air temp setpoint at the unit controller is set to 75°F, the unit will modulate the condenser reheat to meet that supply air condition versus exceed it. Also note that Table PD-30 provides reheat max temp rise data for typical design and part load conditions.
This enables you to determine if the condenser reheat is sufficient to maintain comfort during typical part load conditions.
Given conditions:
• winter outdoor design conditions = 0°F
• heat type = gas
• max temp rise or heating kW/MBh requirement = 80°F temperature rise
To select a single bank gas heater as specified, go to Table PD-73 for the size
031 unit. At 2300 cfm, a 250 MBh gas heater will produce an 80°F temperature rise. Select this heater.
If your application requires electric heat, use the electric heat tables on pages 73 through 74.
Supply Air Fan Selection
Unit supply air fan performance tables include pressure drops for internal cabinet static losses. Add static pressure drops of optional components such as heat and filters to the external duct static pressure to determine the total static pressure.
The supply requirements determined in
Step 4 of the cooling/dehumidification capacity example was 1.077 bhp at
1058 rpm. Thus, the supply fan motor size required is two hp at 1075 rpm.
To determine electrical requirements for wire sizing amps and maximum over-current protection, see in the
Electrical Data section on pages 86–89.
After determining specific unit capacity requirements and considering specific job requirements, determine the complete unit model number by referencing pages 14–16.
STANDARD MOTOR
HIGH EFFICIENCY MOTOR
90
80
70
60
50
40
30
20
120
110
100
10
0
0 5 10 15 20 25 motor brake horsepower
Note: Fan motor heat (MBh) includes 1.1 correction factor for motor efficiency.
30
Figure SP-1. Fan motor heat
35 40
18 MUA-PRC004-EN
Selection
Procedure
Common Terms
Following are definitions of common terms used when selecting a fresh air unit with a total energy wheel.For more information on this subject, reference
Trane application manual, Air-to-Air
Energy Recovery in HVAC Systems,
SYS-APM003-EN.
EATR - exhaust air transfer rate expressed as a percentage, is the tracer gas concentration difference between the outdoor airflow entering the total energy wheel and the supply airflow leaving the wheel divided by the tracer gas concentration difference between the exhaust airflow entering the total energy wheel and the outdoor airflow entering the wheel.
OACF - The outside air correction factor is defined as the supply-side airflow upstream of the wheel divided by the supply-side airflow downstream of the wheel. This value is important for sizing the fans. Also, if the system includes an airflow monitoring station or flowmeasuring damper, it allows for the set point of this device to compensate and assure that the proper amount of outdoor air flows into the wheel so that the required amount of outdoor air leaves the wheel. The OACF is typically small unless the pressure difference between the air streams is greater then
3.0 in H2O.
The term effectiveness is used to describe the heat transfer efficiency of an air-to-air heat exchanger. Effectiveness is defined as the actual energy
(sensible, latent, or total) transferred by
Table SP-1. OACF values
2P3 031 unit size
040 051 066
-2
-1.5
-1
-0.5
0
0.5
1
1.5
2
2.5
3
0.98
0.98
0.99
0.99
1.00
0.99
1.00
1.00
1.01
1.01
1.02
1.01
1.03
1.02
1.03
1.02
1.05
1.04
1.04
1.03
1.06
1.05
1.05
1.04
1.08
1.07
1.06
1.05
1.10
1.08
1.07
1.06
1.12
1.10
1.09
1.07
1.13
1.11
1.10
1.08
1.15
1.13
1.11
1.09
Note: EATR and OACF values are for wheels without purge. EATR for all units = 4%.
MUA-PRC004-EN the device, divided by the maximum possible energy transfer between the two air streams. If the effectiveness of the device were 100% the condition of the air leaving the supply-side of the device would be the same as the condition of the air entering the exhaust-side of the device.
In addition to understanding the wheel performance terms, consideration should be given to airflow performance in applications with a total energy wheel. The terms below explain the air paths through the total energy wheel and should all be considered when selecting an energy recovery device.
Entering exhaust airflow represents the exhaust airflow exiting the building prior to passing through the total energy wheel.
Leaving exhaust airflow represents the exhaust airflow after passing through the total energy wheel.
Net exhaust airflow represents the portion of leaving exhaust airflow that originated as entering exhaust airflow.
Leaving supply airflow represents the sum of the net supply airflow and the additional air picked up in the airstream while passing through the total energy wheel (difference between entering and net exhaust airflow).
Outdoor airflow represents the amount of outdoor air entering the unit.
Net supply airflow represents that portion of the leaving supply airflow that originated as outdoor airflow
(equal to 1 - EATR.
EA/OA is the ratio of net exhaust airflow to net supply airflow (expressed as a percentage).
Given:
4000 cfm, 100% EA/OA, 95/78°F OA conditions, 72/60°F (52 dewpoint) SA conditions, 1” WC supply ESP, 1” WC exhaust ESP, 75/63°F summer RA conditions, 70F/30% RH winter RA conditions
Step 1 - Determine unit size.
To determine which unit size will meet your capacity requirements, first review the airflow ranges found in Table GD-1.
The specified airflow in this example of
4000 falls into unit sizes 040, 051, and
066 airflow ranges.
Step 2 - Determine SA dewpoint capability.
Check the smaller unit size first to determine if it has the capacity to meet the supply air dewpoint requirements.
See Table PD-56 on page 63 to review the supply air dewpoint vs. airflow range that the size 040 unit can provide.
At 95/78°F, the size 040 unit has the capacity at 4000 cfm to provide a 51 DP or higher. Therefore, the size 040 unit meets the supply air dewpoint requirement.
Step 3 - Determine unit and wheel capacity.
The 040 unit with a total energy wheel data can be pulled directly of the unit capacity Tables PD-53 and PD- 54 on pages 62-63:
The 040 unit with a total energy wheel produces 391 MBh total capacity and
155 MBh latent capacity.
The 040 wheel only capacity is 152 MBh total and 92 MBh latent.
Step 4 - Determine exhaust airflow and actual amount of OA supplied to the space.
Use the APD lookup tables to find P2 and P3 below for the 040 unit at 4000 cfm:
Find P2 = energy module OA filters + energy wheel and module (use Table
PD-13)
P2 = 0.23 + 1.34 = 1.57
Find P3 = energy module EA filters + return ESP, using Table PD-13 on page
34:
P3 = 0.23 + 1 = 1.23
2P3 = 1.57 - 1.23 = 0.34
Find EATR and OACF using 2P3 from
Table SP-1:
EATR = 4.0%
OACF = 1.05
Calculate net OA: netOA = SA(1-EATR) netOA = 4000*(1- 0.04) = 3840 cfm
19
Selection
Procedure
Step 5 - Determine supply fan data.
First calculate unit total static pressure at design cfm of 4000 using the appropriate air pressure drop tables. See calculation below: external static pressure = 1.00” energy wheel OA filters = 0.23” energy wheel & module = 1.34”
OA dampers (Traq) = 0.28” reheat evap coil (wet) = 0.31” main evap coil (wet) = 0.62” condenser reheat coil = 0.24” unit total static pressure = 4.02”
Use SA and TSP with the fan curve/ table to determine the supply fan’s operating point.
12-9 FC, 1686 rpm, 5.19 hp
15-11 FC, 1330 rpm, 4.39 hp
Select 15-11 FC, 1350 rpm and 5 hp motor.
Step 6 - Determine exhaust fan data.
EA = SA[OACF + EATR -1 + (1 -
EATR)[net EA/net OA]] net EA = net OA [net EA/net OA]
EA = 4000*(1.05 + 0.04 - 1 + (1 -
0.04)*1.0) = 4200 cfm
NetEA = 3840*0.8 = 3072 cfm
Use EA and P3 with the 040 exhaust fan curve/tables, Chart PD-6 and Table PD-6 on page 27, to determine the exhaust fan’s operating point.
1763 rpm, 5.07 hp
Select 1775 rpm, 7.5 hp
Step 7 - Determine supply air temperature.
The 040 unit with evap coils plus the total energy wheel produce a supply air db of 51°F.
The 040 unit plus wheel produces a reheat rise of 19.8°F. See the size 040 unit/wheel reheat temp rise Table PD-55 on page 63.
Motor temp rise is X (for instructions on calculating motor heat temp rise, review step 5 under FAU selection procedure for unit without total energy wheel).
Supply air temp = 51 + 19.8 + X = 70.8 +
X
Step 8 - Determine wheel frost setpoint.
Find the point on the frost threshold curve (Table SP-2) that intersects with your RA winter relative humidity. Then read the associated OA dry-bulb temperature. The frost threshold chart assumes winter RA dry-bulb or 70°F.
For other conditions, use the TOPSS selection program.
20 outdoor temperature °F
Figure SP-2. Frost threshold based on 70°F return air
MUA-PRC004-EN
General
Data
Table GD-1. Packaged fresh air unit general data
Unit size nominal cfm maximum design cfm minimum design cfm
Compressor data reheat circuit (nom. tons R134a) main circuit (nom. tons R134a) unit cooling capacity steps %
Supply fan data, FC fan 1/FC fan 2 quantity size (diameter-width), in.
maximum hp maximum rpm
Condenser fan data quantity/fan diameter, in.-type cfm (reheat, main) number of motors/hp each
031
3100
3100
1800
3.0T
6.2T + 9.3T
100-66-50-16
1/1
12-9/15-11
7.5/15
2115/1760
1/24;2/26-prop
2900, 8500
3/1.0
Evaporator coil - main size, ft 2 rows/fin s series tube diameter, in./surface
Evaporator coil - reheat size, ft 2 rows/fin series tube diameter, in./surface
Condenser coil - main size, ft 2 rows/fin series tube diameter, in./surface
Condenser coil - reheat outdoor size, ft 2 rows/fin series tube diameter, in./surface
6.67
4/168
0.5/enhanced
6.67
2/168
0.5/enhanced
15.62
2/168
0.5/enhanced
5.35
2/168
0.5/enhanced
Condenser coil - reheat indoor size, ft 2 rows/fin series tube diameter, in./surface
6.67
2/168
0.5/enhanced
Heating data gas heat input, MBh elec. heat input, kW
125-350
20-56
Refrigerant operating charge, lbs., R-134a circuit (circuit 2) reheat circuit (circuit 1) cooling only (circuit 1)
25
29
9
Compressor oil data
main circuit POE oil type
reheat circuit POE oil type
main circuit, # pints
reheat circuit, # pints
Filters number-size, in.
face area, ft 2
Total energy (TE) wheel
wheel diameter (in)
wheel drive motor hp
exhaust fan
quantity
size (dia-width in.)
maximum hp
maximum rpm
outdoor air filters
number/size (in.)
face area (ft 2 )
return air filters
number/size (in.)
face area (ft 2 )
OIL00078
Mobil Artic EAL22CC
7/11.5
4.13
4 - 16x20x2
8.4
1
42
/
1
2
12-9
7.5
2115
4 - 16x20x2
8.4
4 - 16x20x2
8.4
MUA-PRC004-EN
040
4000
4000
2200
4.5T
6.7T + 10.0T
100-69-53-21
1/1
12-9/15-11
7.5/15
2115/1760
3/26-prop
4000, 10500
3/1.0
8.33
4/168
0.5/enhanced
8.33
2/168
0.5/enhanced
17.71
2/168
0.5/enhanced
7.29
2/168
0.5/enhanced
8.33
2/168
0.5/enhanced
125-400
26-84
28
32
13
OIL00078
Mobil Artic EAL22CC
7/11.5
3.75
4 - 16x20x2
8.4
1
48
/
2
1
12-9
7.5
2115
4 - 16x20x2
8.4
4 - 16x20x2
8.4
066
6600
6600
3600
6.2T
10.0T + 10.0T + 10.0T
100-72-45-17
1/1
15-11/18-13
15/13.76
1760/1515
3/26-prop
5500, 13000
3/1.0
14.06
4/168
0.5/enhanced
14.06
2/168
0.5/enhanced
28.13
2/168
0.5/enhanced
9.38
2/168
0.5/enhanced
14.06
2/168
0.5/enhanced
150-800
42-122
48
52
20 main
OIL00078
OIL0007
11.5/11.5/11.5
7
4 - 24x24x2
15.2
3
60
/
4
1
15-11
15
1760
4 - 20x25x2
13.3
4 - 16x25x2
10.5
21
051
5100
5100
2900
6.2T
6.2T + 6.2T + 9.3T
100-67-45-22
1/1
15-11/18-13
15/13.76
1760/1515
3/26-prop
5500, 12000
3/1.0
11.11
4/168
0.5/enhanced
11.11
2/168
0.5/enhanced
23.43
2/168
0.5/enhanced
9.38
2/168
0.5/enhanced
11.11
2/168
0.5/enhanced
125-600
32-100
34
50
18
OIL00078
OIL00078
7/7/11.5
7
4 - 24x24x2
15.2
3
54
/
4
1
15-11
15
1760
4 - 20x25x2
13.3
4 - 16x25x2
10.5
Performance
Data fan data
Chart PD-1. Size 12-9 supply fan, unit size 031
8
50% WO
60% WO
7 25% WO
6
5
2115 rpm
2100 rpm
2000 rpm
1900 rpm
1800 rpm
70% WO
80% WO
4
3
2
1
1700 rpm
1600 rpm
1500 rpm
1400 rpm
1300 rpm
1200 rpm
1100 rpm
1000 rpm
900 rpm
800 rpm
700 rpm
600 rpm
90% WO
0
0 2000 4000 6000 8000 10000
airflow, cfm
Note: Fan curves include internal cabinet static losses. To determine total static pressure to be used with these curves, add filter, damper, gas or electric heat, evaporator and reheat coils, and TE wheel pressure drops to external duct static pressure.
Table PD-1. Size 12-9 supply fan, unit size 031
0.0
0.5
1.0
1.5
2.0
total static pressure, in. wg.
3.0
3.5
4.0
5.0
5.5
6.0
7.0
7.5
8.0
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
1800 401 0.18 609 0.34 802 0.52 976 0.71 1148 0.95 1438 1.46 1565 1.73 1677 2.01
-
2200 490 0.33 658 0.51 827 0.72 982 0.95 1126 1.18 1405 1.73 1532 2.03 1654 2.35 1866 3.01 1965 3.35
-
2600 578 0.55 721 0.75 867 1.02 1005 1.24 1138 1.51 1377 2.06 1499 2.38 1618 2.72 1836 3.44 1935 3.81 2031 4.20
-
-
3100 690 0.93 802 1.14 929 1.42 1052 1.76 1169 2.02 1390 2.66 1493 2.98 1590 3.31 1792 4.05 1893 4.46 1989 4.88 2169 5.73
-
-
-
-
-
-
-
outside 25%WO limit outside rpm limit
22
MUA-PRC004-EN
Performance
Data fan data
Table PD-2. Size 15-11 supply fan, unit size 031
8
50% WO
25% WO
7 1760 rpm
1700 rpm
60% WO
6
1600 rpm 70% WO
5 1500 rpm
1400 rpm
4 80% WO
1300 rpm
1200 rpm
3
2
1
0
1100 rpm
1000 rpm
900 rpm
800 rpm
700 rpm
600 rpm
500 rpm
400 rpm
0
90% WO
2500 5000 7500 10000 12500 15000
airflow, cfm
Note: Fan curves include internal cabinet static losses. To determine total static pressure to be used with these curves, add filter, damper, gas or electric heat, evaporator and reheat coils, and TE wheel pressure drops to external duct static pressure.
Table PD-2. Supply fan size 15-11, unit size 031
0.0
0.5
1.0
1.5
2.0
3.0
total static pressure, in. wg.
3.5
4.0
5.0
5.5
6.0
7.0
7.5
8.0
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
1800 227 0.09 463 0.26 664 0.49 832 0.77 968 1.07
-
2200 277 0.16 479 0.37 648 0.59 813 0.89 956 1.23 1185 1.96
-
-
-
-
-
-
-
-
-
-
2600 327 0.26 501 0.50 657 0.76 798 1.04 936 1.40 1174 2.20 1275 2.62 1366 3.06
-
3100 390 0.44 534 0.69 677 1.03 801 1.33 918 1.66 1150 2.51 1254 2.97 1352 3.47 1523 4.47
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
outside 25%WO limit
MUA-PRC004-EN 23
Performance
Data fan data
Chart PD-3. Size 12-9 exhaust fan, unit size 031
8
7
2115 rpm
2100 rpm
2000 rpm
6
1900 rpm
30% WO
1800 rpm
50% WO
5
4
3
2
1
0
1700 rpm
1600 rpm
1500 rpm
1400 rpm
1300 rpm
1200 rpm
1100 rpm
1000 rpm
900 rpm
800 rpm
700 rpm
600 rpm
0
60% WO
70% WO
1000 2000 3000 4000 airflow, cfm
Note: Fan curves include internal energy module cabinet and wheel losses. Curves represent fan performance with an air density of 0.075 lbm/ft 3 .
80% WO
5000
90% WO
Table PD-3. Exhaust fan size 12-9, unit size 031
0.0
cfm rpm bhp
1800 692 0.37
2200 845 0.68
2600 999 1.13
3100 1191 1.91
0.5
rpm bhp
1.0
rpm bhp total static pressure, in.wg.
1.5
rpm bhp
2.0
rpm bhp
2.5
rpm bhp
895 0.55
1066 0.72
1229 0.94
1013 0.89
1169 1.11
1305 1.33
1143 1.37
1282 1.63
1406 1.87
1314 2.21
1430 2.50
1546 2.81
3.0
rpm bhp
1386 1.16
1536 1.39
1670 1.61
1438 1.58
1568 1.84
1697 2.12
1521 2.13
1634 2.43
1745 2.73
1650 3.10
1747 3.38
1842 3.72
outside 25%WO limit outside rpm limit
3.5
rpm bhp
4.0
rpm bhp
1788 1.83
1893 2.03
1822 2.40
1936 2.67
1856 3.05
1967 3.38
1937 4.08
2032 4.44
4.5
rpm bhp
-
2046 2.95
-
2075 3.71
2124 4.81
24
MUA-PRC004-EN
Performance
Data fan data
Chart PD-4. Unit size 040 with 12-9 supply fan
50% WO
8
25% WO 60% WO
7
2115 rpm
2100 rpm
2000 rpm
70% WO
6
1900 rpm
5 1800 rpm 80% WO
1700 rpm
4
1600 rpm
3
1500 rpm
1400 rpm
1300 rpm
90% WO
2
1
0
1200 rpm
1100 rpm
1000 rpm
900 rpm
800 rpm
700 rpm
600 rpm
0 2000 4000 6000
airflow, cfm
8000
Note: Fan curves include internal cabinet static losses. To determine total static pressure to be used with these curves, add filter, damper, gas or electric heat, evaporator and reheat coils, and TE wheel pressure drops to external duct static pressure.
Chart PD-4. Supply fan size 12-9, unit size 040
0.0
0.5
1.0
1.5
2.0
3.0
total static pressure, in. wg.
3.5
4.0
5.0
5.5
6.0
7.0
7.5
8.0
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
2200 490 0.33 658 0.51 827 0.72 982 0.95 1126 1.18 1405 1.73 1532 2.03 1654 2.35 1866 3.01 1965 3.35
-
2600 578 0.55 721 0.75 867 1.02 1005 1.24 1138 1.51 1377 2.06 1499 2.38 1618 2.72 1836 3.44 1935 3.81 2031 4.20
-
-
3000 667 0.84 786 1.05 915 1.33 1041 1.64 1162 1.91 1386 2.53 1490 2.84 1591 3.17 1800 3.92 1900 4.32 1998 4.74 2179 5.59
3400 756 1.23 853 1.44 975 1.77 1086 2.13 1195 2.41 1405 3.08 1504 3.44 1597 3.78 1780 4.52 1870 4.91 1965 5.35 2145 6.24
-
-
-
-
-
-
3800 845 1.71 929 1.93 1039 2.30 1138 2.61 1240 3.09 1430 3.71 1524 4.10 1615 4.51 1786 5.29 1869 5.69 1949 6.09 2111 6.97 2196 7.46
4000 890 2.00 968 2.23 1072 2.58 1168 2.95 1263 3.38 1448 4.09 1539 4.48 1627 4.89 1793 5.72 1874 6.14 1951 6.54 2104 7.41 2185 7.89
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
outside 25% WO limit outside rpm limit
MUA-PRC004-EN 25
26
Performance
Data fan data
Chart PD-5. Unit size 040 with 15-11 supply fan
50% WO
26% WO
8
1760 rpm
1700 rpm
60% WO
7
1600 rpm
70% WO
6
1500 rpm
5
1400 rpm
80% WO
4
1300 rpm
1200 rpm
3
1100 rpm
2
1
1000 rpm
900 rpm
800 rpm
700 rpm
600 rpm
500 rpm
400 rpm
90% WO
0
0 2500 5000 7500
airflow, cfm
10000 12500 15000
Note: Fan curves include internal cabinet static losses. To determine total static pressure to be used with these curves, add filter, damper, gas or electric heat, evaporator and reheat coils, and TE wheel pressure drops to external duct static pressure.
Table PD-5. Supply fan size 15-11, unit size 040
0.0
0.5
1.0
1.5
2.0
total static pressure, in. wg.
3.0
3.5
4.0
5.0
5.5
6.0
7.0
7.5
8.0
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
2200 277 0.16 479 0.37 648 0.59 813 0.89 956 1.23
-
2600 327 0.26 501 0.50 657 0.76 798 1.04 936 1.40 1174 2.20 1275 2.62
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
3000 377 0.40 526 0.65 672 0.97 800 1.27 920 1.60 1155 2.44 1261 2.91 1354 3.38 1526 4.37
-
3400 428 0.58 560 0.85 692 1.22 812 1.55 922 1.90 1135 2.72 1240 3.20 1337 3.71 1514 4.78 1594 5.33 1670 5.89
-
-
-
-
-
-
3800 478 0.82 593 1.11 713 1.49 829 1.89 933 2.26 1123 3.05 1221 3.54 1317 4.06 1495 5.18 1577 5.77 1654 6.37 1798 7.59
4000 503 0.95 611 1.26 725 1.64 839 2.07 939 2.46 1125 3.28 1215 3.74 1308 4.26 1487 5.41 1568 6.01 1646 6.62 1793 7.89
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
outside 25% WO limit outside rpm limit
MUA-PRC004-EN
Performance
Data fan data
Chart PD-6. Unit size 040 with 12-9 exhaust fan
8
7
2115 rpm
2100 rpm
2000 rpm
6
1900 rpm
5
4
3
2
1
0
1800 rpm
1700 rpm
1600 rpm
1500 rpm
1400 rpm
1300 rpm
1200 rpm
1100 rpm
1000 rpm
900 rpm
800 rpm
700 rpm
600 rpm
37% WO
50% WO
60% WO
70% WO
80% WO
90% WO
0 1000 2000 3000 4000 5000
airflow, cfm
Note: Fan curves include internal energy module cabinet and wheel losses. Curves represent fan performance with an air density of 0.075 ft 3 /lbm.
Table PD-6. Exhaust fan 12-9, unit size 040 cfm
2200
2600
3000
3400
3800
4000
0.00
0.50
rpm bhp rpm
845 0.68
1021
999 1.13
1149
1152 1.73
1284
1306 2.52
1424
1460 3.52
1566
1537 4.11
1638
1.00
1.50
total static pressure, in. wg.
2.00
2.50
3.00
3.50
4.00
4.50
rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp bhp
0.90
1179 1.12
1319 1.35
1457 1.62
1594 1.90
1727 2.18
1853 2.47
1969 2.76 2075 3.03
1.38
1291 1.65
1419 1.90
1538 2.18
1655 2.49
1769 2.80
1884 3.13
1998 3.47 2109 3.82
2.03
1409 2.33
1529 2.63
1639 2.92
1741 3.23
1842 3.58
1944 3.94
2045 4.32 2142 4.68
2.86
1534 3.19
1644 3.54
1748 3.89
1845 4.21
1936 4.54
2025 4.93
2113 5.33 2203 5.74
3.90
1665 4.27
1764 4.64
1861 5.04
1954 5.43
2039 5.78
2123 6.15
2205 6.56
4.50
1733 4.89
1825 5.28
1920 5.70
2010 6.11
2095 6.51
2176 6.89
2254 7.27
-
-
-
-
outside rpm limit
MUA-PRC004-EN 27
Performance
Data fan data
Chart PD-7. Unit size 051 with 15-11 supply fan
9 50% WO
25% WO
60% WO
8
1760 rpm
70% WO
7 1700 rpm
6
1600 rpm 80% WO
1500 rpm
5
1400 rpm
90% WO
4 1300 rpm
1200 rpm
3
1100 rpm
1
0
1000 rpm
2
900 rpm
800 rpm
700 rpm
600 rpm
500 rpm
400 rpm
0 2500 5000 7500
airflow, cfm
10000 12500
Note: Fan curves include internal cabinet static losses. To determine total static pressure to be used with these curves, add filter, damper, gas or electric heat, evaporator and reheat coils, and TE wheel pressure drops to external duct static pressure.
Table PD-7. Supply fan size 15-11, unit size 051
0.0
0.5
1.0
1.5
2.0
3.0
total static pressure, in. wg.
3.5
4.0
5.0
5.5
6.0
7.0
7.5
8.0
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
2900 353 0.35 498 0.56 646 0.87 776 1.15 900 1.48 1138 2.29 1243 2.74 1340 3.20
-
3300 402 0.51 525 0.75 662 1.09 784 1.41 896 1.74 1116 2.54 1220 3.01 1317 3.49 1494 4.52 1574 5.06 1650 5.60
-
-
-
-
-
-
3700 451 0.72 555 0.97 678 1.32 797 1.71 903 2.07 1096 2.83 1196 3.30 1293 3.81 1472 4.89 1554 5.46 1631 6.03 1775 7.22
-
4100 500 0.98 588 1.23 704 1.59 812 2.04 913 2.45 1098 3.26 1184 3.69 1272 4.17 1449 5.29 1531 5.88 1608 6.47 1758 7.74 1827 8.39
-
-
4500 548 1.29 620 1.53 731 1.94 829 2.40 928 2.88 1105 3.76 1187 4.21 1264 4.66 1427 5.73 1507 6.33 1586 6.96 1733 8.25 1805 8.95
4900 597 1.67 653 1.88 759 2.37 853 2.78 945 3.34 1115 4.31 1194 4.79 1271 5.29 1415 6.30 1487 6.86 1563 7.49 1712 8.84 1782 9.54
5100 621 1.88 673 2.09 775 2.59 867 3.00 952 3.57 1122 4.62 1198 5.10 1272 5.61 1415 6.65 1483 7.18 1555 7.80 1701 9.15 1767 9.82
-
-
-
-
-
-
outside 25%WO limit outside rpm limit
28
MUA-PRC004-EN
Performance
Data fan data
Chart PD-8. Unit size 051 with 18-13 supply fan
9
50% WO
1515 rpm
1500 rpm
29% WO
60% WO
8
1400 rpm
70% WO
7
1300 rpm
6
1200 rpm
5
1100 rpm
4
1000 rpm
900 rpm
3
800 rpm
2
1
0
700 rpm
600 rpm
500 rpm
400 rpm
300 rpm
80% WO
90% WO
0 5000 10000
airflow, cfm
15000 20000
Note: Fan curves include internal cabinet static losses. To determine total static pressure to be used with these curves, add filter, damper, gas or electric heat, evaporator and reheat coils, and TE wheel pressure drops to external duct static pressure.
Table PD-8. Supply fan size 18-13, unit size 051
0.00
0.50
1.00
1.50
2.00
3.00
total static pressure, in. wg.
3.50
4.00
5.00
5.50
6.00
7.00
7.50
8.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
2900 217 0.16 411 0.41 573 0.73 707 1.10 827 1.54
3300 246 0.24 419 0.51 573 0.86 701 1.23 817 1.67
-
-
-
-
-
-
-
-
-
-
3700 276 0.34 430 0.63 576 1.00 702 1.41 811 1.84 1008 2.90
-
4100 306 0.46 445 0.77 581 1.16 703 1.61 810 2.06 999 3.10 1086 3.70 1169 4.37
-
-
-
-
-
-
-
-
-
-
-
-
-
-
4500 336 0.61 461 0.94 589 1.35 705 1.81 811 2.31 995 3.36 1080 3.96 1160 4.62
-
4900 366 0.79 478 1.13 598 1.57 709 2.05 813 2.59 992 3.66 1074 4.26 1152 4.91 1298 6.32
-
-
5100 380 0.89 486 1.23 604 1.69 714 2.19 814 2.73 993 3.85 1072 4.43 1148 5.06 1295 6.50 1363 7.27
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
outside 25% WO limit
MUA-PRC004-EN 29
Performance
Data fan data
Chart PD-9. Unit size 051 with 15-11 exhaust fan
8
1760 rpm
1700 rpm
7
1600 rpm
6
1500 rpm
33% WO 50% WO
60% WO
5
1400 rpm
70% WO
1300 rpm
4
3
1200 rpm
1100 rpm
1000 rpm
2
900 rpm
1
800 rpm
700 rpm
600 rpm
500 rpm
400 rpm
0
0 2000 4000 6000
airflow, cfm
8000
Note: Fan curves include internal energy module cabinet and wheel losses. Curves represent fan performance with an air density of 0.075 lbm/ft 3 .
80% WO
90% WO
10000 cfm
2900
3300
3700
4100
4500
4900
5100
Table PD-9. Exhaust fan size 15-11, unit size 051
0.00
0.50
1.00
1.50
total static pressure, in. wg.
2.00
2.50
3.00
3.50
4.00
4.50
rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
537 0.63
700 0.94
612 0.92
759 1.28
686 1.30
820 1.70
760 1.77
883 2.21
840 1.28
979 1.69
1151 2.32
1290 2.93
1393 3.44
1483 3.93
1565 4.41
1640 4.88
885 1.66
1005 2.06
1130 2.56
1283 3.28
1420 4.03
1518 4.63
1606 5.20
1683 5.75
935 2.12
1045 2.55
1153 3.03
1263 3.58
1399 4.37
1533 5.26
1633 5.98
1719 6.66
990 2.66
1091 3.14
1189 3.63
1286 4.17
1384 4.78
1505 5.61
1628 6.56
1740 7.52
834 2.34
947 2.82
1048 3.32
1142 3.83
1232 4.35
1320 4.89
1409 5.50
1498 6.15
1605 7.01
1715 7.99
908 3.02
1013 3.54
1108 4.08
1195 4.63
1281 5.19
1363 5.77
1444 6.37
1524 7.01
1606 7.71
1697 8.55
945 3.41
1046 3.95
1138 4.51
1223 5.07
1306 5.66
1385 6.25
1464 6.86
1541 7.51
1618 8.20
1699 8.97
outside 25%WO limit
30
MUA-PRC004-EN
Performance
Data fan data
Chart PD-10. Unit size 066 with 15-11 supply fan
50% WO
9
60% WO
25% WO
8
1760 rpm
1700 rpm
7
6
1600 rpm
1500 rpm
5
1400 rpm
70% WO
80% WO
90% WO
4 1300 rpm
1200 rpm
3
1100 rpm
1000 rpm
2
1
0
900 rpm
800 rpm
700 rpm
600 rpm
500 rpm
0 2500 5000 7500
airflow, cfm
10000 12500
Note: Fan curves include internal cabinet static losses. To determine total static pressure to be used with these curves, add filter, damper, gas or electric heat, evaporator and reheat coils, and TE wheel pressure drops to external duct static pressure.
Table PD-10. Supply fan size 15-11, unit size 066
0.0
0.5
1.0
1.5
2.0
3.0
total static pressure, in. wg.
3.5
4.0
5.0
5.5
6.0
7.0
7.5
8.0
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3600 439 0.66 548 0.91 673 1.26 793 1.63 900 1.98 1101 2.75 1201 3.22 1298 3.72 1477 4.79 1559 5.35 1639 5.94 1782 7.11
4000 487 0.91 580 1.16 696 1.51 809 1.96 911 2.35 1097 3.15 1185 3.58 1276 4.07 1455 5.19 1535 5.76 1615 6.36 1763 7.62
-
-
4400 536 1.21 613 1.45 725 1.84 824 2.31 924 2.77 1102 3.62 1185 4.07 1265 4.52 1431 5.61 1512 6.21 1591 6.83 1742 8.15 1811 8.81
4800 585 1.57 644 1.78 752 2.26 846 2.68 941 3.23 1113 4.17 1193 4.64 1269 5.12 1416 6.13 1493 6.73 1567 7.34 1716 8.67 1787 9.38
-
-
-
-
-
-
5200 634 1.99 683 2.20 782 2.71 875 3.12 957 3.69 1126 4.79 1201 5.27 1276 5.79 1416 6.84 1484 7.38 1552 7.96 1694 9.29 1763 9.99
-
5600 682 2.49 726 2.71 815 3.20 901 3.69 981 4.21 1141 5.45 1215 5.99 1286 6.53 1423 7.64 1486 8.19 1549 8.75 1675 9.98 1742 10.68 1810 11.44
6000 731 3.06 772 3.30 848 3.76 930 4.35 1010 4.80 1157 6.14 1230 6.77 1299 7.35 1431 8.51 1494 9.10 1556 9.71 1674 10.93 1733 11.56 1791 12.22
6400 780 3.71 818 3.98 879 4.38 961 5.02 1037 5.55 1174 6.84 1247 7.58 1315 8.24 1441 9.45 1504 10.08 1562 10.71 1677 11.98 1736 12.66 1790 13.31
6600 804 4.07 842 4.35 895 4.71 977 5.39 1050 5.97 1185 7.22 1255 7.98 1322 8.68 1449 9.99 1508 10.59 1568 11.26 1680 12.54 1737 13.23 1790 13.88
-
-
-
outside 25% WO limit outside rpm limit but may be used for interpolation purposes
MUA-PRC004-EN 31
Performance
Data fan data
Chart PD-11. Unit size 066 with 18-13 supply fan
8
1515 rpm
1500 rpm
7
1400 rpm
6
1300 rpm
5
1200 rpm
4
1100 rpm
3
1000 rpm
900 rpm
2
1
0
800 rpm
700 rpm
600 rpm
500 rpm
400 rpm
29% WO
50% WO
60% WO
70% WO
80% WO
90% WO
0 5000 10000 15000 20000
airflow, cfm
Note: Fan curves include internal cabinet static losses. To determine total static pressure to be used with these curves, add filter, damper, gas or electric heat, evaporator and reheat coils, and TE wheel pressure drops to external duct static pressure.
Table PD-11. Supply fan size 18-13, unit size 066
0.00
0.50
1.00
1.50
2.00
3.00
total static pressure, in. wg.
3.50
4.00
5.00
5.50
6.00
7.00
7.50
8.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3600 269 0.31 427 0.60 576 0.96 702 1.36 813 1.79 1012 2.86
-
4000 298 0.43 441 0.73 580 1.12 702 1.55 809 1.99 1002 3.05 1090 3.66
-
-
-
-
-
-
-
4400 328 0.57 457 0.90 587 1.30 704 1.76 811 2.25 996 3.29 1081 3.90 1162 4.54
-
4800 358 0.74 474 1.08 595 1.51 708 1.99 812 2.52 992 3.58 1074 4.17 1153 4.83 1303 6.28
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
5200 388 0.94 490 1.29 608 1.76 715 2.26 815 2.80 992 3.94 1072 4.53 1147 5.15 1292 6.59 1361 7.36
-
5600 418 1.18 507 1.52 621 2.03 723 2.55 818 3.11 994 4.34 1071 4.95 1145 5.58 1287 6.99 1352 7.74 1419 8.58
-
-
6000 447 1.45 527 1.79 637 2.35 732 2.88 826 3.48 995 4.75 1072 5.40 1144 6.06 1282 7.45 1346 8.20 1411 9.01 1531 10.71
6400 477 1.76 549 2.10 654 2.69 744 3.25 833 3.86 997 5.17 1073 5.88 1146 6.59 1282 8.01 1343 8.73 1405 9.53
-
6600 492 1.93 560 2.28 662 2.88 752 3.46 838 4.07 999 5.39 1076 6.13 1147 6.86 1281 8.32 1343 9.04 1403 9.80
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
outside 25% WO limit outside rpm or hp limit
32
MUA-PRC004-EN
Performance
Data fan data
Chart PD-12. Unit size 066 with 15-11 exhaust fan
8
1760 rpm
1700 rpm
7
1600 rpm
6
1500 rpm
5
1400 rpm
1300 rpm
4
3
1200 rpm
1100 rpm
1000 rpm
2
900 rpm
800 rpm
1
700 rpm
600 rpm
500 rpm
0
400 rpm
0
31% WO
50% WO
60% WO
70% WO
2000 4000
airflow, cfm
6000 8000
Note: Fan curves include internal energy module cabinet and wheel losses. Curves represent fan performance with an air density of 0.075 lbm/ft 3 .
80% WO
90% WO
3600
4000
4400
4800
5200
5600
6000
6400
6600
Table PD-12. Exhaust fan size 15-11, unit size 066 cfm
0.00
0.50
rpm bhp rpm bhp
1.00
rpm bhp
1.50
rpm total static pressure, in. wg.
bhp
2.00
2.50
3.00
rpm bhp rpm bhp rpm
3.50
4.00
4.50
bhp rpm bhp rpm bhp rpm bhp
608 1.05
755 1.44
675 1.44
810 1.87
879 1.84
992 2.25
1103 2.71 1215 3.23 1353 3.98
1489 4.82
1595 5.56 1682 6.20
927 2.31
1032 2.76
1132 3.23 1232 3.75 1332 4.32
1452 5.10
1578 6.02 1694 6.95
743 1.92
867 2.39
977 2.87
1076 3.36
1169 3.87 1260 4.39 1351 4.96
1440 5.57
1543 6.34 1657 7.29
810 2.50
925 3.00
1029 3.53
1123 4.06
1210 4.60 1296 5.16 1378 5.72
1461 6.34
1545 7.01 1630 7.75
878 3.17
985 3.72
1083 4.29
1173 4.86
1255 5.43 1335 6.03 1413 6.63
1490 7.26
1566 7.91 1643 8.62
945 3.96 1046 4.56
1137 5.15
1224 5.77
1303 6.38 1379 7.02 1453 7.66
1525 8.31
1597 8.98 1667 9.68
1013 4.88 1108 5.52
1194 6.14
1276 6.81
1354 7.47 1425 8.13 1496 8.82
1564 9.50
1633 10.21 1699 10.91
1080 5.92 1171 6.61
1252 7.26
1330 7.97
1405 8.67 1474 9.37 1541 10.09
1607 10.82
1671 11.55 1734 12.29
1114 6.49 1202 7.20
1281 7.88
1358 8.60
1430 9.32 1499 10.05 1565 10.78
1628 11.53
1692 12.29 1754 13.05
MUA-PRC004-EN 33
34
Performance
Data airside pressure drop
Table PD-13. Air pressure drop, in. wg.
coils filters unit main evaps RH evaps size cfm wet dry wet dry
RH
cond dry unit
OA
ER
OA
031 1800 0.26
1900 0.28
2000 0.30
2100 0.33
2200 0.35
2300 0.37
2400 0.40
2500 0.42
2600 0.45
2700 0.48
2800 0.50
2900 0.53
3000 0.56
3100 0.59
ER dampers
RA std.
Traq
100%
RA
TE wheel
& module
0.20
0.13
0.10
0.10
0.05
0.05
0.05
0.01
0.06
0.02
0.77
0.22
0.14
0.11
0.11
0.05
0.05
0.05
0.01
0.06
0.03
0.81
0.23
0.15
0.12
0.12
0.06
0.06
0.06
0.01
0.07
0.03
0.86
0.25
0.16
0.13
0.13
0.06
0.06
0.06
0.01
0.08
0.03
0.91
0.27
0.17
0.14
0.14
0.07
0.07
0.07
0.01
0.08
0.04
0.95
0.29
0.19
0.15
0.15
0.08
0.08
0.08
0.01
0.09
0.04
1.00
0.31
0.20
0.16
0.16
0.08
0.08
0.08
0.01
0.10
0.04
1.05
0.33
0.21
0.17
0.17
0.09
0.09
0.09
0.02
0.11
0.05
1.09
0.35
0.23
0.18
0.18
0.10
0.10
0.10
0.02
0.12
0.05
1.14
0.37
0.24
0.19
0.19
0.11
0.11
0.11
0.02
0.13
0.05
1.19
0.40
0.25
0.20
0.20
0.11
0.11
0.11
0.02
0.13
0.06
1.24
0.42
0.27
0.21
0.21
0.12
0.12
0.12
0.02
0.14
0.06
1.29
0.44
0.28
0.22
0.22
0.13
0.13
0.13
0.02
0.15
0.07
1.34
0.46
0.29
0.23
0.23
0.14
0.14
0.14
0.02
0.17
0.07
1.38
040 2200 0.25
2300 0.27
2400 0.28
2500 0.30
2600 0.32
2700 0.34
2800 0.36
2900 0.38
3000 0.40
3100 0.42
3200 0.44
3300 0.46
3400 0.48
3500 0.50
3600 0.53
3700 0.55
3800 0.57
3900 0.59
4000 0.62
0.19
0.12
0.10
0.10
0.07
0.07
0.07
0.01
0.08
0.04
0.60
0.20
0.13
0.10
0.10
0.08
0.08
0.08
0.01
0.09
0.04
0.64
0.22
0.14
0.11
0.11
0.08
0.08
0.08
0.01
0.10
0.04
0.68
0.23
0.15
0.12
0.12
0.09
0.09
0.09
0.02
0.11
0.05
0.71
0.25
0.16
0.12
0.12
0.10
0.10
0.10
0.02
0.12
0.05
0.75
0.26
0.17
0.13
0.13
0.11
0.11
0.11
0.02
0.13
0.05
0.79
0.28
0.18
0.14
0.14
0.11
0.11
0.11
0.02
0.13
0.06
0.83
0.29
0.19
0.15
0.15
0.12
0.12
0.12
0.02
0.14
0.06
0.87
0.31
0.20
0.16
0.16
0.13
0.13
0.13
0.02
0.15
0.07
0.91
0.33
0.21
0.16
0.16
0.14
0.14
0.14
0.02
0.17
0.07
0.95
0.34
0.22
0.17
0.17
0.15
0.15
0.15
0.03
0.18
0.07
0.99
0.36
0.23
0.18
0.18
0.16
0.16
0.16
0.03
0.19
0.08
1.03
0.38
0.24
0.19
0.19
0.17
0.17
0.17
0.03
0.20
0.08
1.07
0.40
0.25
0.20
0.20
0.18
0.18
0.18
0.03
0.21
0.09
1.12
0.41
0.26
0.21
0.21
0.19
0.19
0.19
0.03
0.22
0.09
1.16
0.43
0.27
0.22
0.22
0.20
0.20
0.20
0.04
0.24
0.10
1.21
0.45
0.29
0.22
0.22
0.21
0.21
0.21
0.04
0.25
0.10
1.25
0.47
0.30
0.23
0.23
0.22
0.22
0.22
0.04
0.26
0.11
1.30
0.49
0.31
0.24
0.24
0.23
0.23
0.23
0.04
0.28
0.12
1.34
MUA-PRC004-EN
MUA-PRC004-EN
Performance
Data airside pressure drop
Table PD-14. Air pressure drop, in. wg.
unit coils
main evaps RH evaps size cfm wet dry wet dry
filters
RH
cond dry unit
OA
ER
OA
5100 0.58
066 3600 0.24
3700 0.25
3800 0.26
3900 0.27
4000 0.28
4100 0.29
4200 0.30
4300 0.31
4400 0.32
4500 0.33
4600 0.35
4700 0.36
4800 0.37
4900 0.38
5000 0.39
5100 0.40
5200 0.42
5300 0.43
5400 0.44
5500 0.45
5600 0.46
5700 0.48
5800 0.49
5900 0.50
6000 0.52
6100 0.53
6200 0.54
6300 0.56
6400 0.57
6500 0.58
6600 0.60
051 2900 0.25
3000 0.26
3100 0.27
3200 0.28
3300 0.30
3400 0.31
3500 0.33
3600 0.34
3700 0.35
3800 0.37
3900 0.38
4000 0.40
4100 0.41
4200 0.43
4300 0.45
4400 0.46
4500 0.48
4600 0.49
4700 0.51
4800 0.53
4900 0.54
5000 0.56
0.27
0.28
0.29
0.29
0.30
0.31
0.32
0.33
0.34
0.35
0.36
0.37
0.38
0.39
0.41
0.42
0.43
0.44
0.45
0.46
0.47
0.45
0.18
0.19
0.20
0.21
0.21
0.22
0.23
0.24
0.25
0.26
0.31
0.32
0.34
0.35
0.36
0.37
0.39
0.40
0.41
0.43
0.44
0.19
0.20
0.21
0.22
0.23
0.24
0.25
0.26
0.27
0.29
0.30
0.12
0.09
0.09
0.04
0.05
0.08
0.01
0.07
0.03
0.13
0.10
0.10
0.04
0.05
0.08
0.01
0.08
0.03
0.14
0.10
0.10
0.04
0.06
0.09
0.01
0.08
0.03
0.14
0.11
0.11
0.04
0.06
0.09
0.01
0.09
0.03
0.15
0.11
0.11
0.05
0.06
0.10
0.01
0.09
0.04
0.16
0.12
0.12
0.05
0.07
0.10
0.01
0.10
0.04
0.16
0.13
0.13
0.05
0.07
0.11
0.01
0.10
0.04
0.17
0.13
0.13
0.06
0.07
0.12
0.01
0.11
0.04
0.18
0.14
0.14
0.06
0.08
0.12
0.01
0.12
0.05
0.18
0.14
0.14
0.06
0.08
0.13
0.01
0.12
0.05
0.19
0.15
0.15
0.07
0.09
0.14
0.01
0.13
0.05
0.20
0.16
0.16
0.07
0.09
0.14
0.01
0.14
0.05
0.21
0.16
0.16
0.07
0.10
0.15
0.01
0.14
0.06
0.21
0.17
0.17
0.08
0.10
0.16
0.01
0.15
0.06
0.22
0.17
0.17
0.08
0.11
0.17
0.02
0.16
0.06
0.23
0.18
0.18
0.08
0.11
0.18
0.02
0.16
0.06
0.24
0.19
0.19
0.09
0.12
0.18
0.02
0.17
0.07
0.25
0.19
0.19
0.09
0.12
0.19
0.02
0.18
0.07
0.25
0.20
0.20
0.10
0.13
0.20
0.02
0.19
0.07
0.26
0.21
0.21
0.10
0.13
0.21
0.02
0.20
0.08
0.27
0.21
0.21
0.11
0.14
0.22
0.02
0.20
0.08
0.28
0.22
0.22
0.11
0.14
0.23
0.02
0.21
0.08
0.29
0.23
0.23
0.11
0.15
0.24
0.02
0.22
0.09
0.12
0.09
0.09
0.06
0.07
0.12
0.01
0.11
0.04
0.12
0.09
0.09
0.06
0.08
0.12
0.01
0.12
0.05
0.13
0.10
0.10
0.06
0.08
0.13
0.01
0.12
0.05
0.13
0.10
0.10
0.07
0.09
0.14
0.01
0.13
0.05
0.14
0.11
0.11
0.07
0.09
0.14
0.01
0.14
0.05
0.15
0.11
0.11
0.07
0.10
0.15
0.01
0.14
0.06
0.15
0.12
0.12
0.08
0.10
0.16
0.01
0.15
0.06
0.16
0.12
0.12
0.08
0.11
0.17
0.02
0.16
0.06
0.16
0.12
0.12
0.08
0.11
0.18
0.02
0.16
0.06
0.17
0.13
0.13
0.09
0.12
0.18
0.02
0.17
0.07
0.17
0.13
0.13
0.09
0.12
0.19
0.02
0.18
0.07
0.18
0.14
0.14
0.10
0.13
0.20
0.02
0.19
0.07
0.18
0.14
0.14
0.10
0.13
0.21
0.02
0.20
0.08
0.19
0.15
0.15
0.11
0.14
0.22
0.02
0.20
0.08
0.20
0.15
0.15
0.11
0.14
0.23
0.02
0.21
0.08
0.20
0.16
0.16
0.11
0.15
0.24
0.02
0.22
0.09
0.21
0.16
0.16
0.12
0.16
0.24
0.02
0.23
0.09
0.21
0.17
0.17
0.12
0.16
0.25
0.02
0.24
0.09
0.22
0.17
0.17
0.13
0.17
0.26
0.02
0.25
0.10
0.23
0.18
0.18
0.13
0.17
0.27
0.02
0.26
0.10
0.23
0.18
0.18
0.14
0.18
0.28
0.03
0.27
0.11
0.24
0.19
0.19
0.14
0.19
0.29
0.03
0.28
0.11
0.25
0.19
0.19
0.15
0.19
0.30
0.03
0.29
0.11
0.25
0.20
0.20
0.15
0.20
0.32
0.03
0.30
0.12
0.26
0.20
0.20
0.16
0.21
0.33
0.03
0.31
0.12
0.26
0.21
0.21
0.16
0.22
0.34
0.03
0.32
0.12
0.27
0.21
0.21
0.17
0.22
0.35
0.03
0.33
0.13
0.28
0.22
0.22
0.17
0.23
0.36
0.03
0.34
0.13
0.28
0.22
0.22
0.18
0.24
0.37
0.03
0.35
0.14
0.29
0.23
0.23
0.18
0.24
0.38
0.03
0.36
0.14
0.30
0.24
0.24
0.19
0.25
0.39
0.04
0.37
0.15
TE wheel
ER dampers
RA
100% & std.
Traq RA module
0.87
0.89
0.92
0.94
0.97
1.00
1.03
1.05
1.08
1.11
1.14
1.17
1.19
1.22
1.25
1.28
1.31
1.34
1.38
1.41
1.44
1.32
0.62
0.65
0.67
0.69
0.72
0.74
0.77
0.79
0.82
0.84
1.00
1.03
1.06
1.09
1.11
1.14
1.17
1.20
1.23
1.26
1.29
0.70
0.73
0.76
0.78
0.81
0.84
0.86
0.89
0.92
0.95
0.97
35
Performance
Data airside pressure drop
Table PD-15. Single gas duct furnace with 12-9 fan, unit sizes 031 & 040, in. wg.
unit size
031
040 cfm
1800
1900
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
3100
2200
2300
2400
2500
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
150/120
0.15
0.17
0.18
0.20
0.22
0.24
0.26
0.29
0.31
0.33
0.36
0.39
0.41
0.44
0.22
0.24
0.26
0.29
0.31
0.33
0.36
0.39
0.41
0.44
0.47
0.50
0.53
0.56
0.60
—
—
—
—
125/100
0.22
0.25
0.28
0.30
0.33
0.36
0.40
0.43
0.47
0.50
0.54
0.58
0.62
—
0.33
0.36
0.40
0.43
0.47
—
—
—
—
—
0.50
0.54
0.58
0.62
—
—
—
—
—
0.19
0.21
0.22
0.24
0.26
0.28
0.31
0.33
0.35
0.37
0.40
0.42
0.45
0.48
0.51
0.53
0.56
0.59
0.62
200/160 gas heat input/output (MBh)
250/200 300/240
0.22
0.25
0.16
0.17
0.19
0.21
0.22
0.24
0.26
0.28
0.31
0.33
0.35
0.37
—
—
—
0.29
0.33
0.37
0.41
0.33
0.37
0.40
0.44
0.47
0.51
0.55
—
—
0.45
0.50
0.54
—
—
—
—
—
0.58
0.63
0.51
0.54
0.33
0.37
0.41
0.33
0.37
0.40
0.44
0.47
0.51
0.55
0.59
0.63
0.67
0.71
0.75
0.80
0.84
0.89
0.94
—
—
—
0.45
0.50
0.54
0.58
0.63
0.51
0.54
0.58
0.62
0.66
0.71
0.75
0.79
0.84
0.88
0.93
400/320
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
350/280
—
—
—
—
—
—
—
—
—
—
—
0.54
0.57
0.61
—
—
0.54
0.57
0.61
0.66
0.70
0.74
0.58
0.61
—
—
—
—
—
0.65
0.69
0.72
0.76
36 MUA-PRC004-EN
Performance
Data airside pressure drop
Table PD-16. Single gas duct furnace with 15-11 fan, unit sizes 031 & 040, in. wg.
unit size
031
040
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
2800
2900
3000
3100
2200
2300
2400
2500
2600
3700
3800
3900
4000 cfm
1800
1900
2000
2100
2200
2300
2400
2500
2600
2700
0.25
0.27
0.29
0.31
0.33
0.36
0.38
0.40
0.43
0.45
0.27
0.29
0.31
0.33
0.17
0.18
0.20
0.22
0.24
—
—
—
—
150/120
0.11
0.13
0.14
0.15
0.17
0.18
0.20
0.22
0.24
0.25
—
—
—
—
—
0.43
0.47
0.50
0.54
—
0.47
0.50
0.54
—
0.29
0.32
0.34
0.37
0.40
—
—
—
—
125/100
0.19
0.22
0.24
0.26
0.29
0.32
0.34
0.37
0.40
0.43
0.19
0.20
0.21
0.23
0.24
0.26
0.28
0.29
0.31
0.33
0.20
0.21
0.23
0.24
0.12
0.13
0.15
0.16
0.17
0.35
0.37
0.39
0.41
200/160 gas heat input/output MBh)
250/200 300/240
0.21
0.24
0.10
0.11
0.12
0.13
0.15
0.16
0.17
0.19
—
—
—
0.26
0.29
0.31
0.34
0.25
0.27
0.29
—
—
0.37
0.40
0.43
—
—
—
—
—
0.32
0.34
0.36
0.39
0.29
0.31
0.34
0.25
0.27
0.29
0.32
0.34
0.36
0.39
0.41
0.44
0.46
0.49
0.52
0.55
0.58
0.61
0.64
0.43
0.46
0.50
0.36
0.38
0.41
0.43
0.46
0.49
0.52
0.46
0.50
0.36
0.38
—
—
—
0.37
0.40
0.54
0.57
0.60
0.64
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
400/320
—
—
—
—
—
—
—
—
—
—
—
—
0.62
0.66
0.71
0.75
0.80
0.85
0.69
0.72
—
0.62
0.66
0.71
—
—
—
—
—
0.76
0.80
0.83
0.87
350/280
—
—
—
—
—
—
—
—
—
—
MUA-PRC004-EN 37
Performance
Data airside pressure drop
Table PD-17. Dual gas duct furnace with 12-9 fan, unit sizes 031 & 040, in. wg.
unit size
031
040
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
2800
2900
3000
3100
2200
2300
2400
2500
2600
3700
3800
3900
4000 cfm
1800
1900
2000
2100
2200
2300
2400
2500
2600
2700
0.91
0.98
1.05
1.13
1.20
1.28
1.36
1.45
1.53
1.62
0.98
1.05
1.13
1.20
0.61
0.66
0.72
0.78
0.85
1.71
1.81
1.90
2.00
250/200
—
—
—
0.55
0.61
0.66
0.72
0.78
0.85
0.91
0.54
0.59
0.63
0.67
0.72
0.76
0.81
0.86
0.91
0.97
0.59
0.63
0.67
0.72
—
—
—
0.47
0.50
1.02
1.08
1.14
1.19
300/240
—
—
0.47
0.50
0.54
—
—
—
—
— gas heat input/output (MBh)
350/280
—
—
—
—
—
—
—
—
—
—
—
—
0.48
0.52
0.55
0.59
0.63
0.67
0.71
0.75
—
0.48
0.52
0.55
—
—
—
—
—
0.79
0.83
0.88
0.92
—
0.63
0.67
0.71
0.75
—
—
—
—
—
—
—
—
—
—
—
—
—
—
0.79
0.83
0.88
0.92
400/320
—
—
—
—
—
—
—
—
—
—
38 MUA-PRC004-EN
Performance
Data airside pressure drop
Table PD-18. Dual gas duct furnace with 15-11 fan, unit sizes 031 & 040, in. wg.
gas heat input/output (MBh) unit size
031
040 cfm
1800
1900
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
3100
2200
2300
2400
2500
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
250/200
—
—
—
0.51
0.56
0.61
0.67
0.72
0.78
0.84
0.91
0.97
1.04
1.11
0.56
0.61
0.67
0.72
0.78
0.84
0.91
0.97
1.04
1.11
1.19
1.26
1.34
1.42
1.50
1.59
1.67
1.76
1.85
300/240
—
—
0.40
0.43
0.46
—
—
—
—
—
0.50
0.53
0.57
0.61
—
—
—
0.40
0.43
0.46
0.50
0.53
0.57
0.61
0.65
0.69
0.73
0.78
0.82
0.87
0.92
0.97
1.02
350/280
—
—
—
—
—
—
—
—
—
—
—
0.37
0.40
0.42
—
—
0.37
0.40
0.42
0.45
0.48
0.51
0.54
0.57
—
—
—
—
—
0.60
0.64
0.67
0.70
400/320
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
0.48
0.51
0.54
0.57
—
—
—
—
—
—
—
—
—
—
0.60
0.64
0.67
0.70
MUA-PRC004-EN 39
Performance
Data airside pressure drop
Table PD-19. Electric heat with 12-9 fan, unit sizes 031 & 040, in. wg.
unit size
031
040 cfm
1800
1900
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
3100
2200
2300
2400
2500
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000 electric heat
0.07
0.08
0.09
0.10
0.11
0.12
0.13
0.14
0.15
0.17
0.18
0.19
0.21
0.22
0.11
0.12
0.13
0.14
0.15
0.17
0.18
0.19
0.21
0.22
0.23
0.25
0.26
0.28
0.30
0.31
0.33
0.35
0.37
no heat
0.07
0.07
0.08
0.09
0.10
0.11
0.12
0.13
0.14
0.15
0.16
0.17
0.19
0.20
0.10
0.11
0.12
0.13
0.14
0.15
0.16
0.17
0.19
0.20
0.21
0.22
0.24
0.25
0.27
0.28
0.30
0.31
0.33
40 MUA-PRC004-EN
Performance
Data airside pressure drop
Table PD-20. Electric heat with 15-11 fan, unit sizes 031 & 040, in. wg.
unit size
031
040 cfm
1800
1900
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
3100
2200
2300
2400
2500
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000 electric heat
0.04
0.04
0.05
0.05
0.06
0.06
0.07
0.08
0.08
0.09
0.10
0.10
0.11
0.12
0.06
0.06
0.07
0.08
0.08
0.09
0.10
0.10
0.11
0.12
0.13
0.13
0.14
0.15
0.16
0.17
0.18
0.19
0.20
no heat
0.03
0.04
0.04
0.04
0.05
0.05
0.06
0.06
0.07
0.07
0.08
0.08
0.09
0.10
0.05
0.05
0.06
0.06
0.07
0.07
0.08
0.08
0.09
0.10
0.10
0.11
0.12
0.12
0.13
0.14
0.14
0.15
0.16
MUA-PRC004-EN 41
Performance
Data airside pressure drop
Table PD-21. Single gas duct furnace with 15-11 fan, unit sizes 051 & 066, in. wg.
unit size
051
066 cfm
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
5100
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
5100
5200
5300
5400
5500
5600
5700
5800
5900
6000
6100
6200
6300
6400
6500
6600
125/100
0.50
0.54
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
150/120
0.29
0.31
0.33
0.36
0.38
—
—
—
—
—
0.40
0.43
0.45
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
0.45
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
200/160
0.21
0.23
0.24
0.26
0.28
gas heat input/output (MBh)
250/200
0.34
0.36
0.39
0.41
0.44
300/240
0.50
0.36
0.38
0.41
0.43
0.59
0.61
—
—
0.33
0.35
0.37
0.39
0.41
0.43
0.45
0.47
0.49
0.51
0.29
0.31
0.33
0.35
0.37
0.39
0.41
0.43
0.45
0.47
0.49
0.51
0.54
0.56
—
—
—
—
—
0.54
0.56
0.59
0.61
—
—
—
—
—
—
—
—
—
—
—
—
0.46
0.49
0.52
0.55
0.58
0.61
0.64
0.67
0.71
0.74
0.78
0.81
0.85
0.89
0.93
0.96
1.00
1.05
0.52
0.55
0.58
0.61
0.64
0.67
0.71
0.74
0.78
0.81
0.85
0.89
0.93
0.96
1.00
1.05
1.09
1.13
1.17
1.22
1.26
1.31
1.35
1.40
1.45
1.50
—
—
—
—
—
0.84
0.88
0.92
0.96
0.99
1.04
1.08
1.12
1.16
1.20
1.25
1.29
1.34
1.39
1.43
1.48
1.53
1.58
1.63
1.68
1.74
0.92
0.96
0.99
1.04
0.52
0.54
0.57
0.60
0.64
0.67
0.70
0.74
0.77
0.81
0.46
0.49
0.52
0.54
0.57
0.60
0.64
0.67
0.70
0.74
0.77
0.81
0.84
0.88
400/320
—
—
—
—
0.64
0.67
0.71
0.75
0.79
0.83
0.88
0.71
0.74
0.78
0.82
0.85
0.89
0.94
0.98
1.02
1.06
1.11
1.16
0.86
0.90
0.95
0.99
0.71
0.74
0.78
0.82
0.85
0.89
0.94
0.98
1.02
1.06
1.11
1.16
1.20
1.25
1.30
1.35
1.41
1.46
1.51
1.57
1.63
1.68
1.74
1.80
1.86
1.92
1.99
350/280
0.48
0.52
0.56
0.60
0.64
0.68
0.52
0.55
0.59
0.62
0.65
0.69
0.72
0.75
0.79
0.82
0.86
0.90
0.93
0.97
1.00
1.04
1.08
0.55
0.59
0.62
0.65
0.69
0.72
0.75
0.79
0.82
0.86
0.90
0.93
0.97
1.00
1.04
1.08
1.12
1.16
1.19
1.23
1.27
1.31
1.35
1.39
1.43
1.47
1.52
1.56
1.60
1.64
1.69
MUA-PRC004-EN 42
Performance
Data airside pressure drop
Table PD-22. Single gas duct furnace with 18-13 fan, unit sizes 051 & 066, in. wg.
gas heat input/output (MBh) unit size
051
066
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
5100
5200
5300
5400
5500
5600
5700
5800
5900
6000
6100
6200
6300
6400
6500
6600 cfm
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
5100
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
125/100
—
—
—
—
—
0.49
0.52
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
0.39
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
150/120
0.25
0.27
0.29
0.31
0.33
0.35
0.37
0.39
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
0.28
0.29
0.31
0.33
0.34
0.36
0.38
0.40
0.42
0.44
0.46
0.48
0.50
0.52
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
200/160
0.18
0.19
0.21
0.22
0.23
0.25
0.26
0.28
0.29
0.31
0.33
0.34
0.36
0.38
0.40
0.42
0.44
0.46
0.48
0.50
0.52
—
—
0.40
0.42
0.44
0.47
0.49
0.52
0.54
0.57
0.59
0.62
0.65
0.68
0.71
0.74
0.77
0.80
0.83
0.87
0.90
0.93
0.97
1.00
1.04
1.08
1.12
1.15
—
—
—
—
—
250/200
0.26
0.28
0.30
0.32
0.34
0.36
0.38
0.40
0.42
0.44
0.47
0.49
0.52
0.54
0.57
0.59
0.62
0.65
0.68
0.71
0.74
0.77
0.80
0.39
0.42
0.44
0.46
0.48
0.51
0.53
0.56
0.59
0.61
0.64
0.67
0.70
0.73
0.76
0.79
0.82
0.85
0.89
0.92
0.96
0.99
1.03
1.06
1.10
1.14
1.18
1.22
1.26
1.30
1.34
300/240
0.42
0.28
0.30
0.31
0.33
0.35
0.37
0.39
0.42
0.44
0.46
0.48
0.51
0.53
0.56
0.59
0.61
0.64
0.67
0.70
0.73
0.76
0.79
0.77
0.81
0.86
0.90
0.73
0.76
0.80
0.83
0.87
0.90
0.94
0.97
1.01
1.05
1.08
1.12
1.15
1.19
1.23
1.26
1.30
1.34
1.38
1.42
1.45
1.49
1.53
1.57
1.61
1.65
1.69
400/320
—
—
—
—
0.71
0.76
0.80
0.85
0.89
0.94
0.99
0.82
0.85
0.89
0.93
0.96
1.00
1.04
1.07
1.11
1.15
1.19
1.22
0.39
0.41
0.43
0.45
0.47
0.50
0.52
0.55
0.57
0.60
0.63
0.65
0.68
0.71
0.74
0.77
0.80
0.83
0.86
0.90
0.93
0.96
1.00
1.03
1.07
1.11
1.14
1.18
1.22
1.26
1.30
350/280
0.40
0.42
0.45
0.48
0.51
0.54
0.37
0.39
0.41
0.43
0.45
0.47
0.50
0.52
0.55
0.57
0.60
0.63
0.65
0.68
0.71
0.74
0.77
MUA-PRC004-EN 43
Performance
Data airside pressure drop
Table PD-23. Dual gas duct furnace with 15-11 fan, unit sizes 051 & 066, in. wg.
unit size cfm
051
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
5100
061
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
5100
5200
5300
5400
5500
5600
5700
5800
5900
6000
6100
6200
6300
6400
6500
6600
0.57
0.60
0.64
0.67
0.70
0.74
0.78
0.81
0.85
0.89
0.93
0.97
1.01
1.06
1.10
1.15
1.19
1.24
1.28
1.33
1.38
1.43
1.48
1.53
1.59
1.64
1.69
1.75
1.80
—
—
350/280
0.37
0.40
0.42
0.45
0.48
0.51
0.54
0.57
0.60
0.64
0.67
0.70
0.74
0.78
0.81
0.85
0.89
0.93
0.97
1.01
1.06
1.10
1.15
1.50
1.59
1.67
1.76
1.85
1.95
2.04
2.14
2.24
2.35
—
—
—
—
—
2.45
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
250/200
0.97
1.04
1.11
1.19
1.26
1.34
1.42
1.50
1.59
1.67
1.76
1.85
1.95
2.04
2.14
2.24
2.35
2.45
—
—
—
—
—
0.82
0.87
0.92
0.97
1.02
1.07
1.12
1.18
1.23
1.29
1.35
1.40
1.46
1.53
1.59
1.65
1.72
1.79
1.85
1.92
—
—
—
—
—
—
—
—
—
—
—
300/240
0.53
0.57
0.61
0.65
0.69
0.73
0.78
0.82
0.87
0.92
0.97
1.02
1.07
1.12
1.18
1.23
1.29
1.35
1.40
1.46
1.53
1.59
1.65
0.57
0.60
0.64
0.67
0.70
0.74
0.78
0.81
0.85
0.89
0.93
0.97
1.01
1.06
1.10
1.15
1.19
1.24
1.28
1.33
1.38
1.43
1.48
1.53
1.59
1.64
1.69
1.75
1.80
1.86
1.92
400/320 gas heat input/output (MBh)
500/400 600/480
—
—
—
—
0.48
0.51
0.54
0.57
0.60
0.64
0.67
0.70
0.74
0.78
0.81
0.85
0.89
0.93
0.97
1.01
1.06
1.10
1.15
—
—
—
—
—
—
—
—
—
—
—
—
0.86
0.90
0.94
0.99
1.03
1.08
1.13
1.18
1.23
1.28
1.33
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
1.26
1.31
0.86
0.90
0.94
0.99
1.03
—
—
—
—
—
1.08
1.13
1.18
1.23
1.28
1.33
1.38
1.43
1.49
1.54
1.60
1.66
1.72
1.78
1.84
1.90
1.96
2.03
2.09
2.16
2.23
—
—
—
—
—
—
—
—
—
—
—
—
—
—
1.26
1.31
1.36
1.41
1.47
1.52
1.58
1.63
1.69
1.75
1.81
1.87
1.93
2.00
2.06
2.13
2.19
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
2.24
—
—
—
—
—
800/640
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
1.61
1.66
1.71
1.76
1.81
1.86
1.91
1.96
2.02
700/560
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
MUA-PRC004-EN 44
Performance
Data airside pressure drop
Table PD-24. Dual gas duct furnace with 18-13 fan, unit sizes 051 & 066, in. wg.
unit size
051
066 cfm
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
5100
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
5100
5200
5300
5400
5500
5600
5700
5800
5900
6000
6100
6200
6300
6400
6500
6600
350/280
0.34
0.36
0.39
0.41
0.44
0.46
0.49
0.52
0.55
0.58
0.61
0.64
0.67
0.71
0.74
0.78
0.81
0.85
0.89
0.92
0.96
1.00
1.04
0.52
0.55
0.58
0.61
0.64
0.67
0.71
0.74
0.78
0.81
0.85
0.89
0.92
0.96
1.00
1.04
1.09
1.13
1.17
1.21
1.26
1.30
1.35
1.40
1.44
1.49
1.54
1.59
1.64
—
—
250/200
0.96
1.03
1.10
1.17
1.24
1.32
1.40
1.48
1.56
1.65
1.74
1.83
1.92
2.01
2.11
2.21
2.31
2.42
—
—
—
—
—
1.48
1.56
1.65
1.74
1.83
1.92
2.01
2.11
2.21
2.31
—
—
—
—
—
2.42
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
300/240
0.50
0.53
0.57
0.60
0.64
0.68
0.72
0.76
0.81
0.85
0.90
0.94
0.99
1.04
1.09
1.14
1.19
1.25
1.30
1.36
1.42
1.47
1.53
0.76
0.81
0.85
0.90
0.94
0.99
1.04
1.09
1.14
1.19
1.25
1.30
1.36
1.42
1.47
1.53
1.59
1.66
1.72
1.78
—
—
—
—
—
—
—
—
—
—
—
400/320
—
—
—
—
0.44
gas heat input/output (MBh)
500/400
—
—
—
—
—
600/480
—
—
—
—
—
0.92
0.96
1.00
1.04
0.52
0.55
0.58
0.61
0.64
0.67
0.71
0.74
0.78
0.81
0.46
0.49
0.52
0.55
0.58
0.61
0.64
0.67
0.71
0.74
0.78
0.81
0.85
0.89
0.85
0.89
0.92
0.96
1.00
1.04
1.09
1.13
1.17
1.21
1.26
1.30
1.35
1.40
1.44
1.49
1.54
1.59
1.64
1.70
1.75
—
—
—
—
—
—
—
0.70
0.73
0.77
0.80
0.84
0.88
0.92
0.96
1.00
1.04
1.08
—
—
—
—
—
0.70
0.73
0.77
0.80
0.84
0.88
0.92
0.96
1.00
1.04
1.08
1.13
1.17
1.22
1.26
1.31
1.36
1.41
1.46
1.51
1.56
1.61
1.66
1.72
1.77
1.83
—
—
—
—
1.02
1.06
1.11
1.15
1.19
1.24
1.29
1.33
1.38
1.43
1.48
1.53
1.58
1.63
1.69
1.74
1.80
—
—
1.02
1.06
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
700/560
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
1.25
1.30
1.34
1.39
1.43
1.48
1.53
1.58
1.63
800/640
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
1.94
—
—
—
—
—
MUA-PRC004-EN 45
46
Performance
Data airside pressure drop
Table PD-25. Electric heat with 15-11 fan, unit sizes 051 & 066, in. wg.
unit size
051
066
4800
4900
5000
5100
3600
3700
3800
3900
4000
3900
4000
4100
4200
4300
4400
4500
4600
4700
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000 cfm
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
5100
5200
5300
5400
5500
5600
5700
5800
5900
6000
6100
6200
6300
6400
6500
6600
0.28
0.29
0.31
0.32
0.16
0.17
0.18
0.19
0.20
0.19
0.20
0.21
0.22
0.23
0.24
0.25
0.26
0.27
0.21
0.22
0.23
0.24
0.25
0.26
0.27
0.28
0.29
0.31
electric heat
0.10
0.11
0.12
0.13
0.13
0.14
0.15
0.16
0.17
0.18
0.32
0.33
0.34
0.36
0.37
0.38
0.40
0.41
0.43
0.44
0.46
0.47
0.49
0.50
0.52
0.53
0.23
0.24
0.25
0.26
0.13
0.14
0.14
0.15
0.16
0.15
0.16
0.17
0.18
0.19
0.19
0.20
0.21
0.22
0.17
0.18
0.19
0.19
0.20
0.21
0.22
0.23
0.24
0.25
no heat
0.08
0.09
0.10
0.10
0.11
0.12
0.12
0.13
0.14
0.14
0.26
0.27
0.28
0.29
0.30
0.31
0.33
0.34
0.35
0.36
0.37
0.39
0.40
0.41
0.42
0.44
MUA-PRC004-EN
Performance
Data airside pressure drop
Table PD-26. Electric heat with 18-13 fan, unit sizes 051 & 066, in. wg.
unit size
051
066 cfm
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
5100
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
5100
5200
5300
5400
5500
5600
5700
5800
5900
6000
6100
6200
6300
6400
6500
6600 electric heat
0.06
0.07
0.07
0.07
0.08
0.08
0.09
0.09
0.10
0.11
0.11
0.12
0.12
0.13
0.13
0.14
0.15
0.15
0.16
0.17
0.17
0.18
0.19
0.09
0.10
0.11
0.11
0.12
0.12
0.13
0.13
0.14
0.15
0.15
0.16
0.17
0.17
0.18
0.19
0.20
0.20
0.21
0.22
0.23
0.24
0.24
0.25
0.26
0.27
0.28
0.29
0.30
0.31
0.32
no heat
0.04
0.05
0.05
0.05
0.05
0.06
0.06
0.07
0.07
0.07
0.08
0.08
0.08
0.09
0.09
0.10
0.10
0.11
0.11
0.12
0.12
0.13
0.13
0.07
0.07
0.07
0.08
0.08
0.08
0.09
0.09
0.10
0.10
0.11
0.11
0.12
0.12
0.13
0.13
0.14
0.14
0.15
0.15
0.16
0.16
0.17
0.17
0.18
0.19
0.19
0.20
0.21
0.21
0.22
MUA-PRC004-EN 47
Performance
Data unit capacity total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent
Table PD-27. Size 031 cooling capacity without reheat installed, MBh cfm
1800
1900
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
3100
189.76
79.00
192.46
79.57
195.01
80.04
197.42
80.41
199.70
80.70
95/76
173.48
74.21
177.18
75.45
180.63
76.51
183.86
77.46
186.90
78.30
201.88
80.91
203.96
81.05
205.96
81.14
207.87
81.18
212.29
132.38
215.31
134.60
218.15
136.67
220.81
138.59
223.32
140.39
85/80
193.74
118.48
197.98
121.69
201.93
124.66
205.62
127.43
209.06
129.99
225.69
142.06
227.93
143.63
230.05
145.09
232.05
146.46
204.41
119.24
207.35
121.17
210.12
122.94
212.73
124.59
215.18
126.11
85/78
186.37
107.02
190.49
109.87
194.33
112.49
197.91
114.92
201.26
117.17
217.50
127.53
219.69
128.83
221.77
130.05
223.74
131.17
196.79
106.47
199.66
108.09
202.36
109.58
204.90
110.94
207.30
112.20
85/76
179.28
95.94
183.27
98.41
187.00
100.69
190.48
102.78
193.74
104.70
209.57
113.34
211.71
114.39
213.74
115.35
215.67
116.23
196.97
91.11
199.69
91.86
202.24
92.48
204.66
93.03
206.94
93.51
dry-bulb / wet-bulb temperature (°F)
95/78 95/80 105/76 105/78
180.28
84.98
187.35
96.11
168.58
53.76
174.16
63.66
184.10
86.58
187.65
87.97
190.97
89.18
194.07
90.22
191.29
98.05
194.95
99.78
198.36
101.31
201.55
102.66
172.35
54.21
175.87
54.49
179.16
54.63
182.24
54.63
177.98
64.34
181.58
64.44
184.95
64.84
188.10
65.10
209.10
93.90
211.15
94.20
213.09
94.42
214.94
94.58
204.52
103.85
207.31
104.88
209.92
105.77
212.38
106.54
214.69
107.20
216.88
107.75
218.93
108.20
220.88
108.57
222.72
108.85
185.14
54.51
187.86
54.27
190.42
53.94
192.84
53.51
195.12
53.01
197.28
52.43
199.33
51.77
201.27
51.07
203.11
50.30
203.42
64.22
205.50
63.77
207.47
63.25
209.33
62.67
191.05
65.22
193.83
65.22
196.45
65.11
198.91
64.90
201.23
64.60
180.46
30.99
183.02
29.81
185.43
28.55
187.71
27.21
189.85
25.80
115/76
164.83
35.19
168.39
34.62
171.71
33.90
174.82
33.04
177.73
32.07
191.88
24.33
193.80
22.80
195.61
21.23
197.37
19.85
197.21
76.63
200.02
76.43
202.68
76.54
205.18
76.54
207.54
76.46
105/80
180.52
73.84
184.24
74.69
187.74
75.36
191.03
75.88
194.17
76.29
209.77
76.28
211.88
76.02
213.87
75.69
215.76
75.29
191.97
52.05
194.64
51.32
197.14
50.49
199.49
49.56
201.71
48.56
115/80
175.65
53.70
179.38
53.69
182.86
53.50
186.11
53.15
189.14
52.66
203.80
47.48
205.78
46.34
207.65
45.14
209.43
43.89
186.10
41.39
188.72
40.44
191.17
39.39
193.49
38.26
195.67
37.05
115/78
170.12
44.31
173.77
44.02
177.17
43.57
180.35
42.97
183.32
42.24
197.73
35.78
199.68
34.45
201.53
33.06
203.28
31.63
Table PD-28. Size 031 cooling capacity with reheat installed, MBh cfm
1800
1900
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
3100 total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent
95/76
177.53
75.51
181.40
76.86
185.03
78.03
188.43
79.02
191.63
79.86
194.64
80.56
197.49
81.14
200.18
81.60
202.75
81.97
205.20
82.24
207.54
82.45
209.80
82.79
211.92
82.98
213.94
83.10
85/80
196.07
119.54
200.41
122.81
204.44
125.83
208.21
128.64
211.72
131.24
215.01
133.66
218.08
135.91
220.97
138.00
223.69
139.94
226.25
141.76
228.66
143.44
230.93
145.02
233.08
146.48
235.12
147.85
85/78
188.99
108.09
193.20
110.98
197.12
113.65
200.78
116.11
204.20
118.39
207.41
120.49
210.41
122.43
213.23
124.22
215.89
125.88
218.39
127.41
220.75
128.83
222.98
130.13
225.09
131.34
227.08
132.45
85/76
182.16
96.98
186.24
99.50
190.05
101.81
193.60
103.93
196.93
105.88
200.05
107.66
202.98
109.29
205.73
110.78
208.32
112.15
210.76
113.40
213.07
114.54
215.25
115.57
217.31
116.52
219.27
117.38
dry-bulb / wet-bulb temperature (°F)
95/78 95/80 105/76 105/78
184.02
86.16
187.99
87.84
190.84
97.29
194.91
99.28
174.42
55.83
178.41
56.41
179.76
65.23
183.84
66.11
191.69
89.32
195.15
90.61
198.38
91.72
201.42
92.68
204.28
93.50
206.97
94.19
209.51
94.76
211.91
95.23
198.70
101.05
202.22
102.61
205.52
104.01
208.60
105.25
211.50
106.33
214.21
107.27
216.77
108.08
219.18
108.78
182.14
56.83
185.64
57.10
188.92
57.22
192.00
57.21
194.90
57.09
197.64
56.86
200.22
56.53
202.65
56.11
187.66
66.80
191.22
67.33
194.57
67.70
197.71
67.94
200.66
68.05
203.44
68.04
206.06
67.93
208.53
67.72
214.18
95.60
216.35
95.88
218.40
96.08
220.36
96.21
221.46
109.36
223.61
109.85
225.65
110.25
227.60
110.57
204.96
55.61
207.14
55.04
209.21
54.41
211.18
53.71
210.87
67.42
213.08
67.04
215.17
66.60
217.17
66.09
48
105/80
185.68
75.55
189.67
76.45
193.44
77.18
197.03
77.76
200.45
78.45
203.64
78.93
206.63
79.26
209.45
79.47
212.11
79.58
214.61
79.57
216.98
79.47
219.22
79.29
221.34
79.03
223.35
78.71
115/76
172.31
37.93
176.19
37.55
179.82
37.02
183.23
36.34
186.43
35.54
189.44
34.62
192.27
33.60
194.93
32.48
197.45
31.28
199.83
30.01
202.08
28.66
204.22
27.25
206.24
25.79
208.16
24.28
115/78
177.36
47.08
181.34
46.98
185.05
46.72
188.52
46.30
191.78
45.74
194.84
45.05
197.71
44.25
200.42
43.35
202.97
42.36
205.39
41.29
207.67
40.14
209.83
38.92
211.87
37.65
213.82
36.32
115/80
182.67
56.49
186.72
56.67
190.50
56.67
194.04
56.50
197.35
56.19
200.46
55.73
203.38
55.15
206.12
54.47
208.71
53.68
211.15
52.81
213.46
51.85
215.64
50.83
217.72
49.73
219.68
48.58
MUA-PRC004-EN
Performance
Data unit capacity
Table PD-29. Size 031 reheat data, MBh dry-bulb / wet-bulb temperature (°F) cfm 55/48 55/50 55/52 65/56 65/58 65/60 75/66 75/68 75/70 85/76 85/78 85/80 95/76 95/78 95/80 105/76 105/78 105/80 115/76 115/78 115/80
1800 39.3
40.9
42.4
45.4
46.9
48.4
52.8
54.2
55.7
60.0
61.4
62.8
59.9
61.2
62.6
62.9
62.8
63.2
68.1
67.9
67.8
1900 39.7
41.2
42.8
45.8
47.3
48.8
53.1
54.6
56.1
60.3
61.8
63.2
60.3
61.6
63.0
63.9
63.7
63.8
69.2
69.0
68.8
2000 40.0
41.6
43.1
46.1
47.6
49.1
53.5
54.9
56.4
60.7
62.1
63.6
60.7
61.9
63.3
64.8
64.6
64.5
70.2
70.0
69.8
2100 40.3
41.9
43.4
46.4
47.9
49.4
53.8
55.2
56.7
61.0
62.4
63.9
61.2
62.3
63.6
65.6
65.4
65.2
71.1
70.9
70.7
2200 40.6
42.1
43.7
46.7
48.2
49.7
54.0
55.5
57.0
61.2
62.7
64.1
61.5
62.6
63.9
66.3
66.2
66.0
71.9
71.7
71.5
2300 40.8
42.4
43.9
46.9
48.4
49.9
54.3
55.8
57.2
61.5
62.9
64.4
61.9
62.9
64.2
67.0
66.9
66.7
72.7
72.5
72.3
2400 41.1
42.6
44.1
47.2
48.6
50.1
54.5
56.0
57.5
61.7
63.2
64.6
62.3
63.2
64.4
67.7
67.5
67.3
73.5
73.2
73.0
2500 41.3
42.8
44.3
47.4
48.8
50.3
54.7
56.2
57.7
61.9
63.4
64.8
62.7
63.5
64.7
68.3
68.1
67.9
74.2
73.9
73.7
2600 41.5
43.0
44.5
47.6
49.0
50.5
54.9
56.4
57.9
62.1
63.6
65.0
63.1
63.8
64.9
68.9
68.7
68.5
74.8
74.6
74.3
2700 41.7
43.1
44.7
47.8
49.2
50.7
55.0
56.5
58.0
62.3
63.8
65.2
63.5
64.1
65.1
69.4
69.2
69.0
75.4
75.2
74.9
2800 41.9
43.3
44.9
48.0
49.3
50.9
55.2
56.7
58.2
62.4
63.9
65.4
63.9
64.3
65.3
70.0
69.8
69.5
76.0
75.8
75.5
2900 42.1
43.5
45.0
48.2
49.5
51.0
55.3
56.8
58.3
62.6
64.1
65.5
64.4
64.6
65.5
70.4
70.2
70.0
76.5
76.3
76.0
3000 42.2
43.6
45.2
48.3
49.6
51.1
55.5
57.0
58.5
62.7
64.2
65.7
64.8
64.9
65.7
70.9
70.7
70.5
77.1
76.8
76.6
3100 42.4
43.7
45.3
48.5
49.8
51.3
55.6
57.1
58.6
62.9
64.3
65.8
65.1
65.1
65.9
71.3
71.1
70.9
77.5
77.3
77.0
Table PD-30. Size 031 condenser reheat max temperature rise,°F dry-bulb / wet-bulb temperature (°F) cfm 55/48 55/50 55/52 65/56 65/58 65/60 75/66 75/68 75/70 85/76 85/78 85/80 95/76 95/78 95/80 105/76 105/78 105/80 115/76 115/78 115/80
1800 20.1
20.9
21.7
23.2
24.0
24.7
26.9
27.7
28.4
30.4
31.1
31.8
30.4
31.0
31.7
1900 19.2
20.0
20.7
22.2
22.9
23.6
25.7
26.4
27.1
29.0
29.7
30.3
29.0
29.6
30.2
2000 18.4
19.1
19.9
21.2
21.9
22.6
24.5
25.2
25.8
27.7
28.3
28.9
27.7
28.2
28.8
2100 17.7
18.4
19.0
20.3
21.0
21.6
23.5
24.1
24.7
26.5
27.1
27.7
26.6
27.0
27.6
2200 17.0
17.6
18.3
19.5
20.1
20.7
22.5
23.1
23.7
25.4
26.0
26.5
25.5
25.9
26.4
2300 16.3
17.0
17.6
18.8
19.3
19.9
21.6
22.2
22.8
24.4
24.9
25.5
24.5
24.9
25.4
2400 15.8
16.3
16.9
18.1
18.6
19.2
20.8
21.3
21.9
23.4
23.9
24.5
23.6
24.0
24.4
31.9
30.7
29.6
28.5
27.5
26.6
25.7
31.8
30.6
29.4
28.4
27.4
26.5
25.6
32.0
30.6
29.3
28.3
27.3
26.3
25.5
34.6
33.3
32.0
30.9
29.8
28.8
27.9
34.5
33.1
31.9
30.8
29.7
28.7
27.8
34.3
33.0
31.8
30.6
29.6
28.6
27.6
2500 15.2
15.8
16.3
17.4
17.9
18.5
20.0
20.6
21.1
22.6
23.1
23.5
22.8
23.1
23.5
2600 14.7
15.2
15.8
16.8
17.3
17.8
19.3
19.8
20.3
21.7
22.2
22.7
22.1
22.3
22.6
2700 14.2
14.7
15.2
16.3
16.7
17.2
18.7
19.1
19.6
21.0
21.5
21.9
21.4
21.6
21.9
2800 13.8
14.2
14.7
15.7
16.2
16.7
18.0
18.5
19.0
20.3
20.7
21.2
20.8
20.9
21.1
2900 13.4
13.8
14.3
15.3
15.7
16.1
17.5
17.9
18.4
19.6
20.1
20.5
20.2
20.2
20.5
3000 13.0
13.4
13.8
14.8
15.2
15.6
16.9
17.3
17.8
19.0
19.4
19.8
19.6
19.6
19.8
3100 12.6
13.0
13.4
14.4
14.7
15.2
16.4
16.8
17.2
18.4
18.8
19.2
19.1
19.0
19.2
24.9
24.8
24.7
27.0
26.9
26.8
24.1
24.0
23.9
26.2
26.1
26.0
23.4
23.3
23.2
25.4
25.3
25.2
22.7
22.6
22.5
24.7
24.6
24.5
22.1
22.0
21.9
24.0
23.9
23.8
21.5
21.4
21.3
23.4
23.3
23.1
20.9
20.8
20.7
22.8
22.6
22.5
Table PD-31. Size 031 design supply air dew point, cfm dry-bulb
(°F)
85
95
105
115 wet-bulb
(°F)
76
78
80
76
78
80
76
78
80
76
78
80
46
1896
—
—
1863
—
—
1898
—
—
1996
—
—
48
2069
1868
—
2037
1827
—
2098
1813
—
2211
1893
— design supply air dew point (°F)
50 52 54 56
2267
2038
1840
2497
2231
2005
2767
2455
2194
3090
2717
2412
2239
1995
—
2332
2003
—
2466
2093
1801
2476
2188
1957
2611
2223
1926
2779
2330
1989
2762
2414
2143
2952
2483
2122
—
2615
2210
—
2969
2474
—
2683
2360
—
2798
2369
58
—
3031
2668
—
3010
2617
—
—
2663
—
—
2797
60
—
—
2972
—
—
2928
—
—
3024
—
—
—
—
—
—
—
—
—
62
—
—
—
—
—
—
MUA-PRC004-EN 49
Performance
Data unit capacity
Table PD-32. Size 040 cooling capacity without reheat installed, MBh cfm 85/76 85/78 85/80 95/76 dry-bulb / wet-bulb temperature (°F)
95/78 95/80 105/76 105/78
2200
2300
2400
2500
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000 total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent
242.98
131.97
245.67
133.47
248.22
134.85
250.64
136.13
252.95
137.33
255.16
138.43
257.26
139.46
259.26
140.41
219.44
117.88
223.41
120.35
227.15
122.65
230.68
124.80
234.01
126.79
237.16
128.65
240.15
130.37
261.18
141.29
263.01
142.10
264.77
142.85
266.45
143.54
252.28
147.83
255.03
149.60
257.63
151.26
260.11
152.82
262.47
154.28
264.71
155.64
266.86
156.92
268.90
158.12
228.12
131.46
232.20
134.29
236.05
136.94
239.67
139.42
243.09
141.74
246.33
143.90
249.38
145.93
270.85
159.24
272.71
160.29
274.50
161.28
276.21
162.20
261.88
164.10
264.68
166.16
267.34
168.09
269.87
169.92
272.27
171.64
274.56
173.26
276.73
174.79
278.81
176.23
237.12
145.48
241.32
148.67
245.27
151.66
248.98
154.47
252.48
157.11
255.79
159.58
258.92
161.91
280.79
177.60
282.69
178.88
284.50
180.10
286.23
181.25
234.08
96.96
236.57
97.29
238.93
97.54
241.17
97.70
243.32
97.84
245.38
97.94
247.35
97.99
249.23
97.97
212.23
91.23
215.93
92.48
219.40
93.56
222.68
94.49
225.77
95.29
228.70
95.96
231.46
96.51
251.04
97.90
252.78
97.77
254.45
97.61
256.05
97.40
243.02
112.34
245.55
112.96
247.96
113.47
250.25
113.89
252.43
114.22
254.50
114.47
256.48
114.64
258.36
114.75
220.60
104.45
224.39
106.03
227.97
107.45
231.33
108.70
234.51
109.81
237.50
110.78
240.34
111.62
260.16
114.79
261.88
114.77
263.52
114.69
265.10
114.56
252.23
128.13
254.82
129.01
257.28
129.79
259.62
130.47
261.84
131.06
263.94
131.55
265.95
131.97
267.87
132.32
229.27
118.07
233.17
120.00
236.84
121.74
240.29
123.32
243.53
124.73
246.60
125.99
249.49
127.12
269.70
132.59
271.45
132.80
273.11
132.94
274.70
133.04
227.39
64.73
230.02
64.37
232.53
63.94
234.91
63.44
237.18
62.86
239.36
62.23
241.44
61.53
243.42
60.79
204.86
65.34
208.50
65.65
212.00
65.85
215.42
66.01
218.65
65.25
221.72
65.17
224.62
65.00
245.33
60.00
247.16
59.17
248.91
58.29
250.59
57.38
234.30
78.56
236.99
78.42
239.54
77.43
241.95
77.13
244.26
76.76
246.46
76.32
248.56
75.82
250.57
75.26
212.50
77.44
216.09
77.95
219.49
78.32
222.72
78.55
225.79
78.68
228.73
78.71
231.56
78.67
252.49
74.65
254.33
73.99
256.10
73.29
257.79
72.55
242.26
92.65
244.75
92.56
247.14
92.39
249.43
92.15
251.63
91.86
253.77
91.52
255.85
91.15
257.89
90.76
105/80
220.74
90.34
224.35
91.01
227.75
91.56
230.97
92.02
234.01
92.35
236.90
92.55
239.65
92.65
259.86
89.57
261.72
89.09
263.50
88.56
265.20
87.99
229.32
48.27
231.88
47.22
234.33
46.10
236.66
44.91
238.87
43.66
240.99
42.35
243.01
40.99
244.95
39.58
115/78
206.97
52.89
210.72
52.59
214.27
52.15
217.61
51.59
220.78
50.91
223.77
50.12
226.62
49.24
246.80
38.13
248.57
36.64
250.27
35.12
251.90
33.57
222.65
35.55
225.18
34.29
227.60
32.96
229.89
31.57
232.09
30.12
234.18
28.62
236.18
27.08
238.10
25.49
115/76
200.66
41.86
204.34
41.29
207.82
40.60
211.11
39.78
214.23
38.86
217.18
37.85
219.99
36.74
239.93
23.86
241.76
22.80
243.54
21.89
245.28
20.98
236.21
61.27
238.81
60.43
241.28
59.51
243.63
58.51
245.87
57.45
248.01
56.33
250.06
55.16
252.01
53.93
115/80
213.53
64.21
217.34
64.18
220.95
64.00
224.35
63.68
227.56
63.24
230.60
62.68
233.48
62.02
253.87
52.66
255.66
51.34
257.37
49.99
259.02
48.61
50 MUA-PRC004-EN
Performance
Data unit capacity
Table PD-33. Size 040 cooling capacity with reheat installed, MBh cfm 85/76 85/78 85/80 95/76 dry-bulb / wet-bulb temperature (°F)
95/78 95/80 105/76 105/78
2200
2300
2400
2500
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000 total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent
246.80
133.36
249.58
134.87
252.22
136.28
254.72
137.59
257.11
138.80
259.38
139.91
261.55
140.95
263.62
141.90
222.46
118.93
226.56
121.47
230.43
123.83
234.08
126.02
237.53
128.06
240.79
129.96
243.88
131.72
265.60
142.78
267.49
143.59
269.30
144.33
271.03
145.02
255.57
149.15
258.41
150.96
261.10
152.66
263.66
154.24
266.09
155.73
268.41
157.11
270.62
158.41
272.73
159.62
230.61
132.42
234.83
135.31
238.80
138.02
242.55
140.56
246.08
142.93
249.42
145.14
252.58
147.21
274.74
160.75
276.66
161.81
278.50
162.80
280.26
163.73
264.57
165.31
267.46
167.41
270.21
169.39
272.82
171.26
275.30
173.01
277.65
174.66
279.90
176.22
282.04
177.69
239.01
146.28
243.34
149.54
247.42
152.60
251.25
155.47
254.87
158.17
258.28
160.70
261.51
163.08
284.09
179.07
286.04
180.38
287.91
181.61
289.70
182.78
239.91
98.90
242.58
99.34
245.12
99.69
247.55
99.95
249.87
100.12
252.10
100.23
254.23
100.26
256.27
100.24
216.71
92.44
220.61
93.80
224.28
94.99
227.76
96.03
231.04
96.94
234.15
97.71
237.10
98.36
258.24
100.16
260.14
100.02
261.97
99.84
263.73
99.62
248.17
113.93
250.86
114.61
253.42
115.20
255.85
115.68
258.17
116.08
260.38
116.39
262.49
116.62
264.51
116.79
224.59
105.57
228.58
107.23
232.33
108.71
235.86
110.02
239.20
111.17
242.35
112.21
245.34
113.13
266.44
116.89
268.30
116.93
270.08
116.91
271.79
116.84
256.82
129.54
259.54
130.45
262.12
131.25
264.57
131.95
266.90
132.55
269.13
133.09
271.25
133.54
273.27
133.92
232.71
119.09
236.81
121.09
240.66
122.91
244.28
124.54
247.69
126.01
250.91
127.33
253.94
128.50
275.21
134.23
277.05
134.47
278.82
134.65
280.52
134.77
236.16
68.29
239.00
68.05
241.70
67.73
244.27
67.34
246.73
66.87
249.08
66.33
251.32
65.73
253.47
65.08
211.69
67.18
215.78
67.60
219.64
67.95
223.30
68.24
226.77
68.42
230.06
68.48
233.19
68.43
255.53
64.37
257.50
63.62
259.40
62.82
261.21
61.98
242.78
81.34
245.64
81.32
248.37
81.21
250.96
81.02
253.44
80.75
255.80
80.40
258.07
80.00
260.23
79.53
218.58
79.36
222.51
79.95
226.25
80.40
229.82
80.72
233.26
80.93
236.59
81.06
239.77
81.27
262.30
79.00
264.29
78.42
266.19
77.79
268.02
77.12
233.47
40.04
236.27
38.93
238.94
37.75
241.49
36.50
243.93
35.19
246.26
33.82
248.48
32.40
250.61
30.93
115/76
209.29
45.08
213.32
44.71
217.14
44.21
220.75
43.58
224.18
42.84
227.43
42.00
230.52
41.06
252.66
29.41
254.61
27.86
256.49
26.27
258.29
24.64
249.74
95.09
252.53
95.06
255.23
94.96
257.86
94.81
260.37
94.89
262.75
94.74
265.02
94.51
267.20
94.22
105/80
226.08
92.13
230.02
92.99
233.75
93.68
237.27
94.21
240.62
94.61
243.80
94.88
246.83
95.04
269.28
93.88
271.28
93.47
273.19
93.01
275.02
92.51
239.76
52.76
242.59
51.86
245.28
50.89
247.85
49.83
250.31
48.71
252.65
47.53
254.89
46.30
257.04
45.00
115/78
215.28
56.13
219.37
56.02
223.24
55.78
226.90
55.40
230.37
54.90
233.66
54.29
236.79
53.57
259.09
43.67
261.06
42.28
262.94
40.86
264.76
39.41
246.27
65.74
249.12
65.05
251.84
64.28
254.43
63.42
256.90
62.49
259.25
61.49
261.51
60.44
263.66
59.32
115/80
221.52
67.45
225.66
67.61
229.58
67.62
233.28
67.49
236.79
67.22
240.12
66.84
243.27
66.34
265.72
58.16
267.70
56.95
269.60
55.69
271.42
54.40
MUA-PRC004-EN 51
Performance
Data unit capacity cfm
2200
2300
2400
2500
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
Table PD-34. Size 040 reheat data, MBh dry-bulb / wet-bulb temperature (°F)
55/48 55/50 55/52 65/56 65/58 65/60 75/66 75/68 75/70 85/76 85/78 85/80 95/76 95/78 95/80 105/76 105/78 105/80 115/76 115/78 115/80
58.8
60.8
62.7
66.7
68.8
71.0
77.4
79.7
82.0
88.5
90.7
92.9
88.2
90.5
92.7
90.2
91.2
92.8
97.6
97.5
59.3
61.2
63.2
67.2
69.3
71.5
78.0
80.2
82.5
89.0
91.3
93.5
88.8
91.0
93.2
91.4
92.0
93.5
98.9
98.8
97.4
98.7
59.7
61.7
63.7
67.7
69.8
72.0
78.5
80.7
83.0
89.5
91.8
94.0
89.3
91.5
93.7
92.6
92.8
94.1
100.2
100.1
100.0
60.1
62.1
64.1
68.1
70.2
72.4
78.9
81.2
83.5
90.0
92.3
94.5
89.9
92.0
94.2
93.6
93.7
94.8
101.4
101.3
101.2
60.5
62.4
64.4
68.5
70.6
72.8
79.3
81.6
83.9
90.4
92.7
94.9
90.3
92.4
94.6
94.7
94.5
95.4
102.6
102.4
102.3
60.8
62.8
64.8
68.9
71.0
73.2
79.7
82.0
84.3
90.8
93.1
95.3
90.8
92.8
95.0
95.6
95.5
96.1
103.6
103.5
103.4
61.1
63.1
65.1
69.2
71.4
73.6
80.1
82.4
84.6
91.2
93.5
95.7
91.2
93.2
95.4
96.6
96.4
96.7
104.7
104.5
104.4
61.4
63.4
65.4
69.5
71.7
73.9
80.4
82.7
85.0
91.6
93.8
96.1
91.7
93.6
95.8
97.4
97.3
97.4
105.6
105.5
105.3
61.7
63.7
65.7
69.8
72.0
74.2
80.8
83.0
85.3
91.9
94.2
96.4
92.1
94.0
96.1
98.3
98.1
98.0
106.6
106.4
106.2
61.9
64.0
66.0
70.1
72.3
74.5
81.1
83.3
85.6
92.2
94.5
96.7
92.5
94.3
96.4
99.1
98.9
98.7
107.5
107.3
107.1
62.2
64.2
66.3
70.4
72.6
74.8
81.3
83.6
85.9
92.5
94.8
97.0
92.9
94.7
96.7
99.8
99.7
99.5
108.3
108.1
107.9
62.4
64.4
66.5
70.6
72.8
75.0
81.6
83.9
86.2
92.8
95.0
97.3
93.3
95.0
97.0
100.5
100.4
100.2
109.1
108.9
108.7
62.6
64.7
66.7
70.9
73.1
75.3
81.9
84.1
86.4
93.0
95.3
97.6
93.6
95.3
97.3
101.2
101.1
100.9
109.9
109.7
109.5
62.9
64.9
67.0
71.1
73.3
75.5
82.1
84.4
86.7
93.3
95.6
97.8
94.0
95.6
97.5
101.9
101.7
101.5
110.6
110.4
110.2
63.1
65.1
67.2
71.3
73.5
75.7
82.3
84.6
86.9
93.5
95.8
98.0
94.4
95.9
97.8
102.5
102.3
102.2
111.3
111.1
110.9
63.3
65.3
67.4
71.6
73.7
75.9
82.5
84.8
87.1
93.7
96.0
98.3
94.8
96.1
98.0
103.1
102.9
102.8
112.0
111.8
111.6
63.5
65.5
67.5
71.8
73.9
76.1
82.7
85.0
87.3
93.9
96.2
98.5
95.1
96.4
98.3
103.7
103.5
103.3
112.7
112.4
112.2
63.6
65.6
67.7
72.0
74.1
76.3
82.9
85.2
87.5
94.1
96.4
98.7
95.5
96.7
98.5
104.3
104.1
103.9
113.3
113.1
112.8
63.8
65.8
67.9
72.2
74.3
76.5
83.1
85.4
87.7
94.3
96.6
98.9
95.9
97.0
98.7
104.8
104.6
104.4
113.9
113.7
113.4
Table PD-35. Size 040 condenser reheat max temperature rise, °F dry-bulb / wet-bulbtemperature (°F) cfm 55/48 55/50 55/52 65/56 65/58 65/60 75/66 75/68 75/70 85/76 85/78 85/80 95/76 95/78 95/80 105/76 105/78 105/80 115/76 115/78 115/80
2200 24.7
25.5
26.3
27.9
28.8 29.7
32.3
33.2
34.2
36.8
37.6 38.5
36.7
37.5
38.4
37.5
37.8
38.4
2300 23.8
24.5
25.3
26.9
27.7 28.6
31.1
32.0
32.9
35.4
36.2 37.0
35.3
36.1
36.9
36.3
36.5
37.0
2400 22.9
23.7
24.4
26.0
26.8 27.6
30.0
30.8
31.7
34.1
34.9 35.7
34.0
34.8
35.6
35.2
35.3
35.7
2500 22.2
22.9
23.6
25.1
25.8 26.6
29.0
29.8
30.6
32.9
33.6 34.4
32.8
33.5
34.3
34.2
34.1
34.5
2600 21.4
22.1
22.8
24.2
25.0 25.7
28.0
28.8
29.5
31.7
32.5 33.2
31.7
32.4
33.1
33.2
33.1
33.4
40.5
39.3
38.1
37.0
36.0
40.4
39.2
38.0
36.9
35.9
40.4
39.1
37.9
36.8
35.8
2700 20.7
21.4
22.1
23.5
24.2 24.9
27.1
27.8
28.6
30.7
31.4 32.1
30.7
31.3
32.0
32.3
32.2
32.3
2800 20.1
20.8
21.4
22.7
23.4 24.1
26.2
26.9
27.7
29.7
30.4 31.1
29.7
30.3
31.0
31.4
31.3
31.4
2900 19.5
20.1
20.8
22.0
22.7 23.4
25.4
26.1
26.8
28.8
29.4 30.1
28.8
29.4
30.0
30.6
30.5
30.5
3000 18.9
19.5
20.2
21.4
22.1 22.7
24.7
25.3
26.0
27.9
28.5 29.2
28.0
28.5
29.1
29.8
29.7
29.7
3100 18.4
19.0
19.6
20.8
21.4 22.1
23.9
24.6
25.2
27.1
27.7 28.3
27.2
27.7
28.2
29.1
29.0
28.9
3200 17.9
18.5
19.1
20.2
20.8 21.4
23.3
23.9
24.5
26.3
26.9 27.5
26.4
26.9
27.4
28.4
28.3
28.2
3300 17.4
18.0
18.5
19.7
20.3 20.9
22.6
23.2
23.9
25.6
26.2 26.7
25.7
26.1
26.7
27.7
27.6
27.5
3400 17.0
17.5
18.1
19.2
19.7 20.3
22.0
22.6
23.2
24.9
25.5 26.0
25.0
25.4
25.9
27.1
27.0
26.9
3500 16.5
17.1
17.6
18.7
19.2 19.8
21.5
22.0
22.6
24.2
24.8 25.3
24.4
24.8
25.2
26.5
26.4
26.3
3600 16.1
16.6
17.2
18.2
18.7 19.3
20.9
21.5
22.0
23.6
24.1 24.7
23.8
24.2
24.6
25.9
25.8
25.7
3700 15.7
16.2
16.7
17.8
18.3 18.8
20.4
20.9
21.5
23.0
23.5 24.1
23.3
23.6
24.0
25.3
25.2
25.1
3800 15.4
15.8
16.3
17.3
17.8 18.4
19.9
20.4
21.0
22.5
23.0 23.5
22.7
23.0
23.4
24.8
24.7
24.6
3900 15.0
15.5
16.0
16.9
17.4 17.9
19.4
19.9
20.5
21.9
22.4 22.9
22.2
22.5
22.9
24.3
24.2
24.1
4000 14.7
15.1
15.6
16.6
17.0 17.5
19.0
19.5
20.0
21.4
21.9 22.4
21.8
22.0
22.3
23.8
23.7
23.6
35.0
34.1
33.2
32.4
31.6
30.8
30.1
29.4
28.8
28.1
27.5
27.0
26.4
25.9
34.9
34.0
33.1
32.3
31.5
30.7
30.0
29.3
28.7
28.0
27.4
26.9
26.3
25.8
34.8
33.9
33.0
32.2
31.4
30.6
29.9
29.2
28.5
27.9
27.3
26.7
26.2
25.7
Table PD-36. SIze 040 design supply air dew point, cfm drybulb
(°F)
85
95
105
115
76
78
80
76
78
80 wetbulb
(°F)
76
78
80
76
78
80
2271
—
—
2387
—
—
46
2329
—
—
2280
—
—
2509
2200
—
2648
2260
—
48
2539
2291
—
2491
2238
—
2792
2410
—
2958
2503
—
50
2780
2497
2252
2734
2441
—
3127
2658
2343
3334
2789
2375 design supply air dew point (°F)
52 54 56
3058
2731
2452
3018
2673
2395
3385
3002
2680
3358
2945
2620
3776
3319
2944
3772
3268
2881
3535
2969
2573
3804
3133
2641
—
3345
2845
—
3556
2958
—
3812
3174
—
—
3346
58
—
3698
3252
—
3658
3188
60
—
—
3620
—
—
3560
—
—
3609
—
—
3833
—
—
—
—
—
—
62
—
—
—
—
—
—
52 MUA-PRC004-EN
Performance
Data unit capacity total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent
314.81
170.17
317.15
171.42
319.39
172.60
321.56
173.72
323.65
174.78
325.67
175.78
327.61
176.72
329.49
177.62
331.31
178.46
333.07
179.26
334.77
180.01
292.38
157.29
295.62
159.22
298.72
161.06
301.69
162.79
304.55
164.44
307.24
165.98
309.87
167.45
312.39
168.85
85/76
278.02
148.46
281.82
150.83
285.49
153.09
289.01
155.25
Table PD-37. Size 051 cooling capacity without reheat installed, MBh cfm
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
5100
339.28
212.46
341.71
214.22
344.05
215.91
346.29
217.52
348.46
219.06
350.55
220.54
352.56
221.95
354.51
223.31
356.39
224.61
358.20
225.85
359.95
227.04
326.87
191.05
329.26
192.56
331.55
194.00
333.76
195.37
335.89
196.67
337.95
197.91
339.93
199.09
341.85
200.22
343.69
201.29
345.48
202.32
347.18
203.27
303.93
175.90
307.26
178.15
310.39
180.27
313.43
182.29
316.34
184.22
319.13
186.06
321.82
187.81
324.39
189.47
dry-bulb / wet-bulb temperature (°F)
85/78 85/80 95/76 95/78
289.08
165.70
300.62
183.52
268.58
114.49
279.28
131.30
293.05
168.44
296.84
171.05
300.46
173.54
304.71
186.62
308.61
189.57
312.29
192.37
272.15
115.70
275.56
116.80
278.81
117.79
282.96
132.84
286.47
134.27
289.83
135.57
315.84
195.04
319.23
197.59
322.47
200.03
325.58
202.35
328.55
204.56
331.41
206.68
334.12
208.68
336.75
210.61
281.93
118.67
284.92
119.46
287.77
120.16
290.48
120.75
293.09
121.27
295.60
121.71
298.01
122.09
300.33
122.39
292.99
136.74
296.04
137.82
298.96
138.80
301.76
139.69
304.43
140.48
307.00
141.20
309.47
141.83
311.83
142.40
302.56
122.62
304.70
122.80
306.76
122.92
308.75
122.98
310.66
122.99
312.52
123.05
314.33
123.10
316.08
123.11
317.77
123.08
319.41
123.01
321.00
122.92
314.11
142.89
316.29
143.31
318.40
143.67
320.43
143.98
322.38
144.23
324.26
144.42
326.08
144.57
327.81
144.65
329.49
144.70
331.13
144.72
332.70
144.69
326.00
163.64
328.22
164.31
330.36
164.91
332.43
165.45
334.41
165.93
336.32
166.35
338.17
166.72
339.94
167.04
341.66
167.31
343.32
167.54
344.92
167.73
304.44
155.33
307.56
156.71
310.55
157.98
313.39
159.13
316.13
160.20
318.75
161.18
321.26
162.08
323.68
162.90
95/80
290.40
148.63
294.15
150.50
297.74
152.24
301.17
153.85
301.95
97.61
304.19
97.32
306.39
97.00
308.54
96.67
310.66
96.32
312.76
95.97
314.79
94.01
316.71
93.60
318.57
93.16
320.37
92.69
322.12
92.20
281.37
98.19
284.27
98.34
287.05
98.41
289.75
98.42
292.35
98.36
294.86
98.25
297.29
98.07
299.65
97.86
105/78
268.53
96.68
271.96
97.21
275.21
97.63
278.35
97.95
293.51
79.62
295.85
79.29
298.10
78.92
300.28
78.50
302.39
78.05
304.42
77.56
306.39
77.03
308.30
76.47
310.14
75.88
311.93
75.26
313.67
74.62
271.67
82.27
274.64
82.28
277.56
82.24
280.41
82.17
283.21
82.08
285.99
81.97
288.60
80.13
291.09
79.89
105/76
258.64
81.51
262.07
81.82
265.38
82.04
268.58
82.19
288.48
43.37
290.76
42.28
292.95
41.16
295.07
40.00
297.12
38.81
299.10
37.59
301.02
36.34
302.88
35.07
304.68
33.78
306.42
32.46
308.11
31.15
266.94
50.35
270.01
49.68
272.96
48.95
275.80
48.15
278.53
47.29
281.16
46.38
283.69
45.42
286.13
44.42
115/76
253.32
52.28
256.95
51.93
260.43
51.49
263.77
50.97
312.18
115.76
314.31
115.56
316.37
115.31
318.36
115.02
320.30
114.69
322.18
114.33
324.01
113.93
325.79
113.50
327.53
113.05
329.22
112.57
330.87
112.08
292.01
115.12
294.88
115.46
297.65
115.73
300.31
115.91
302.86
116.01
305.32
116.04
307.69
116.01
309.97
115.91
105/80
279.12
113.21
282.58
113.86
285.87
114.38
289.01
114.79
304.51
74.74
306.82
73.99
309.05
73.20
311.20
72.36
313.28
71.49
315.29
70.58
317.23
69.64
319.11
68.67
320.93
67.67
322.70
66.64
324.41
65.59
282.50
78.69
285.64
78.44
288.67
78.10
291.57
77.70
294.36
77.22
297.04
76.69
299.62
76.09
302.11
75.44
115/80
268.53
80.43
272.18
80.42
275.80
80.39
279.22
78.86
296.37
58.91
298.67
57.99
300.88
57.03
303.02
56.04
305.08
55.01
307.08
53.94
309.01
52.85
310.88
51.73
312.69
50.58
314.45
49.41
316.15
48.22
274.59
64.36
277.70
63.90
280.68
63.37
283.55
62.76
286.31
62.10
288.97
61.38
291.53
60.60
294.00
59.78
115/78
260.79
65.40
264.45
65.27
267.97
65.05
271.35
64.75
MUA-PRC004-EN 53
Performance
Data unit capacity
Table PD-38. Size 051 cooling capacity with reheat installed, MBh cfm
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
5100
85/76 total 281.82
latent 149.66
total 285.78
latent 152.10
total 289.58
latent 154.41
total 293.26
latent 156.62
total 296.78
latent 158.72
total 300.15
latent 160.70
total 303.38
latent 162.58
total 306.48
latent 164.36
total 309.46
latent 166.05
total 312.32
latent 167.64
total 315.02
latent 169.13
total 317.64
latent 170.55
total 320.17
latent 171.89
total 322.60
latent 173.16
total 324.94
latent 174.36
total 327.19
latent 175.49
total 329.37
latent 176.56
total 331.46
latent 177.57
total 333.49
latent 178.52
total 335.44
latent 179.42
total 337.33
latent 180.26
total 339.15
latent 181.06
total 340.91
latent 181.80
297.94
122.62
300.71
123.24
303.41
123.79
306.00
124.26
308.50
124.67
310.90
125.00
313.22
125.28
315.46
125.50
95/76
274.57
115.78
278.37
117.06
281.99
118.21
285.45
119.25
288.77
120.20
291.95
121.10
295.00
121.91
317.62
125.66
319.71
125.78
321.73
125.84
323.69
125.86
325.58
125.83
327.41
125.77
329.19
125.67
330.92
125.53
317.34
183.72
320.37
185.70
323.29
187.58
326.08
189.37
328.75
191.06
331.32
192.67
333.80
194.21
336.19
195.68
85/78
291.93
166.68
296.07
169.50
300.03
172.18
303.81
174.73
307.43
177.16
310.90
179.47
314.18
181.64
338.49
197.07
340.70
198.39
342.84
199.65
344.90
200.85
346.89
201.99
348.81
203.07
350.66
204.10
352.46
205.08
328.46
203.52
331.56
205.79
334.53
207.96
337.38
210.03
340.12
212.01
342.75
213.90
345.28
215.71
347.72
217.43
85/80
302.45
184.21
306.71
187.38
310.78
190.41
314.62
193.28
318.31
196.03
321.84
198.64
325.22
201.14
350.06
219.08
352.31
220.66
354.49
222.17
356.58
223.61
358.61
225.00
360.56
226.32
362.44
227.58
364.27
228.80
328.17
145.84
330.26
146.15
332.28
146.41
334.22
146.61
336.10
146.77
337.92
146.88
339.68
146.95
341.38
146.97
308.33
141.22
311.17
142.05
313.90
142.79
316.52
143.44
319.01
144.00
321.44
144.56
323.77
145.05
326.01
145.48
dry-bulb / wet-bulb temperature – °F
95/78 95/80 105/76 105/78
284.42
132.42
294.57
149.51
267.62
83.56
276.50
98.93
288.33
134.05
292.06
135.54
298.58
151.47
302.37
153.28
271.41
83.91
275.08
84.17
280.29
99.52
283.92
99.99
295.63
136.90
299.04
138.15
302.25
139.27
305.36
140.29
306.02
154.96
309.49
156.51
312.81
157.95
315.99
159.27
278.63
84.35
282.07
84.46
285.44
84.52
288.75
84.53
287.40
100.37
290.71
100.63
293.93
100.81
297.02
100.91
319.02
160.48
321.93
161.60
324.72
162.62
327.40
163.54
329.96
164.39
332.42
165.15
334.79
165.84
337.07
166.45
291.93
84.23
294.96
84.29
297.88
84.28
300.69
84.22
303.40
84.09
306.01
83.91
308.54
83.67
310.97
83.39
300.01
100.93
302.91
100.89
305.72
100.80
308.45
100.64
311.12
100.45
313.74
100.22
316.31
99.96
318.83
99.71
339.25
167.00
341.36
167.48
343.39
167.90
345.34
168.26
347.23
168.57
349.05
168.83
350.81
169.03
352.51
169.22
313.33
83.06
315.60
82.69
317.81
82.28
319.94
81.83
322.00
81.34
323.99
80.82
325.93
80.27
327.80
79.68
321.20
99.55
323.49
99.34
325.70
99.09
327.85
98.79
329.92
98.46
331.92
98.09
333.86
97.69
335.75
97.25
309.43
118.56
312.27
118.69
315.00
118.75
317.63
118.73
320.18
118.65
322.64
118.51
325.03
118.31
327.34
118.07
105/80
285.98
114.97
289.76
115.81
293.40
116.54
296.89
117.15
300.22
117.65
303.41
118.05
306.48
118.35
329.58
117.77
331.76
117.44
333.89
117.07
335.96
116.66
337.99
116.23
339.99
115.78
341.95
115.31
343.89
114.83
289.68
52.85
292.69
52.13
295.60
51.36
298.40
50.54
301.10
49.66
303.71
48.73
306.22
47.76
308.65
46.75
115/76
264.92
55.86
268.90
55.67
272.72
55.40
276.39
55.04
279.92
54.61
283.31
54.10
286.58
53.51
311.00
45.70
313.28
44.62
315.47
43.50
317.60
42.35
319.66
41.17
321.65
39.96
323.58
38.73
325.46
37.48
304.47
82.42
307.53
82.09
310.48
81.68
313.32
81.22
316.06
80.69
318.69
80.11
321.24
79.48
323.70
78.80
115/80
279.17
82.74
283.28
82.72
287.18
82.90
290.93
82.98
294.52
82.97
297.97
82.86
301.28
82.68
326.07
78.07
328.36
77.30
330.58
76.49
332.72
75.64
334.80
74.76
336.80
73.84
338.75
72.90
340.63
71.93
296.95
67.49
299.99
66.96
302.92
66.38
305.74
65.73
308.46
65.03
311.08
64.28
313.62
63.48
316.06
62.64
115/78
271.94
68.99
275.97
69.05
279.85
69.01
283.53
68.86
287.09
68.63
290.50
68.32
293.79
67.94
318.42
61.75
320.71
60.83
322.91
59.86
325.05
58.86
327.12
57.83
329.12
56.78
331.06
55.69
332.94
54.58
54 MUA-PRC004-EN
Performance
Data unit capacity
Table PD-39. Size 051 reheat data, MBh cfm dry-bulb / wet-bulb temperature (°F)
55/48 55/50 55/52 65/56 65/58 65/60 75/66 75/68 75/70 85/76 85/78 85/80 95/76 95/78 95/80 105/76 105/78 105/80 115/76115/78115/80
2900 82.8
85.5
88.4
94.1
97.2
100.3 109.7 113.0 116.4 126.4 129.9
133.4 126.0 129.5 133.0 127.3 129.8
132.8 137.0 137.0 137.0
3000 83.3
86.1
89.0
94.7
97.8
100.9 110.3 113.7 117.0 127.1 130.6
134.1 126.7 130.2 133.7 128.3 130.6
133.5 138.5 138.5 138.6
3100 83.8
86.6
89.5
95.3
98.4
101.5 110.9 114.3 117.7 127.7 131.2
134.7 127.3 130.8 134.3 129.3 131.4
134.3 140.0 140.0 140.0
3200 84.3
87.1
90.0
95.8
98.9
102.1 111.5 114.9 118.3 128.3 131.8
135.3 127.9 131.4 134.9 130.3 132.3
135.0 141.4 141.4 141.4
3300 84.8
87.6
90.5
96.3
99.4
102.6 112.1 115.4 118.8 128.9 132.4
135.9 128.5 132.0 135.5 131.4 133.0
135.6 142.7 142.7 142.7
3400 85.2
88.1
91.0
96.8
99.9
103.1 112.6 115.9 119.4 129.4 132.9
136.5 129.0 132.5 136.0 132.5 133.8
136.3 144.1 144.0 144.0
3500 85.6
88.5
91.5
97.3
100.4 103.6 113.1 116.4 119.9 129.9 133.5
137.0 129.5 133.0 136.5 133.6 134.6
137.0 145.3 145.3 145.2
3600 86.0
88.9
91.9
97.7
100.8 104.0 113.6 116.9 120.3 130.4 133.9
137.5 130.0 133.5 137.0 134.8 135.4
137.6 146.5 146.5 146.4
3700 86.4
89.3
92.3
98.1
101.3 104.4 114.0 117.4 120.8 130.9 134.4
137.9 130.5 134.0 137.5 135.9 136.2
138.2 147.7 147.6 147.6
3800 86.8
89.7
92.7
98.5
101.7 104.9 114.4 117.8 121.2 131.3 134.9
138.4 131.0 134.4 137.9 136.9 137.0
138.8 148.8 148.8 148.7
3900 87.1
90.0
93.0
98.9
102.0 105.2 114.8 118.2 121.6 131.7 135.3
138.8 131.5 134.8 138.3 137.8 137.8
139.4 149.9 149.8 149.8
4000 87.5
90.4
93.4
99.3
102.4 105.6 115.2 118.6 122.0 132.1 135.6
139.2 131.9 135.2 138.7 138.8 138.6
140.0 151.0 150.9 150.8
4100 87.8
90.7
93.7
99.6
102.8 106.0 115.6 119.0 122.4 132.5 136.0
139.6 132.4 135.6 139.1 139.7 139.5
140.6 152.0 151.9 151.8
4200 88.1
91.0
94.0
99.9
103.1 106.3 115.9 119.3 122.7 132.9 136.4
140.0 132.8 136.0 139.5 140.6 140.4
141.2 153.0 152.9 152.8
4300 88.4
91.3
94.3
100.2 103.4 106.6 116.2 119.6 123.1 133.2 136.7
140.3 133.2 136.3 139.8 141.4 141.3
141.8 153.9 153.8 153.7
4400 88.6
91.6
94.6
100.5 103.7 106.9 116.6 120.0 123.4 133.5 137.1
140.6 133.6 136.7 140.2 142.2 142.1
142.4 154.9 154.7 154.6
4500 88.9
91.9
94.9
100.8 104.0 107.2 116.9 120.3 123.7 133.9 137.4
141.0 134.0 137.0 140.5 143.0 142.9
143.0 155.7 155.6 155.5
4600 89.2
92.1
95.2
101.1 104.3 107.5 117.2 120.6 124.0 134.2 137.7
141.3 134.4 137.3 140.8 143.8 143.7
143.7 156.6 156.5 156.4
4700 89.4
92.4
95.4
101.4 104.6 107.8 117.4 120.9 124.3 134.5 138.0
141.6 134.8 137.7 141.1 144.5 144.4
144.3 157.4 157.3 157.2
4800 89.6
92.6
95.7
101.6 104.8 108.1 117.7 121.1 124.6 134.7 138.3
141.9 135.1 138.0 141.4 145.3 145.1
144.9 158.3 158.1 158.0
4900 89.9
92.8
95.9
101.9 105.1 108.3 118.0 121.4 124.8 135.0 138.6
142.1 135.5 138.3 141.6 146.0 145.8
145.6 159.0 158.9 158.8
5000 90.1
93.1
96.1
102.1 105.3 108.5 118.2 121.6 125.1 135.3 138.8
142.4 135.9 138.6 141.9 146.6 146.5
146.2 159.8 159.6 159.5
5100 90.3
93.3
96.3
102.3 105.5 108.8 118.4 121.9 125.3 135.5 139.1
142.7 136.2 138.9 142.1 147.3 147.1
147.0 160.5 160.4 160.2
Table PD-40. Size 051 condenser reheat max temperature rise, °F dry-bulb / wet-bulb temperature – °F cfm 55/48 55/50 55/52 65/56 65/58 65/60 75/66 75/68 75/70 85/76 85/78 85/80 95/76 95/78 95/80 105/76 105/78 105/80 115/76 115/78 115/80
2900 26.3
27.2
28.1
29.9
30.8
31.8
34.7
35.7
36.8
39.8
40.8
41.9
39.7
40.7
41.8
40.1
40.8
41.7
43.1
3000 25.6
26.5
27.3
29.1
30.0
30.9
33.7
34.7
35.7
38.7
39.7
40.7
38.5
39.6
40.6
39.0
39.7
40.5
42.2
3100 24.9
25.7
26.6
28.3
29.2
30.1
32.8
33.8
34.7
37.6
38.6
39.5
37.5
38.4
39.4
38.1
38.6
39.4
41.2
3200 24.3
25.1
25.9
27.5
28.4
29.3
32.0
32.9
33.8
36.6
37.5
38.5
36.5
37.4
38.3
37.2
37.6
38.4
40.3
3300 23.7
24.5
25.3
26.9
27.7
28.6
31.1
32.0
32.9
35.6
36.5
37.4
35.5
36.4
37.3
36.3
36.7
37.4
39.5
3400 23.1
23.9
24.6
26.2
27.0
27.8
30.3
31.2
32.1
34.7
35.6
36.5
34.6
35.5
36.4
35.5
35.8
36.4
38.7
3500 22.5
23.3
24.0
25.6
26.4
27.2
29.6
30.5
31.3
33.8
34.7
35.6
33.7
34.6
35.4
34.8
35.0
35.5
37.9
3600 22.0
22.7
23.5
25.0
25.7
26.5
28.9
29.7
30.6
33.0
33.8
34.7
32.9
33.7
34.6
34.1
34.2
34.7
37.1
3700 21.5
22.2
22.9
24.4
25.1
25.9
28.2
29.0
29.8
32.2
33.0
33.8
32.1
32.9
33.7
33.4
33.5
33.9
36.4
3800 21.0
21.7
22.4
23.8
24.6
25.3
27.6
28.4
29.2
31.5
32.3
33.1
31.4
32.2
32.9
32.8
32.8
33.2
35.7
3900 20.6
21.2
21.9
23.3
24.0
24.8
27.0
27.7
28.5
30.7
31.5
32.3
30.7
31.4
32.2
32.2
32.1
32.4
35.0
4000 20.1
20.8
21.5
22.8
23.5
24.2
26.4
27.1
27.9
30.1
30.8
31.6
30.0
30.7
31.5
31.6
31.5
31.8
34.4
4100 19.7
20.4
21.0
22.3
23.0
23.7
25.8
26.5
27.3
29.4
30.1
30.9
29.4
30.0
30.8
31.0
30.9
31.1
33.8
4200 19.3
19.9
20.6
21.9
22.5
23.2
25.3
26.0
26.7
28.8
29.5
30.2
28.8
29.4
30.1
30.5
30.4
30.5
33.2
4300 18.9
19.5
20.2
21.4
22.1
22.7
24.7
25.4
26.1
28.2
28.9
29.6
28.2
28.8
29.5
29.9
29.8
29.9
32.6
4400 18.5
19.1
19.8
21.0
21.6
22.3
24.2
24.9
25.6
27.6
28.3
29.0
27.6
28.2
28.9
29.4
29.3
29.3
32.0
4500 18.2
18.8
19.4
20.6
21.2
21.8
23.8
24.4
25.1
27.0
27.7
28.4
27.1
27.6
28.3
28.9
28.8
28.8
31.5
4600 17.8
18.4
19.0
20.2
20.8
21.4
23.3
23.9
24.6
26.5
27.2
27.8
26.5
27.1
27.7
28.4
28.3
28.3
31.0
4700 17.5
18.1
18.7
19.8
20.4
21.0
22.8
23.5
24.1
26.0
26.6
27.3
26.0
26.6
27.2
28.0
27.9
27.8
30.5
4800 17.2
17.7
18.3
19.4
20.0
20.6
22.4
23.0
23.7
25.5
26.1
26.7
25.6
26.1
26.6
27.5
27.4
27.3
30.0
4900 16.9
17.4
18.0
19.1
19.7
20.3
22.0
22.6
23.2
25.0
25.6
26.2
25.1
25.6
26.1
27.1
27.0
26.9
29.5
5000 16.6
17.1
17.7
18.7
19.3
19.9
21.6
22.2
22.8
24.6
25.2
25.8
24.7
25.1
25.7
26.6
26.6
26.5
29.1
5100 16.3
16.8
17.4
18.4
19.0
19.5
21.2
21.8
22.4
24.1
24.7
25.3
24.2
24.7
25.2
26.2
26.2
26.1
28.6
30.4
29.9
29.4
29.0
28.5
30.3
29.8
29.3
28.9
28.4
43.1
43.0
42.1
42.0
41.2
41.1
40.3
40.2
39.4
39.3
38.6
38.5
37.8
37.7
37.0
37.0
36.3
36.2
35.6
35.5
34.9
34.9
34.3
34.2
33.7
33.6
33.1
33.0
32.5
32.4
32.0
31.9
31.4
31.3
30.9
30.8
Table PD-41. Size 051 design supply air dew point, cfm drybulb
(°F)
85
95
105
115
76
78
80
76
78
80
76
78
80 wetbulb
(°F)
76
78
80
46
—
—
—
—
—
—
—
—
—
3000
—
—
48
3083
—
—
3054
—
—
3091
—
—
3380
—
—
50
3399
3023
—
3372
2989
—
3447
2975
—
3833
3117
— design supply air dew point – °F
52 54 56
3764
3332
2962
4190
3685
3262
4700
4098
3606
3748
3296
2923
3894
3298
—
4393
3525
2905
4195
3649
3220
4468
3681
3185
—
4020
3267
4741
4067
3563
—
4153
3541
—
4639
3713
58
—
4590
4006
—
4579
3966
—
4791
3969
—
—
4262
60
—
—
4482
—
—
4448
—
—
4497
—
—
4964
62
—
—
5058
—
—
5041
—
—
—
—
—
—
MUA-PRC004-EN 55
Performance
Data unit capacity total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent
391.97
210.58
393.78
211.42
395.54
212.22
397.24
212.98
398.91
213.70
400.52
214.38
402.10
215.03
403.63
215.65
405.12
216.24
406.57
216.79
375.37
202.19
377.67
203.42
379.91
204.60
382.07
205.72
384.17
206.79
386.21
207.81
388.19
208.78
390.11
209.70
85/76
337.10
179.72
340.68
181.95
344.13
184.08
347.50
186.13
350.75
188.09
353.88
189.96
356.90
191.75
359.81
193.46
362.63
195.09
365.35
196.64
367.98
198.13
370.52
199.55
372.98
200.90
406.39
237.36
408.24
238.43
410.02
239.46
411.76
240.44
413.45
241.38
415.09
242.29
416.69
243.16
418.25
243.99
419.76
244.79
421.23
245.55
389.47
227.01
391.83
228.50
394.11
229.93
396.32
231.30
398.46
232.62
400.53
233.88
402.55
235.09
404.50
236.25
85/78
350.17
200.65
353.90
203.23
357.49
205.71
360.94
208.08
364.27
210.35
367.48
212.53
370.58
214.62
373.57
216.62
376.45
218.54
379.23
220.38
381.92
222.14
384.52
223.83
387.04
225.45
421.23
264.74
423.10
266.04
424.92
267.29
426.68
268.50
428.39
269.66
430.06
270.78
431.68
271.86
433.26
272.91
434.79
273.92
436.28
274.89
404.02
252.45
406.41
254.19
408.74
255.88
410.98
257.49
413.16
259.05
415.27
260.56
417.32
262.00
419.31
263.40
85/80
363.81
222.26
367.64
225.18
371.32
227.99
374.86
230.68
378.27
233.26
381.56
235.75
384.73
238.13
387.78
240.43
390.73
242.63
393.57
244.75
396.32
246.79
398.97
248.75
401.54
250.63
Table PD-42. Size 066 cooling capacity without reheat installed, MBh cfm
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
5100
5200
5300
5400
5500
5600
5700
5800
5900
6000
6100
6200
6300
6400
6500
6600
373.65
387.56
168.93
193.57
375.80
389.75
169.32
194.20
377.88
391.86
169.65
194.78
379.89
393.91
169.94
195.30
381.84
395.90
170.17
195.77
383.73
397.82
170.36
196.19
385.56
399.68
170.50
196.57
387.34
401.49
170.61
196.90
389.06
403.24
170.67
197.18
390.74
404.94
170.70
197.43
392.38
406.59
170.77
197.64
393.98
408.20
170.84
197.81
395.54
409.75
170.87
197.94
397.05
411.27
170.88
198.05
398.53
412.74
170.87
198.11
399.97
414.17
170.83
198.15
401.37
415.56
170.76
198.16
402.74
416.91
170.68
198.14
dry-bulb / wet-bulb temperature (°F)
95/78 95/80 105/76 105/78
337.61
350.70
157.65
178.63
313.71
98.17
324.30
115.68
341.04
354.22
159.02
180.33
344.35
357.61
160.30
181.92
317.21
96.85
320.58
97.19
327.59
116.13
330.78
116.50
347.52
360.87
161.48
183.40
350.58
364.00
162.57
184.79
353.53
367.02
163.57
186.08
356.37
369.92
164.49
187.29
323.84
97.45
326.98
97.64
330.02
97.77
332.96
97.83
333.88
116.81
336.90
117.07
339.85
117.28
342.75
117.46
359.11
372.72
165.34
188.41
361.75
375.42
166.10
189.45
364.30
378.02
166.80
190.41
366.76
380.53
167.43
191.30
369.13
382.95
167.99
192.12
371.44
385.30
168.49
192.88
335.80
97.83
338.54
97.78
341.20
97.66
343.78
97.50
346.27
97.29
348.70
97.04
345.61
117.61
348.46
117.78
351.12
116.22
353.73
116.26
356.25
116.23
358.69
116.16
367.47
92.98
369.27
92.38
371.03
91.74
372.73
91.09
374.40
90.41
376.02
89.70
377.60
88.98
379.14
88.24
380.64
87.48
382.10
86.70
351.03
96.73
353.30
96.39
355.51
96.01
357.65
95.59
359.73
95.13
361.75
94.64
363.71
94.12
365.61
93.57
377.64
113.64
379.46
113.19
381.22
112.71
382.94
112.21
384.62
111.68
386.25
111.12
387.83
110.54
389.38
109.94
390.89
109.32
392.36
108.69
361.06
116.04
363.35
115.88
365.58
115.67
367.74
115.42
369.84
115.14
371.87
114.81
373.85
114.46
375.77
114.07
375.79
146.45
377.50
146.45
379.18
146.42
380.82
146.36
382.41
146.28
383.98
146.18
385.50
146.05
387.00
145.91
388.46
145.75
389.90
145.58
360.24
145.27
362.38
145.56
364.46
145.80
366.48
146.00
368.45
146.16
370.36
146.29
372.21
146.38
374.02
146.43
95/76
324.98
137.28
328.32
138.34
331.53
139.30
334.63
140.17
337.61
140.96
340.49
141.67
343.26
142.31
345.93
142.87
348.51
143.36
351.01
143.78
353.41
144.15
355.76
144.55
358.03
144.94
56
359.33
43.26
361.15
42.72
362.93
42.15
364.68
41.56
366.40
40.96
368.09
40.35
369.75
39.73
371.39
39.09
373.00
38.45
374.58
37.80
343.43
52.33
345.62
51.19
347.74
50.02
349.80
48.83
351.81
47.60
353.75
46.34
355.64
45.07
357.48
43.79
115/76
307.48
63.01
310.85
62.53
314.10
61.99
317.24
61.37
320.27
60.70
323.19
59.96
326.02
59.17
328.76
58.33
331.40
57.44
333.96
56.50
336.44
55.52
338.84
54.49
341.17
53.43
388.09
134.67
389.92
134.37
391.69
134.04
393.42
133.68
395.11
133.30
396.74
132.89
398.34
132.45
399.89
131.99
401.40
131.51
402.88
131.01
371.46
137.55
373.69
137.44
375.89
137.32
378.06
137.19
380.23
137.06
382.29
135.36
384.28
135.16
386.21
134.93
105/80
336.34
134.66
339.60
135.30
342.75
135.86
345.79
136.32
348.72
136.71
351.55
137.03
354.30
137.28
356.96
137.47
359.54
137.60
362.05
137.67
364.49
137.70
366.86
137.69
369.19
137.64
378.80
82.84
380.56
81.80
382.27
80.73
383.93
79.64
385.55
78.53
387.13
77.40
388.66
76.25
390.16
75.08
391.61
73.90
393.03
72.71
362.74
90.15
364.97
89.35
367.12
88.52
369.22
87.65
371.25
86.75
373.22
85.82
375.13
84.85
376.99
83.86
115/80
325.94
95.64
329.41
95.62
332.75
95.53
335.98
95.35
339.09
95.10
342.09
94.78
344.98
94.39
347.78
93.95
350.48
93.44
353.10
92.88
355.63
92.27
358.08
91.61
360.45
90.90
MUA-PRC004-EN
368.90
62.47
370.65
61.28
372.35
60.06
374.01
58.83
375.62
57.58
377.19
56.30
378.72
55.02
380.21
53.71
381.72
52.97
383.21
52.30
352.94
71.06
355.15
70.09
357.29
69.10
359.37
68.07
361.39
67.00
363.35
65.91
365.25
64.79
367.10
63.64
115/78
316.54
79.12
319.96
78.88
323.26
78.56
326.45
78.17
329.52
77.70
332.48
77.18
335.35
76.59
338.11
75.95
340.79
75.25
343.38
74.50
345.89
73.71
348.31
72.87
350.66
71.98
Performance
Data unit capacity
Table PD-43. Size 066 cooling cpacity with reheat installed, MBh cfm 85/76 85/78 85/80 95/76 dry-bulb / wet-bulb temperature (°F)
95/78 95/80 105/76 105/78
3600 total latent
343.28
181.96
355.54
202.82
368.32
224.32
333.64
139.62
345.54
159.91
357.84
180.84
325.90
100.12
335.63
118.67
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
5100
5200
5300
5400
5500
5600
5700
5800
5900
6000
6100
6200
6300
6400
6500
6600 total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent
407.21
216.43
408.88
217.10
410.50
217.74
412.07
218.34
413.61
218.91
415.10
219.44
392.01
209.54
394.11
210.57
396.15
211.54
398.13
212.46
400.05
213.34
401.92
214.18
403.73
214.97
405.50
215.72
372.53
199.26
375.25
200.77
377.89
202.21
380.43
203.59
382.90
204.90
385.29
206.15
387.60
207.34
389.83
208.47
346.99
184.24
350.57
186.42
354.02
188.51
357.39
190.52
360.64
192.43
363.77
194.26
366.79
196.01
369.71
197.67
421.03
244.35
422.72
245.25
424.37
246.12
425.97
246.95
427.53
247.74
429.05
248.50
405.55
235.50
407.70
236.78
409.78
238.01
411.79
239.18
413.75
240.30
415.65
241.38
417.49
242.41
419.29
243.40
385.67
223.04
388.45
224.84
391.14
226.57
393.75
228.22
396.26
229.80
398.70
231.32
401.06
232.77
403.34
234.17
359.41
205.47
363.13
208.01
366.71
210.45
370.17
212.78
373.49
215.01
376.70
217.15
379.80
219.20
382.78
221.16
435.16
272.78
436.88
273.91
438.55
275.01
440.17
276.06
441.76
277.08
443.30
278.06
419.43
262.00
421.61
263.53
423.73
265.00
425.78
266.42
427.77
267.79
429.70
269.11
431.57
270.38
433.39
271.60
399.16
247.38
402.01
249.46
404.75
251.47
407.41
253.40
409.97
255.25
412.45
257.04
414.86
258.75
417.18
260.41
372.29
227.32
376.11
230.19
379.78
232.95
383.32
235.61
386.73
238.15
390.00
240.60
393.17
242.95
396.22
245.20
395.14
149.36
396.84
149.21
398.51
149.04
400.14
148.85
401.75
148.64
403.34
148.42
380.07
149.59
382.12
149.68
384.12
149.73
386.06
149.74
387.96
149.73
389.82
149.68
391.63
149.60
393.40
149.49
361.37
147.23
363.96
147.71
366.47
148.13
368.91
148.50
371.27
148.81
373.56
149.07
375.79
149.29
377.96
149.46
337.16
140.79
340.57
141.88
343.86
142.88
347.04
143.80
350.10
144.63
353.06
145.38
355.92
146.07
358.69
146.68
407.08
174.60
408.70
174.57
410.29
174.51
411.83
174.43
413.34
174.31
414.82
174.18
392.37
173.59
394.39
173.85
396.36
174.08
398.27
174.26
400.14
174.40
401.94
174.50
403.70
174.57
405.41
174.60
373.69
169.57
376.30
170.28
378.82
170.92
381.26
171.51
383.63
172.03
385.92
172.50
388.13
172.91
390.28
173.27
349.16
161.35
352.65
162.68
356.00
163.91
359.22
165.04
362.33
166.08
365.32
167.04
368.20
167.93
371.00
168.78
420.09
201.00
421.70
201.14
423.26
201.24
424.78
201.32
426.26
201.36
427.70
201.38
405.44
198.51
407.47
198.96
409.43
199.38
411.34
199.75
413.19
200.08
414.99
200.37
416.74
200.62
418.43
200.82
386.63
193.06
389.28
193.98
391.83
194.82
394.29
195.59
396.67
196.30
398.98
196.94
401.20
197.52
403.36
198.04
361.56
182.60
365.13
184.25
368.56
185.80
371.86
187.24
375.04
188.58
378.10
189.83
381.04
190.99
383.89
192.07
391.12
96.48
392.87
95.84
394.57
95.17
396.22
94.48
397.84
93.78
399.41
93.05
375.33
100.64
377.50
100.23
379.61
99.78
381.66
99.31
383.66
98.80
385.60
98.26
387.49
97.69
389.33
97.10
355.39
102.43
358.16
102.37
360.85
102.26
363.44
102.10
365.97
101.89
368.41
101.64
370.79
101.35
373.09
101.02
329.64
100.67
333.26
101.13
336.75
101.52
340.12
101.84
343.38
102.08
346.53
102.26
349.59
102.38
352.54
102.43
400.82
117.76
402.57
117.26
404.27
116.74
405.93
116.20
407.55
115.63
409.13
115.04
384.94
120.67
387.13
120.43
389.25
120.14
391.32
119.83
393.32
119.47
395.27
119.09
397.17
118.68
399.02
118.23
364.86
121.02
367.65
121.16
370.35
121.24
372.98
121.26
375.52
121.24
377.98
121.16
380.37
121.04
382.69
120.88
339.22
119.14
342.71
119.54
346.10
119.86
349.42
120.12
352.66
120.34
355.87
120.52
358.99
120.57
361.97
120.83
MUA-PRC004-EN
386.56
44.95
388.31
44.38
390.04
43.79
391.74
43.19
393.41
42.58
395.05
41.95
370.93
54.54
373.08
53.39
375.16
52.20
377.19
51.00
379.17
49.76
381.09
48.51
382.96
47.23
384.77
45.93
351.25
62.49
353.98
61.64
356.63
60.74
359.20
59.80
361.69
58.82
364.10
57.80
366.44
56.75
368.72
55.66
115/76
322.18
67.63
325.87
67.32
329.43
66.94
332.87
66.49
336.19
65.97
339.41
65.39
342.51
64.74
345.52
64.04
348.43
63.29
410.77
139.38
412.53
139.02
414.23
138.64
415.90
138.23
417.52
137.80
419.10
137.35
394.84
141.06
397.04
140.98
399.17
140.85
401.24
140.69
403.25
140.49
405.21
140.26
407.12
140.00
408.97
139.70
374.87
141.24
377.56
141.27
380.19
141.26
382.76
141.20
385.30
141.12
387.81
141.02
390.25
141.10
392.58
141.10
105/80
346.72
138.02
350.28
138.71
353.72
139.30
357.04
139.80
360.24
140.22
363.35
140.56
366.36
140.83
369.28
141.03
372.11
141.16
404.99
86.24
406.72
85.18
408.41
84.10
410.05
83.00
411.65
81.89
413.21
80.76
389.27
93.76
391.44
92.93
393.54
92.06
395.58
91.16
397.57
90.23
399.50
89.27
401.38
88.28
403.21
87.27
369.36
98.96
372.13
98.48
374.82
97.94
377.42
97.36
379.93
96.72
382.38
96.04
384.74
95.32
387.04
94.56
115/80
339.71
100.36
343.49
100.51
347.13
100.58
350.65
100.56
354.04
100.47
357.32
100.30
360.48
100.06
363.54
99.76
366.50
99.39
395.64
65.27
397.37
64.08
399.06
62.86
400.70
61.63
402.30
60.38
403.86
59.11
379.97
73.99
382.12
72.99
384.22
71.97
386.26
70.92
388.24
69.84
390.17
68.73
392.04
67.60
393.87
66.45
360.16
80.55
362.91
79.88
365.58
79.17
368.16
78.41
370.67
77.60
373.10
76.76
375.46
75.87
377.74
74.95
115/78
330.78
83.80
334.52
83.72
338.12
83.57
341.60
83.34
344.96
83.03
348.21
82.66
351.35
82.22
354.38
81.72
357.32
81.16
57
Performance
Data unit capacity
Table PD-44. Size 066 reheat data, MBh dry-bulb / wet-bulb temperature – °F cfm 55/48 55/50 55/52 65/56 65/58 65/60 75/66 75/68 75/70 85/76 85/78 85/80 95/76 95/78 95/80 105/76 105/78 105/80 115/76 115/78 115/80
3600 88.1
91.0
94.1 100.1 103.3 106.5 116.3 119.7 123.2 133.5 137.1 140.8
133.1 136.7 140.3
137.1
138.0
140.5
149.0
149.0
148.9
3700 88.5
91.5
94.5 100.5 103.7 107.0 116.8 120.2 123.7 134.0 137.7 141.3
133.6 137.2 140.8
138.2
138.8
141.2
150.3
150.3
150.2
3800 88.9
91.9
94.9 100.9 104.2 107.4 117.2 120.7 124.2 134.5 138.1 141.8
134.1 137.6 141.3
139.3
139.6
141.8
151.6
151.5
151.4
3900 89.3
92.2
95.3 101.3 104.6 107.9 117.7 121.1 124.7 135.0 138.6 142.3
134.6 138.1 141.8
140.4
140.5
142.5
152.8
152.7
152.6
4000 89.6
92.6
95.7 101.7 105.0 108.3 118.1 121.6 125.1 135.4 139.1 142.7
135.1 138.5 142.2
141.5
141.4
143.1
154.0
153.9
153.8
4100 89.9
93.0
96.0 102.1 105.3 108.6 118.5 122.0 125.5 135.8 139.5 143.2
135.5 139.0 142.6
142.5
142.3
143.7
155.1
155.0
154.9
4200 90.3
93.3
96.4 102.5 105.7 109.0 118.9 122.4 125.9 136.2 139.9 143.6
136.0 139.4 143.0
143.5
143.3
144.4
156.3
156.1
156.0
4300 90.6
93.6
96.7 102.8 106.1 109.4 119.2 122.7 126.3 136.6 140.3 143.9
136.4 139.7 143.4
144.4
144.3
145.0
157.3
157.2
157.0
4400 90.9
93.9
97.0 103.1 106.4 109.7 119.6 123.1 126.6 137.0 140.6 144.3
136.8 140.1 143.8
145.3
145.2
145.6
158.4
158.2
158.1
4500 91.2
94.2
97.3 103.4 106.7 110.0 119.9 123.4 127.0 137.3 141.0 144.7
137.3 140.5 144.1
146.2
146.1
146.3
159.4
159.2
159.1
4600 91.4
94.5
97.6 103.7 107.0 110.3 120.2 123.7 127.3 137.6 141.3 145.0
137.7 140.8 144.5
147.1
146.9
147.0
160.3
160.2
160.0
4700 91.7
94.8
97.9 104.0 107.3 110.6 120.5 124.0 127.6 138.0 141.6 145.3
138.1 141.2 144.8
147.9
147.8
147.6
161.3
161.1
160.9
4800 92.0
95.0
98.2 104.3 107.6 110.9 120.8 124.3 127.9 138.3 141.9 145.7
138.5 141.5 145.1
148.7
148.6
148.3
162.2
162.0
161.9
4900 92.2
95.3
98.4 104.5 107.8 111.2 121.1 124.6 128.2 138.6 142.2 146.0
138.9 141.9 145.4
149.5
149.3
149.1
163.1
162.9
162.7
5000 92.4
95.5
98.6 104.8 108.1 111.4 121.4 124.9 128.4 138.8 142.5 146.2
139.2 142.2 145.7
150.3
150.1
149.9
164.0
163.8
163.6
5100 92.6
95.7
98.9 105.0 108.3 111.7 121.6 125.1 128.7 139.1 142.8 146.5
139.6 142.5 146.0
151.0
150.8
150.6
164.8
164.6
164.4
5200 92.9
96.0
99.1 105.3 108.6 111.9 121.9 125.4 129.0 139.4 143.1 146.8
140.0 142.8 146.2
151.7
151.5
151.4
165.6
165.4
165.2
5300 93.1
96.2
99.3 105.5 108.8 112.2 122.1 125.6 129.2 139.6 143.3 147.0
140.4 143.1 146.5
152.4
152.2
152.0
166.4
166.2
166.0
5400 93.3
96.4
99.5 105.7 109.0 112.4 122.3 125.9 129.4 139.9 143.6 147.3
140.7 143.4 146.7
153.1
152.9
152.7
167.2
167.0
166.8
5500 93.5
96.6
99.7 105.9 109.2 112.6 122.6 126.1 129.7 140.1 143.8 147.5
141.1 143.7 147.0
153.8
153.6
153.4
167.9
167.7
167.5
5600 93.7
96.8
99.9 106.2 109.4 112.8 122.8 126.3 129.9 140.3 144.0 147.8
141.5 144.0 147.2
154.4
154.2
154.0
168.7
168.4
168.2
5700 93.9
96.9 100.1 106.4 109.6 113.0 123.0 126.5 130.1 140.5 144.2 148.0
141.8 144.3 147.5
155.0
154.8
154.6
169.4
169.1
168.9
5800 94.1
97.1 100.3 106.6 109.8 113.2 123.2 126.7 130.3 140.7 144.5 148.2
142.2 144.5 147.7
155.7
155.4
155.2
170.1
169.8
169.6
5900 94.2
97.3 100.5 106.8 110.0 113.4 123.4 126.9 130.5 140.9 144.7 148.4
142.6 144.8 147.9
156.2
156.0
155.8
170.7
170.5
170.3
6000 94.4
97.5 100.6 107.0 110.2 113.6 123.5 127.1 130.7 141.1 144.9 148.6
143.0 145.1 148.1
156.8
156.6
156.4
171.4
171.1
170.9
6100 94.6
97.6 100.8 107.1 110.3 113.7 123.7 127.3 130.9 141.3 145.0 148.8
143.3 145.3 148.4
157.4
157.1
156.9
172.0
171.8
171.5
6200 94.8
97.8 101.0 107.3 110.5 113.9 123.9 127.4 131.0 141.5 145.2 149.0
143.7 145.6 148.6
157.9
157.7
157.5
172.6
172.4
172.2
6300 94.9
97.9 101.1 107.5 110.7 114.1 124.1 127.6 131.2 141.7 145.4 149.2
144.1 145.8 148.8
158.5
158.2
158.0
173.2
173.0
172.8
6400 95.1
98.1 101.3 107.7 110.8 114.2 124.2 127.8 131.4 141.8 145.6 149.3
144.5 146.1 149.0
159.0
158.7
158.5
173.8
173.6
173.3
6500 95.2
98.2 101.4 107.9 111.0 114.4 124.4 127.9 131.5 142.0 145.7 149.5
144.9 146.4 149.2
159.5
159.2
159.0
174.3
174.2
173.9
6600 95.4
98.3 101.5 108.0 111.1 114.5 124.5 128.1 131.7 142.2 145.9 149.7
145.3 146.6 149.4
160.0
159.7
159.5
174.9
174.7
174.5
Table PD-45. Size 066 condenser reheat max temperature rise, °F dry-bulb / wet-bulb temperature – °F cfm 55/48 55/50 55/52 65/56 65/58 65/60 75/66 75/68 75/70 85/76 85/78 85/80 95/76 95/78 95/80 105/76 105/78 105/80 115/76 115/78 115/80
3600 22.5
23.3
24.1
25.6
26.4
27.2
29.6
30.5
31.3
33.9
34.7
35.6
33.7
34.6
35.5
34.7
3700 22.0
22.8
23.6
25.0
25.8
26.6
28.9
29.8
30.6
33.1
33.9
34.8
32.9
33.8
34.6
34.1
3800 21.6
22.3
23.0
24.4
25.2
26.0
28.3
29.1
29.9
32.3
33.1
34.0
32.2
33.0
33.8
33.5
3900 21.1
21.8
22.5
23.9
24.6
25.4
27.7
28.5
29.3
31.6
32.4
33.2
31.5
32.2
33.1
32.8
4000 20.6
21.3
22.0
23.4
24.1
24.9
27.1
27.8
28.6
30.9
31.7
32.4
30.8
31.5
32.3
32.3
4100 20.2
20.9
21.6
22.9
23.6
24.3
26.5
27.2
28.0
30.2
31.0
31.7
30.1
30.8
31.6
31.7
4200 19.8
20.5
21.1
22.4
23.1
23.8
25.9
26.7
27.4
29.6
30.3
31.1
29.5
30.2
30.9
31.1
4300 19.4
20.0
20.7
22.0
22.7
23.4
25.4
26.1
26.8
28.9
29.7
30.4
28.9
29.6
30.3
30.6
4400 19.0
19.6
20.3
21.5
22.2
22.9
24.9
25.6
26.3
28.3
29.1
29.8
28.3
29.0
29.7
30.1
4500 18.7
19.3
19.9
21.1
21.8
22.4
24.4
25.1
25.8
27.8
28.5
29.2
27.8
28.4
29.1
29.6
34.9
32.8
32.2
31.6
31.0
30.5
30.0
29.5
35.5
34.2
34.7
37.1
37.0
33.5
33.9
36.4
36.3
33.2
32.5
31.9
31.2
30.6
30.0
29.5
37.8
35.8
35.1
34.5
33.9
33.4
32.8
32.3
37.7
35.7
35.0
34.4
33.8
33.3
32.7
32.2
37.6
36.9
36.2
35.6
35.0
34.3
33.8
33.2
32.6
32.1
4600 18.3
18.9
19.5
20.7
21.4
22.0
23.9
24.6
25.3
27.2
27.9
28.6
27.2
27.8
28.5
29.1
4700 18.0
18.6
19.2
20.3
21.0
21.6
23.5
24.1
24.8
26.7
27.4
28.1
26.7
27.3
27.9
28.7
4800 17.6
18.2
18.8
20.0
20.6
21.2
23.0
23.7
24.3
26.2
26.9
27.5
26.2
26.8
27.4
28.2
4900 17.3
17.9
18.5
19.6
20.2
20.8
22.6
23.3
23.9
25.7
26.4
27.0
25.8
26.3
26.9
27.8
5000 17.0
17.6
18.1
19.3
19.8
20.4
22.2
22.8
23.5
25.3
25.9
26.5
25.3
25.8
26.4
27.4
5100 16.7
17.3
17.8
18.9
19.5
20.1
21.8
22.4
23.0
24.8
25.4
26.0
24.9
25.4
25.9
26.9
5200 16.4
17.0
17.5
18.6
19.2
19.7
21.4
22.0
22.6
24.4
25.0
25.6
24.5
24.9
25.5
26.5
5300 16.2
16.7
17.2
18.3
18.8
19.4
21.1
21.7
22.2
23.9
24.5
25.1
24.1
24.5
25.0
26.2
5400 15.9
16.4
16.9
18.0
18.5
19.1
20.7
21.3
21.9
23.5
24.1
24.7
23.7
24.1
24.6
25.8
5500 15.6
16.1
16.7
17.7
18.2
18.8
20.4
20.9
21.5
23.1
23.7
24.3
23.3
23.7
24.2
25.4
5600 15.4
15.9
16.4
17.4
17.9
18.5
20.0
20.6
21.2
22.8
23.3
23.9
23.0
23.3
23.8
25.1
5700 15.2
15.6
16.1
17.1
17.6
18.2
19.7
20.3
20.8
22.4
22.9
23.5
22.6
22.9
23.4
24.7
5800 14.9
15.4
15.9
16.9
17.4
17.9
19.4
19.9
20.5
22.0
22.6
23.1
22.3
22.6
23.0
24.4
5900 14.7
15.2
15.6
16.6
17.1
17.6
19.1
19.6
20.2
21.7
22.2
22.8
21.9
22.2
22.7
24.1
6000 14.5
14.9
15.4
16.4
16.8
17.3
18.8
19.3
19.9
21.4
21.9
22.4
21.6
21.9
22.3
23.7
6100 14.3
14.7
15.2
16.1
16.6
17.1
18.5
19.0
19.6
21.0
21.5
22.1
21.3
21.6
22.0
23.4
6200 14.1
14.5
15.0
15.9
16.3
16.8
18.3
18.8
19.3
20.7
21.2
21.7
21.0
21.3
21.7
23.1
6300 13.9
14.3
14.7
15.7
16.1
16.6
18.0
18.5
19.0
20.4
20.9
21.4
20.8
21.0
21.3
22.8
6400 13.7
14.1
14.5
15.4
15.9
16.3
17.7
18.2
18.7
20.1
20.6
21.1
20.5
20.7
21.0
22.6
6500 13.5
13.9
14.3
15.2
15.6
16.1
17.5
18.0
18.4
19.8
20.3
20.8
20.2
20.4
20.7
22.3
6600 13.3
13.7
14.1
15.0
15.4
15.9
17.2
17.7
18.2
19.5
20.0
20.5
20.0
20.1
20.4
22.0
29.0
28.6
28.1
27.7
27.3
29.0
28.5
28.0
27.6
27.2
31.8
31.3
30.8
30.3
29.9
31.7
31.2
30.7
30.2
29.8
26.9
26.8
29.4
29.3
26.5
26.4
29.0
28.9
26.1
26.0
28.6
28.5
25.7
25.6
28.2
28.1
25.3
25.3
27.8
27.7
25.0
24.9
27.4
27.3
24.6
24.6
27.0
26.9
24.3
24.2
26.7
26.6
24.0
23.9
26.3
26.2
23.7
23.6
26.0
25.9
23.4
23.3
25.6
25.6
23.1
23.0
25.3
25.2
22.8
22.7
25.0
24.9
22.5
22.4
24.7
24.6
22.2
22.1
24.4
24.3
21.9
21.8
24.1
24.0
27.2
26.8
26.5
26.1
25.8
25.5
25.1
24.8
24.5
24.2
23.9
31.6
31.1
30.6
30.1
29.7
29.2
28.8
28.4
28.0
27.6
58 MUA-PRC004-EN
Performance
Data unit capacity
Table PD-46. Size 066 design supply air dew point, cfm dry-bulb
°F
85
95
105
115 wet-bulb
°F
76
78
80
76
78
80
76
78
80
76
78
80
—
—
—
—
—
—
46
—
—
—
3638
—
—
48
3680
—
—
3636
—
—
3700
—
—
4083
—
— design supply air dew point, °F
50 52 54
4054
3610
—
4485
3975
—
4990
4395
3896
4018
—
—
4169
—
—
4614
3777
—
4463
3918
—
4725
3933
—
5267
4257
—
6128
4837
3956
4994
4337
3833
5405
4410
3790
56
5593
4884
4304
5643
4838
4238
6267
5026
4213
—
5562
4482
58
6328
5467
4779
6468
5444
4712
—
5793
4725
—
6508
5126
60
—
6175
5342
—
6198
5279
—
—
5399
—
—
5948
62
—
—
6025
—
—
5986
—
—
6285
—
—
—
MUA-PRC004-EN 59
Performance
Data unit w/TE wheel capacity
Table PD-47. Size 031 cooling capacity without reheat, MBh cfm
2200
2300
2400
2500
2600
2700
2800
2900
3000
3100 total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent
85/76
332.54
142.54
-
-
334.92
143.45
337.20
144.36
339.37
145.75
342.53
141.73
344.56
142.46
-
-
-
-
-
-
85/78
334.18
145.91
-
-
336.62
147.03
338.95
148.09
341.18
149.64
344.39
145.78
346.48
146.66
-
-
-
-
-
-
85/80
330.52
146.41
-
-
-
-
334.11
143.45
335.82
149.28
338.32
150.60
340.71
151.82
342.99
153.53
346.26
149.82
348.40
150.87
95/76 entering dry-bulb/wet-bulb °F
95/78 95/80 105/76
327.29
134.30
-
-
329.56
134.82
331.73
135.35
333.81
136.11
336.87
131.71
338.81
132.04
-
-
-
-
-
-
-
-
-
-
-
-
-
328.93
137.67
331.26
138.40
333.49
139.08
335.62
140.00
338.73
135.75
340.73
136.24
-
-
-
-
325.51
138.96
328.99
135.57
330.57
141.04
332.96
141.97
335.24
142.81
337.43
143.89
340.60
139.80
342.65
140.45
322.05
126.05
-
-
324.20
126.19
326.26
126.34
328.24
126.47
331.21
121.68
333.06
121.62
-
-
-
-
-
-
105/78
323.69
129.42
-
-
325.90
129.77
328.02
130.07
330.05
130.36
333.07
125.73
334.98
125.82
-
-
-
-
-
-
105/80
320.50
131.50
-
-
-
-
323.88
127.70
325.33
132.79
327.60
133.34
329.78
133.80
331.86
134.25
334.94
129.77
336.90
130.03
115/76
316.81
117.81
-
-
318.84
117.56
320.80
117.33
322.67
116.84
325.54
111.65
327.31
111.20
-
-
-
-
-
-
115/78
318.45
121.18
-
-
320.54
121.13
322.55
121.06
324.48
120.72
327.41
115.70
329.23
115.40
-
-
-
-
-
-
115/80
315.50
124.04
-
-
-
-
318.76
119.83
320.09
124.55
322.24
124.71
324.31
124.79
326.29
124.61
329.27
119.75
331.15
119.61
Note: Capacities are with all compressors runnning, balanced supply and exhaust airflow, and ARI 1060 return air conditions of 75/63°F. Dashed fields indicate that the unit will cycle compressor to maintain the DP setpoint above 45°F.
Table PD-48. Size 031 cooling capacity with reheat, MBh cfm
2200
2300
2400
2500
2600
2700
2800
2900
3000
3100 total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent
85/76
342.40
142.16
344.68
143.04
-
-
-
-
-
-
-
-
-
-
-
-
346.86
143.85
348.95
144.61
85/78
341.72
144.94
-
-
344.16
146.03
346.50
147.05
-
-
-
-
-
-
-
-
348.73
148.02
350.88
148.94
85/80
338.10
146.01
-
-
-
-
-
-
340.81
147.29
343.44
148.66
345.93
149.90
348.32
151.07
350.60
152.19
352.80
153.26
95/76 entering dry-bulb/wet-bulb °F
95/78 95/80 105/76
338.19
133.28
340.40
133.76
-
-
-
-
-
-
-
-
-
-
-
-
342.52
134.19
344.55
134.56
337.60
136.44
-
-
339.96
137.14
342.22
137.78
-
-
-
-
-
-
-
-
344.39
138.35
346.48
138.88
334.16
138.29
-
-
-
-
-
-
336.78
139.19
339.32
140.16
341.73
141.01
344.04
141.79
346.26
142.52
348.40
143.20
336.12
124.48
-
-
-
-
-
-
-
-
-
-
-
-
-
-
338.18
124.52
340.15
124.50
105/78
333.48
127.94
-
-
335.75
128.26
337.94
128.50
-
-
-
-
-
-
-
-
340.05
128.69
342.08
128.83
105/80
332.75
131.09
335.19
131.66
337.52
132.12
339.76
132.52
-
-
-
-
-
-
-
-
341.92
132.85
344.00
133.15
115/76
331.84
115.21
-
-
-
-
-
-
-
-
-
-
-
-
-
-
333.83
114.85
335.75
114.45
115/78
329.35
119.44
-
-
331.55
119.37
333.66
119.22
-
-
-
-
-
-
-
-
335.70
119.02
337.68
118.77
115/80
328.72
122.99
331.07
123.16
333.32
123.24
335.48
123.24
-
-
-
-
-
-
-
-
337.57
123.19
339.60
123.09
Note: Capacities are with all compressors runnning, balanced supply and exhaust airflow, and ARI 1060 return air conditions of 75/63°F. Dashed fields indicate that the unit will cycle compressor to maintain the DP setpoint above 45°F.
60 MUA-PRC004-EN
Performance
Data unit w/TE wheel capacity
Table PD-49. Size 031 reheat, MBh cfm
1800
2200
2600
3100 entering dry-bulb/wet-bulb °F
55/48 55/50 55/52 65/56 65/58 65/60 75/66 75/68 75/70 85/76 85/78 85/80 95/76 95/78 95/80 105/76 105/78 105/80 115/76 115/78 115/80
46.5
46.8
47.0
47.8
48.0
48.3
49.3
49.5
49.8
50.8
51.0
51.2
51.1
51.3
51.5
51.4
51.6
51.8
51.6
47.9
48.1
48.3
49.2
49.4
49.6
50.8
51.0
51.2
52.3
52.5
52.7
52.9
53.1
53.3
53.5
53.7
53.9
54.1
49.2
49.4
49.5
50.6
50.8
50.9
52.2
52.3
52.5
53.7
53.9
54.0
54.6
54.8
54.9
55.5
55.6
55.8
56.4
49.8
49.9
50.0
51.5
51.6
51.7
53.4
53.5
53.6
55.2
55.3
55.5
56.5
56.6
56.7
57.7
57.8
57.9
58.9
51.9
54.3
56.5
59.1
52.1
54.4
56.7
59.2
Note: Capacities are for balanced supply and exhaust airflow with ARI 1060 return air conditions (75/63°F).
Table PD-50. Size 031 condenser reheat max temperature rise, °F cfm entering dry-bulb/wet-bulb °F
55/48 55/50 55/52 65/56 65/58 65/60 75/66 75/68 75/70 85/76 85/78 85/80 95/76 95/78 95/80 105/76 105/78 105/80 115/76 115/78 115/80
1800 24.4
24.5
24.7
25.0
25.1
25.3
25.8
25.9
26.0
26.5
26.6
26.7
26.6
26.7
26.9
26.8
26.9
2200 20.6
20.7
20.7
21.1
21.2
21.3
21.7
21.8
21.9
22.3
22.4
22.5
22.6
22.6
22.7
22.8
22.9
2600 17.9
18.0
18.0
18.4
18.4
18.5
18.9
18.9
19.0
19.4
19.4
19.5
19.7
19.7
19.8
20.0
20.1
3100 15.2
15.3
15.3
15.7
15.7
15.8
16.2
16.2
16.3
16.7
16.7
16.8
17.1
17.1
17.1
17.4
17.5
27.0
23.0
20.1
17.5
26.9
23.0
20.3
17.8
27.0
23.1
20.4
17.8
27.1
23.2
20.4
17.9
Note: Temperature rises are for balanced supply and exhaust airflow with ARI 1060 return air conditions (75/63°F).
Table PD-51. Size 031 design supply air dew point, cfm dry-bulb
(°F)
85
95
105
115 wet-bulb
(°F)
76
78
80
76
78
80
76
78
80
76
78
80
46
2781
2656
2531
2742
2617
2492
2704
2579
2453
2665
2540
2415
48
3043
2918
2792
3004
2879
2754
2965
2840
2715
2927
2802
2677
—
—
2977
—
3063
2938 design supply air dew point (°F)
50 52 54 56
—
—
3054
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
58
—
—
—
—
—
—
—
—
—
—
—
—
Note: Dew point temps are with all compressors running, balanced supply and exhaust airflow and ARI 1060 return air conditions of 75/63°F.
60
—
—
—
—
—
—
—
—
—
—
—
—
62
—
—
—
—
—
—
—
—
—
—
—
—
MUA-PRC004-EN 61
Performance
Data unit w/TE wheel capacity
Table PD-52. Size 040 cooling capacity without reheat, MBh cfm
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000 total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent
85/80
378.18
169.32
380.27
170.30
382.40
171.33
384.46
172.32
387.96
167.30
389.92
168.20
342.99
153.53
368.38
163.79
368.38
163.79
370.95
165.08
373.41
166.87
377.11
162.29
85/78
376.20
165.05
378.19
165.84
380.28
166.73
382.29
167.57
385.75
162.40
387.66
163.15
341.18
149.64
366.53
160.06
366.53
160.06
369.05
161.20
371.47
162.85
375.13
158.12
85/76
374.21
160.79
376.12
161.38
378.16
162.12
380.13
162.81
383.53
157.50
385.41
158.11
369.53
158.83
373.14
153.96
-
-
-
-
-
-
-
-
369.32
154.07
371.32
154.57
373.34
155.10
375.29
155.58
378.68
150.04
380.54
150.42
335.62
140.00
360.07
150.84
360.07
150.84
362.50
151.63
364.83
152.67
368.41
147.58
95/76 entering dry-bulb/wet-bulb °F
95/78 95/80 105/76
367.33
149.81
369.25
150.11
371.22
150.50
373.12
150.83
376.47
145.14
378.28
145.38
362.89
148.65
366.42
143.42
-
-
-
-
-
-
-
-
371.31
158.34
373.40
159.03
375.46
159.71
377.46
160.33
380.89
154.94
382.80
155.46
337.43
143.89
361.92
154.56
361.92
154.56
364.39
155.50
366.77
156.69
370.39
151.75
360.46
138.82
362.38
138.85
364.28
138.87
366.12
138.84
369.40
132.78
371.16
132.64
356.25
138.48
359.70
132.87
-
-
-
-
-
-
-
-
105/78 105/80
330.05
331.86
130.36
134.25
353.61
355.45
141.61
145.34
353.61
355.45
141.61
145.34
355.94
357.84
142.05
145.92
358.19
360.13
142.50
146.52
361.68
363.67
137.04
141.20
362.44
364.43
143.09
147.35
364.45
366.53
143.31
147.77
366.40
368.52
143.48
148.09
368.28
370.45
143.59
148.35
371.61
373.83
137.68
142.58
373.41
375.67
137.68
142.72
115/76
353.58
127.84
355.50
127.59
357.34
127.25
359.11
126.85
362.34
120.42
364.03
119.90
349.61
128.30
352.98
122.33
-
-
-
-
-
-
-
-
115/78
355.57
132.11
357.58
132.05
359.46
131.86
361.28
131.61
364.55
125.32
366.29
124.94
324.48
120.72
347.15
132.38
347.15
132.38
349.39
132.47
351.55
132.32
354.96
126.50
115/80
357.55
136.37
359.66
136.51
361.58
136.46
363.45
136.36
366.76
130.22
368.55
129.99
326.29
124.61
348.99
136.11
348.99
136.11
351.28
136.34
353.49
136.34
356.95
130.66
Note: Capacities are with all compressors runnning, balanced supply and exhaust airflow, and ARI 1060 return air conditions of 75/63°F. Dashed fields indicate that the unit will cycle compressor to maintain the DP setpoint above 45°F.
Table PD-53. Size 040 cooling capacity with reheat, MBh cfm
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000 total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent
85/76
381.56
158.11
-
-
383.66
158.77
385.82
159.51
-
-
-
-
-
-
-
-
387.89
160.67
389.91
161.33
391.86
161.98
393.75
162.60
85/78
381.13
161.45
383.60
162.56
385.78
163.40
387.98
164.29
-
-
-
-
-
-
-
-
390.09
165.61
392.15
166.43
394.14
167.22
396.07
167.99
85/80
378.05
163.33
380.66
164.59
-
-
-
-
383.17
165.80
385.64
167.01
387.90
168.04
390.14
169.08
392.29
170.54
394.39
171.53
396.42
172.47
398.39
173.38
95/76 entering dry-bulb/wet-bulb °F
95/78 95/80 105/76
376.22
147.54
-
-
378.35
147.90
380.47
148.28
-
-
-
-
-
-
-
-
382.51
148.80
384.51
149.10
386.43
149.37
388.30
149.61
375.91
151.31
378.26
151.99
380.47
152.53
382.63
153.06
-
-
-
-
-
-
-
-
384.71
153.74
386.75
154.19
388.71
154.61
390.62
155.00
372.95
153.96
375.50
154.84
-
-
-
-
377.95
155.66
380.30
156.44
382.59
157.17
384.79
157.85
386.91
158.68
388.98
159.29
390.99
159.86
392.94
160.39
373.03
137.03
375.12
137.05
-
-
-
-
-
-
-
-
-
-
-
-
377.14
136.94
379.10
136.86
381.00
136.76
382.85
136.63
105/78 105/80
-
-
-
-
-
-
-
-
367.86
144.59
370.33
145.10
-
-
-
-
370.69
372.73
141.18
145.53
372.93
374.97
141.41
145.87
375.15
377.27
141.66
146.30
377.28
379.44
141.84
146.62
379.34
381.54
141.88
146.81
381.34
383.58
141.96
147.06
383.28
385.56
142.00
147.25
385.17
387.49
142.01
147.40
115/76
367.72
126.16
369.77
125.82
-
-
-
-
-
-
-
-
-
-
-
-
371.77
125.07
373.70
124.63
375.57
124.15
377.39
123.64
115/80
362.76
135.22
365.17
135.35
-
-
-
-
367.51
135.39
369.63
135.29
371.96
135.43
374.09
135.39
376.17
134.95
378.18
134.82
380.13
134.64
382.03
134.41
115/78
365.47
131.04
367.59
130.84
369.84
130.79
371.93
130.61
-
-
-
-
-
-
-
-
373.97
130.01
375.94
129.73
377.85
129.39
379.71
129.03
Note: Capacities are with all compressors runnning, balanced supply and exhaust airflow, and ARI 1060 return air conditions of 75/63°F. Dashed fields indicate that the unit will cycle compressor to maintain the DP setpoint above 45°F.
62 MUA-PRC004-EN
Performance
Data unit w/TE wheel capacity
Table PD-54. Size 040 reheat, MBh cfm entering dry-bulb/wet-bulb °F
55/48 55/50 55/52 65/56 65/58 65/60 75/66 75/68 75/70 85/76 85/78 85/80 95/76 95/78 95/80 105/76 105/78 105/80 115/76 115/78 115/80
2200
2600
3000
3400
3800
4000
68.6 69.0
69.4
70.4
70.8
71.2
72.7
73.1
73.5
75.0
75.4
75.8
75.2
75.6
76.0
75.5
75.9
70.1 70.5
70.9
72.1
72.5
72.9
74.5
74.9
75.3
77.0
77.3
77.7
77.4
77.8
78.2
77.9
78.3
71.3 71.7
72.0
73.5
73.9
74.2
76.1
76.4
76.8
78.6
79.0
79.4
79.4
79.7
80.1
80.1
80.5
72.6 72.9
73.2
74.9
75.2
75.6
77.6
77.9
78.2
80.2
80.5
80.8
81.2
81.6
81.9
82.3
82.6
73.3 73.6
74.0
75.9
76.2
76.4
78.7
79.0
79.3
81.5
81.8
82.1
82.9
83.2
83.5
84.3
84.6
73.7 74.0
74.2
76.3
76.6
76.9
79.3
79.5
79.8
82.2
82.5
82.8
83.7
84.0
84.3
85.3
85.6
76.3
75.8
78.7
78.3
80.8
80.9
82.9
83.3
84.9
85.7
85.8
86.8
76.2
78.7
81.2
83.6
86.0
87.1
76.6
79.1
81.6
84.0
86.3
87.4
Note: Capacities are for balanced supply and exhaust airflow with ARI 1060 return air conditions (75/63°F).
cfm
2200
2600
3000
3400
3800
4000
Table PD-55. Size 040 condenser reheat max temperature rise, °F entering dry-bulb/wet-bulb °F
55/48 55/50 55/52 65/56 65/58 65/60 75/66 75/68 75/70 85/76 85/78 85/80 95/76 95/78 95/80 105/76 105/78 105/80 115/76 115/78 115/80
29.3 29.4
29.6
30.0
30.2
30.3
30.9
31.1
31.2
31.8
32.0
32.1
31.9
32.1
32.2
32.0
32.2
32.4
32.1
25.4 25.5
25.6
26.0
26.2
26.3
26.8
27.0
27.1
27.6
27.8
27.9
27.8
27.9
28.1
27.9
28.1
28.2
28.1
22.4 22.5
22.6
23.0
23.1
23.2
23.7
23.8
23.9
24.5
24.6
24.7
24.7
24.8
24.9
24.9
25.0
25.1
25.1
20.1 20.2
20.3
20.7
20.8
20.9
21.4
21.4
21.5
22.0
22.1
22.2
22.3
22.4
22.4
22.6
22.6
22.7
22.8
18.2 18.3
18.3
18.8
18.8
18.9
19.4
19.4
19.5
20.0
20.1
20.1
20.3
20.4
20.5
20.7
20.7
20.8
21.0
17.4 17.4
17.5
17.9
18.0
18.0
18.6
18.6
18.7
19.2
19.2
19.3
19.5
19.6
19.6
19.9
19.9
20.0
20.2
32.3
28.2
25.2
22.9
21.1
20.3
32.5
28.4
25.3
23.0
21.1
20.3
Note: Capacities are for balanced supply and exhaust airflow with ARI 1060 return air conditions (75/63°F).
Table PD-56. Size 040 design supply air dewpoint, cfm dry-bulb
(°F)
85
95
105
115 wet-bulb
(°F)
76
78
80
76
78
80
76
78
80
76
78
80
46
3422
3271
3121
3368
3218
3067
3315
3164
3014
3261
3111
2960
48
3754
3603
3453
3700
3550
3399
3647
3496
3346
3593
3443
3292
3979
3828
3678
3925
3775
3624 design supply air dew point (°F)
50 52 54 56
—
3936
3785
—
3882
3731
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
3956
—
—
—
—
—
—
—
—
—
—
—
—
58
—
—
—
—
—
—
—
—
—
—
—
—
Note: Dew point temps are with all compressors running, balanced supply and exhaust airflow and ARI 1060 return air conditions of 75/63°F.
60
—
—
—
—
—
—
—
—
—
—
—
—
62
—
—
—
—
—
—
—
—
—
—
—
—
MUA-PRC004-EN 63
Performance
Data unit w/TE wheel capacity
Table PD-57. Size 051 cooling capacity without reheat, MBh cfm
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
5100 total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent
85/76
422.97
181.48
425.27
182.39
427.50
183.23
429.68
183.99
433.68
177.91
433.86
185.50
435.87
186.20
437.82
186.87
439.72
187.55
418.18
179.55
420.61
180.55
-
-
-
-
-
-
-
-
-
-
-
-
-
-
443.61
181.25
445.43
181.86
85/78
425.46
186.53
427.81
187.56
430.09
188.53
432.31
189.44
436.35
183.50
436.57
191.23
438.63
192.08
440.62
192.89
442.56
193.71
415.39
182.04
418.02
183.20
420.58
184.35
423.06
185.47
-
-
-
-
-
-
-
-
-
-
446.49
187.54
448.36
188.28
85/80
427.96
191.58
430.35
192.73
432.67
193.83
434.93
194.89
439.02
189.09
439.29
196.97
441.38
197.96
443.42
198.92
445.40
199.87
414.93
185.25
-
-
-
-
-
-
-
-
417.69
186.60
420.38
187.88
422.98
189.15
425.50
190.39
449.38
193.82
451.28
194.69
95/76 entering dry-bulb/wet-bulb °F
95/78 95/80 105/76
414.30
168.92
416.51
169.47
418.66
169.98
420.75
170.41
424.68
164.00
424.79
171.26
426.73
171.64
428.63
171.97
430.46
172.32
409.70
167.66
412.03
168.32
-
-
-
-
-
-
-
-
-
-
-
-
-
-
434.30
165.68
436.07
165.96
416.79
173.97
419.05
174.65
421.24
175.28
423.38
175.86
427.35
169.59
427.50
176.99
429.49
177.51
431.43
178.00
433.31
178.48
407.12
170.86
409.65
171.66
412.10
172.47
414.48
173.24
-
-
-
-
-
-
-
-
-
-
437.19
171.97
439.00
172.37
419.29
179.02
421.59
179.82
423.82
180.58
426.01
181.31
430.02
175.19
430.22
182.73
432.25
183.39
434.23
184.02
436.15
184.64
406.78
174.41
-
-
-
-
-
-
-
-
409.43
175.42
412.00
176.34
414.50
177.27
416.93
178.17
440.07
178.25
441.93
178.79
405.63
156.35
407.75
156.56
409.81
156.73
411.83
156.83
415.68
150.09
415.72
157.02
417.60
157.07
419.43
157.07
421.21
157.09
401.22
155.78
403.45
156.09
-
-
-
-
-
-
-
-
-
-
-
-
-
-
425.00
150.11
426.72
150.05
105/78 105/80
-
-
-
-
-
-
-
-
-
-
396.03
162.87
-
-
398.63
163.58
-
-
-
-
398.86
401.16
159.67
164.23
401.28
403.63
160.12
164.80
403.62
406.02
160.58
165.38
405.90
408.35
161.02
165.94
408.12
410.62
161.40
166.45
410.29
412.83
161.74
166.91
412.40
414.98
162.03
167.33
414.46
417.08
162.28
167.73
418.35
421.02
155.68
161.28
418.44
421.15
162.75
168.49
420.36
423.11
162.95
168.82
422.23
425.03
163.10
169.12
424.05
426.90
163.25
169.41
427.88
430.77
156.39
162.68
429.64
432.57
156.47
162.89
115/76 115/78
-
-
-
-
-
-
-
-
-
-
-
-
-
390.59
148.49
392.90
148.58
392.74
395.14
143.89
148.70
394.88
397.33
143.86
148.79
-
-
-
-
-
-
-
-
-
-
396.96
399.45
143.78
148.83
398.99
401.53
143.65
148.82
400.97
403.55
143.49
148.78
402.90
405.53
143.25
148.70
406.68
409.35
136.18
141.77
406.65
409.37
142.78
148.51
408.46
411.22
142.50
148.38
410.23
413.03
142.18
148.20
411.96
414.80
141.87
148.02
415.69
418.58
134.54
140.82
417.36
420.28
134.15
140.57
115/80
401.95
153.88
404.07
154.00
406.13
154.08
408.16
154.15
412.03
147.37
412.08
154.25
413.98
154.26
415.83
154.23
417.64
154.18
388.00
152.38
-
-
390.48
152.74
-
-
-
-
392.89
153.05
395.25
153.26
397.54
153.50
399.77
153.71
421.46
147.11
423.21
146.99
Note: Capacities are with all compressors runnning, balanced supply and exhaust airflow, and ARI 1060 return air conditions of 75/63°F. Dashed fields indicate that the unit will cycle compressor to maintain the DP setpoint above 45°F.
64 MUA-PRC004-EN
Performance
Data unit w/TE wheel capacity
Table PD-58. Size 051 cooling capacity with reheat installed, MBh cfm
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
5100 total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent
85/80
431.84
187.47
434.52
188.73
437.08
189.86
439.63
191.15
-
-
-
-
-
-
-
-
-
-
-
-
-
-
442.07
192.29
444.45
193.39
446.77
194.45
449.01
195.49
451.20
196.50
453.33
197.48
455.65
198.80
457.43
199.39
459.40
200.31
85/76
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
436.78
180.99
439.07
181.83
441.30
182.63
443.47
183.41
445.57
184.15
447.63
184.86
449.87
185.91
451.58
186.24
453.48
186.91
85/78
434.55
184.56
437.02
185.62
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
439.43
186.64
441.76
187.61
444.03
188.54
446.24
189.45
448.38
190.33
450.48
191.17
452.76
192.36
454.50
192.82
456.44
193.61
95/76 entering dry-bulb/wet-bulb °F
95/78 95/80 105/76
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
430.29
168.11
432.51
168.60
434.68
169.05
436.80
169.48
438.86
169.87
440.87
170.23
443.21
171.07
444.75
170.84
446.61
171.15
428.20
172.43
430.60
173.10
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
432.93
173.76
435.20
174.38
437.42
174.96
439.57
175.52
441.67
176.04
443.72
176.54
446.10
177.51
447.67
177.42
449.57
177.85
425.64
176.06
428.24
176.96
430.72
177.74
433.20
178.62
-
-
-
-
-
-
-
-
-
-
-
-
-
-
435.58
179.42
437.89
180.16
440.15
180.87
442.35
181.56
444.48
182.22
446.57
182.84
448.99
183.96
450.60
183.99
452.53
184.56
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
425.96
155.38
-
-
428.07
155.47
430.13
155.54
432.14
155.58
434.11
155.59
436.56
156.23
437.92
155.44
439.75
155.39
105/78 105/80
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
419.45
164.64
421.95
165.18
421.84
424.37
160.31
165.62
424.17
426.77
160.58
166.10
-
-
-
-
-
-
-
-
-
-
-
-
-
-
426.44
429.09
160.89
166.54
428.65
431.34
161.16
166.94
430.80
433.53
161.38
167.29
432.90
435.68
161.58
167.62
434.95
437.77
161.76
167.93
436.96
439.81
161.90
168.21
439.44
442.33
162.67
169.11
440.84
443.76
162.01
168.59
442.71
445.67
162.10
168.80
115/76 115/78
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
419.95
148.02
422.09
147.93
421.45
424.18
141.89
147.80
423.46
426.24
141.61
147.65
425.43
428.24
141.30
147.47
427.35
430.20
140.96
147.26
429.90
432.78
141.38
147.83
431.09
434.01
140.04
146.61
432.88
435.84
139.64
146.34
417.75
148.06
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
115/80
413.25
153.23
415.67
153.40
418.02
153.49
420.35
153.58
-
-
-
-
-
-
-
-
-
-
-
-
-
-
422.59
153.67
424.78
153.71
426.92
153.71
429.01
153.69
431.05
153.65
433.05
153.57
435.67
154.27
436.93
153.19
438.80
153.04
Note: Capacities are with all compressors runnning, balanced supply and exhaust airflow, and ARI 1060 return air conditions of 75/63°F. Dashed fields indicate that the unit will cycle compressor to maintain the DP setpoint above 45°F.
MUA-PRC004-EN 65
Performance
Data unit w/TE wheel capacity
Table PD-59. Size 051 reheat data, MBh cfm entering dry-bulb/wet-bulb °F
55/48 55/50 55/52 65/56 65/58 65/60 75/66 75/68 75/70 85/76 85/78 85/80 95/76 95/78 95/80 105/76 105/78 105/80 115/76 115/78 115/80
2900 96.9
97.5
98.2
99.7
100.4 101.0 103.2 103.8 104.4 106.6 107.2 107.9 106.9 107.6
108.2 107.3 107.9
108.5
107.6
108.2
108.8
3300 98.5
99.1
99.8 101.6 102.2 102.9 105.3 106.0 106.6 109.1 109.7 110.4 109.5 110.2
110.8 110.0 110.6
111.3
110.4
111.1
111.8
3700 100.0 100.6 101.3 103.2 103.9 104.5 107.2 107.8 108.5 111.1 111.8 112.4 111.8 112.4
113.1 112.5 113.1
113.8
113.2
113.8
114.5
4100 102.1 102.6 103.2 105.3 105.9 106.5 109.2 109.8 110.3 113.0 113.6 114.2 114.0 114.6
115.1 115.0 115.5
116.1
115.9
116.5
117.1
4500 102.5 103.1 103.7 106.1 106.7 107.3 110.4 111.0 111.6 114.6 115.2 115.8 115.9 116.5
117.1 117.2 117.7
118.3
118.4
119.0
119.6
4900 103.5 104.0 104.6 107.3 107.9 108.5 111.8 112.3 112.9 116.2 116.8 117.3 117.8 118.4
119.0 119.5 120.0
120.6
121.1
121.7
122.2
5100 103.9 104.5 105.0 107.9 108.4 109.0 112.4 113.0 113.5 116.9 117.5 118.0 118.7 119.2
119.8 120.5 121.0
121.6
122.2
122.8
123.3
Note: Capacities are for balanced supply and exhaust airflow with ARI 1060 return air conditions (75/63°F).
Table PD-60. Size 051 condenser reheat max temperature rise, °F cfm entering dry-bulb/wet-bulb °F
55/48 55/50 55/52 65/56 65/58 65/60 75/66 75/68 75/70 85/76 85/78 85/80 95/76 95/78 95/80 105/76 105/78 105/80 115/76 115/78 115/80
2900 32.1
32.3
32.5
32.9
33.1
33.3
34.0
34.2
34.3
35.0
35.2
35.4
35.1
35.3
35.5
35.2
35.4
3300 28.7
28.9
29.1
29.5
29.7
29.9
30.5
30.7
30.9
31.5
31.7
31.8
31.6
31.8
32.0
31.8
31.9
3700 26.0
26.2
26.3
26.8
27.0
27.1
27.7
27.9
28.0
28.7
28.8
29.0
28.8
29.0
29.1
29.0
29.1
4100 24.0
24.2
24.3
24.7
24.8
25.0
25.5
25.6
25.8
26.3
26.4
26.6
26.5
26.7
26.8
26.7
26.9
4500 22.0
22.1
22.2
22.7
22.8
22.9
23.5
23.6
23.7
24.3
24.4
24.6
24.6
24.7
24.8
24.8
25.0
4900 20.5
20.5
20.6
21.1
21.2
21.3
21.9
22.0
22.1
22.7
22.8
22.9
23.0
23.1
23.2
23.3
23.4
5100 19.8
19.8
19.9
20.4
20.5
20.6
21.2
21.3
21.3
21.9
22.0
22.1
22.2
22.3
22.4
22.6
22.6
35.6
32.1
29.3
27.0
25.1
23.5
22.7
35.3
31.9
29.1
27.0
25.1
23.6
22.9
35.5
32.0
29.3
27.1
25.2
23.7
23.0
35.7
32.2
29.5
27.2
25.3
23.8
23.0
Note: Capacities are for balanced supply and exhaust airflow with ARI 1060 return air conditions (75/63°F).
Table PD-61. Size 051 design supply air dew point, cfm dry-bulb
(°F)
85
95
105
115 wet-bulb
(°F)
76
78
80
76
78
80
76
78
80
76
78
80
46
4263
4063
3863
4211
4011
3811
4159
3959
3759
4107
3907
3707
48
4701
4501
4301
4649
4449
4249
4597
4397
4197
4545
4345
4145 design supply air dew point (°F)
50 52 54 56
—
4939
4739
—
—
—
—
—
—
—
—
—
5087
4887
4687
5035
4835
4635
4983
4783
4583
—
—
—
—
—
5073
—
—
5021
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
58
—
—
—
—
—
—
Note: Dew point temps are with all compressors running, balanced supply and exhaust airflow and ARI 1060 return air conditions of 75/63°F.
—
—
—
—
—
—
60
—
—
—
—
—
—
—
—
—
—
—
—
62
—
—
—
—
—
—
66 MUA-PRC004-EN
Performance
Data unit w/TE wheel capacity
Table PD-62. Size 066 cooling capacity without reheat, MBh cfm
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
5100
5200
5300
5400
5500
5600
5700
5800
5900
6000
6100
6200
6300
6400
6500
6600 total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent
85/76
482.61
206.50
484.68
207.27
486.71
208.03
488.68
208.75
490.62
209.44
492.52
210.11
494.37
210.78
498.61
203.15
497.95
212.01
499.67
212.60
501.37
213.17
503.01
213.72
507.23
207.00
508.85
207.49
471.48
202.20
473.82
203.13
476.10
204.03
478.31
204.89
480.49
205.71
469.07
201.28
-
-
-
-
-
-
-
-
-
-
-
-
-
-
85/78
485.61
212.85
487.72
213.77
489.79
214.66
491.81
215.52
493.79
216.35
495.72
217.16
497.62
217.96
501.90
210.46
501.27
219.46
503.04
220.18
504.77
220.88
506.46
221.56
510.71
214.96
512.37
215.58
474.25
207.90
476.63
208.96
478.96
209.99
481.23
210.98
483.44
211.93
466.71
204.62
-
-
469.29
205.74
471.80
206.84
-
-
-
-
-
-
-
-
85/80
488.61
219.20
490.76
220.26
492.87
221.29
494.94
222.29
496.95
223.26
498.93
224.21
500.87
225.14
505.19
217.77
504.60
226.90
506.41
227.75
508.18
228.59
509.90
229.40
514.19
222.93
515.89
223.68
477.02
213.59
479.45
214.79
481.83
215.95
484.14
217.07
486.40
218.16
463.88
207.28
-
-
-
-
-
-
466.64
208.62
469.34
209.93
471.97
211.17
474.52
212.41
95/76 entering dry-bulb/wet-bulb °F
95/78 95/80 105/76
471.56
190.66
473.55
191.12
475.49
191.55
477.39
191.95
479.25
192.31
481.07
192.66
482.86
193.00
487.03
185.04
486.30
193.57
487.97
193.83
489.60
194.06
491.20
194.27
495.36
186.58
496.92
186.73
460.90
187.95
463.14
188.56
465.32
189.15
467.45
189.68
469.53
190.19
458.59
187.36
-
-
-
-
-
-
-
-
-
-
-
-
-
-
474.56
197.02
476.59
197.61
478.58
198.18
480.52
198.72
482.42
199.23
484.28
199.71
486.11
200.18
490.32
192.35
489.63
201.02
491.34
201.41
493.01
201.77
494.64
202.11
498.84
194.54
500.45
194.82
463.67
193.64
465.96
194.39
468.19
195.11
470.36
195.78
472.48
196.41
453.92
190.48
456.45
191.34
458.92
192.14
461.32
192.92
-
-
-
-
-
-
-
-
477.56
203.37
479.64
204.10
481.66
204.81
483.65
205.49
485.59
206.14
487.49
206.76
489.36
207.36
493.61
199.66
492.96
208.46
494.70
208.98
496.42
209.48
498.09
209.95
502.32
202.51
503.97
202.91
466.44
199.33
468.77
200.22
471.05
201.06
473.27
201.87
475.44
202.64
451.16
193.59
453.86
194.64
-
-
-
-
456.50
195.67
459.08
196.65
461.60
197.57
464.05
198.48
460.52
174.83
462.42
174.96
464.28
175.07
466.10
175.15
467.89
175.19
469.63
175.22
471.35
175.23
475.46
166.93
474.66
175.13
476.27
175.06
477.84
174.95
479.38
174.82
483.49
166.16
485.00
165.97
450.32
173.69
452.46
173.99
454.55
174.26
456.58
174.48
458.57
174.67
448.12
173.43
-
-
-
-
-
-
-
-
-
-
-
-
-
-
105/80
466.52
187.54
468.51
187.95
470.45
188.34
472.36
188.69
474.22
189.02
476.05
189.31
477.85
189.58
482.03
181.55
481.32
190.02
483.00
190.21
484.65
190.37
486.27
190.50
490.45
182.09
492.04
182.15
455.86
185.07
458.09
185.65
460.28
186.18
462.40
186.67
464.48
187.12
441.27
181.30
443.84
182.01
-
-
-
-
446.35
182.71
448.82
183.37
451.23
183.96
453.57
184.56
115/76
449.48
158.99
451.30
158.81
453.07
158.60
454.81
158.35
456.52
158.07
458.19
157.77
459.84
157.45
463.88
148.82
463.02
156.69
464.56
156.29
466.08
155.85
467.56
155.37
471.61
145.74
473.07
145.20
439.74
159.43
441.78
159.42
443.77
159.38
445.71
159.28
447.62
159.15
437.64
159.51
-
-
-
-
-
-
-
-
-
-
-
-
-
-
115/78
452.47
165.35
454.34
165.30
456.16
165.23
457.94
165.12
459.69
164.99
461.40
164.82
463.09
164.63
467.17
156.13
466.35
164.13
467.93
163.86
469.49
163.55
471.01
163.21
475.10
153.71
476.59
153.30
442.51
165.12
444.60
165.25
446.63
165.34
448.62
165.37
450.57
165.38
433.63
164.57
435.93
164.78
438.18
164.92
440.37
165.07
-
-
-
-
-
-
-
-
105/78
463.52
181.18
465.47
181.46
467.37
181.71
469.23
181.92
471.05
182.11
472.84
182.26
474.60
182.40
478.74
174.24
477.99
182.58
479.63
182.63
481.25
182.66
482.82
182.66
486.97
174.13
488.52
174.06
453.09
179.38
455.28
179.82
457.41
180.22
459.49
180.57
461.53
180.89
443.77
177.52
446.19
178.06
448.55
178.53
450.84
179.00
-
-
-
-
-
-
-
-
115/80
455.47
171.70
457.38
171.79
459.24
171.86
461.07
171.89
462.85
171.90
464.61
171.86
466.33
171.81
470.45
163.44
469.68
171.58
471.30
171.44
472.89
171.26
474.45
171.05
478.58
161.67
480.11
161.39
445.28
170.82
447.42
171.08
449.50
171.30
451.53
171.46
453.53
171.60
431.38
169.00
433.82
169.37
-
-
-
-
436.21
169.75
438.56
170.09
440.86
170.36
443.10
170.63
Note: Capacities are with all compressors runnning, balanced supply and exhaust airflow, and ARI 1060 return air conditions of 75/63°F. Dashed fields indicate that the unit will cycle compressor to maintain the DP setpoint above 45°F.
MUA-PRC004-EN 67
Performance
Data unit w/TE wheel capacity
Table PD-63. Size 066 cooling capacity with reheat, MBh cfm
4400
4500
4600
4700
4800
4900
5000
5100
5200
5300
5400
5500
5600
5700
5800
5900
6000
6100
6200
6300
6400
6500
6600 total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent total latent
85/76
491.74
203.14
493.97
203.93
496.14
204.68
498.27
205.41
500.35
206.12
489.47
202.30
-
-
-
-
-
-
-
-
-
-
-
-
-
-
502.39
206.81
504.38
207.46
506.34
208.05
508.24
208.71
510.11
209.35
511.93
209.95
513.71
210.55
515.46
211.12
517.16
211.67
518.83
212.20
85/78
494.76
209.65
497.02
210.58
499.24
211.47
501.41
212.32
503.52
213.17
485.14
205.61
487.63
206.66
490.07
207.72
492.45
208.69
-
-
-
-
-
-
-
-
505.60
214.00
507.62
214.82
509.61
215.56
511.56
216.35
513.46
217.12
515.32
217.84
517.13
218.58
518.91
219.28
520.65
219.96
522.35
220.62
85/80
497.78
216.17
500.08
217.22
502.34
218.25
504.54
219.24
506.70
220.22
486.89
212.09
-
-
-
-
-
-
487.99
211.63
490.52
212.79
493.00
213.98
495.42
215.08
508.80
221.19
510.87
222.18
512.89
223.07
514.87
223.99
516.81
224.89
518.70
225.74
520.55
226.61
522.36
227.44
524.14
228.25
525.87
229.05
95/76 entering dry-bulb/wet-bulb °F
95/78 95/80 105/76
483.29
187.71
485.45
188.18
487.56
188.61
489.63
189.01
491.66
189.39
481.08
187.21
-
-
-
-
-
-
-
-
-
-
-
-
-
-
493.64
189.76
495.58
190.07
497.49
190.34
499.35
190.65
501.17
190.96
502.96
191.22
504.71
191.48
506.41
191.72
508.09
191.94
509.73
192.13
486.31
194.23
488.51
194.83
490.66
195.39
492.77
195.92
494.83
196.44
479.39
192.31
-
-
481.75
192.98
484.06
193.60
-
-
-
-
-
-
-
-
496.85
196.95
498.83
197.43
500.77
197.84
502.66
198.30
504.52
198.73
506.35
199.11
508.13
199.51
509.87
199.88
511.58
200.23
513.25
200.55
489.33
200.74
491.57
201.47
493.76
202.17
495.90
202.84
498.00
203.49
478.28
197.87
-
-
-
-
-
-
479.82
197.63
482.28
198.45
484.68
199.25
487.04
199.98
500.06
204.14
502.07
204.79
504.04
205.35
505.98
205.94
507.87
206.50
509.73
207.01
511.55
207.54
513.32
208.04
515.07
208.52
516.77
208.98
474.84
172.28
476.93
172.43
478.98
172.53
480.99
172.61
482.96
172.66
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
484.89
172.70
486.78
172.69
488.64
172.62
490.46
172.60
492.24
172.57
493.99
172.48
495.70
172.42
497.37
172.32
499.02
172.20
500.63
172.06
105/80
491.31
187.08
493.27
187.40
495.19
187.63
497.08
187.88
498.93
188.11
500.76
188.28
502.54
188.48
504.28
188.65
505.99
188.79
507.67
188.91
115/76
468.41
156.68
-
-
470.40
156.46
472.35
156.21
474.27
155.93
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
476.14
155.65
477.98
155.30
479.79
154.91
481.56
154.55
483.30
154.18
485.02
153.75
486.69
153.35
488.33
152.93
489.95
152.47
491.53
151.99
105/78
477.86
178.80
479.99
179.08
482.08
179.32
484.13
179.52
486.13
179.71
471.14
177.97
-
-
473.43
178.25
475.68
178.50
-
-
-
-
-
-
-
-
488.10
179.89
490.03
180.04
491.92
180.13
493.77
180.24
495.59
180.34
497.37
180.38
499.12
180.45
500.83
180.49
502.51
180.50
504.15
180.48
480.87
185.31
483.05
185.72
485.18
186.10
487.26
186.44
489.30
186.76
469.67
183.66
-
-
-
-
-
-
471.65
183.64
474.03
184.11
476.37
184.51
478.65
184.89
115/78
469.40
163.37
471.47
163.33
473.50
163.24
475.49
163.12
477.44
162.98
462.90
163.62
-
-
465.12
163.51
467.29
163.41
-
-
-
-
-
-
-
-
479.35
162.84
481.23
162.66
483.07
162.41
484.88
162.19
486.65
161.95
488.40
161.65
490.11
161.38
491.79
161.09
493.43
160.76
495.05
160.42
115/80
472.42
169.89
474.53
169.97
476.60
170.02
478.62
170.04
480.61
170.04
461.07
169.45
-
-
-
-
-
-
463.49
169.64
465.79
169.76
468.05
169.77
470.27
169.80
482.56
170.03
484.47
170.01
486.35
169.92
488.19
169.83
490.00
169.73
491.79
169.55
493.53
169.41
495.24
169.25
496.92
169.06
498.58
168.84
Note: Capacities are with all compressors runnning, balanced supply and exhaust airflow, and ARI 1060 return air conditions of 75/63°F. Dashed fields indicate that the unit will cycle compressor to maintain the DP setpoint above 45°F.
68 MUA-PRC004-EN
Performance
Data unit w/TE wheel capacity
Table PD-64. Size 066 reheat data, MBh cfm entering dry-bulb/wet-bulb °F
55/48 55/50 55/52 65/56 65/58 65/60 75/66 75/68 75/70 85/76 85/78 85/80 95/76 95/78 95/80 105/76 105/78 105/80 115/76 115/78 115/80
3600 102.6 103.2 103.8 105.4 106.1 106.7 108.9 109.5 110.1 112.3 112.9 113.5 112.8 113.4 114.0 113.2
113.8
114.4
113.6
114.2
114.8
4000 104.0 104.6 105.2 107.0 107.6 108.2 110.6 111.2 111.8 114.2 114.8 115.4 114.9 115.5 116.1 115.5
116.1
116.7
116.1
116.7
117.3
4400 105.4 106.0 106.5 108.5 109.1 109.7 112.2 112.8 113.3 115.9 116.5 117.0 116.8 117.4 117.9 117.7
118.3
118.8
118.6
119.2
119.7
4800 106.6 107.1 107.6 109.9 110.4 110.9 113.7 114.2 114.7 117.5 118.0 118.5 118.7 119.2 119.7 119.9
120.4
120.9
121.1
121.6
122.1
5200 107.6 108.1 108.6 111.1 111.5 112.0 115.0 115.5 116.0 119.0 119.5 119.9 120.5 121.0 121.5 122.0
122.5
123.0
123.6
124.0
124.5
5600 108.6 109.0 109.5 112.2 112.7 113.1 116.3 116.8 117.2 120.4 120.8 121.3 122.2 122.7 123.1 124.1
124.5
125.0
125.9
126.4
126.8
6000 109.5 109.9 110.3 113.3 113.7 114.1 117.5 118.0 118.4 121.8 122.2 122.6 123.9 124.3 124.7 126.1
126.5
126.9
128.2
128.6
129.1
6400 110.1 110.5 110.9 114.2 114.6 115.0 118.6 119.0 119.4 123.0 123.4 123.8 125.5 125.9 126.3 128.0
128.4
128.8
130.5
130.8
131.2
6600 110.4 110.8 111.2 114.6 114.9 115.3 119.1 119.5 119.9 123.6 124.0 124.4 126.3 126.6 127.0 128.9
129.3
129.7
131.5
131.9
132.3
Note: Capacities are for balanced supply and exhaust airflow with ARI 1060 return air conditions (75/63°F).
cfm
3600
4000
4400
4800
5200
5600
6000
6400
6600
Table PD-65. Size 066 condenser reheat max temperature rise, °F entering dry-bulb/wet-bulb °F
55/48 55/50 55/52 65/56 65/58 65/60 75/66 75/68 75/70 85/76 85/78 85/80 95/76 95/78 95/80 105/76 105/78 105/80 115/76 115/78 115/80
27.3
27.4
27.5
27.9
28.1
28.2
28.8
28.9
29.1
29.6
29.7
29.9
29.7
29.8
30.0
29.8
29.9
30.1
29.9
24.9
25.0
25.2
25.6
25.7
25.8
26.3
26.5
26.6
27.1
27.2
27.4
27.2
27.4
27.5
27.4
27.5
27.6
27.5
23.0
23.1
23.2
23.6
23.7
23.8
24.3
24.4
24.5
25.0
25.1
25.2
25.2
25.3
25.4
25.4
25.5
25.6
25.6
21.3
21.4
21.5
21.9
22.0
22.1
22.6
22.7
22.8
23.3
23.3
23.4
23.5
23.6
23.7
23.7
23.8
23.9
23.9
19.9
20.0
20.0
20.5
20.5
20.6
21.1
21.2
21.3
21.7
21.8
21.9
22.0
22.1
22.2
22.3
22.4
22.4
22.6
18.7
18.7
18.8
19.2
19.3
19.3
19.8
19.9
20.0
20.4
20.5
20.6
20.7
20.8
20.9
21.0
21.1
21.2
21.3
17.6
17.6
17.7
18.1
18.2
18.2
18.7
18.8
18.8
19.3
19.4
19.4
19.6
19.7
19.7
20.0
20.0
20.1
20.3
16.6
16.6
16.7
17.1
17.2
17.2
17.7
17.8
17.8
18.3
18.3
18.4
18.6
18.7
18.7
19.0
19.0
19.1
19.4
16.1
16.2
16.2
16.7
16.7
16.8
17.2
17.3
17.3
17.8
17.9
17.9
18.2
18.2
18.3
18.6
18.6
18.6
18.9
30.0
27.7
25.7
24.0
22.6
21.4
20.3
19.4
19.0
30.2
27.8
25.8
24.1
22.7
21.5
20.4
19.4
19.0
Note: Capacities are for balanced supply and exhaust airflow with ARI 1060 return air conditions (75/63°F).
Table PD-66. Size 066 design supply air dew point, cfm dry-bulb
(°F)
85
95
105
115 wet-bulb
(°F)
76
78
80
76
78
80
76
78
80
76
78
80
46
5079
4809
4538
5031
4760
4489
4982
4711
4440
4933
4662
4392
48
5652
5381
5111
5603
5333
5062
5554
5284
5013
5505
5235
4964 design supply air dew point (°F)
50 52 54 56
6225
5954
5683
—
6527
6256
—
—
—
—
—
—
6176
5905
5635
6127
5856
5586
6078
5807
5537
—
6478
6207
—
6429
6158
—
6380
6109
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
58
—
—
—
Note: Dew point temps are with all compressors running, balanced supply and exhaust airflow and ARI 1060 return air conditions of 75/63°F.
—
—
—
—
—
—
—
—
—
60
—
—
—
—
—
—
—
—
—
—
—
—
62
—
—
—
MUA-PRC004-EN 69
Performance
Data
TE wheel capacity
Table PD-67. Total energy wheel (only) cooling capacity unit size cfm 85/76 85/78 85/80 95/76 entering dry-bulb/wet-bulb °F
95/78 95/80 105/76 105/78 105/80 115/76 115/78 115/80
031 1800
040
051
066
2200
2600
3100
2200
2600
3000
3400
3800
4000
2900
3300
3700
4100
4500
4900
5100
3600
4000
4400
4800
5200
5600
6000
6400
6600 total latent total latent
67.21
51.67
78.71
60.35
79.25
63.73
91.82
66.16
76.33
35.71
92.78
107.46
77.61
74.45
89.16
41.72
78.03
47.62
90.42
65.02
60.05
20.22
91.50
105.98
76.38
55.63
70.15
23.62
76.74
31.97
88.96
44.24
90.09
104.39
37.35
51.68
total latent
89.13
105.02
121.61
68.17
84.09
100.71
88.04
47.12
103.74
62.83
120.11
79.23
86.75
26.68
102.28
42.18
118.45
58.37
total 100.74
118.66
137.36
99.73
117.45
135.91
98.43
115.97
134.23
latent 76.81
94.75
113.47
53.09
70.79
89.27
30.06
47.53
65.77
total latent
83.14
63.95
98.04
113.59
81.79
78.89
94.48
44.21
96.49
111.81
80.36
58.94
74.33
25.03
94.86
109.98
39.57
54.76
63.84
5.16
75.06
6.03
75.41
16.76
88.62
19.58
87.47
28.88
102.74
33.73
85.34
100.70
116.69
6.81
78.88
6.39
22.12
93.19
20.75
38.10
96.95
114.31
132.38
7.67
24.92
42.93
108.11
35.74
total latent
95.08
112.09
129.85
73.00
90.05
107.85
93.67
50.46
110.46
67.28
127.96
84.84
92.12
28.57
108.70
45.17
125.97
62.51
90.49
106.86
123.92
7.29
23.68
40.80
total 106.16
125.13
144.92
104.73
123.46
142.98
103.10
121.60
140.88
101.35
119.64
138.69
latent 81.36
100.36
120.19
56.24
74.99
94.56
31.84
50.34
69.66
8.13
26.40
45.47
total 116.44
137.21
158.87
115.02
135.54
156.92
113.34
133.63
154.75
111.51
131.57
152.45
latent 89.06
109.86
131.57
61.56
82.08
103.51
34.85
55.11
76.26
8.90
28.89
49.77
total 125.94
148.37
171.76
124.58
146.74
169.84
122.88
144.81
167.64
120.98
142.68
165.27
latent 96.14
118.59
142.03
66.45
88.61
111.73
37.62
59.49
82.32
9.60
31.19
53.73
total 130.42
153.62
177.82
129.09
152.03
175.94
127.39
150.10
173.74
125.47
147.95
171.33
latent 99.46
122.68
146.93
68.75
91.67
115.59
38.92
61.54
85.16
9.93
32.27
55.59
total 108.90
128.41
148.77
107.17
126.41
146.48
105.30
124.30
144.10
103.38
122.13
141.67
latent 83.74
103.30
123.71
57.88
77.18
97.32
32.77
51.82
71.70
8.36
27.17
46.80
total 120.76
142.38
164.93
118.97
140.29
162.53
117.00
138.05
159.99
114.93
135.72
157.39
latent 92.73
114.38
136.98
64.10
85.46
107.77
36.29
57.38
79.40
9.26
30.08
51.82
total 131.96
155.54
180.15
130.13
153.41
177.68
128.08
151.07
175.04
125.88
148.61
172.29
latent 101.17
124.79
149.46
69.93
93.24
117.58
39.59
62.60
86.62
10.11
32.82
56.54
total 142.50
167.94
194.48
140.69
165.80
191.99
138.57
163.40
189.26
136.28
160.83
186.39
latent 109.09
134.57
161.16
75.41
100.54
126.79
42.69
67.50
93.41
10.90
35.39
60.97
total 152.43
179.60
207.95
150.65
177.49
205.47
148.49
175.04
202.69
146.12
172.39
199.73
latent 116.51
143.72
172.12
80.54
107.39
135.41
45.60
72.10
99.76
11.64
37.80
65.12
total 161.76
190.56
220.61
160.04
188.50
218.17
157.87
186.04
215.37
155.44
183.33
212.33
latent 123.45
152.29
182.38
85.34
113.79
143.48
48.31
76.39
105.71
12.33
40.05
69.00
total 166.21
195.79
226.64
164.53
193.77
224.23
162.36
191.30
221.43
159.91
188.56
218.37
latent 126.75
156.36
187.25
87.62
116.83
147.32
49.61
78.43
108.53
12.66
41.12
70.84
total 135.14
159.35
184.62
132.99
156.87
181.78
130.68
154.25
178.82
128.29
151.57
175.81
latent 103.92
128.19
153.52
71.83
95.78
120.77
40.67
64.30
88.98
10.38
33.71
58.08
total 147.06
173.39
200.85
144.85
170.82
197.90
142.43
168.07
194.79
139.89
165.22
191.60
latent 112.95
139.33
166.86
78.07
104.10
131.27
44.20
69.89
96.71
11.28
36.64
63.13
total 158.44
186.77
216.33
156.19
184.15
213.30
153.67
181.29
210.07
151.01
178.30
206.72
latent 121.54
149.92
179.55
84.01
112.02
141.26
47.56
75.21
104.07
12.14
39.43
67.93
total 169.29
199.53
231.08
167.03
196.88
228.00
164.44
193.94
224.68
161.67
190.83
221.20
latent 129.70
159.99
191.61
89.66
119.54
150.75
50.76
80.26
111.06
12.96
42.08
72.49
total 179.62
211.67
245.11
177.38
209.03
242.03
174.74
206.03
238.63
171.87
202.82
235.04
latent 137.45
169.55
203.06
95.01
126.69
159.75
53.79
85.06
117.69
13.73
44.59
76.82
total 189.46
223.23
258.47
187.25
220.62
255.40
184.58
217.58
251.95
181.64
214.29
248.27
latent 144.80
178.62
213.92
100.09
133.46
168.30
56.67
89.60
123.99
14.46
46.98
80.93
total 198.82
234.23
271.16
196.67
231.66
268.13
193.99
228.61
264.66
190.99
225.26
260.91
latent 151.77
187.22
224.21
104.91
139.88
176.39
59.40
93.91
129.95
15.16
49.24
84.82
total 207.72
244.67
283.21
205.65
242.18
280.25
202.97
239.13
276.78
199.92
235.73
272.98
latent 158.37
195.35
233.95
109.47
145.96
184.06
61.98
98.00
135.60
15.82
51.38
88.51
total 212.00
249.69
289.01
209.98
247.25
286.09
207.30
244.21
282.62
204.24
240.79
278.80
latent 161.53
199.25
238.63
111.65
148.88
187.73
63.21
99.95
138.31
16.13
52.41
90.28
70 MUA-PRC004-EN
Performance
Data
TE wheel capacity
Table PD-68. Total energy wheel (only) heating capacity, MBh
031
040
051
066
4900
5100
3600
4000
4400
4800
5200
5600
6000
6400
6600
3400
3800
4000
2900
3300
3700
4100
4500 cfm
1800
2200
2600
3100
2200
2600
3000
189.89
195.36
156.58
170.76
184.36
197.40
209.89
221.85
233.30
244.25
249.54
25
77.92
91.65
104.23
118.44
96.27
110.46
123.75
136.18
147.78
153.28
126.17
140.29
153.70
166.41
178.47
213.19
219.33
175.80
191.72
206.98
221.62
235.65
249.08
261.93
274.22
280.16
20
87.48
102.89
117.01
132.97
108.08
124.02
138.94
152.89
165.91
172.09
141.66
157.51
172.56
186.83
200.37
236.98
243.81
195.42
213.11
230.08
246.35
261.94
276.87
291.16
304.82
311.42
15
97.24
114.37
130.07
147.81
120.14
137.86
154.44
169.95
184.43
191.29
157.46
175.08
191.81
207.68
222.73
261.27
268.81
215.45
234.96
253.67
271.61
288.80
305.26
321.01
336.07
343.35
10
107.21
126.10
143.41
162.97
132.46
151.99
170.28
187.37
203.33
210.90
173.61
193.03
211.48
228.98
245.56
157.02
167.06
171.88
137.76
150.24
162.20
173.67
184.66
195.19
205.26
214.89
219.55
30 winter outdoor dry-bulb, °F
35 40
68.55
80.63
59.38
69.84
50.39
59.26
91.70
104.21
84.69
97.19
79.42
90.26
73.36
84.18
67.40
76.59
62.25
71.43
108.88
119.81
130.02
134.86
111.01
123.43
135.22
146.41
94.31
103.77
112.61
116.81
96.15
106.91
117.12
126.81
80.02
88.06
95.56
99.12
81.59
90.72
99.39
107.61
136.00
144.70
148.87
119.32
130.13
140.49
150.43
159.95
169.06
177.78
186.13
190.16
115.40
122.79
126.33
101.25
110.42
119.21
127.65
135.72
143.46
150.86
157.94
161.36
101.31
104.23
83.54
91.10
98.36
105.32
111.98
118.36
124.47
130.31
133.13
72.65
78.84
81.78
67.32
74.85
82.00
88.78
95.22
45
41.57
48.89
55.61
63.19
51.36
58.93
66.02
80.25
82.56
66.18
72.17
77.91
83.42
88.70
93.76
98.60
103.22
105.46
57.55
62.45
64.78
53.32
59.29
64.95
70.33
75.42
50
32.93
38.73
44.05
50.06
40.68
46.68
52.30
55
24.46
28.77
32.71
37.18
30.22
34.67
38.84
42.74
46.38
48.11
39.60
44.03
48.24
52.23
56.02
59.60
61.32
49.15
53.60
57.87
61.96
65.88
69.63
73.23
76.66
78.32
39.35
40.49
32.45
35.39
38.21
40.91
43.50
45.98
48.35
50.62
51.71
28.22
30.62
31.76
26.15
29.07
31.85
34.49
36.99
60
16.15
18.99
21.60
24.55
19.95
22.89
25.65
Note: Capacities based on ARI 1060 return air conditions, 70/58°F. Outdoor air is assumed to have a relative humidity of 80%. The supply and exhaust airflow are equal.
19.49
20.05
16.07
17.52
18.92
20.26
21.54
22.77
23.94
25.07
25.61
13.98
15.17
15.73
12.95
14.40
15.77
17.08
18.32
65
8.00
9.41
10.70
12.16
9.88
11.34
12.70
MUA-PRC004-EN 71
72
Performance
Data
TE wheel capacity cfm
031 1800
2200
2600
3100
040 2200
2600
3000
3400
3800
4000
051 2900
3300
3700
4100
4500
4900
5100
066 3600
4000
4400
4800
5200
5600
6000
6400
6600
Table PD-69. Total energy wheel performance data
74.8%
73.0%
72.2%
82.0%
80.5%
79.0%
77.5%
76.1%
74.7%
73.3%
71.9%
71.3%
effectiveness sensible latent
81.6%
78.6%
79.2%
75.7%
75.6%
72.1%
82.5%
80.1%
72.3%
68.4%
80.1%
77.4%
77.8%
75.5%
73.3%
72.3%
82.0%
80.1%
78.3%
76.5%
74.8%
72.2%
69.8%
68.6%
79.6%
77.5%
75.4%
73.3%
71.4%
69.5%
68.5%
79.6%
77.8%
76.1%
74.5%
72.9%
71.3%
69.7%
68.2%
67.5%
71.3%
70.5%
80.8%
79.2%
77.6%
76.1%
74.6%
73.1%
71.6%
70.2%
69.5% total
80.5%
77.2%
74.1%
70.3%
81.4%
78.8%
76.3%
74.0%
71.6%
70.5%
80.9%
78.9%
76.9%
75.0%
73.1%
Note: Performance based on ARI 1060 test conditions.
3800
4000
2900
3300
3700
4100
4500
4900
1800
2200
2600
3100
2200
2600
3000
3400
5100
3600
4000
4400
4800
5200
5600
6000
6400
6600
Table PD-70. Total energy wheel temperature rise unit size cfm 10 15 winter outdoor dry-bulb, °F
20 25 30 35 40
031
040
051
066
45 50 55 60 65
48.96 44.88 40.80 36.72 32.64 28.56 24.48 20.40 16.32 12.24
8.16
4.08
47.11 43.19 39.26 35.33 31.41 27.48 23.56 19.63 15.70 11.78
7.85
3.93
45.34 41.56 37.78 34.00 30.22 26.45 22.67 18.89 15.11 11.33
7.56
3.78
43.21 39.61 36.01 32.41 28.81 25.21 21.61 18.00 14.40 10.80
7.20
3.60
49.49 45.36 41.24 37.12 32.99 28.87 24.74 20.62 16.50 12.37
8.25
4.12
48.05 44.05 40.04 36.04 32.03 28.03 24.02 20.02 16.02 12.01
8.01
4.00
46.65 42.77 38.88 34.99 31.10 27.21 23.33 19.44 15.55 11.66
7.78
3.89
45.30 41.52 37.75 33.97 30.20 26.42 22.65 18.87 15.10 11.32
7.55
3.77
43.98 40.32 36.65 32.99 29.32 25.66 21.99 18.33 14.66 11.00
7.33
3.67
43.34 39.73 36.12 32.50 28.89 25.28 21.67 18.06 14.45 10.83
7.22
3.61
49.21 45.11 41.01 36.90 32.80 28.70 24.60 20.50 16.40 12.30
8.20
4.10
48.08 44.07 40.07 36.06 32.05 28.05 24.04 20.03 16.03 12.02
8.01
4.01
46.98 43.07 39.15 35.24 31.32 27.41 23.49 19.58 15.66 11.75
7.83
3.92
45.90 42.08 38.25 34.43 30.60 26.78 22.95 19.13 15.30 11.48
7.65
3.83
44.85 41.12 37.38 33.64 29.90 26.16 22.43 18.69 14.95 11.21
7.48
3.74
43.83 40.18 36.52 32.87 29.22 25.57 21.91 18.26 14.61 10.96
7.30
3.65
43.32 39.71 36.10 32.49 28.88 25.27 21.66 18.05 14.44 10.83
7.22
3.61
49.19 45.09 40.99 36.89 32.79 28.70 24.60 20.50 16.40 12.30
8.20
4.10
48.28 44.26 40.23 36.21 32.19 28.16 24.14 20.12 16.09 12.07
8.05
4.02
47.39 43.44 39.49 35.54 31.59 27.64 23.69 19.75 15.80 11.85
7.90
3.95
46.51 42.64 38.76 34.88 31.01 27.13 23.26 19.38 15.50 11.63
7.75
3.88
45.65 41.85 38.04 34.24 30.43 26.63 22.83 19.02 15.22 11.41
7.61
3.80
44.81 41.07 37.34 33.60 29.87 26.14 22.40 18.67 14.94 11.20
7.47
3.73
43.98 40.31 36.65 32.98 29.32 25.65 21.99 18.32 14.66 10.99
7.33
3.66
43.16 39.57 35.97 32.37 28.77 25.18 21.58 17.98 14.39 10.79
7.19
3.60
42.76 39.20 35.63 32.07 28.51 24.94 21.38 17.82 14.25 10.69
7.13
3.56
Note: Temperature rises based on ARI 1060 return air conditions, 70/58°F. Outdoor air is assumed to have a relative humidity of 80%. The supply and exhaust airflow are equal.
MUA-PRC004-EN
Performance
Data electric heat
Table PD-71. Electric heat temperature rise,°F, sizes 031 & 040 unit size cfm 20 26 32 42
3-stage [33,66,100%]
56 heat input (kW)
70 84 100
7-stage [14,27,41,59,68,86,100%]
031
040
—
—
—
—
68
65
63
61
59
57
65
63
61
59
57
48
46
45
44
55
53
52
50
49
—
—
—
—
68
—
—
—
—
—
60
57
55
53
51
49
47
46
44
43
49
47
46
44
43
36
35
34
33
41
40
39
38
37
60
57
55
53
51
—
—
70
66
63
46
44
42
40
39
37
36
35
34
32
37
36
35
34
32
—
—
—
—
31
30
—
—
—
46
44
42
40
39
59
56
53
50
48
37
36
34
33
31
30
—
—
—
—
30
—
—
—
—
—
—
—
—
—
—
—
—
—
37
36
34
33
31
48
45
43
41
39
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
37
35
33
31
—
2700
2800
2900
3000
3100
2200
2300
2400
2500
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
1700
1800
1900
2000
2100
2200
2300
2400
2500
2600
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
59
58
56
55
69
67
65
63
61
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
70
68
66
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Notes: entries with ‘’—‘’ have temperature rises less than 30°F or greater than 70°F low rise = 30 – 40ºF intermediate rise = 40 – 60ºF medium rise = 60 – 70ºF
122
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
MUA-PRC004-EN 73
74
Performance
Data electric heat
Table PD-72. Electric heat temperature rise, °F, sizes 051 & 066 unit size cfm 20 26 32 42 heat input (kW)
56
3-stage [33, 66, 100%]
051
066
4800
4900
5000
5100
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
5100
5200
5300
5400
5500
5600
5700
5800
5900
6000
6100
6200
6300
6400
6500
6600
Notes: entries with ‘’—‘’ have temperature rises less than 30°F or greater than 70° F
low rise = 30 – 40°F
intermediate rise = 40 – 60°F
medium rise = 60 – 70°F
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
49
48
46
45
44
37
36
35
35
38
37
37
36
35
43
42
41
40
39
53
52
50
49
48
63
61
59
57
55
41
40
39
38
37
46
45
44
43
42
31
31
30
—
—
35
34
33
33
32
—
—
—
—
—
—
37
36
35
34
33
—
—
—
—
—
—
—
—
—
32
31
31
30
—
40
39
38
37
36
47
46
44
43
41
31
30
—
—
—
35
34
33
32
31
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
30
—
—
—
—
36
35
34
32
31
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
70 84 100 122
39
39
38
37
37
43
42
42
41
40
36
36
35
34
34
33
61
59
58
56
55
46
45
44
43
48
47
46
45
44
54
52
51
50
49
7-stage [14, 27, 41, 59, 68, 86, 100%]
—
—
—
—
69
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
51
50
49
48
47
58
56
55
54
52
67
65
63
61
59
—
—
—
—
—
70
68
66
64
63
61
60
59
57
56
—
—
—
—
—
—
—
—
—
—
—
—
70
68
67
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
47
46
46
45
44
52
51
50
49
48
43
43
42
41
41
40
—
—
70
68
66
55
54
53
52
57
56
55
54
53
64
63
61
60
59
56
55
54
53
52
62
60
59
58
57
52
51
50
49
48
48
—
—
—
—
—
66
64
63
62
68
67
66
64
63
—
—
—
—
70
69
67
66
65
64
—
—
—
—
70
63
62
61
60
59
58
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
MUA-PRC004-EN
Performance
Data gas heat
Table PD-73. Gas heat temperature rise, °F, sizes 031 & 040 unit size cfm
1700
1800
1900
2000
2100 input (MBh) output (MBh)
031
2200
2300
2400
2500
2600
2700
2800
2900
3000
3100
2200
2300
2400
2500
2600
040
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
125
100
150
120
—
—
—
—
—
34
33
32
31
—
—
—
—
—
34
33
32
31
—
42
40
38
37
35
42
40
38
37
35
54
51
49
46
44
35
34
33
32
31
41
39
38
37
36
—
—
—
—
41
39
38
37
36
50
48
46
44
43
50
48
46
44
43
65
61
58
55
53
200
160
46
45
43
42
41
55
53
51
49
48
40
39
38
37
55
53
51
49
48
67
64
61
59
57
67
64
61
59
57
87
82
78
74
70
250
200
58*
56*
54*
53*
51*
68*
66*
64*
61*
59*
50*
49*
47*
46*
68*
66*
64*
61*
59*
84*
80*
77*
74*
71*
84*
80*
77*
74*
71*
—
—
—
—
87*
300
240
69*
67*
65*
63*
61*
82*
79*
76*
74*
71*
60*
58*
57*
55*
82*
79*
76*
74*
71*
—
—
—
88*
85*
—
—
—
88*
85*
—
—
—
—
—
400
320
—
89*
87*
84*
82*
—
—
—
—
—
80*
78*
76*
74*
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
350
280
81*
78*
76*
74*
72*
—
—
89*
86*
83*
70*
68*
66*
65*
—
—
89*
86*
83*
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
500 600 700 800
400 480 560
(dual heaters only)
640
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Notes: entries with ‘’—’’ have temperature rises less than 30°F or greater than 90°F
250/300/350/400 MBh inputs have option for dual or single heaters, except there is no 400 MBh single heater in small cabinet
* = dual (lo-rise) = 40 – 90°F
single lo-rise = 30 – 75°F
single hi-rise = 75 – 90°F
MUA-PRC004-EN 75
Performance
Data gas heat
Table PD-74. Gas heat temperature rise °F, sizes 051 & 066 input (MBh) output (MBh) unit size cfm
051
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
4800
4900
5000
5100
3600
3700
3800
3900
4000
066
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
5100
5200
5300
5400
5500
5600
5700
5800
5900
6000
6100
6200
6300
6400
6500
6600
125
100
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
33
32
31
—
—
—
—
—
—
—
—
—
—
—
150
120
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
34
33
32
31
—
39
38
37
36
35
31
—
—
—
—
—
—
—
—
200
160
32
31
31
30
—
36
35
34
34
33
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
34
34
33
32
31
39
38
37
36
35
45
43
42
41
40
53
51
49
48
46
41
40
39
38
37
31
30
—
—
250
200
300
240
350
280
40*
39
38
38
37
45*
44*
43*
42*
41*
33
32
32
31
31
36
35
35
34
34
30
—
—
—
—
—
43*
42*
41*
40*
39
49*
47*
46*
45*
44*
64*
61*
59*
58*
56*
54*
53*
51*
50*
38
38
37
36
51*
50*
49*
47*
46*
Notes: entries with ‘’—’’ have temperature rises less than 30°F or greater than 90°F
250/300/350/400 MBh inputs have option for dual or single heaters, except there is no 400 MBh single heater in small cabinet
* = dual (lo-rise) = 40 – 90°F
single lo-rise = 30 – 75°F
single hi-rise = 75 – 90°F
48*
47*
46*
45*
44*
54*
53*
51*
50*
49*
39
39
38
37
37
43*
43*
42*
41*
40*
36
36
35
35
34
34
51*
50*
49*
48*
47*
58*
57*
55*
54*
53*
67*
65*
63*
61*
60*
66*
76*
74*
71*
69*
46*
45*
44*
43*
61*
60*
58*
57*
55*
56*
55*
54*
53*
52*
63*
61*
60*
59*
57*
46*
45*
44*
44*
43*
51*
50*
49*
48*
47*
42*
42*
41*
40*
40*
39
60*
59*
57*
56*
55*
68*
66*
65*
63*
61*
78*
76*
74*
72*
70*
79*
89*
86*
83*
81*
54*
53*
52*
51*
72*
70*
68*
66*
65*
64*
63*
61*
60*
59*
72*
70*
69*
67*
66*
53*
52*
51*
50*
49*
58*
57*
56*
55*
54*
48*
48*
47*
46*
45*
45*
80*
78*
77*
75*
74*
90*
88*
86*
84*
82*
66*
65*
64*
62*
61*
72*
71*
70*
68*
67*
60*
59*
59*
58*
57*
56*
86*
84*
82*
80*
78*
—
—
—
90*
88*
—
—
—
—
—
—
—
—
—
—
77*
75*
74*
72*
—
—
—
—
—
400
320
500
400
600
480
700
560
(dual heaters only)
800
640
69*
67*
66*
64*
63*
78*
76*
74*
72*
70*
89*
87*
84*
82*
80*
—
—
—
—
—
61*
60*
59*
58*
82*
80*
78*
76*
74*
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
88*
87*
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
— —
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
88*
—
—
—
—
—
79*
78*
76*
75*
74*
87*
85*
83*
82*
80*
73*
71*
70*
69*
68*
67*
—
—
—
—
—
—
—
—
—
—
—
—
89*
87*
86*
—
—
—
—
—
85*
83*
82*
81*
79*
78*
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
89*
76 MUA-PRC004-EN
Controls
with
The Intelligent Air-Cooled Chillers
We have designed the Trane Packaged
Fresh Air unit with the latest control technology. Modular DDC controls with human interface (HI) panel make
Packaged Fresh Air units flexible and easy to operate.
Controls are Trane-designed to work with Trane equipment for optimum efficiency. The factory installs and commissions each control component to ensure simple and reliable operation.
Furthermore, the DDC control’s modular design allows greater application flexibility using up to twelve different modules, dependent upon unit options.
You can order exactly what the job requires as options, instead of one large control package. And since unit features are distributed among multiple printed circuit boards, field replacement is easy.
Depending on unit options, IntelliPak™ units can operate as:
1) stand-alone
2) interface with Trane’s Tracer Summit™ building management system
3) interface with a generic (non-Trane) building management system (via
LCI-I using LonTalk ® DAC profile).
4) interface with a generic hard-wired
(non-Trane) building management system via analog input and binary output interface board (GBAS)
Available Input and Output Points Base
Unit (RTM module on all units)
Binary inputs
• emergency stop
• external auto/stop
• unoccupied/occupied
• dirty filter
• exhaust fan air proving
Binary outputs
• unoccupied mode indicator
• alarm
• exhaust fan enable
Analog input
• OA damper minimum position heating option
• analog output (hydronic heat interface)
LonTalk ® communication interface
(LCI-I ) option
MUA-PRC004-EN
Binary input
• enthalpy enable unoccupied economizer
Binary outputs
• compressor on/off status
• ventilation status
• heat status
Analog outputs
• supply air pressure
• supply air temperature
• suction temperature of each circuit
• zone temperature
• supply air temperature reset signal
• morning warmup sensor temperature
• entering air temperature
Analog inputs
• cooling and heating setpoints
• VAV discharge air temperature setpoints
• supply air pressure setpoint
• cooling and heating enable/disable
• unoccupied economizer enable/disable
• economizer minimum position
• unit priority shutdown
Generic BAS Option (GBAS)
Binary inputs
• demand limit contacts
Binary outputs
• dirty filter relay
• refrigeration fail relay
• heat fail relay
• supply fan fail relay
• active diagnostics
Analog inputs
• occupied zone cooling setpoint
• occupied zone heating setpoint
• unoccupied zone cooling setpoint
• unoccupied zone heating setpoint or minimum outside air flow setpoint
• supply air cooling setpoint
• supply air heating setpoint
• supply air static pressure setpoint
Zone Humidity Options (ECEM)
Analog inputs
• zone relative humidity
Traq™ Damper Option (VCM)
Analog inputs
• ventilation airflow
Ventilation Override Module (VOM)
Option
Binary inputs
• VOM mode A, unit off
• VOM mode B, pressurize
• VOM mode C, exhaust
• VOM mode D, purge
• VOM mode E, purge
Binary output
• V.O. relay
Standard IntelliPak Unit Control
Features
All set-up parameters are preset from the factory, requiring less startup time during installation.
The human interface panel is easy to read and requires less time for building maintenance personnel to learn to interact with the unit. It features a clear language display (in English, Spanish, or
French) that shows all of the Packaged
Fresh Air unit control parameters, including system on/off, demand limiting type, night setback setpoints, and many other setpoints. All adjustments are done through the human interface keypad. Also, the human interface panel allows you to monitor diagnostic points such as sensor failures, supply airflow loss, and inoperative refrigerant circuit.
No special tools are required for servicing the unit. Diagnostics are held in memory, even during power loss.
This allows the operator/servicer to diagnose the failure root cause.
IntelliPak Unit Features
• Unit mounted human interface panel with a two line x 40 character display in English, Spanish, or French language and a 16-function keypad that includes CUSTOM, DIAGNOSTICS, and SERVICE TEST MODE menu keys
• Frostat™ coil frost protection on all units
• Supply air or zone dehumidification control
• Supply air or zone temperature control
• Efficient condenser hot gas reheat with modulating capacity (optional)
• Morning warmup operation
• unoccupied airside economizer
77
Controls
(optional) when unit has return air damper option
• supply airflow proving
• supply air tempering control with heating option
• mappable sensors and setpoint sources
• occupied/unoccupied switching
• timed override activation
Human Interface Panel (HI)
The human interface panel provides a
16-button keypad for monitoring, setting, editing and controlling. The HI panel is mounted in the unit’s main control panel, accessible through the unit’s control panel door.
The optional remote-mount version of the human interface (RHI) panel has all the functions of the unit-mounted version, except for the service mode. To use a RHI, the unit must be equipped with the remote HI interface option, which includes an interprocessor communications bridge (IPCB). The RHI can be located up to 1,000 feet (304.8
m) from the unit. A single RHI can be used to monitor and control up to four fresh air units, that have each been supplied with a RHI interface option
(IPCB module).
The main menus of the human interface panels are:
• STATUS monitors temperature, pressure, humidity, setpoints, and input and output status.
• CUSTOM key allows the user to customize a status report - consisting of up to four screens of the data available in the main Status menu.
• SETPOINT allows the user to edit all factory preset default setpoints.
• DIAGNOSTICS allows the user to review active and historical lists of diagnostic conditions. A total of 49 different diagnostics can be read at the human interface (HI) panel and the last 20 diagnostics can be held in an active history buffer log at the HI panel.
• SETUP allows the user to edit control parameters, sensor selections, setpoint source selections, output definitions, and numerous other points in this menu. All points have factory preset values to keep unnecessary editing to a minimum.
• CONFIGURATION allows changing of factory-preset unit configuration
78
Figure C-1. The human interface panel on the Trane Packaged Fresh Air unit information. This information can be edited only if certain options are fieldinstalled or deleted from the unit. For example, if a communication interface
(LCI-I) module or ventilation override module (VOM) were field-installed, the unit configuration will require editing to reflect those options for proper unit operation.
• SERVICE allows servicing or troubleshooting the unit by selecting component control outputs such as compressors, fans, damper position, etc. This menu is accessible only at the unitmounted human interface panel.
1
Occupied Sequence
During occupied mode, the primary function of the unit is to provide ventilation air to the space. Upon entering the occupied mode, the outside air damper is opened and the supply air fan will start.
Drying Mode
The unit will enter the drying mode when the OA dew point exceeds the SA drying setpoint (dew point). The SA drying setpoint can be reset down based on OA dew point conditions.
Drying functions will have priority over cooling mode. Upon entering drying mode, the first compressor will stage up. While in drying mode, the first compressor stage will always remain active. This allows condenser reheat
(when ordered) to be available as required during drying operation.
Additional compressors will be sequenced to match unit capacity to the latent load.
Reheat will be controlled to meet a supply air reheat setpoint that is a minimum of 3°F greater than the supply air drying setpoint. The supply air reheat setpoint can be reset up based on OA or zone temperature conditions. When available, condenser reheat will be cycled to achieve a time-weighted average of the reheat setpoint. If primary heat reheat is user-enabled, additional reheat capacity will be made available to match sensible load.
Cooling Sequence
When not in drying mode, the unit will stage cooling capacity to maintain the supply air cooling setpoint. The supply air cooling setpoint can be reset down based on HI selectable parameters (OA sensor, zone sensor if installed).
MUA-PRC004-EN
Controls
Sequence of
Operation
Heating Sequence
When not in drying mode, the unit will stage heating capacity to maintain the supply air heating setpoint. The supply air heating setpoint can be reset up based on HI selectable parameters (OA sensor, zone sensor if installed). The supply air heating setpoint must be lower than the supply air cooling setpoint.
2
Unoccupied Sequence
In unoccupied mode, the fan is stopped and the OA damper is closed.
1
Occupied Sequence
During occupied mode, the primary function of the unit is to provide ventilation air to the space. Upon entering the occupied mode, the outside air damper is opened and the supply air fan will start.
Drying Mode
The unit will enter the drying mode when the OA dew point exceeds the SA drying setpoint (dew point). The SA drying setpoint can be reset down based on zone relative humidity conditions or OA dew point conditions.
Drying functions will have priority over cooling mode. Upon entering drying mode, the first compressor will stage up. While in drying mode, the first compressor stage will always remain active. This allows condenser reheat
(when ordered) to be available as required during drying operation.
Additional compressors will be sequenced to match unit capacity to the latent load.
Reheat will be controlled to meet a supply air reheat setpoint that is a minimum of 3°F greater than the supply air drying setpoint. The supply air reheat setpoint can be reset up based on OA or zone temperature conditions. When available, condenser reheat will be cycled to achieve a time-weighted average of the reheat setpoint. If primary heat reheat is user-enabled,
MUA-PRC004-EN additional reheat capacity will be made available to match sensible load.
Cooling Sequence
When not in drying mode, the unit will stage cooling capacity to maintain the supply air cooling setpoint. The supply air cooling setpoint can be reset down based on HI selectable parameters (OA sensor, Zone sensor if installed).
Heating Sequence
When not in drying mode, the unit will stage heating capacity to maintain the supply air heating setpoint. The supply air heating setpoint can be reset up based on HI selectable parameters (OA sensor, zone sensor if installed). The supply air heating setpoint must be lower than the supply air cooling setpoint.
2
Unoccupied Sequence
When the return air damper option is installed and a request for unoccupied operation is received, the fan, cooling, and heating capacity will be cycled in a recirculating mode to maintain zone requirements. See below for a detailed description of the operating modes.
If no return air damper is installed, the fan is stopped and the OA damper is closed in unoccupied mode.
Drying Mode
During unoccupied mode (with return air damper option installed), the unit will enter the drying mode when the zone
RH exceeds the unoccupied zone RH setpoint. In the drying mode, capacity will be cycled to maintain the supply air drying (dew point) setpoint. The SA drying setpoint can be reset down based on zone relative humidity conditions and will be based on the unoccupied zone RH setpoint.
Supply air reheat functions will be active to maintain the supply air reheat setpoint. Supply air reheat reset functions will be active and reset based on unoccupied zone setpoints. Exhaust fan operation control will be cycled off during unoccupied modes unless unoccupied economizer operations are active.
Cooling Mode
During unoccupied cooling mode, the fan, economizer and mechanical cooling cycle to control zone temperature.
Economizer functions will be enabled when the difference in the enthalpy of the OA and zone is adequate. Mechanical cooling will supplement economizer capacity as required.
Heating Mode
During unoccupied heating mode, fan and heating capacity are cycled to maintain the unoccupied zone heating setpoint.
1
Occupied Sequence
During occupied mode, the primary function of the unit is to provide ventilation air to the space. Upon entering the occupied mode, the outside air damper is opened and the supply air fan will start.
Drying Mode
The unit enters the drying mode when the zone relative humidity exceeds the zone relative humidity setpoint (%RH).
In the drying mode, the capacity is controlled to meet the default supply air drying setpoint (dewpoint). The SA drying setpoint can be reset down based on zone relative humidity conditions. Drying functions have priority over cooling mode. Upon entering drying mode, the first compressor stages up. While in drying mode, the first compressor stage always remains active. This allows condenser reheat option (if ordered) to be available as required during the drying operation.
Additional compressors will sequence to match unit capacity to the latent load.
Reheat is controlled to meet a supply air reheat setpoint that is a minimum of 3°F greater than the supply air drying setpoint. The supply air reheat setpoint can be reset up based on OA or zone temperature conditions. When available, condenser reheat will cycle to achieve a time-weighted average of the reheat setpoint. If primary heat reheat is user-enabled, additional reheat capacity is made available to match the sensible load.
79
Controls
Sequence of
Operation
Drying mode stops when the zone relative humidity falls below the operator adjustable setpoint for leaving drying mode.
Cooling Sequence
When not in drying mode, the unit stages cooling capacity to maintain the supply air cooling setpoint. The supply air cooling setpoint can be reset down based on HI selectable parameters (OA sensor, zone sensor if installed).
Heating Sequence
When not in drying mode, the unit will stage heating capacity to maintain the supply air heating setpoint. The supply air heating setpoint can be reset up based on HI selectable parameters (OA sensor, zone sensor if installed). The supply air heating setpoint must be lower than the supply air cooling setpoint.
2
Unoccupied Sequence
In unoccupied mode, the fan is stopped and the OA damper is closed.
Drying Mode
During unoccupied mode (with return air damper option installed), the unit enters the drying mode when the zone
RH exceeds the unoccupied zone RH setpoint. In the drying mode, capacity cycles to maintain the supply air drying
(dew point) setpoint. The SA drying setpoint can be reset down based on zone relative humidity conditions and will be based on the unoccupied zone
RH setpoint.
Supply air reheat functions are active to maintain the supply air reheat setpoint.
Supply air reheat reset functions are active and reset based on unoccupied zone setpoints. Exhaust fan operation control cycles off during unoccupied modes unless unoccupied economizer operations are active.
Cooling Mode
During unoccupied cooling mode, the fan, economizer, and mechanical cooling cycle to control zone temperature.
Economizer functions enable when the difference in the enthalpy of the OA and zone is adequate. Mechanical cooling supplements economizer capacity as required.
Heating Mode
During unoccupied heating mode, fan and heating capacity cycle to maintain the unoccupied zone heating setpoint.
1
Occupied Sequence
During occupied mode, the primary function of the unit is to provide ventilation air to the space. Upon entering the occupied mode, the outside air damper opens and the supply air fan starts.
Drying Mode
The unit enters the drying mode when the zone relatiave humidity exceeds the zone relative humidity setpoint (%RH).
In the drying mode, capacity is controlled to meet the default supply air drying setpoint (dew point). The SA drying setpoint can be reset down based on zone relative humidity conditions or OA dew point conditions.
Drying functions will have priority over cooling mode. Upon entering drying mode, the first compressor stages up.
While in drying mode, the first compressor stage always remains active. This allows condenser reheat (when ordered) to be available as required during drying operation. Additional compressors will sequence to match unit capacity to the latent load.
Reheat is controlled to meet a supply air reheat setpoint that is a minimum of 3°F greater than the supply air drying setpoint. The supply air reheat setpoint can be reset up based on OA or zone temperature conditions. When available, condenser reheat will cycle to achieve a time-weighted average of the reheat setpoint. If primary heat reheat is user-enabled, additional reheat capacity is made available to match sensible load.
Drying mode stops when the zone relative humidity falls below the operator-adjustable setpoint for leaving drying mode.
Cooling Sequence
When not in drying mode, the unit stages cooling capacity to maintain the supply air cooling setpoint. The supply air cooling setpoint can be reset down based on HI selectable parameters (OA sensor, zone sensor if installed).
Heating Sequence
When not in drying mode, the unit stages heating capacity to maintain the supply air heating setpoint. The supply air heating setpoint can be reset up based on HI selectable parameters (OA sensor, zone sensor if installed). The supply air heating setpoint must be lower than the supply air cooling setpoint.
2
Unoccupied Sequence
When the return air damper option is installed and a request for unoccupied operation is received, the fan and cooling/heating capacity cycle in a recirculating mode to maintain zone requirements. See below for a detailed description of the operating modes.
If no return air damper is installed, the fan stops and the OA damper closes in unoccupied mode.
Drying Mode
During unoccupied mode (with return air damper option installed), the unit enters the drying mode when the zone
RH exceeds the unoccupied zone RH setpoint. In the drying mode, capacity cycles to maintain the supply air drying
(dew point) setpoint. The SA drying setpoint can be reset down based on zone relative humidity conditions and will be based on the unoccupied zone
RH setpoint.
Supply air reheat functions are active to maintain the supply air reheat setpoint.
Supply air reheat reset functions are active and reset based on unoccupied zone setpoints. Exhaust fan operation control will cycle off during unoccupied modes unless unoccupied economizer operations are active.
Cooling Mode
During unoccupied cooling mode, the fan, economizer, and mechanical cooling cycle to control zone temperature.
Economizer functions will enable when the difference in the enthalpy of the OA
80 MUA-PRC004-EN
Controls
Sequence of
Operation and zone is adequate. Mechanical cooling supplements economizer capacity as required.
Heating Mode
During unoccupied heating mode, fan and heating capacity cycle to maintain the unoccupied zone heating setpoint.
1
Occupied Sequence
During occupied mode, the primary function of the unit is to provide ventilation air to the space. Upon entering the occupied mode, the outside air damper opens and the supply air fan starts.
Cooling Sequence
The unit stages cooling capacity to maintain the supply air cooling setpoint.
The supply air cooling setpoint can be reset down based on HI selectable parameters (OA sensor, zone sensor if installed).
Heating Sequence
The unit stages heating capacity to maintain the supply air heating setpoint.
The supply air heating setpoint can be reset up based on HI selectable parameters (OA sensor, zone sensor if installed). The supply air heating setpoint must be lower than the supply air cooling setpoint.
2
Unoccupied Sequence
In unoccupied mode, the fan stops and the OA damper closes.
1
Occupied Sequence
During occupied mode, the primary function of the unit is to provide ventilation air to the space. Upon entering the occupied mode, the outside air damper opens and the supply air fan starts.
Cooling Sequence
The unit stages cooling capacity to maintain the supply air cooling setpoint.
MUA-PRC004-EN
The supply air cooling setpoint can be reset down based on HI selectable parameters (OA sensor, zone sensor if installed).
Heating Sequence
The unit stages heating capacity to maintain the supply air heating setpoint.
The supply air heating setpoint can be reset up based on HI selectable parameters (OA sensor, zone sensor if installed). The supply air heating setpoint must be lower than the supply air cooling setpoint.
2
Unoccupied Sequence
In unoccupied mode, the fan stops and the OA damper closes.
Morning Warmup
This feature is available on all types of factory-installed heat units and on units with no heat. This function may still be selected to support systems with heat sources not provided by the fresh air unit. At the conclusion of unoccupied mode, the selected zone is heated to the user-defined morning warmup setpoint.
The unit is then released to occupied mode. There are two types of morning warmup: full capacity or cycling capacity.
• Full capacity morning warmup (MWU)
Full capacity morning warmup uses full heating capacity to heat the zone as quickly as possible. Full heating capacity is provided until the morning warmup setpoint is met. At this point, the unit is released to daytime mode.
• Cycling capacity morning warmup
(MWU)
Cycling capacity morning warmup provides gradual heating to overcome
“building sink” as the zone is heated.
Normal zone temperature control with varying capacity raises the zone temperature to the MWU zone temperature setpoint. Cycling capacity
MWU will operate until MWU setpoint is reached or for 60 minutes. Then the unit switches to occupied mode. Cooling will suspend until building load conditions exceed the MWU setpoint of 3°F (1.7°C), which is field adjustable.
Ventilation Override (VOM) Option
The user can customize up to five different override sequences for purposes of ventilation override control.
If more than one VOM sequence is requested, the sequence with the highest priority initiates first. Priority schedule is that sequence “A” (unit off) is first, with sequence “E” (purge sequence) last.
• UNIT OFF sequence “A”
When complete system shut down is required, the following sequence is used.
• supply fan – off
• outside air dampers – closed
• heat – all stages – off, modulating heat output at 0 vdc
• occupied/unoccupied output – deenergized
• VO relay –energized
• exhaust fan (field-installed) – off
• exhaust damper (field-installed) – closed
• PRESSURIZE sequence “B”
This override sequence is for use when a positively pressured space is desired instead of a negatively pressurized space.
• supply fan – on
• outside air dampers – open
• heat – all stages – off, modulating heat output at 0 vdc
• occupied/ unoccupied output – energized
• VO relay – energized
• exhaust fan (field-installed) – Off
• exhaust damper (field-installed) – closed
• EXHAUST sequence “C”
With the building’s exhaust fans running and the unit’s supply fan off, the conditioned space becomes negatively pressurized. This is desirable for clearing the area of smoke when necessary (i.e., from an extinguished fire, to keep smoke out of areas that were not damaged).
• supply fan – off
• outside air dampers – closed
81
Controls
Sequence of
Operation
• heat – all stages – off, modulating heat output at 0 vdc
• occupied/unoccupied output – deenergized
• VO relay – energized
• exhaust fan (field-installed) – on
• exhaust damper (field-installed) – open
• PURGE sequence “D”
This sequence is for purging air out of a building before coming out of unoccupied mode of operation. Also, it can purge smoke or stale air.
• supply fan on
• outside air damper – open
• heat: all stages off, modulating heat output at 0 vdc
• occupied/unoccupied output energized
• VO relay energized
• exhaust fan (field-installed) on
• exhaust damper (field-installed) open
• PURGE sequence “E”
This sequence uses supply air control for smoke control.
• supply fan on
• outside air dampers open
• heat: all stages off, modulating heat output at 0 vdc
• occupied/unoccupied output energized
• VO relay energized
• exhaust fan (field-installed) on
• exhaust damper (field-installed) open
Note: Each system (cooling, exhaust, supply air, etc.) within the unit can be redefined in the field for each of the five sequences, if required. Also the definitions of any or all of the five sequences may be locked into the software by simple key strokes at the human interface panel.
Generic Building Automation System
Module (GBAS) Option
The generic building automation system module (GBAS) provides broad control capabilities for building automation systems other than a Tracer Summit system. Use a field provided potentiometer or a 0-5 vdc signal to any of the
GBAS inputs, to access the following inputs and outputs listed in the paragraphs below.
• GBAS analog inputs
These four analog inputs can be configured to any of the following:
(1) occupied zone cooling
(2) unoccupied zone cooling
(3) uccupied zone heating
(4) unoccupied zone heating
(5) SA cooling setpoint
(6) SA heating setpoint
(7) space static pressure setpoint
(8) SA static pressure setpoint
• GBAS binary outputs
Each of the five (5) relay outputs can be mapped to any/all of the available diagnostics.
• Demand limiting binary input
This function is operational on units with a GBAS and reduces electrical consumption at peak load times. There are two types of demand limiting, 50% and
100%. When demand limiting is needed, mechanical cooling and heating operation are either partially (50%), or completely disabled (100%) to save energy. The demand limit definition is user definable at the human interface panel. Demand limit binary input accepts a field supplied switch or contact closure. When the need for demand limiting discontinues, the unit’s cooling/heating functions will (again) fully enable.
Evaporator Coil Frost Protection
Frostat™
A temperature sensor on the evaporator determines if the coil is getting close to a freezing condition. Mechanical cooling capacity is shed as necessary to prevent icing.
The Frostat™ system eliminates the need for hot gas bypass and adds a suction line surface temperature sensor mounted near the TXV bulb location to shut off cooling when coil frosting conditions occur. The supply fan does not shut off and will de-ice the coil.
Timers prevent the compressors from rapid cycling.
Occupied/Unoccupied Switching
There are four ways to switch occupied/ unoccupied:
(1) programmable night setback sensor
(2) field-supplied contact closure
(hardwired binary input to RTM)
(3) Tracer Summit or other BAS (via LCI with LonTalk DAC profile)
(4) factory-mounted time clock
• Field supplied occupied/unoccupied input on the RTM
This input accepts a field supplied switch or contacts closure such as a time clock.
• Tracer system
The Tracer system can control the occupied/unoccupied status of the fresh air unit.
• Factory mounted time cock
A time clock can control the occupied/unoccupied status of the fresh air unit.
Timed Override Activation - ICS
This function is operational whenever the unit’s RTM module board is used as the zone temperature sensor source, which can be set at the human interface panel. Initiate this function by pressing the override button on the zone sensor, to switch the unit to the occupied mode.
Unit operation (occupied mode) during timed override will terminate by a signal from Tracer.
Timed Override Activation - Non-ICS
This function is active whenever the user selects the unit’s RTM module board as the zone temperature source
(can be set at the human interface panel). Initiate this function by pressing the override button on the zone sensor, which will switch the unit to the occupied mode. Automatic cancellation of the timed override mode occurs after three hours of operation.
Low Ambient Compressor Lockout
This function will lock out the compressor if the outdoor air temperature is below the low ambient compressor lock-out temperature setpoint when using a field-installed outside air sensor.
This setpoint is adjustable at the human interface panel. Compressors will lock
82 MUA-PRC004-EN
MUA-PRC004-EN
Controls
Sequence of
Operation out when outdoor air temperature falls below that selected temperature and will start again when the temperature rises 5°F above the setpoint.
Comparative Enthalpy Control of
Unoccupied Economizer Operation
An optional comparative enthalpy system controls the economizer operation and measures the temperature and humidity of both return air and outside air to determine which source has lower enthalpy. This system allows true comparison of outdoor air and return air enthalpy by measurement of outdoor and return air temperature and humidity. The comparative enthalpy option should always be ordered with a return air damper.
Note: If the unit does not have comparative enthalpy, the Packaged Fresh Air unit compares outdoor air enthalpy with a fixed reference enthalpy, set through the human interface panel. If ordering the reference enthalpy option, you should also order a return air damper.
Also, either supply air dehumidification with zone RH reference or zone dehumidification with OA RH reference must be ordered to utilize either comparative enthalpy or reference enthalpy control.
Emergency Stop Input
A binary input is provided on the unit’s
RTM module board for installation of a field-provided switch or contacts to immediately shutdown all unit functions.
Total Energy Wheel with Occupancy
Control
The optional total energy wheel recovers energy from the exhaust airstream and preconditions the outdoor air. The total energy wheel enables when the unit is in occupied mode and the exhaust fan is running.
The wheel disables during unoccupied mode or any time that the exhaust fan is not running. This includes the unoccupied economizer mode when the wheel disables, but the exhaust fan enables.
The wheel also disables via a factoryinstalled thermostat at any time a frost condition occurs (default setpoint 12°F).
This frost protection thermostat utilizes a setpoint range of -30 to 100°F.
Total Energy Wheel with Dry-Bulb
Control
The optional total energy wheel recovers energy from the exhaust airstream and preconditions the outdoor air. The total energy wheel enables when all of the following are true:
• unit is in occupied mode
• exhaust fan is enabled
• outside air temperature is above the upper limit setpoint (default setpoint
80°F) or below the lower limit setpoint
(default setpoint 45°F)
• outside air temperature is above the frost protection setpoint (default setpoint 12°F)
Always set the upper limit setpoint to the anticipated return air dry-bulb temperature. Set the lower limit setpoint to 10°F less than the unit supply air dry-bulb setpoint. The wheel will disable during unoccupied mode or when the exhaust fan is not running.
This includes the unoccupied economizer mode when the wheel will disable, but the exhaust fan will enable.
The wheel also disables via a factory installed thermostat when a frost condition occurs. This frost protection thermostat utilizes a setpoint range of
-30 to 100°F.
83
Controls
Zone Sensor
Options
Zone temperature sensor, accessory model number digit 16 = A, BAYSENS017
Dual setpoint, manual/automatic changeover sensor, accessory model number digit 20 = A
This wall-mounted zone sensor ships with every Packaged Fresh Air unit.
Additional sensors are also available for order using the accessory model number. This zone sensor includes an internal thermistor and should be mounted in the zone. This sensor is available for use with all zone sensor options to provide remote sensing capabilities.
Standard with All Units if Supply Air
Dehumidification w/Zone Reference or
Zone Dehumidification
This zone sensor module is for use with cooling/heating applications. It provides the following features and system control functions:
• System control switch (auto/off):
Allows you to automatically select heating or cooling as required, or turn the system off.
• Dual temperature setpoint levers allow you to set different cooling (blue lever) and heating setpoints (red lever).
• Thermometer to indicate temperature in the zone.
• System control switch to select AUTO mode for automatic selection of heating or cooling as required, or OFF to turn the system off.
• Dual temperature setpoint levers for setting cooling (blue lever) or heating
(red lever).
• Thermometer to indicate temperature in the zone.
• Function status indicator lights:
SYS ON glows continuously during normal operation, or blinks if system is in test mode.
COOL glows continuously during cooling cycles or blinks to indicate a cooling system failure.
HEAT glows continuously during heating cycles or blinks to indicate a heating system failure.
SERVICE blinks or glows to indicate a problem. These signals vary depending on the particular equipment used.
Carbon dioxide zone sensor, accessory model number digit 23 = A
This zone sensor is for use with Packaged Fresh Air units to monitor CO
2 levels in the space.
Zone relative humidity sensor
This wall-mounted zone sensor ships with every Packaged Fresh Air unit when the system control options above are ordered. Additional sensors are also available for order using the accessory model number and ordering the space relative humidity kit.
Dual setpoint, manual/automatic changeover sensor with system function lights, accessory model number digit 21 = A
This zone sensor is for use with cooling/ heating applications. It provides the following features and system control functions:
84 MUA-PRC004-EN
MUA-PRC004-EN
Controls
Zone Sensor
Options
Zone temperature sensor w/timed override buttons and local setpoint adjustment, accessory model number digit 18 = A, BAYSENS014
Zone temperature sensor w/timed override buttons, accessory model number digit 17 = A, BAYSENS013
This zone sensor is for use with cooling/ heating ICS™. It provides the following features and system control functions:
• Remote temperature sensing in the zone
• A timed override button to move an
Integrated Comfort ™ System or a building management system from unoccupied to occupied mode.
• Setpoint thumbwheel for local setpoint adjustment
• Cancel button to cancel the unoccupied override command.
This zone sensor is for use with cooling/ heating Integrated Comfort™ Systems
(ICS). It provides the following features and system control functions:
• Remote temperature sensing in the zone
• A timed override button to move an
ICS or building management system from it unoccupied to occupied mode.
• Cancel button to cancel the unoccupied override command.
85
Electrical
Data
Each type of unit has its own set of calculations for MCA (minimum circuit ampacity) and MOP (maximum overcurrent protection. For units with multiple modes of operation, you must consider each individual field-wired hazardous voltage circuit. Use the load that provides the highest value in the applicable circuit. To correctly size the unit’s electrical service wiring, read the load definitions that follow and then find the appropriate set of calculations based on your unit type.
Load Definitions
Load 1 = current of the largest motor
(compressor or fan motor)
Load 2 = sum of the currents of all remaining motors
Load 3 = current of electric heaters
Load 4 = control power transformer
= any other load rated at one amp or more (gas heat, factory-wired convenience outlet)
Set #1: Cooling Only Units and Cooling with Gas Heat, All Single Source Power
MCA = (1.25 x load 1) + load 2 + load 4
MOP = (2.25 x load 1) + load 2 + load 4
Select an overcurrent protective device rating equal to the MOP value. If the
MOP value does not equal a standard device size as listed in NEC 240-6, select the next lower standard device rating. If the selected MOP is less than the MCA, then reselect the lowest standard maximum overcurrent protective device size that is equal to or larger than the MCA, provided the reselected device size does not exceed 800 amps.
Disconnect Switch Sizing (DSS) – if field provided and installed
If the unit has a factory-installed, nonfused disconnect switch, this sizing equation is not necessary. If the disconnect is field-provided and installed, use the following equation to determine its rating:
DSS = 1.15 x (load 1 + load 2 + load 4)
Select a disconnect switch (DSS) size equal to or larger than the DSS value calculated.
86
Set #2: Units with Electric Heat, Single
Source Power, Non-Concurrent Load
To arrive at the correct MCA and MOP values, you must perform two sets of calculations: one for cooling only (set #1) and one for electric heat only (set #2).
Calculate the MCA and MOP values as if the unit were in the cooling mode (use the equations given in set #1). Then repeat the calculations for MCA and
MOP for the unit in the heating mode using set #2. When determining loads, keep in mind that the compressors and condenser fans do not run while the unit is in the heating mode.
For units using heaters:
• less than 50 kW, use the formula,
MCA = 1.25 x (load 1 + load 2 + load 4)
+ (1.25 x load 3)
• equal to or greater than 50 kW, use
the formula, MCA = 1.25 x (load 1 + load 2 + load 4) + load 3
Select the nameplate MCA value that is the larger of the cooling (set #1) or the heating mode MCA calculated above.
MOP = (2.25 x load 1) + load 2 + load 3 + load 4
Select an overcurrent protective device rating equal to the MOP value. If the
MOP value does not equal a standard device size as listed in NEC 240-6, select the next lower standard device rating. If the next lower standard rating is less than 125% of the current rating of the electric heater load, select the next higher standard device rating. If the selected MOP is less than the MCA, then reselect the lowest standard device size which is equal to or larger than the
MCA, provided the reselected device size does not exceed 800 amps.
Select the MOP value that is the larger of the cooling (set #1) mode MOP value or the heating MOP value calculated above.
Disconnect Switch Sizing (DSS) – if field provided and installed
If the unit is ordered with a factoryinstalled non-fused disconnect switch, this sizing equation is not necessary. If the disconnect is to be field-provided and installed, use the following equation to determine its rating:
DSS = 1.15 x (load 1 + load 2 + load 3 + load 4)
Select the DSS value that is the larger of the cooling (set #1) mode DSS or the heating mode DSS value calculated above. Select a disconnect switch size equal to or greater than the DSS value calculated.
Set #3: Units with Electric Heat, Single
Source Power, Concurrent Load
Concurrent load = 2 compressors and first stage electric heat
Primary Heat Reheat Selection
You may enable primary heat reheat to take advantage of the primary heat source as supplemental reheat for the condenser reheat. Although in most cases, the MCA and MOP values are unaffected by the concurrent loads of compressors, condenser fans, and first stage of electric heat, there are a few circumstances where the MCA and
MOP are increased when this sequence is employed.
You must perform three sets of calculations to obtain the correct MCA and
MOP values: one for cooling (set #1) only, one for electric heat (set #2) only, and one for when the unit is in the cooling mode with compressors and electric heat on concurrently (set #3).
For size 031 and 040 units, compressors
A (1K1) and B (1K2) can run concurrently with 1 /
3
of three-stage electric heat or 1 /
7
of seven-stage electric heat.
For size 051 and 066 size units, compressors A (1K1) and D (1K4) can run concurrently with 1 /
3
of three-stage electric heat or 1 /
7
of seven-stage electric heat.
For units using heaters less than 50 kW:
MCA = (1.25 x load 1) + load 2 + load 4 +
(1.25 x load 3)
For unit using heaters equal to or greater than 50 kW:
MCA = (1.25 X load 1) + load 2 + load 3 + load 4
Select the nameplate MCA value that is the largest of the three sets of MCA calculations.
MOP = (2.25 x load 1) + load 2 + load 3 + load 4
Select an overcurrent protective device rating equal to the MOP value. If the
MOP value does not equal a standard device size as listed in NEC 240-6, select
MUA-PRC004-EN
Electrical
Data the next lower standard device rating. If the next lower standard rating is less than 125% of the current rating of the electric heater load, select the next higher standard device rating. If the selected MOP is less than the MCA, then reselect the lowest standard device size which is equal to or larger than the
MCA, provided the reselected device size does not exceed 800 amps.
The MOP value selected should be the largest of the three sets of MOP value calculations.
Disconnect Switch Sizing (DSS) – if field provided and installed
If the unit is ordered with a factoryinstalled non-fused disconnect switch, this sizing equation is not necessary. If the disconnect is to be field-provided and installed, use the following equation to determine its rating:
DSS = 1.15 x (load 1 + load 2 + load 3 + load 4)
Select the DSS that is the largest of the three sets of DSS calculations. Select a disconnect switch size equal to or greater than the DSS value calculated.
Set #4: Units with Electric Heat, Dual
Source Power
Dual source power is required only on some 208V and 230V units when provided with electric heat. Those units are: size voltage elec ht kW
031
040
051
066
208V or 230V
208V or 230V
208V or 230V
208V or 230V
42 kW or larger
42 kW or larger
70 kW or larger
70 kW or larger
Dual Source Power
For units with dual source power, use two different sets or MCA and MOP calculations, one for each power connection. MCA1 and MOP1 represent the values calculated for the operation of the compressors and condenser fans.
For the calculations of MCA1 and MOP1, use the instructions from set #1 previously in this section.
MCA2 and MOP2 represent the values calculated for the operation of the unit in heating mode:
MCA2 = (1.25 x load 3) if heater kW is less than 50kW or
(1.0 x load 3) if heater kW is 50kW or greater, MOP2 = (1.25 x load 3)
Select an overcurrent protective device rating for the heating circuit equal to the
MOP2 value. If the MOP2 value does not equal a standard device size as listed in
NEC 240-6, select the next lower standard device rating. If the selected
MOP2 is less than the MCA2, then reselect the lowest standard device size that is equal to or larger than the MCA2, provided the reselected device size does not exceed 800 amps.
Disconnect Switch Sizing (DSS) – if field provided and installed:
If the unit is ordered with a factoryinstalled non-fused disconnect switch, this sizing equation is not necessary. If the disconnect is to be field-provided and installed, use the following equation to determine its rating:
DSS2 = 1.15 x (load 3)
Select the DSS2 value that is the largest of the three sets of DSS2 calculations.
Select a disconnect switch size equal to or greater than the DSS2 value calculated.
Load Definitions
Load 1
Supply Fan Exhaust Fan
Reheat Comp (A) Condenser Fan 1 (A)
Main Comp 1 (B) Condenser Fan 2 (B)
Main Comp 2 (C) Condenser Fan 3 (C)
Main Comp 3 (D) [5100/6600] total Energy Wheel
Load 3
Electric Heat kW < 50 kW > 50
Load 4
Control Power Transformer (Loads > 1
Amp [1T1 - 208/230])
Gas Heat
Factory-Wired Convenience Outlet
MUA-PRC004-EN 87
88
Electrical
Data
Table ED-1. Electrical Service Sizing Data unit size
031
040
056
066 reheat comp (A) main comp 1 (B) main comp 2 (C) main comp 3 (D) voltage tons* rla lra tons* rla lra tons* rla lra tons* rla lra
208/60/3 4.5
15 124
230/60/3 4.5
15 124
9.0
9.0
460/60/3 4.5
8 59.6
9.0
208/60/3 6.75
23 164 10.0
230/60/3 6.75
23 164 10.0
460/60/3 6.75
11 100 10.0
208/60/3 9.0
35 222 14.0
230/60/3 9.0
31 251 14.0
460/60/3 9.0
16 117 14.0
208/60/3 9.0
35 222 15.0
230/60/3 9.0
31 251 15.0
460/60/3 9.0
16 117 15.0
35
31
16
35
31
16
48
43
23
51
46
23
222
251
117
222
251
117
337
376
178
337
376
178
14.0
14.0
14.0
15.0
15.0
15.0
9.0
9.0
9.0
15.0
15.0
15.0
48
43
23
51
46
23
35
31
16
51
46
23
337
376
178
337
376
178
222
251
117
337
376
178
—
—
—
—
—
—
9.0
9.0
9.0
15.0
15.0
15.0
—
—
—
—
—
—
35
31
—
—
—
—
—
—
222
251
16 117
51 337
46 376
23 178
*tons refers to nominal R22 tons electric heat FLA is determined at 208, 240, & 480 volts
Table ED-2. Supply fan motor fla standard efficiency high efficiency
Voltage 1 hp 2 hp 3 hp 5 hp 7.5 hp 10 hp 15 hp 1 hp 2 hp 3 hp 5 hp 7.5 hp 10 hp 15 hp
208/60/3 3.1
5.9
8.7
14.0
22.2
28.2
40.7
230/60/3 2.8
5.6
8.0
13.2
21.6
28.0
40.6
460/60/3 1.4
2.8
4.0
6.6
10.8
14.0
20.3
3.1
2.8
1.4
6.1
5.4
2.7
9.3
8.2
4.1
14.9
12.8
6.4
21.3
20.0
10.0
29.0
25.8
12.9
40.7
35.4
17.7
Table ED-3. Exhaust fan motor fla standard efficiency high efficiency
Voltage 1 hp 2 hp 3 hp 5 hp 7.5 hp 10 hp 15 hp 1 hp 2 hp 3 hp 5 hp 7.5 hp 10 hp 15 hp
208/60/3 3.1
5.9
8.7
14.0
22.2
28.2
40.7
230/60/3 2.8
5.6
8.0
13.2
21.6
28.0
—
460/60/3 1.4
2.8
4.0
6.6
10.8
14.0
—
3.1
6.1
9.3
14.9
21.3
29.0
2.8
5.4
8.2
12.8
20.0
25.8
1.4
2.7
4.1
6.4
10.0
12.9
—
—
—
Table ED-4. Energy wheel motor fla unit size voltage
208/60/3
230/60/3
460/60/3
031 040
1/2 hp 1/2
2.7
2.7
2.4
1.2
2.4
1.2
051
3/4
3.6
3.0
1.5
066
3/4
3.6
3.0
1.5
Table ED-5. Condenser fan motors voltage
208/60/3
230/60/3
460/60/3
Table ED-6. Factory-wired convenience outlet voltage
208/60/3
230/60/3
460/60/3 amps
7.21
6.52
3.26
Table ED-7. total gas heat amps with combustion blower voltage
208/60/3
230/60/3
460/60/3 amps
2.54
2.30
1.15
fla
3.8
3.6
1.8
Table ED-8. Control power transformer (loads greater than 1 amp) voltage
208/60/3
230/60/3 amps
1.20
1.09
MUA-PRC004-EN
MUA-PRC004-EN
Electrical
Data
Table ED-9. Electric heat FLA unit size
031
040
051
066 voltage
208/60/3
230/60/3
460/60/3
208/60/3
230/60/3
460/60/3
208/60/3
230/60/3
460/60/3
208/60/3
230/60/3
460/60/3 kW kW kW
20 26 32 kW
42 kW kW
56 70
55.5
72.2
88.8
116.6
155.4
48.1
62.5
77.0
101.0
134.7
24.1
31.3
38.5
50.5
67.4
—
—
— kW kW kW
84 100 122
—
—
—
—
—
—
—
—
—
— 72.2
88.8
116.6
155.4 194.3 233.2
— 62.5
77.0
101.0
134.7 168.4 202.1
— 31.3
38.5
50.5
67.4
84.2 101.0
—
—
—
—
—
—
88.8
77.0
38.5
116.6
101.0
50.5
—
—
—
155.4 194.3 233.2 277.6
134.7 168.4 202.1 240.6
67.4
84.2 101.0 120.3
—
—
—
—
—
—
— 116.6
155.4 194.3 233.2 277.6 338.6
— 101.0
134.7 168.4 202.1 240.6 293.5
— 50.5
67.4
84.2 101.0 120.3 146.7
—
—
—
—
—
—
Note: Electric heat FLA is determined at 208, 240 & 480 volts.
Table ED-10. Dual source electric heat - customer wire gauge, AWG unit size
031
040 voltage
208/60/3
230/60/3
208/60/3
230/60/3 kW kW kW
42 56 70
1/0 2/0
1 1/0
—
—
1/0 2/0
1 1/0 kW
84
—
—
3/0 250
2/0 4/0 kW
100
—
—
—
— kW
122
—
—
—
—
051
066
208/60/3
230/60/3
208/60/3
230/60/3
— —
— —
— —
— —
3/0 250 300
2/0 4/0 250
—
—
3/0 250 300 500
2/0 4/0 250 350
Table ED-11. Voltage utilization range voltage
208/60/3
230/60/3
460/60/3 utilization range
187-220
208-254
416-508
89
Dimensions &
Weights
outdoor side view, unit without total energy wheel
OUTDOOR SIDE VIEW
LIFTING HOLE
DETAIL A outdoor side view, unit with total energy wheel
DETAIL B detail B lifting hole detail A
INLET HOOD
END VIEW
CONTROL PANEL
END VIEW inlet hood end view control panel end view
90 unit size A B C without TE wheel
031, 041 18' - 10" 2' - 7" 4' - 2"
051, 066 19' - 3" 3' 5' - 10" with TE wheel
031, 041
051, 066
24' - 2"
24' - 7"
2' - 7"
3'
4' - 2"
5' - 10"
D
3' - 10"
4' - 1"
E
—
— dimensions (ft and in)
F
3' - 2"
3' - 6"
G
10"
1' - 3"
H
9"
10 1’4"
J
1' - 11 1/2"
2' - 4 1/2"
K
1 1/4"
1 1/4"
L
1' - 6 1’4"
3' - 6 3/4"
M
ø 2 1/2"
ø 3"
N
—
P
—
3' - 10" 9 1/4" 3' - 2"
4' - 1" 8" 3' - 6"
10"
1' - 3"
9"
10 - 1’4"
1' - 11 1/2"
2' - 4 1/2"
1' 6"
1' 8"
1' - 6 1’4"
3' - 6 3/4"
ø 2 1/2"
ø 3"
7"
7"
1' - 3/4"
11"
MUA-PRC004-EN
Dimensions &
Weights
unit without TE wheel - indoor side view (electric heat version shown) unit with TE wheel - indoor side view (electric heat version shown) single & dual gas heater options
MUA-PRC004-EN 91
Dimensions &
Weights unit without TE wheel
unit without TE wheel unit with TE wheel
92 MUA-PRC004-EN
Dimensions &
Weights
unit without TE wheel unit with TE wheel
MUA-PRC004-EN 93
94
Dimensions &
Weights
detail A
3x
THRU-BASE MAIN POWER WIRING ENTRANCE
HOLE Ø3.000’’
NOTE: DRILL OR PUNCH HOLE IN COVER PLATE FOR
SMALLER CONDUIT CONNECTION
MUA-PRC004-EN
Dimensions &
Weights
CONDENSER FANS
CONVENIENCE OUTLET (OPTION)
LIFTING HOLES
MAIN COMPRESSOR ACCESS PANEL
(40x35)
REHEAT COMPRESSOR/COIL ACCESS PANEL
(34x36)
MAIN CONDENSER
COIL ACCESS PANEL
(68x36)
MAIN POWER WIRING ENTRANCE
(CAN ALSO BE RUN THRU-BASE)
HORIZONTAL DISCHARGE
(OPTION)
HUMAN INTERFACE
ACCESS DOOR
UNIT CONTROL PANEL
24 VOLT CONTROL CIRCUIT WIRING ENTRANCE
(CAN ALSO BE RUN THRU-BASE)
DUAL GAS HEAT ACCESS PANEL
(EACH HEATER HAS SEPARATE PANEL)
(16x23)
GAS CONNECTION–DUAL GAS HEAT
(EACH HEATER HAS SEPARATE GAS CONNECTIONS)
NATURAL GAS 250–400 MBH:
∅
.500 NPT INTERNAL
ELECTRIC HEAT POWER WIRING ENTRANCE
(ALSO CAN BE RUN THRU-BASE)
ELECTRIC HEATER ELECTRICAL PANEL (24x30)
-OR-
GAS HEAT PANEL (16x23)
-OR-
FIXED PANEL FOR NO-HEAT OPTION
OR HYDRONIC HEAT INTERFACE OPTION (24x47)
SUPPLY FAN ACCESS DOOR
(33X34)
MUA-PRC004-EN
CONDENSATE
DRAIN CONNECTION
INLET HOOD
FILTER AND DAMPER ACCESS DOOR
(25x39)
EVAP COIL AND
CONDENSATE DRAIN PAN
ACCESS DOOR (18x34)
95
Dimensions &
Weights
96 MUA-PRC004-EN
Dimensions &
Weights
CONDENSER FANS
LIFTING HOLES
REHEAT COMPRESSOR/
COIL ACCESS PANEL (40x52)
MAIN COMPRESSOR/
COIL ACCESS PANEL (34x52)
CONVENIENCE OUTLET
(OPTION)
MAIN COMPRESSOR/
COIL ACCESS PANEL
(68x52)
MAIN POWER WIRING ENTRANCE
(CAN ALSO BE RUN THRU-BASE)
HORIZONTAL DISCHARGE
(OPTION)
HUMAN INTERFACE
ACCESS DOOR
UNIT CONTROL PANEL
24 VOLT CONTROL CIRCUIT WIRING ENTRANCE
(CAN ALSO BE RUN THRU-BASE)
DUAL GAS HEAT ACCESS PANEL
(EACH HEATER HAS SEPARATE PANEL)
(16x23)
GAS CONNECTION–DUAL GAS HEAT
(EACH HEATER HAS SEPARATE GAS CONNECTIONS)
ELECTRIC HEAT POWER WIRING ENTRANCE
FOR 208/230 V: 70, 84, 100, 122 kW
(CAN ALSO BE RUN THRU-BASE)
ELECTRIC HEATER ELECTRICAL PANEL (24x49)
-OR-
SINGLE GAS HEAT ACCESS PANEL (16x23)
-OR-
FIXED PANEL FOR NO-HEAT OPTION
OR HYDRONIC HEAT INTERFACE OPTION (24x67)
GAS CONNECTION–SINGLE GAS HEATER
MUA-PRC004-EN
CONDENSATE DRAIN
CONNECTION
SUPPLY FAN ACCESS DOOR
(33x54)
INLET HOOD
FILTER AND DAMPER ACCESS DOOR
(25x59)
97
Dimensions &
Weights
98 MUA-PRC004-EN
Dimensions &
Weights
MUA-PRC004-EN
6’’ WOOD NAILER
99
Dimensions &
Weights
100
6" WOOD NAILER
MUA-PRC004-EN
Dimensions &
Weights
MUA-PRC004-EN
6’’ WOOD NAILER
101
Dimensions &
Weights
102
6" WOOD NAILER
MUA-PRC004-EN
Dimensions &
Weights
6’’ WOOD NAILER
MUA-PRC004-EN 103
Dimensions &
Weights
104
6" WOOD NAILER
MUA-PRC004-EN
Dimensions &
Weights
6’’ WOOD NAILER
MUA-PRC004-EN 105
Dimensions &
Weights
106
6" WOOD NAILER
MUA-PRC004-EN
Dimensions &
Weights
Table I-DW-1. Typical unit, unit with total energy wheel, and roof curb weights unit size
031
040
051
066 base unit total energy wheel unit roof curb for unit w/o TE wheel roof curb for unit with TE wheel weight 1 base weight 1 low high acoustic low high
4600
4700
5600
6000
1460
1520
1920
1970
282
282
282
282
613
613
613
613
1500
1500
1500
1500
350
350
350
350
766
766
766
766
1. Base unit operating weight is for units with the condenser hot gas reheat option, return air, and no heat. Subtract condenser hot gas reheat weight for cooling only units. See Table
I-DW-2 for weight.
Table I-DW-2. Typical component weights unit size
031
040
051
066 single gas (MBh)
125 150 200
201 217 247
201 217 247
201 217 247
201 217 247
250 300 350
295 295 333
295 295 333
400
—
—
250 300 dual gas (MBh)
400
402 434 —
402 434 494
500
—
—
600
—
—
700
—
—
electric heaters
800
—
—
295 295 333 361 402 434 494 590 590 — —
295 295 333 361 402 434 494 590 590 666 722
20-84 kW
60
60
60
60
100,122 kW
—
—
100
100 condenser hot gas reheat 2
150
150
270
270
D E F
C
Figure I-DW-1. Fresh air unit weight and center of gravity unit size center of gravity
X (in) Y (in) units without total energy wheel
031 90 50
040
051
066
90
100
100
50
51
51 units with total energy wheel
031 123 50
040
051
066
123
130
130
50
51
51 max operational weight (lbs)
4934
5194
6190
6722
6394
6718
8081
8663
A
16
16
13
13
16
16
19
19
B typical point loading—% of unit weight
B C D E
16
16
15
15
18
18
18
18
19
19
17
17
17
16
17
17
18
18
15
15
18
17
20
21
17
17
18
18
16
16
15
15
F
16
17
16
16
14
14
16
16
MUA-PRC004-EN
A
107
Dimensions &
Weights unit without TE wheel unit sizes 031 & 040 unit with TE wheel
108 MUA-PRC004-EN
Dimensions &
Weights unit withouth TE wheel unit with TE wheel
MUA-PRC004-EN 109
Dimensions &
Weights
unit size 031 unit size 040 unit size 051 unit size 066
110 MUA-PRC004-EN
Dimensions &
Weights unit without TE wheel unit without TE wheel
TOP: CLEAR OF ALL OBSTACLES OR OVERHANGS unit with TE wheel
MUA-PRC004-EN
TOP: CLEAR OF ALL OBSTACLES OR OVERHANGS
111
Mechanical
Specifications
Fan Motors
The supply and exhast fan motors are either standard-efficiency open dripproof or high-efficiency open drip-proof.
All supply fan motors meet the U.S.
Energy Policy Act of 1992 (EPACT).
Exhaust Backdraft Damper
A backdraft damper prevents outside air entry into the building through the exhaust fan. Damper frame is extruded aluminum with mitered corners. Blades are formed aluminum with extruded vinyl edge seals that mechanically lock into the blade edge. Bearings are corrosion resistant synthetic and the linkage is concealed in frame for low pressure drop and noise.
Condenser Fan and Motors
The unit condenser fans are vertical discharge, direct-drive fans. They are statically and dynamically balanced. The blades and spider are constructed of zinc-plated steel. Condenser fan motors are three-phase motors with permanently lubricated ball bearings, built-in current and thermal overload protection, and weather-tight slingers over the motor bearings.
Filters
The filter racks (see Figure MS-4) accommodate 2” filter media and are field convertible to allow 4” filter media.
Figure MS-4. Filter racks
112
Dampers – Low Leak
The outside air damper has a unitcontrolled actuator with parallel-blades.
The blade construction is a 14-gage galvanized steel, roll-formed airfoil-type.
Figure MS-5. Traq ™ Damper
Figure MS-6. Return air damper building comfort. A centralized microprocessor provides anti-short cycle timing and time delay between compressors to provide a higher level of machine protection. The unit controls can function as a stand-alone controller ling. The character font is 5 x 7 dot matrix plus cursor. The display is a supertwist liquid crystal display (LCD) with blue characters on a gray/green background, which provides high visibility and interface ease. Meaningful diagnostics are also reported and displayed at the HI panel display.
The HI keypad is equipped with 16 individual touch-sensitive membrane key switches. The switches are divided into four separate sections and password protected to prevent tampering by unauthorized personnel. The six main menus are STATUS, SETPOINTS,
DIAGNOSTICS, SETUP, CONFIGURA-
TION, and SERVICE MODE.
Electric Heating Option
High nickel chrome alloy resistance wire is mechanically staked and welded to corrosion-resistant terminals. Heaters are provided with both manual and automatic temperature control devices.
See Figure MS-4.
3-Stage Electric Heat
These electric heaters have three balanced stages with heating steps of
33, 66, and 100%.
7-Stage Electric Heat
These heaters have three unbalanced stages, resulting in seven steps of 14,
27, 41, 59, 68, 86, and 100%.
Controls
The Trane Packaged Fresh Air unit is completely factory-wired with necessary controls and terminal block for power wiring. Microprocessor controls are provided for all 24-volt and 115-volt control functions. The resident control algorithms make all heating, cooling, drying, and/or ventilating decisions in response to electronic signals from sensors measuring indoor temperature, outdoor temperature, and humidity.
The control algorithm maintains accurate temperature, dew point, and/ or humidity control. It also minimizes setpoint drift and provides better Figure MS-7. Electric heat option
MUA-PRC004-EN
Mechanical
Specifications
Gas-Fired Heating Option
The Packaged Fresh Air unit’s furnaces are certified for 80% thermal efficiency.
The heaters include an integral power vent system. All natural gas-fired units are completely assembled and wired at the factory. The burner and bottom pans are type 409 stainless steel.
409 Stainless Steel Heat Exchanger
Heat exchanger headers and tubing are type 409 stainless steel.
321 Stainless Steel Heat Exchanger
Heat exchanger headers and tubing are type 321 stainless steel.
Single Bank Staged
A single heater unit with a two-stage gas valve provides two steps of heat.
Single Bank Modulated
A single heater unit with solid state controls provides close temperature control through regulating manifold pressure. The controls modulate between 50 and 100%.
Dual Bank Staged
The heater bank contains a single-stage and a two-stage unit. This combination results in steps of 25, 50, 75, and 100%.
Dual Bank Modulated
The heater bank contains a single-stage and a modulating unit. The microprocessor sequences the single stage bank with the modulating bank to provide capacity control between 25-100% heating capacity. This combination results in 25 to 50% modulation, a 25% step, and 75 to 100% modulation.
Hydronic Heat Interface
A bulkhead and coil support is provided downstream of the fan to accept a fieldinstalled one or two-row hydronic heating coil. The unit controller provides a modulating output to control a fieldinstalled water valve and accepts a low temperature limit input signal. The coil supports accept a standard Trane
33X36” heating coil for the small cabinet and 33X48” coil for the large cabinet. Large cabinets may require field-provided blockoffs. Also, if fieldinstalling smaller coils than recommended, additional field modifications or blockoffs must be made. Openings in the unit side panels for piping must also be field constructed.
Condenser Hot Gas Reheat
An indoor reheat condenser is mounted downstream of the evaporator coils.
The indoor and outdoor reheat condenser has parallel circuits. A liquid solenoid valve controls where refrigerant condensation occurs.
Traq™ Damper
Traq outdoor air dampers with flow measurement rings and a ventilation control module are available for airflow measurement and verification. Each damper has a unit-controlled actuator.
See Figure MS-5.
Return Air/Reference Enthalpy
Air returns vertically through the unit base. Dampers are low-leak. Each damper has a unit-controlled actuator.
Inputs are provided for unoccupied economizer control, based upon a comparison of the outside air stream to a definable enthalpy reference point.
See Figure MS-6.
Return Air/Comparative Enthalpy
Air returns vertically through the unit base. Dampers are low-leak. Each damper has a unit-controlled actuator.
Inputs are provided for unoccupied economizer control, based upon a comparison of enthalpies of the return and outdoor air streams.
External Exhaust Interface
The exhaust plenum is internal to the unit cabinet and has one-inch, doublewall, foamed construction. The unit controller provides a binary exhaust fan signal and accepts a binary fan airflow proving input signal from a fieldinstalled exhaust fan.
Corrosion-Inhibiting Coil Coating
The indoor and outdoor coils have a four to six mil protective coating applied by a multiple dip and bake process.
Corrosion-Inhibiting Cabinet Coating
The unit’s interior and exterior surfaces have a four to six mil spray-on protective coating applied with an air-dry process.
Two-Inch Throwaway Filter
The Fresh Air Unit’s filters are UL class
2. Filters are 30% efficient based on
ASHRAE test standard 52-76 with an arrestance of 90-92%.
Dirty Filter Switch
This option indicates when there is a dirty filter. The dirty filter switch triggers an information-only diagnostic message on the human interface or lights the service LED on the zone sensor, and will allow continued unit operation.
Non-Fused Disconnect Switch
A through-the-door, non-fused disconnect switch with external handle is factory-installed. See Figure MS-7.
Figure MS-8. Non-fused disconnect switch
Convenience Outlet
A convenience outlet is provided on the condenser side of the unit. The GFI outlet is 115 volt, and capable of manual resetting.
Figure MS-9. Convenience outlet
Extended Grease Lines
Factory installed extended grease lines provide a common location for regreasing the supply and exhaust fan bearings. The grease fittings are easily accessible within the fan compartment.
MUA-PRC004-EN 113
114
Mechanical
Specifications
LonTalk ® Communications Interface
(LCI-I)
The LCI-I provides an interface to a
Tracer Summit system or other control system that supports LonTalk and the
DAC profile. The LCI-I is a factoryinstalled device and provides a Comm5 interface to a Trane Integrated Comfort
System (ICS). The LCI-I allows control and monitoring of the unit via a twowire communication link.
Generic Building Automation
System (GBAS)
The GBAS module is for use with a non-
Trane building management system.
The module provides a binary input for demand limiting, four analog inputs for setpoint adjustment, and five relay outputs for diagnostic reporting. Inputs can use a potentiometer or 0-5 VDC signal.
Ventilation Override Module (VOM)
The VOM allows programming of the unit with up to five ventilation sequences: smoke purge, evacuation, pressurization, purge, and purge with duct control. Typically a hard-wire short from a smoke detector or fire control panel will cause a binary input on the
VOM to close, thus causing the programmed sequence to occur. These points can be permanently locked to prevent tampering.
Interface for Remote Human
Interface (RHI)
This interface consists of an interprocesor communication board
(IPCB) and is factory-installed in the unit control panel. This component provides a communication bridge for the RHI to up to four units. This option must be installed in the unit to communicate with a remote HI.
Roof Mounting Curb
The roof mounting curb is fabricated of
14-gage galvanized steel with a nominal two x two-inch nailer setup. The curb ships knocked down with a curb gasket.
Curb height options are 14 or 24-inches.
Acoustical Roof Curb
The acoustical roof curb ships fully assembled and has prefabricated, noncombustible construction with sealing gasket around perimeter members to ensure air/water tight integrity. The curb construction is a minimum 14 gage galvanized steel structural members with minimum 20 gage galvanized steel flashing with overlapping continuous rubber counter flashing. Curbs have a 2”x2” nailer strip for attaching roof felts. The base contains acoustically nonconductive floor pans with the supply and return openings framed for duct attachment.
The roof curb incorporates an integral spring-vibration isolation rail with adjustable 1” deflection isolators, and is properly sized and selected for unit point loading. Spring isolators have a minimum 90% isolation efficiency.
Permanent Filters
Permanent filters are provided with a
2” metal frame and permanent wire mesh media. The filter media is cleanable.
LonTalk Communications Interface
(LCI-I) Kit
A field-installed LCI-I kit is provided to interface with a Tracer Summit system or other control system that supports
LonTalk and the DAC (discharge air control) profile. The LCI-I kit provides a
Comm5 interface to control and monitor the unit via a two-wire communication link.
Generic BAS (GBAS) Interface Kit
A field-installed GBAS kit is provided for use with a non-Trane building management system. The GBAS module provides a binary input for demand limiting, four analog inputs for setpoint adjustment, and five relay outputs for diagnostic reporting. Inputs use a potentiometer or a 0-5VDC signal.
Ventilation Override Module (VOM)
Kit
This field kit allows ventilation override capability. The VOM module allows programming of the unit with up to five ventilation sequences: smoke purge, evacuation, pressurization, purge and purge with duct control. Typically a hard-wire short from a smoke detector or fire control panel will cause a binary input on the VOM to close, thus causing the programmed sequence to occur.
These points can be permanently locked to prevent tampering.
MUA-PRC004-EN
MUA-PRC004-EN
Mechanical
Specifications
Electronic Time Clock
The electronic time clock is fieldinstalled. It allows night setback and unoccupied functions when using a standard (dual setpoint) zone sensor module.
Remote Human Interface
The remote human interface (RHI) panel can perform all the same functions as the unit mounted human interface, except for the service mode. It uses the same two line x 40-character display and keypad as the HI. Also, the RHI can monitor up to four units.
Zone Temperature Sensor
A remote zone temperature sensor is available for use when using zone sensors for morning warmup (with all units or as a zone sensor with the Tracer
Integrated Comfort system).
Zone Sensor with Timed Override
A zone temperature sensor with timed override buttons is available for use with the Tracer Integrated Comfort system.
Zone Sensor with Local Setpoints
A zone temperature sensor with local temperature adjustment control and timed override buttons is available for use with the Tracer Integrated Comfort system or for use as a morning warmup setpoint and sensor.
Remote Minimum Position
Potentiometer Control
A remote minimum position potentiometer allows remote control of the minimum outside air damper position.
Dual Setpoint Sensor
The dual setpoint sensor is for use with zone heating and cooling setpoints, and supply air cooling and heating resets.
The zone sensor has two temperature setpoint levers and an auto-off system switch.
Dual Setpoint Sensor with System
Function Lights
The dual setpoint sensor is for use with zone heating and cooling setpoints, as well as supply air cooling and heating resets. The zone sensor has two temperature setpoint levers, an auto-off system switch, and status indication
LED lights for: system on, heat, cool, and service.
Space Relative Humidity Kit
The zone relative humidity sensor initiates the dehumidification mode for zone dehumidification units. It can also reset the supply air-drying or zone relative humidity setpoints.
Carbon Dioxide Sensor
The carbon dioxide sensor is fieldinstalled. It monitors carbon dioxide concentrations and displays on the human interface panel.
Dry-bulb Duct Sensor
This field-installed bullet-type sensor option is for use as a temperature input from a location such as a return air duct.
115
A business of American Standard Inc.
www.trane.com
Literature Order Number
File Number
Supersedes
Stocking Location
For more information contact your local Trane office or email comfort@trane.com
MUA-PRC004-EN
PL-AH-MUA-PRC004-EN 1202
MUA-PRC004-EN 0402
LaCrosse–Inland
Trane has a policy of continuous product improvement, and reserves the right to change designs and specifications without notice.