Relay Socket for Industrial Relay

advertisement
Relay Socket for Industrial Relay
1/2
for Relay (2 and 4 changeover contacts)
Data sheet
42
A2
32
22
A1
12
Item-No.
Description
Relay socket for 2 and 4 CO industrial relays
858-100
•
Relay socket for DIN 35 carrier rails.
Technical Data
•
For industrial relays with standard pinning.
•
Contact side and coil connections are separated from
each other.
Input nominal voltage UN
max. switching voltage
max. continuous current
•
Status indication through pluggable LED module (red).
(Accessory).
•
CAGE CLAMP® CCSC connection.
•
Quick exchange of the relay and the status indication
during maintenance, without having to detach the wiring.
•
Safe electrical isolation in accordance with DIN VDE 0140
Part 1. (Relay-dependently)
44
41
34
24
14
31
21
11
Pack.-unit
pcs
1
Relay-dependently, max. AC 250 V
AC 250 V
4 x 8 A (4 changeover contacts)
2 x 12 A (2 changeover contacts)
AC 4000 VA
100 % continuous duty
max. switching power
Operation at normal rating
Dielectric strength
contact/coil (1.2/50 µs)
4 kV (Relay-dependently)
Nominal voltage acc. to
VDE 0110 Part1 / 4.97
IEC 60664-1
250 V / 4 kV / 2
Degree of protection
IP 20
Ambient operating temperature -25 °C ... +70 °C (Relay-dependently)
Storage temperature
-40 °C ... +80 °C
Dimensions (WxHxD)
(31 x 39* x 97) mm (Relay-dependently)
* from upper edge of DIN 35 rail
Note: Inductive loads have to be attenuated by
an appropriate protective circuit in order to
protect relay coils and contacts !
WAGO Kontakttechnik GmbH & Co. KG
Subject to design changes
10.11.2009 / dt10000e.doc
Postfach 2880 • D-32385 Minden
Hansastr. 27 • D-32423 Minden
Tel.:
Fax.:
05 71 / 8 87-0
E-Mail:
05 71 / 8 87-169 Web:
info@wago.com
http://www.wago.com
Relay Socket for Industrial Relay
2/2
for Relay (2 and 4 changeover contacts)
Data sheet
Wire connection
Retaining clip (Accessory)
CAGE CLAMP® CCSC
0.34-1.5 mm² / AWG 22-16
9-10 mm / 0.37 in
Stripped length
Standards / prescriptions
Accessories:
Retaining clip for relay
Operation indicator DC 24 V
Operation indicator AC 115 V
Operation indicator AC 230 V
Relay:
1. Industrial relay
Indicator (Accessory)
2. Industrial relay
3. Industrial relay
4. Industrial relay
Relay (Accessory)
WAGO Kontakttechnik GmbH & Co. KG
Subject to design changes
10.11.2009 / dt10000e.doc
Postfach 2880 • D-32385 Minden
Hansastr. 27 • D-32423 Minden
Tel.:
Fax.:
IEC60664 / IEC60664A / DIN VDE0110
Pollution degree 2
Overvoltage category 2
858-110
788-120
788-124
788-125
858-150
4 changeover contacts coil DC24 V
28 x 21 mm, max. 36 mm height
e.g. Hongfa JZX
858-151
4 changeover contacts coil AC230 V
28 x 21 mm, max. 36 mm height
e.g. Hongfa JZX
858-152
4 changeover contacts coil DC24 V (Au)
28 x 21 mm, max. 36 mm height
e.g. Hongfa JZX
858-153
4 changeover contact coil AC230V (Au)
28 x 21 mm, max. 36 mm height
e.g. Hongfa JZX
05 71 / 8 87-0
E-Mail:
05 71 / 8 87-169 Web:
info@wago.com
http://www.wago.com
Download