Low Voltage A GE Power Controls Company ME 07 - Air Circuit Breakers ME 07 Air Circuit Breakers Low Voltage AEG Niederspannungstechnik GmbH & Co KG Berliner Platz 2-6 D-24534 Neumünster (Germany) Tel. +49/4321201-0 Fax +49/4321201-144 Low Voltage Ref. I/3070/E/X 7.0 Ed. 01/99 A GE Power Controls Company ME07 - Air circuit breakers Contents 3 Ranges 4 Fixed circuit breaker 5 Withdrawable circuit breaker 7 Technical data 7 Economy range N 8 Standard range S1/S 10 High performance range H 11 Busbars 12 Electronic trip units type bse 15 Drives 17 Auxiliary trips 18 Auxiliary switches 19 Withdrawable technique 20 How to order 21 Special versions 21 Up to 1000V AC 22 Up to 750V DC 23 Up to 1200V/1500V DC 24 Order codes 46 Trip curves 48 Wiring diagrams 68 Overall dimensions 121 Numerical index 1 Notes 2 ME07 - Air circuit breakers Rated short-circuit breaking capacity at 415V according to IEC 947-2 100 80 Icu (kA) 60 40 H range S1/S range N range 6400 5000 4000 3200 2500 2000 1600 1250 1000 0 800 20 630 Air circuit breakers 630 to 6400A Ie (A) Three ranges of circuit breakers Series ME for time delayed selectivity with different breaking capacities in each frame size offer a compact and economic solution for all installations. Economy range N The economic solution for medium power distribution systems. Standard range S1/S The solution for heavy power distribution requirements with sufficiently high breaking capacity for complete time selective discrimination. High performance range H The compact solution for distribution of extremely high power levels up to 100 kA in industrial and marine installations in each frame size. Complete line • • • • • • • • • Compact, robust steel frame construction which reduces the space requirements within enclosures. Circuit breakers and disconnecting switches. 3- and 4-pole devices. Fixed and withdrawable versions. Appearance of the operator control panel in a modern industry design is identical for the complete productline. Drive mechanisms, trip units and accessories e.g. undervoltage trip, shunt trip and auxiliary contacts are common for all frame sizes. Manual or motor operated stored energy drive mechanism for direct and remote actuation. Microprocessor controlled trip units for all round protection. Bus connection. Conformity The circuit breakers Series ME07 comply with the standard “Low-voltage switchgear and controlgear” VDE 0660 Part 101, respectively IEC 947-2 and VDE 0113. The disconnecting switches Series MET are in accordance with the standard “Low-voltage switchgear and controlgear” VDE 0660 Part 107, respectively IEC 947-3 and VDE 0113. Certifications ABS BV DNV GL LRoS RINA RMRoS American Bureau of Shipping Bureau Veritas Det Norske Veritas German Lloyd Lloyd’s Register of Shipping Registro Italiano Navale Russian Maritime Register of Shipping Design and specifications are subject to change without notice. 3 ME07 - Air circuit breakers Fixed circuit breaker Description The circuit breaker Series ME is provided with an engaged latch mechanism with a trip-free feature housed in a steel frame construction. They are equipped with a hand operated drive mechanism, an electronic trip unit and auxiliary contacts. On request a wide range of accessories e.g. motor operated drive mechanism, auxiliary trips etc. can be ordered. The disconnecting switch Series MET is identical with the circuit breaker but non automatic. Degree of protection IP00, however IP54 can be achieved with an additional sealing kit for the door cut-out. Terminations are available at the rear in horizontal or vertical plane, the design is interchangeable (ME637 to ME3207). Horizontal connection for stationary mounting and withdrawable technique are the same (ME1607 to ME3207).The devices ME4007/5007 are equipped with horizontal terminals. Installation Base or rear mounting (vertical or horizontal traverse) is possible without additional parts. In combination with rear mounting and vertical terminations the use of two angular spacers is necessary to ensure the required creepage and clearance distances (ME637 to ME3207). The devices ME4007 to ME5007 allow only rear side mounting. Power supply Either on the upper or on the lower terminals. Wiring of control circuits on plug- and socket connectors, finger-safe. 4 ME07 - Air circuit breakers Withdrawable circuit breaker Description The Series ME withdrawable version consists of the both components circuit breaker and cradle. The withdrawable version enables three defined positions 1. Disconnected Both main and control circuits are disconnected. 2. Test The main circuit contacts are open and the control circuit contacts are connected to allow functional tests of the device. 3. Connected Both main and control circuit are connected. The main contacts are provided with a full and positive personnel protection. The position of the circuit breaker within the cradle can be optionally indicated by position switches for monitoring and electrical interlocking. A mechanical interlock operates directly on the latch mechanism to prevent the circuit breaker being inserted or withdrawn in the closed position. • Rated current up to 3200A After locating on the integrated telescopic extension rails and locking in the disconnected position the circuit breaker remains in this position. The electrical connection of the main circuit is achieved by a separate movable contact system operated by a cranking handle. It is located in a movable frame within the cradle. The position of the circuit breaker behind the switchboard door is independent of the positions disconnected, test and connected. The cradle is provided with a positively driven mechanical position indicator. • Rated current 4000 to 6400A After locating on the rails the circuit breaker is inserted or withdrawn by means of a cranking handle worm drive. For easier service or exchange of the circuit breaker an optional extension rail is available to draw out the breaker in front of the cradle. Installation • Rated current up to 3200A Base mounting of the cradle, terminations at the rear in horizontal, vertical or combined plane. Wiring of the control circuits on plug and socket connectors on the upper left side, finger safe, accessible from the front. Automatic contact in the test and connected position. Optional position indication switches on the upper right side are accessible from the front as well. • Rated current 4000 to 6400A Base mounting of cradle, terminations at the rear in horizontal or combined (upper horizontal, lower vertical) plane (4000A), in horizontal plane (5000A and 6400A). Easy wiring of the control circuit contacts and position indication switches. Power supply Either on the upper or on the lower terminals. 5 Notes 6 ME07 - Air circuit breakers Economy range N 3- and 4-pole Frame size Series ME Rated insulation voltage Ui Rated impulse withstand voltage Uimp Pollution degree Rated voltage Ue Rated current Ie Protection degree IP00 Temperature For use in enclosures with interior 40 °C (A) temperatures of 40 to 60ºC, 45 °C (A) the relevant IP00 values can be 50 °C (A) applied basically. Connection cross sections are to be rated to 55 °C (A) the rated current of the equipment. 60 °C (A) Rated breaking capacity Icn according to IEC 947-2 (RMS values) Power supply to top or bottom Icu = Ics 3 AC 400/415V (kA) cos ϕ Rated making capacity Icm Peak values 3 AC 400/415V (kA) Rated short 0.3s (kA) time current Icw 1.0s (kA) 3.0s (kA) Selectivity up to (kA) RMS values cos ϕ Total breaking time via bse trip unit - s channel (ms) via bse trip unit - k channel (ms) Number of poles Mechanical endurance without maintenance x103 ops. with maintenance x103 ops. Switching frequency ops. /h Total power losses (3-pole) at rated current and breaker at operating temperature fixed version (W) withdrawable version (W) 10 637N 807N AC 1000V 8 kV 3 Up to 3 AC 415V Fixed and withdrawable 1007N 1257N 20 1607N 2007N 30 2507N 40 3207N 630 630 630 630 630 800 800 800 800 800 1000 1000 1000 1000 1000 1250 1250 1250 1250 1250 1600 1600 1600 1600 1600 2000 1980 1920 1840 1760 2500 2500 2400 2360 2250 3200 3200 3200 3200 3100 30 0.25 30 0.25 30 0.25 30 0.25 35 0.25 35 0.25 40 0.25 40 0.25 63 30 30 20 30 0.25 63 30 30 20 30 0.25 63 30 30 20 30 0.25 63 30 30 20 30 0.25 73.5 35 35 30 35 0.25 73.5 35 35 30 35 0.25 84 40 40 35 40 0.25 84 40 40 35 40 0.25 65 45 3/4 65 45 3/4 65 45 3/4 65 45 3/4 65 45 3/4 65 45 3/4 65 45 3/4 65 45 3/- 5 10 60 5 10 60 5 10 60 5 10 60 5 10 60 5 10 60 2.5 5 30 2.5 5 30 75 110 105 162 145 234 205 344 230 444 325 503 405 600 445 708 7 ME07 - Air circuit breakers Standard range S1/S 3- and 4-pole Frame size Series ME Rated insulation voltage Ui Rated impulse withstand voltage Uimp Pollution degree Rated voltage Ue Rated current Ie Temperature Protection degree IP00 For use in enclosures with interior 40 °C (A) temperatures of 40 to 60ºC, 45 °C (A) the relevant IP00 values can be 50 °C (A) applied basically. Connection cross sections are to be rated to 55 °C (A) the rated current of the equipment. 60 °C (A) Rated breaking capacity Icn according to IEC 947-2 (RMS values) Power supply to top or bottom Icu = Ics 3 AC 400/415V (kA) cos ϕ 3 AC 500V (kA) cos ϕ 3 AC 690V (kA) cos ϕ Rated making capacity Icm Peak values 3 AC 400/415V (kA) 3 AC 500V (kA) 3 AC 690V (kA) Rated short time current Icw 0.3s (kA) 1.0s (kA) 3.0s (kA) Selectivity when “Switching ON” (kA) RMS values cos ϕ (making current trip type kse) Setting value kse-trip (RMS value) (kA) Selectivity with breaker “ON” (kA) cos ϕ Total breaking time via kse trip (ms) via bse trip unit - s channel (ms) via bse trip unit - k channel (ms) Number of poles Mechanical endurance without maintenance x103 ops. with maintenance x103 ops. Switching frequency ops. /h Total power losses (3-pole) at rated current and breaker at operating temperature fixed version (W) withdrawable version (W) (1) Second value for 4th pole 8 10 637S1 807S1 1007S1 AC 1000V 8 kV 3 Up to 3 AC 690V Fixed and withdrawable 1257S1 20 1607S1 2007S1 30 2507S1 40 3207S1 630 630 630 630 630 800 800 800 800 800 1000 1000 1000 1000 1000 1250 1250 1250 1250 1250 1600 1600 1600 1600 1600 2000 1980 1920 1840 1760 2500 2500 2400 2360 2250 3200/2000(1) 3200/1980 3200/1920 3200/1840 3100/1760 III- IV-pole 50 0.25 50 0.25 50 0.25 50 0.25 50 0.25 50 0.25 50 0.25 50 0.25 50 0.25 50 0.25 50 0.25 50 0.25 55 0.25 55 0.25 55 0.25 55 0.25 55 0.25 55 0.25 65 0.2 65 0.2 65 0.2 70 0.2 70 0.2 70 0.2 105 105 105 105 105 105 105 105 105 105 105 105 121 121 121 121 121 121 143 143 143 154 143/121(1) 154 143/121 154 143/121 50 50 20 23 0.25 50 50 20 23 0.25 50 50 20 23 0.25 50 50 20 23 0.25 55 55 30 30 0.25 55 55 30 30 0.25 65 55 35 35 0.25 70 65/55(1) 65 65/55 40 40/30 40 0.25 35 50 0.25 35 50 0.25 35 50 0.25 35 50 0.25 45 55 0.2 45 55 0.2 52 65 0.2 60 70 0.2 20 65 45 3/4 20 65 45 3/4 20 65 45 3/4 20 65 45 3/4 20 65 45 3/4 20 65 45 3/4 20 65 45 3/4 20 65 45 3/4 10 20 60 10 20 60 10 20 60 10 20 60 10 20 60 10 20 60 5 10 30 5 10 30 75 110 105 162 145 234 205 344 230 444 325 503 405 600 445 708 65/55 (1) 0.2/0.25 65/55 0.2/0.25 65/55 0.2/0.25 ME07 - Air circuit breakers 50 4007S 60 5007S 70 6307S Withdrawable 4000 4000 4000 – – 5000 5000 5000 – – 6400 6300 6300 – – 100 0.2 100 0.2 100 0.2 100 0.2 100 0.2 100 0.2 100 0.2 100 0.2 100 0.2 220 220 220 220 220 220 220 220 220 100 100 55 – – 100 100 55 – – 100 100 55 – – – 100 0.2 – 100 0.2 – 100 0.2 – 50 40 3/4 – 50 40 3/- – 50 40 3/- 2.5 5 30 2.5 5 30 2.5 5 30 540 705 670 975 – 1510 9 ME07 - Air circuit breakers High performance range H 3- and 4-pole Frame size Series ME Rated insulation voltage Ui Rated impulse withstand voltage Uimp Pollution degree Rated voltage Ie Rated current Ie Temperature Protection degree IP00 For use in enclosures with interior 40 °C (A) temperatures of 40 to 60ºC, 45 °C (A) the relevant IP00 values can be 50 °C (A) applied basically. Connection cross sections are to be rated to 55 °C (A) the rated current of the equipment. 60 °C (A) Rated breaking 3 AC 400/415V (kA) capacity Icn according cos ϕ to IEC 947-2 3 AC 440V (kA) (RMS values) cos ϕ Power supply to top or bottom 3 AC 500V (kA) Icu = Ics cos ϕ 3 AC 690V (kA) cos ϕ 3 AC 1000V(4) (kA) cos ϕ DC 220V, T = L/R = 15 ms(1) (kA) (1) DC 440V, T = L/R = 15 ms (kA) DC 750V, T = L/R = 15 ms(1) (kA) Rated making 3 AC 400/415V (kA) capacity Icm 3 AC 440V (kA) Peak values 3 AC 500V (kA) 3 AC 690V (kA) 3 AC 1000V (kA) Rated short time 0,3s (kA) current Icw 1,0s (kA) 3,0s (kA) Selectivity up to (at ON operation as well) RMS values cos ϕ Instantaneous short circuit trip type ks RMS values (kA) Peak values (kA) Total breaking via ks trip (ms) time via bse trip unit - s channel (ms) via bse trip unit - k channel (ms) Number of poles Mechanical without maintenance x103 ops. endurance with maintenance x103 ops. Switching frequency ops. /h Total power losses (3-pole) at rated current and breaker at operating temperature fixed version (W) withdrawable version (W) 10 673H 807H 1007H 1275H AC 1000V 8 kV 3 Up to 3 AC 1000V / up to DC 750V(1) Fixed and withdrawable 20 1607H 630 630 630 630 630 100(2) 0.2 100(2) 0.2 70 0.2 50 0.25 25 0.25 50 40 20 220 220 154 105 52.5 50 50 20 23 0.25 800 800 800 800 800 100(2) 0.2 100(2) 0.2 70 0.2 50 0.25 25 0.25 50 40 20 220 220 154 105 52.5 50 50 20 23 0.25 1000 1000 1000 1000 1000 100(2) 0.2 100(2) 0.2 70 0.2 50 0.25 25 0.25 50 40 20 220 220 154 105 52.5 50 50 20 23 0.25 1250 1250 1250 1250 1250 100(2) 0.2 100(2) 0.2 70 0.2 50 0.25 25 0.25 50 40 20 220 220 154 105 52.5 50 50 20 23 0.25 35 50 20 65 45 3/4 10 20 60 35 50 20 65 45 3/4 10 20 60 35 50 20 65 45 3/4 10 20 60 75 110 105 162 145 234 (1) (2) (3) (4) 10 2007H 30 2507H 40 3207H 1600 1600 1600 1600 1600 100 0.2 100 0.2 80 0.2 60 0.25 35 0.25 60 45 20 220 220 176 132 73.5 55 55 30 30 0.25 2000 1980 1920 1840 1760 100 0.2 100 0.2 80 0.2 60 0.25 35 0.25 60 45 20 220 220 176 132 73.5 55 55 30 30 0.25 2500 2500 2400 2360 2250 100 0.2 100 0.2 90 0.2 75 0.25 40 0.25 60 45 30 220 220 198 165 84 65 55 35 35 0.25 3200/2000(3) 3200/1980 3200/1920 3200/1840 3100/1760 100/100(3) 0.2/0.2 100/100 0.2/0.2 90/80 0.2/0.2 80/60 0.2/0.25 50 0.25 65/60 50/45 30/20 220/220 220/220 198/176 176/132 105/73.5 70/55 65/55 40/30 40/30 0.25/0.25 35 50 20 65 45 3/4 10 20 60 45 63 20 65 45 3/4 10 20 60 45 63 20 65 45 3/4 10 20 60 52 74 20 65 45 3/4 5 10 30 60/45 85/63 20 65 45 3/4 5 10 30 205 344 230 444 325 503 405 600 445 708 For DC applications see section Air circuit breakers Series ME07 for DC Applications Withdrawable version - Icu 80kA Second value for 4th pole Only 3-pole version on request with horizontal termination, power supply upper terminals only, see also Air circuit breakers Series ME07 for AC 1000V on page 21 ME07 - Air circuit breakers Terminal dimensions and cross section of copper busbars Frame size 10 Series ME 637 Ie (A) 630 Terminals (mm) 40x20 Busbars (mm) 1x40x8 Copper black painted (mm2) 320 807 800 40x20 1x40x10 400 1007 1000 40x20 1x40x12 480 1257 1250 40x20 2x40x10 800 20 1607 1600 60x20 2x50x10 1000 2007 2000 60x20 2x60x12 1440 30 2507 2500 80x20 2x80x12 1920 40 3207 3200 130x20 4x60x12 2880 50 4007 4000 190x20 6x60x12 4320 60 5007 5000 255x20 8x60x12 5760 70 6307 6400 3x120x12 6x120x12 8640 11 ME07 - Air circuit breakers Electronic trip units type bse Protection The electronic trip units offer the protection as specified below: • Overload, current depending time delay - b-Channel • Short-circuit, current independent time delay, adjustable - s-Channel • Short-circuit, instantaneous- k-Channel • Short-circuit with ZSI - Zone selective interlock. This interlocking feature monitors the signal states of circuit breakers connected in series to reduce the pre-set delay time to a minimum and optimise the scheme for selectivity (see figure below). • Earth fault, current independent time delay, adjustable - g-Channel The electronic trip units type bse 3-x rms and bse 4-x rms are designed for applications in networks with harmonics and comply with the standard IEC 947-2, Appendix F. Level A ME07 Construction The electronic tripping system consists of the components • trip unit and • current transformers. The components are separately integrated into the circuit breaker. The current transformers supply the protection device of the trip unit and generate the output signal for the measuring unit. Level B ME07 Signalling line The principle of construction and function is shown in figure below. Level C ME07 Block diagram ZSI - Zone selective interlock The trip units are available for 3 and 4 pole circuit breakers. The adaptation to the different rated currents is realised by the corresponding current transformers. The sampler receives the output signal from the current transformer and transfers the information to the Analog - Digital - Converter. The processing unit analyses the signal and compares the results with the parameter settings. In case of a fault condition, e.g. overload, the activator will be energised to trip the circuit breaker. The current transformer output signal for each phase is sampled 15 times per cycle in order to establish a TRUE RMS value of the current independent of the network, type of load or installation. 12 The current transformer for the 4th pole of the trip unit is fitted inside the 4 pole version of the circuit breaker. On request a separately mounting outside the breaker e.g. in the neutral phase is possible. Then the connection between current transformer and trip unit must be field installed by applicant. Contacts for TRIP indication are provided as well as TRIP indication LED’s for types bse 3/4-3 rms to bse 3/4-6 rms. For additional functions like indication, parameterizing, messages and BUSconnection (if available) an auxiliary power supply is necessary. ME07 - Air circuit breakers Functions Type b-Channel adjustable Long time delay fixed on 20sec Long time delay adjustable within 5...40 sec Long time delay adjustable within 5...35 sec Overload memory (ON/OFF) Overload memory (ON/OFF) via BUS Unbalanced load/ Phase loss sensitivity (ON/OFF) Unbalanced load/ Phase loss sensitivity (ON/OFF) via BUS Contact for indication TRIPPED Indication TRIPPED via BUS s-Channel adjustable Time delay adjustable I2t -tripping characteristic (ON/OFF) Contact for indication TRIPPED Indication TRIPPED via BUS Contact for immediate indication of s-channel threshold k-Channel (ON/OFF) Setting fixed Setting adjustable Contact for indication TRIPPED Indication TRIPPED via BUS g-Channel (Earth fault) (ONOFF) Time delay adjustable I2t -tripping characteristic (ON/OFF) Contact for indication TRIPPED Indication TRIPPED via BUS v-Channel (pre-alarm value adjustable via BUS) Time delay adjustable via BUS Indication via BUS Indications bs-Channel Contact for indication TRIPPED (approx. 20ms if spring system is charged) b-Channel with LED indication and contact (1 NO) for indication TRIPPED s- Channel with LED indication and contact (1 NO) for indication TRIPPED k- Channel with LED indication and contact (1 NO) for indication TRIPPED g- Channel with LED indication and contact (1 NO) for indication TRIPPED RESET button Remote reset (24...230V AC/DC) Auxiliary voltage 24 V DC ± 15% 60 to 230 V AC ZSI (ON/OFF) Watchdog (ON/OFF) BUS connection Test socket bse 3-1 rms bse 4-1 rms • • – – – – – bse 3-2 rms bse 4-2 rms • • – – – – – bse 3-3 rms bse 4-3 rms • – • – – – – bse 3-3.1 rms bse 4-3.1 rms • – • – – – – bse 3-4 rms bse 4-4 rms • – • – – – – bse 3-5 rms bse 4-5 rms • – • – – – – bse 3-6 rms bse 4-6 rms • – – • • – • bse 3-7 rms bse 4-7 rms • – – • – • – – – – – – – – • – – • – – – – – – – • • – – – – • – • • – • – • • – • • – • – • • – • • – • – • • – • • – • – • • – • • • • – • – • • • • • • • – – – – – – – – – – – – – – – – – – – – – – – – – – • • – • – – – – – – – – – • • – • – – – – – – – – – • • – • – • • – • – – – – • • – • – • • – • – – – – • – • • – • • • • – – – – • – • – • • • • – • • • • o o – – – – – – – – • • • • • • – – • • • • • • – – • • • • • • – – – – • • • • – – – – – – – • – – – – – – – • • – • • – – – • • – • • • – – • • – • – – – – • • – • – • – – • • • • – • • – • • • • – • • • • o - accessory to be ordered separately 13 ME07 - Air circuit breakers Electronic trip units type bse Channels and settings Overload channel type b Earth fault channel type g bse 3/4-1 rms to bse 3/4-5 rms: centrally adjustable in 10 steps within 0.4 to 1.0 Ict (Ict = rated current of current transformer) bse 3/4-6 rms: centrally adjustable in 10 steps within 0.45 to 1.0 Ict Adjustable in 7 steps within 0.2 to 0.8 times Ict (for use of settings 0.2 to 0.3 times Ict an external power supply is necessary) with a time delay function adjustable within 0.1 to 0.3 sec bse 3/4-7 rms: adjustable via bus or RS-232 within 0.5 to 1.0 Ict bse 3/4-4 ms to bse 3/4-6 rms: centrally setting bse 3/4-7 : setting via bus or RS-232 Long time delay bse 3/4-1 rms to bse 3/4-2 rms: fixed setting 20 sec Pre-alarm channel type v bse 3/4-3 rms to bse 3/4-6 rms: centrally adjustable in 8 steps within 5 to 40 sec. bse 3/4-6 rms: centrally adjustable in 8 steps within 5 to 35 sec, OFF Available only on bse 3/4-7 rms, current independent delayed signal adjustable within 0.8 to 0.95 times of operating current setting Ib in steps of 0.05 times Ib, time delay adjustable within 25 to 100sec in 4 steps, setting via BUS or RS-232. bse 3/4-7 rms: adjustable via bus or RS-232 within 5 to 40 sec, ON/OFF switchable Trip indications Short-circuit channel type s bse 3/4-1 rms to bse 3/4-2 rms: Trip indications by microswitch 1NO with automatic reset, short time contact 15 to 20ms if spring energy system charged. bse 3/4-1 rms to bse 3/4-5 rms At Ie up to 1250A 2500A 3200A 4000A 5000A 6400A within 1.5 to 14 times Ict in 14 steps within 1.5 to 8 times Ict in 10 steps within 1.5 to 5 times Ict in 7 steps within 1.5 to 4 times Ict in 6 steps within 1.5 to 3 times Ict in 3 steps within 1.5 to 3 times Ict in 3 steps bse3/4-3 rms to bse3/4-6 rms: Trip indication by LED and potential free, bistabile relay contact 1NC of the relevant channel (b, s, k or g) that initiated tripping. An auxiliary power supply is necessary for reset. The trip unit is provided with a potential free monostabile relay contact 1NC for the indication of s-channel threshold, ZSI and watchdog (bse3/4-6 only) . bse3/4-7 rms: Messages on operation, failures, disturbances, alarms and maintenance requirements are available via BUS, e.g. trip indication on the relevant channels, s-channel pre-alarm, v-channel, ZSI messages and watchdog are additionally signalled by potential free relay contacts bse 3/4-6 rms At Ie up to 1250A 2500A 3200A 4000A 5000A 6400A within 1.5 to 14 times Ict in 10 steps within 1.5 to 8 times Ict in 8 steps within 1.5 to 5 times Ict in 5 steps within 1.5 to 4 times Ict in 4 steps within 1.5 to 3 times Ict in 3 steps within 1.5 to 3 times Ict in 3 steps bse 3/4-1 rms to bse 3/4-6 rms: centrally adjustable bse 3/4-7 rms: adjustable via bus or RS232 Technical data Power consumption Type Trip unit 24VDC ±15% bse 3/4 - 3 rms to 0.6W bse 3/4 - 5 rms bse 3/4 - 6 rms 1.5W bse 3/4 - 7 rms 3.6W bse 3/4 - 3 rms to bse 3/4 - 7 rms Trip unit 60 ... 230VAC 0.6W Relays LED - - - 30mA 5mA Short time delay bse 3/4-2 rms to bse 3/4-5 rms: centrally adjustable within 30 to 300ms bse 3/4-6 rms: centrally adjustable within 0 to 300ms bse 3/4-7 rms: adjustable via bus or RS-232 within 0 to 300ms Short-circuit channel type k Instantaneously acting short circuit channel, can be switched OFF bse 3/4-3 rms to bse 3/4-5 rms: fixed setting At Ie up to 1250A 2500A 3200A 5000/6400A 18 times Ict 10 times Ict 7 times Ict 10 times Ict bse 3/4-6 rms to bse 3/4-7 rms: centrally adjustable on trip unit At Ie up to 1250A 2500A 3200A 4000A 5000/6400A 14 within 4 to 18 times Ict in 6 steps, OFF within 4 to 10 times Ict in 4 steps, OFF within 4 to 7 times Ict in 3 steps , OFF within 4 to 10 times Ict in 4 steps , OFF within 4 to 10 times Ict in 4 steps, OFF Trip indication switch bse 3-1/4-1, bse 3-2/4-2 rms Rated operating voltage Uc (V) AC - rated current ohmic (A) AC - rated current inductive (A) bse 3-3/4-3 to bse3-7/4-7 rms (V) Rated operating voltage Uc Rated current AC-11 (A) Rated current DC-11 (mA) 250 6 2 24 to 110 24 to 230 – max. 1 200 – ME07 - Air circuit breakers Drives The drive mechanism with an energy storage facility is equipped with integral service facilities for immediate actuation without any additional coupling parts, e.g. through a door cut-out. Opening and closing action of the circuit breaker is made by pushbuttons. A positive operated indicator of the switch position and spring charge condition is provided along with a wide field of visibility to the trip unit. Mechanism: ON operation mechanically with ON pushbutton or electrically with closing coil. OFF operation mechanically with OFF pushbutton or electrically with undervoltage- or shunt trip. Interlock with cylindrical lock or padlock All mechanisms provided with a closing coil are suitable for synchronisation applications. Manual operated mechanism with storage type x2, xv The spring energy storage is charged by a pumping handle. The closing action is performed mechanically by means of the ON pushbutton or electrically by actuating the closing coil from a remote position. Indication switch type m3 - Spring energy system charged - optional Indication switch type m4 - Breaker ready for closure - optional Motor operated mechanism with storage type fv and automatic control unit The spring energy storage is charged by a motor drive. The automatic control unit operating with a short control impulse (app. 20 ms) disconnects the motor from supply after the spring is charged. The remote ON-operation is performed by actuating the closing coil. Manual charging and ON or OFF operations are possible as well. The indication “Spring energy system charged“ is included in control unit, indication switch type m4 - “Breaker ready for closure” is optional available. Five charging modes are available which can subsequently be changed in the field Type fv1 Type fv2 Type fv3.1 Type fv3.2 Type fv4 Separate commands for charging and closing Automatic charging after circuit breaker is opened. Automatic charging after circuit breaker is closed with manual first-charging Automatic charging after circuit breaker is closed with automatic first-changing Automatic closing when spring is charged. 15 ME07 - Air circuit breakers Drives (continued) Technical data Motor charging time of spring energy storage: 3 to 6 sec Min. control impulse time: > 20 ms Closing time: < 40 ms Motor operated drive mechanism Operating range (Uc) (V) Rated control voltage Uc Current 50/60Hz Power input (VA) Current input (making) (A) Current input (200ms) (A) Current DC Power input (W) Current input (making) (A) Current input (200ms) (A) Closing coil Operating range Rated control voltage Uc Current 50/60Hz Power input Current input Current DC Power input Current input 085 - 1.1 24 42 48 60 110 - 120 125 220 - 240 – – – – – – – – – 450 12.9 3.8 – – – max. 500 7.5 2.7 410 21 8.5 420 440 19 11 7 4 500 12 4 max. 440 5.5 2 (Uc) 0,85 - 1,1 (V) 24 42 48 60 (VA) 350 350 (A) 14.6 8.3 350 7.3 350 350 5.8 3.2 185 3.8 185 185 3.1 1.7 300 20 7 400 – 32 – 16.5 – (W) 185 (A) 7.7 – – 110 - 120 125 Indication switch m3 - “Spring energy storage charged” (potential free and potential tied) Rated operating voltage Uc (V) 30 120 240 250(1) AC - rated current Ohmic (A) – 10 7.5 6 Inductive (cos w = 0,3) (A) – 7.5 5 1.5 DC rated current Ohmic (A) 10 – – – Inductive (L/R=7ms) (A) 7.5 – – – (1) Valid only for manual operated drive mechanism Indication switch m4 - “Breaker ready for closure” (V) 24 50 110 Rated operating voltage Uc AC - rated current Ohmic (A) – – – Inductive (A) – – – DC rated current Inductive (A) 3 0.5 0.03 16 220 250 – – 5 5 0.03 – 220 220 - 240 – – – – 350 1.5 185 1.5 185 0.8 – – ME07 - Accessories Auxiliary trips Technical data Shunt trip Operating range Actuation time min/max. Rated control voltage Uc Current 50/60Hz Power input Current input Current DC Power input Current input The unit is suitable for remote tripping and short time rated. An integral microswitch is provided for self disconnecting from the power supply. Undervoltage trip continuous operation Operation range “Responding” Operation range “Releasing” Rated control voltage Uc Current 50/60Hz AC/DC Undervoltage trip type “r” Capacitor trip unit type “n” The unit is suitable for remote tripping, voltage monitoring and for interlocking purposes trip free. The circuit breaker cannot be closed manually or electrically if the trip is deenergised. Type n1 Type n2 Shunt trip and undervoltage trip facilitate the tripping of the circuit breaker from a remote position. Shunt trip type “a” Auxiliary trip combinations Max. 2 shunt trips and 1 undervoltage trip. Uc 0.7 to 1.1 20 ms / 5 s (V) 24 42 48 60 (VA) 350 350 (A) 14.6 8.3 350 7.3 350 350 5.8 3.2 185 3.8 48 420 (W) 185 (A) 7.7 – – 110...120 125 220 220 - 240 – – – – 350 1.5 185 185 3.1 1.7 185 1.5 185 0.8 – – 60 110 330 190 120/125 220 to 230 240 160 max. 90 80 100% Uc 0.85 to 1.1 Uc 0.7 to 0.35 (V) 24 42 (mA) 910 490 Rated voltage Uc 220/230V, operation range 0.85 to 1.1 Uc Rated voltage Uc 220/230V, operation range 0.0 to 1.1 Uc Time delay unit type “c” Rated voltage AC 50/60 Hz, 230V Rated voltage AC 50/60 Hz, 110V, 220V, 380V, 400V, 440V, 500V with separate transformer Accessories Capacitor trip unit type “n” • Type n1 - internal version mounted in the enclosure of the trip unit, acting directly on the latch mechanism of the circuit breaker, no external shunt trip type “a” is necessary. • Type n2 - external version mounted in a plastic enclosure for separate fitting. A shunt trip type “a” 220V DC is necessary for tripping the circuit breaker (not included, please order separately). Time delay unit type “c” for undervoltage trip type r mounted in the steel enclosure type CK1 for separate fitting, delay time tv=1.5 ± 0.5 s. An undervoltage trip type “r” 220V DC is necessary for tripping the circuit breaker (not included, please order separately). 17 ME07 - Accessories With cylindrical lock Auxiliary switches The auxiliary switches are actuated directly by the cross bar and switch simultaneously with the main contacts. Technical data Auxiliary switch Rated operational voltage Ue Rated insulation voltage Ui Continuous current Ith Rated operating Voltage Uc AC11 duty DC11 duty 500V 1000V 10A (V) 24 60 (A) – – (A) 10 4 Max. number of auxiliary contacts Key no. Frame size Breaker type Z 10 - 40 fixed/withdr. X 10 - 40 fixed/ withdr. V 10 - 40 fixed/ withdr. U 10 - 40 fixed/ withdr. C 50 - 60 fixed D 50 - 60 fixed E 50 - 60 fixed F 50 - 60 fixed G 50 - 70 withdr. H 50 - 70 withdr. J 50 - 70 withdr. K 50 - 70 withdr. 110 – 2 220 – 1 230 10 – Plug no. bse type Aux. contacts X1 / X2 3-1/3-2 5NO 6NC X1 / X2 3-3 5NO 5NC X1 / X2 3-3.1/3-4/3-5 4NO 4NC X1 / X2 3-6 3NO 4NC X1 / X2 3-1/3-2 5NO 6NC X1 / X2 3-3 5NO 5NC X1 / X2 3-3.1/3-4/3-5 4NO 4NC X1 / X2 3-6 3NO 4NC X20 3-1/3-2 5NO 6NC X20 3-3 5NO 5 NC X20 3-3.1/3-4/3-5 4NO 4 NC X20 3-6 3NO 4 NC Type y1 ON- and OFF push-button locked. The key is removable in both positions. The conditions of the breaker do not change when locked. Type y2 ON - push-button locked. The key is removable in both positions. By means of locking the circuit breaker is switching off being in the ON position. Type y3 ON - push-button locked. The key is removable in both positions. The conditions of the breaker do not change when locked. Type y7 ON- and OFF push-button locked. The key is removable only in the locked position. Functions like y1 Type y8 ON - push-button locked. The key is removable only in the locked position. Functions like y2 Type y9 ON - push-button locked. The key is removable only in the locked position. Functions like y3 For 3 padlocks (bow diameter 6 to 8 mm) Type y4 ON- and OFF push-button locked. Functions like y1 Type y5 ON - push-button locked. Functions like y2 Type y6 ON - push-button locked. Functions like y3 Sealing cover type “p” Covers protect the ON and OFF push-buttons against unauthorised actuation. Door adjustment frame type “ü” The frame compensates tolerances between door cut out and front cover, suitable for fixed and/or withdrawable circuit breakers. Sealing kit type “d” Mounting kit to achieve protection degree IP54 in door cut-out for pumping handle and trip unit cover. Locking devices Door interlock type “q” Interlock prevents opening of door when circuit breaker is closed, suitable for fixed installation (ME637 to ME3207) Angular spacer Two spacers are to be used for rear mounting in combination with vertical terminations to ensure the required creepage and clearance distances (ME637 to ME3207) Bowden wire interlock type “g1” Mounting kit for mechanical interlock of two circuit breakers for fixed installation (supplementary provide electrical interlock), installation alternatively side-by-side or superposed. Max. length of bowden wire: 2300 mm Cylindrical lock. Sealing cover Padlock. Sealing cover The locking devices type “y” are suitable for use on manual or motor operated mechanisms with a mechanical and if available an electrical interlock of the drive mechanism. 18 ME07 - Accessories Withdrawable technique Position indication switch Locking facility type “wi” The device prevents insertion of the cranking handle into the aperture by means of a cylindrical lock (ME637 to ME3207). Auxiliary switches are provided for monitoring the positions DISCONNECTED - TEST - CONNECTED of the circuit breaker in the cradle and are suitable for electrical interlocking purposes. ME637 to ME3207 A block is fitted on upright side of the cradle and contains max. 6 microswitches with 1CO contact each. ME4007 to ME6307 Max. 4 auxiliary switches type HS5 with 2 NC and 2 NO each can be mounted inside the cradle. (max. 3 auxiliary switches possible with cradle having vertical terminations, ME4007S only). Position indication switch Type ME Rated operating Voltage Uc (V) AC - Rated current Ohmic (A) Inductive (A) DC - Rated current Ohmic (A) Inductive (A) Locking facility type “we” This mechanical interlock prevents insertion of the cranking handle into the aperture when circuit breaker is in the ON position (ME637 to ME3207). Door sealing frame Mounting kit for actuation the circuit breaker with door closed. The kit is provided with a cover to prevent insertion of cranking handle (ME4007S to ME6307S) Bowden wire interlock type “g2” 637 to 3207 4007 to 6307 30 50 125 250 250 400 – – – – 25 15 25 15 – – 25 – 15 5 3 1 0.5 0.5 0.25 0.25 6 – – – Mounting kit for mechanical interlock of two circuit breakers for withdrawable pattern, (supplementary provide electrical interlock), installation alternatively side-by-side or superposed. Max length of bowden wire ME637 to ME3207: 1600 mm ME4007 to ME6307: 2200 mm Extension rail Allows the withdrawal of the circuit breaker to the front of the cradle, e.g. for maintenance (ME4007 to ME6307). Door interlocks The interlocks prevent door opening when the circuit breaker is in the ON and TEST position. ME637 to ME3207 Type lly Type lln Type lry Type lrn Door (hinged left side ) defeatable Door hinged (left side) not defeatable Door (hinged right side ) defeatable (1) Door (hinged right side) not defeatable (1) (1) 2 auxiliary switches (1NC and 1NO) have been dropped ME4007 to ME6307 Type ly Type ln Door defeatable Door not defeatable 19 ME07 - Air circuit breakers Specify on the order 1. Type 2. Line 3. Rated current 4. No. of poles 5. Version 6. Drive 7. Trip unit 8. Arc chute - Ceramic inserts 9. Auxiliary trips 10. Control voltage 11. Indication switch 12. Locking facilities 13. Miscellaneous 14. Cradle 15. Position indication switch 16. for ME637 to 3207 for ME4007 to 6307 16. Locking facilities 17. Withdrawable Version 17. Miscellaneous 20 Circuit breaker ❒ up to 500V ❒ up to 690V ❒ up to 1000V (only H-line) Disconnecting switch ❒ up to 500V ❒ up to 690V ❒ up to 1000V (only H-line) ❒ N (up to 415V) ❒ S1/S (only ME4007/6307) ❒H ❒ 250A ❒ 400A ❒ 630A ❒ 800A ❒ 1000A ❒ 1250A ❒ 1600A ❒ 2000A ❒ 2500A ❒ 3200A ❒ 4000A ❒ 5000A ❒ 6400A ❒ 3-pole ❒ 4-pole up to 4000A Neutral ❒ left or ❒ right (up to 2500A) ❒ Fixed - Termination horizontal ❒ Fixed - Termination vertical up to 3200A ❒ Withdrawable ❒ Manual operated Type x2 ❒ Manual operated Type xv ❒ Motor operated with automatic control ❒ Type fv1 ❒ Type fv2 ❒ Type fv3.1 ❒ Type fv3.2 ❒ Type fv4 Control voltage see item 10 ❒ bse 3-1 rms ❒ bse 3-2 rms ❒ bse 3-3 rms ❒ bse 3-3.1 rms ❒ bse 3-4 rms ❒ bse 3-5 rms ❒ bse 3-6 rms ❒ bse 3-7 rms ❒ bse 4-1 rms ❒ bse 4-2 rms ❒ bse 4-3 rms ❒ bse 4-3.1 rms ❒ bse 4-4 rms ❒ bse 4-5 rms ❒ bse 4-6 rms ❒ bse 4-7 rms ❒ only for S1 and H - Line up to 500V ❒ Undervoltage trip ❒ 1. Shunt trip ❒ 2. Shunt trip Control voltage see item 10 ❒ Time delay unit Type c, AC 50/60 Hz 230V ❒ Other voltage ______ V ❒ Internal capacitor trip unit Type n1, AC 220/230V ❒ External capacitor trip unit Type n2, AC 220/230V Motor Closing Coil UV trip 1./2. Shunt trip AC 50/60 Hz 42V ❒ ❒ ❒ ❒ / ❒ AC 50/60 Hz 110V ❒ ❒ ❒ ❒ / ❒ AC 50/60 Hz 220V ❒ ❒ ❒ ❒ / ❒ AC 50/60 Hz 230V ❒ ❒ ❒ ❒ / ❒ AC 50/60 Hz 240V ❒ ❒ ❒ ❒ / ❒ DC 24V ❒ ❒ ❒ ❒ / ❒ DC 48V ❒ ❒ ❒ ❒ / ❒ DC 60V ❒ ❒ ❒ ❒ / ❒ DC 110V ❒ ❒ ❒ ❒ / ❒ DC 125V ❒ ❒ ❒ ❒ / ❒ DC 220V ❒ ❒ ❒ ❒ / ❒ ❒ Trip Unit bse 3-1/4-1 rms, bse 3-2/4-2 rms - Indication m5: b+s Channel tripped ❒ Manual operated drive - Indication m3: spring energy storage charged ❒ Manual, motor operated drive with automatic control - Indication m4: breaker ready for closure. With cylindrical lock ❒ Type y1 ❒ Type y2 ❒ Type y3 ❒ Type y7 ❒ Type y8 ❒ Type y9 With 3 padlocks ❒ Type y4 ❒ Type y5 ❒ Type y6 ❒ Door interlock Type q ❒ Bowden wire interlock Type g1 ❒ Sealing cover Type p ❒ Door adjustment frame Type ü ❒ Sealing kit Type d ❒ Angular spacer ❒ Termination top/bottom vertical (ME637 tot ME3207) ❒ Termination top/bottom horizontal (ME 637 to ME 6307) ❒ Termination top horizontal/bottom vertical (ME 637 to ME4007S) ❒ 1CO ❒ Connected ____ ❒ 1 HS 5 ❒ Connected ____ ❒ 2CO ❒ 2 HS 5 ❒ 3CO ❒ Test ____ ❒ 3 HS 5 ❒ Test ____ Door interlock ❒ Type lly ❒ Type lln ME637 to ME3207 ME4007 to ME6307 ❒ Type ly ❒ Type ln ❒ Locking facility type wi (ME637 to ME3207) ❒ Locking facility type we (ME637 to ME3207) ❒ Bowden wire interlock Type g2 ❒ Door sealing frame (ME4007 to ME6307) ❒ Extension rail (ME4007 to ME6307) ❒ ❒ ❒ ❒ 4CO Isolated ____ 4 HS 5 Isolated ____ ❒ Type lry ❒ 5CO ❒ Type lrn ❒ 6CO ME07 - Special versions Up to 1000V AC Description The air circuit breakers are suitable for use in distributions of high power levels up to a rated voltage of AC 1000V. For these applications the standard types ME07H are provided with modified heightened arc chutes to cover the requirements at the higher rated voltage. Terminations are rear side suitable only for horizontal plane. Power supply can be either on upper or lower terminals. The fixed version of the circuit breaker can be mounted on the base without additional parts. A withdrawable version is not available. For accessories eg. motor drives, trip units, auxiliary trips please refer to the pages 12-18. Conformity The circuit breakers type ME07 comply with the standard “Low-voltage switchgear and controlgear” VDE 0660 Part 101, respectively IEC 947-2. Technical values Frame size Series ME Rated insulation voltage Ui Rated impulse withstand voltage Uimp Pollution degree Rated voltage Ue Rated current Ie Protection degree IP00 Temperature For use in enclosures with interior 40 °C (A) temperatures of 40 to 60ºC, 45 °C (A) the relevant IP00 values can be 50 °C (A) applied basically. Connection cross sections are to be rated to 55 °C (A) the rated current of the equipment. 60 °C (A) Rated breaking capacity Icn according to IEC 947-2 (RMS values) Power supply to top 3 AC 1000V (kA) Icu = Ics cos ϕ Rated making capacity Icm Peak values 3 AC 1000V (kA) 10 637H 807H AC 1000V 8 kV 3 Up to 3 AC 1000V Fixed 1007H 1257H 20 1607H 2007H 40 3207H 50 4007S (1)(2) 630 630 630 630 630 800 800 800 800 800 1000 1000 1000 1000 1000 1250 1250 1250 1250 1250 1600 1600 1600 1600 1600 2000 1980 1920 1840 1760 3200 3200 3200 3200 3100 4000 4000 4000 – – 30 0.25 30 0.25 30 0.25 30 0.25 35 0.25 35 0.25 50 0.25 55 0.2 63 63 63 63 73.5 73.5 105 121 (1) Power supply only on upper terminals. (2) Rated currents 5000A and 6300A on request. 21 ME07 - Special versions Up to 750V DC Description For DC applications up to DC 750 V the standard 3-pole types MET07H - 690V version can be selected. An external overcurrent release operating on a shunt trip or on an undervoltage trip must be provided for overload and short circuit protection. The release and the auxiliary trip is to order separately. For overcurrent releases, see below. Due to identical dimensions the circuit breakers are available as fixed and withdrawable types. For accessories e.g. motordrives, auxiliary trips, cradles, please refer to the pages 12-19. Installation +(–) The three pole breaker must be connected in the DC network as shown in the diagram. –(+) Power supply Power supply can be either on upper or lower terminals. Conformity Technical values Frame size Type ME Rated insulation voltage Ui Rated impulse withstand voltage Uimp Pollution degree Rated voltage Ue Rated current Ie Temperature Protection degree IP00 For use in enclosures with interior 40 °C (A) temperatures of 40 to 60ºC, 45 °C (A) the relevant IP00 values can be 50 °C (A) applied basically. Connection cross sections are to be rated to 55 °C (A) the rated current of the equipment. 60 °C (A) Rated breaking capacity Icn according to IEC 947-2 Power supply DC 220V, T = L/R = 15 ms (kA) to top DC 440V, T = L/R = 15 ms (kA) or bottom DC 750V, T = L/R = 15 ms (kA) Icu = Ics The circuit breakers series ME07 comply with the standard “Low-voltage switchgear and controlgear” VDE 0660 Part 101, respectively IEC 947-2. 10 637H 807H DC 1000V 8 kV 3 Up to DC 750V Fixed and withdrawable 1007H 1257H 20 1607H 2007H 30 2507H 40 3207H 630 630 630 630 630 800 800 800 800 800 1000 1000 1000 1000 1000 1250 1250 1250 1250 1250 1600 1600 1600 1600 1600 2000 1980 1920 1840 1760 2500 2500 2400 2360 2250 3200 3200 3200 3200 3100 50 40 20 50 40 20 50 40 20 50 40 20 60 45 20 60 45 20 60 45 30 65 50 30 Overcurrent release for DC The overcurrent release mounted separately consists of an electromagnetic system for short circuit protection operating on a micro switch (1CO). Technical data 22 Overcurrent release Rated insulation voltage Ui Rated voltage Ue Rated current Ie Adjusted setting values (continuously) DC 1500V up to DC 1500V 630-1250A 800/1200/1800A Micro switch Rated insulation voltage Ui Continuous current Ith Rated operating Voltage Uc AC-11 duty DC-11 duty (with arc deflector) 380V 10 60 — 3 (V) (A) (V) (A) (A) 110 — 0.6 1600-3600A 1600-3600 1600/2000/3000A 2500/3200/3600A 220 4 0.3 ME07 - Special versions Series MEG07 up to 1200V -1500V DC Description The air circuit breakers are suitable for use in DC distributions up to a rated voltage of DC 1200V (single pole breaking) and DC 1500V (two pole breaking in series). For these applications the standard 3-pole types MET07H are provided with modified heightened arc chutes to cover the requirements. The circuit breaker type MEG07 is equipped with an external overcurrent release operating on a shunt trip (standard) or if requested on a undervoltage trip (accessory). Details of overcurrent release see page 22. The disconnecting switch type MEGT07 is identical with the circuit breaker type but non automatic. For accessories e.g. motordrives, auxiliary trips please refer to pages 12-18. Installation Terminations are rear side suitable only for horizontal plane. The circuit breaker can be mounted on the base without additional parts. A withdrawable version is not available. Power supply 1200V: upper terminals / 1500V: either on upper or lower terminals. The circuit breaker must be connected in the DC network as shown in the diagrams below. 1200 V - Single pole breaking(2) + 1200 V - Single pole breaking for MEG 3207/10 and 5007/20 + – – 1500V - Single pole breaking - Two poles in series +(–) –(+) Conformity The circuit breakers type MEG07 comply with the standard “Low-voltage switchgear and controlgear” VDE 0660 Part 101, respectively IEC 947-2. The disconnecting switch MEGT07 comply with the standard “Low-voltage switchgear and control gear” VDE 0660 Part 107, respectively IEC 947-3. Technical values Frame Size Type MEG Rated insulation voltage Ui Rated impulse withstand voltage Uimp Pollution degree Rated voltage Ue Rated current Ie Protection degree IP00 Temperature For use in enclosures with interior 40 °C (A) temperatures of 40 to 60ºC, 45 °C (A) the relevant IP00 values can be 50 °C (A) applied basically. Connection cross sections are to be rated to the 55 °C (A) rated current of the equipment. 60 °C (A) Rated breaking capacity Icn according to IEC 947-2 Power supply to top DC 750V(3) (kA) DC 1200V (kA) Icu = Ics DC 1500V (kA) 10 20 1257 2007 DC 1500V 8 kV 3 Up to DC 1500V Fixed 40 3207 50 4007 60 5007 (1) 70 6307 (1) 1250 1250 1250 1250 1250 2000 1980 1920 1840 1760 3200 3200 3200 3200 3100 4000 4000 4000 5000 5000 5000 6400 6300 6300 30 20 30 20 35 25 40 25 45 30 45 30 10 3207/10 20 5007/20 DC 1200V(3) 3200 3200 3200 5000 5000 5000 10 30 - 10 20 - (1) On request (2) Two pole breaking on request (3) Version for stationary railway application acc. to EN 50123-2 and -3, only type MEGT for DC 750V 23 ME07 - Order codes Economy range N Circuit breaker type ME07 3-pole, 4-pole up to 415V AC Circuit breaker 3-pole, 4-pole equipped with: • current transformer • electronic trip unit type bse 3-1 rms • handoperated mechanism type X2 • 11 auxiliary contacts 5 NO, 6 NC(1) Neutral conductor Unprotected with bse 3-1 rms, alternatively 100%, 63% or 50% protection of main circuit with bse 4-1 rms. Please refer to ordering details electronic trip unit on page 39 (1) For other trip unit types please refer to table on page 18 24 Frame Type size Rated current of breaker Iu A 3-pole 10 ME637N 630 10 ME637N 630 10 ME637N 630 10 ME800N 800 10 ME1007N 1000 10 ME1257N 1250 20 ME1607N 1600 20 ME2007N 2000 30 ME2507N 2500 40 ME3207N 3200 4-pole - Neutral conductor left 10 ME637N/IV 630 10 ME637N/IV 630 10 ME637N/IV 630 10 ME800N/IV 800 10 ME1007N/IV 1000 10 ME1257N/V 1250 20 ME1607N/IV 1600 20 ME2007N/IV 2000 30 ME2507N/IV 2500 4-pole - Neutral conductor right 10 ME637N/IV 630 10 ME637N/IV 630 10 ME637N/IV 630 10 ME800N/IV 800 10 ME1007N/IV 1000 10 ME1257N/IV 1250 20 ME1607N/IV 1600 20 ME2007N/IV 2000 30 ME2507N/IV 2500 Rated current of current transformer ICT A Horizontal terminals Vertical terminals Ref. No. kg Ref. No. kg 250 400 630 800 1000 1250 1600 2000 2500 3200 758100 758102 758104 758106 758108 758110 758112 758114 758116 758118 44 44 44 45 45 46 52 52 76 89 758101 758103 758105 758107 758109 758111 758113 758115 758117 758119 47 47 47 48 50 53 62 62 90 109 250 400 630 800 1000 1250 1600 2000 2500 758516 758504 758472 758440 758997 758992 758267 758235 758166 59 59 59 60 60 61 73 73 88 758388 758394 758400 758408 758414 758421 758442 758448 758460 65 65 65 66 68 71 88 88 107 250 400 630 800 1000 1250 1600 2000 2500 758410 758412 758414 758416 758418 758420 758422 758424 758426 59 59 59 60 60 61 73 73 88 758411 758413 758415 758417 758419 758421 758423 758425 758427 65 65 65 66 68 71 88 88 107 ME07 - Order codes Standard range S1 Circuit breaker type ME07 3-pole, 4-pole up to 500VAC Circuit breaker 3-pole, 4-pole equipped with: • current transformer, • electronic trip unit type bse 3-1 rms • handoperated mechanism type X2 • 11 auxiliary contacts 5 NO, 6 NC(1) Neutral conductor Unprotected with bse 3-1 rms, 100%, 63% or 50% protection (ME637 to 2507S1/IV), 63% or 50% protection (ME3207S1/IV) of main circuit with bse 4-1 rms. Please refer to ordering details electronic trip unit on page 39 Frame Type size Rated current of breaker Iu A 3-pole 10 ME637S1 630 10 ME637S1 630 10 ME637S1 630 10 ME800S1 800 10 ME1007S1 1000 10 ME1257S1 1250 20 ME1607S1 1600 20 ME2007S1 2000 30 ME2507S1 2500 40 ME3207S1 3200 4-pole - Neutral conductor left 10 ME637S1/IV 630 10 ME637S1/IV 630 10 ME637S1/IV 630 10 ME800S1/IV 800 10 ME1007S1/IV 1000 10 ME1257S1/IV 1250 20 ME1607S1/IV 1600 20 ME2007S1/IV 2000 30 ME2507S1/IV 2500 40 ME3207S1IV 3200/2000 4-pole - Neutral conductor right 10 ME637S1/IV 630 10 ME637S1/IV 630 10 ME637S1/IV 630 10 ME800S1/IV 800 10 ME1007S1/IV 1000 10 ME1257S1/IV 1250 20 ME1607S1/IV 1600 20 ME2007S1/IV 2000 30 ME2507S1/IV 2500 Rated current of current transformer ICT A Horizontal terminals Vertical terminals Ref. No. kg Ref. No. kg 250 400 630 800 1000 1250 1600 2000 2500 3200 758140 758142 758144 758146 758148 758150 758152 758154 758156 758158 44 44 44 45 45 46 52 52 76 89 758141 758143 758145 758147 758149 758151 758153 758155 758157 758159 47 47 47 48 50 53 62 62 90 109 250 400 630 800 1000 1250 1600 2000 2500 3200/2000 758164 758496 758464 758999 758995 758990 758259 758227 758971 759540 59 59 59 60 60 61 73 73 88 104 758390 758395 758403 758409 758417 758423 758444 758449 758461 759541 65 65 65 66 68 71 88 88 107 128 250 400 630 800 1000 1250 1600 2000 2500 758430 758432 758434 758436 758438 758440 758442 758444 758446 59 59 59 60 60 61 73 73 88 758431 758433 758435 758437 758439 758441 758443 758445 758447 65 65 65 66 68 71 88 88 107 (1) For other trip unit types please refer to table on page 18 25 ME07 - Order codes High performance range H Circuit breaker type ME07 3-pole, 4-pole up to 500V AC Circuit breaker 3-pole, 4-pole equipped with: • current transformer • electronic trip unit type bse 3-1 rms • handoperated mechanism type X2 • 11 auxiliary contacts 5 NO, 6 NC(1) Neutral conductor Unprotected with bse 3-1 rms, 100%, 63% or 50% protection (ME637 to 2507H/IV), 63% or 50% protection (ME3207H/IV) of main circuit with bse 4-1 rms. Please refer to ordering details electronic trip unit on page 39 (1) For other trip unit types please refer to table on page 18 26 Frame Type size Rated current of breaker Iu A 3-pole 10 ME637H 630 10 ME637H 630 10 ME637H 630 10 ME800H 800 10 ME1007H 1000 10 ME1257H 1250 20 ME1607H 1600 20 ME2007H 2000 30 ME2507H 2500 40 ME3207H 3200 4-pole - Neutral conductor left 10 ME637H/IV 630 10 ME637H/IV 630 10 ME637H/IV 630 10 ME800H/IV 800 10 ME1007H/IV 1000 10 ME1257H/IV 1250 20 ME1607H/IV 1600 20 ME2007H/IV 2000 30 ME2507H/IV 2500 40 ME3207H/IV 3200/2000 4-pole - Neutral conductor right 10 ME637H/IV 630 10 ME637H/IV 630 10 ME637H/IV 630 10 ME800H/IV 800 10 ME1007H/IV 1000 10 ME1257H/IV 1250 20 ME1607H/IV 1600 20 ME2007H/IV 2000 30 ME2507H/IV 2500 Rated current of current transformer ICT A Horizontal terminals Vertical terminals Ref. No. kg Ref. No. kg 250 400 630 800 1000 1250 1600 2000 2500 3200 758190 758192 758194 758196 758198 758200 758202 758204 758206 758208 44 44 44 45 45 46 52 52 76 89 758191 758193 758195 758197 758199 758201 758203 758205 758207 758209 47 47 47 48 50 53 62 62 90 109 250 400 630 800 1000 1250 1600 2000 2500 3200/2000 758519 758514 758482 758383 758998 758386 758277 758981 758176 759543 59 59 59 60 60 61 73 73 88 104 758329 758331 758326 758406 758323 758420 758188 758447 758126 758229 65 65 65 66 68 71 88 88 107 128 250 400 630 800 1000 1250 1600 2000 2500 758450 758452 758454 758456 758458 758460 758462 758464 758466 59 59 59 60 60 61 73 73 88 758451 758453 758455 758457 758459 758461 758463 758465 758467 65 65 65 66 68 71 88 88 107 ME07 - Order codes Standard range S1/S Circuit breaker type ME07 3-pole, 4-pole up to 690V AC Frame Type size Circuit breaker 3-pole, 4-pole equipped with: • current transformer, • electronic trip unit type bse 3-1 rms • handoperated mechanism type X2 • 11 auxiliary contacts 5 NO, 6 NC(1) 3-pole 10 ME637S1 630 10 ME637S1 630 10 ME637S1 630 10 ME800S1 800 10 ME1007S1 1000 10 ME1257S1 1250 20 ME1607S1 1600 20 ME2007S1 2000 30 ME2507S1 2500 40 ME3207S1 3200 50 ME4007S 4000 60 ME5007S 5000 70 ME6307S(2) 6400 4-pole - Neutral conductor left 10 ME637S1/IV 630 10 ME637S1/IV 630 10 ME637S1/IV 630 10 ME800S1/IV 800 10 ME1007S1/IV 1000 10 ME1275S1/IV 1250 20 ME1607S1/IV 1600 20 ME2007S1/IV 2000 30 ME2507S1/IV 2500 40 ME3207S1IV 3200/2000 50 ME4007S/IV(3) 4000 4-pole - Neutral conductor right 10 ME637S1/IV 630 10 ME637S1/IV 630 10 ME637S1/IV 630 10 ME800S1/IV 800 10 ME1007S1/IV 1000 10 ME1257S1/IV 1250 20 ME1607S1/IV 1600 20 ME2007S1/IV 2000 30 ME2507S1/IV 2500 Neutral conductor Unprotected with bse 3-1 rms, 100%, 63% or 50% protection (ME637 to 2507S1/IV; ME4007S/ IV), 63% or 50% protection (ME3207S1/IV), of main circuit with bse 4-1 rms. Please refer to ordering details electronic trip unit on page 39 Rated current of breaker Iu A Rated current of current transformer ICT A Horizontal terminals Vertical terminals Ref. No. kg Ref. No. kg 250 400 630 800 1000 1250 1600 2000 2500 3200 4000 5000 6400 758570 758572 758574 758576 758578 758580 758582 758584 758586 758588 758160 758162 758726 44 44 44 45 45 46 52 52 76 89 145 175 205 758571 758573 758575 758577 758579 758581 758583 758585 758587 758589 – – – 47 47 47 48 50 53 62 62 90 109 – – – 250 400 630 800 1000 1250 1600 2000 2500 3200/2000 4000 758592 758594 758596 758598 758600 758602 758604 758606 758608 758610 759542 59 59 59 60 60 61 73 73 88 104 175 758593 758595 758597 758599 758601 758603 758605 758607 758609 758611 – 65 65 65 66 68 71 88 88 107 128 – 250 400 630 800 1000 1250 1600 2000 2500 758612 758614 758616 758618 758620 758622 758624 758626 758628 59 59 59 60 60 61 73 73 88 758613 758615 758617 758619 758621 758623 758625 758627 758629 65 65 65 66 68 71 88 88 107 (1) For other trip unit types please refer to table on page 18 (2) Only available with withdrawable technique (3) Type ME5007S/IV, 5000A withdrawable breaker on request 27 ME07 - Order codes High performance range H Circuit breaker type ME07 3-pole, 4-pole up to 690V AC Circuit breaker 3-pole, 4-pole equipped with: • current transformer • electronic trip unit type bse 3-1 rms • handoperated mechanism type X2 • 11 auxiliary contacts 5 NO, 6 NC(1) Neutral conductor Unprotected with bse 3-1 rms, 100%, 63% or 50% protection (ME637 to 2507H/IV), 63% or 50% protection (ME3207H/IV) of main circuit with bse 4-1 rms. Please refer to ordering details electronic trip unit on page 39 (1) For other trip unit types please refer to table on page 18 28 Frame Type size Rated current of breaker Iu A 3-pole 10 ME637H 630 10 ME637H 630 10 ME637H 630 10 ME800H 800 10 ME1007H 1000 10 ME1257H 1250 20 ME1607H 1600 20 ME2007H 2000 30 ME2507H 2500 40 ME3207H 3200 4-pole - Neutral conductor left 10 ME637H/IV 630 10 ME637H/IV 630 10 ME637H/IV 630 10 ME800H/IV 800 10 ME1007H/IV 1000 10 ME1257H/IV 1250 20 ME1607H/IV 1600 20 ME2007H/IV 2000 30 ME2507H/IV 2500 40 ME3207H/IV 3200/2000 4-pole - Neutral conductor right 10 ME637H/IV 630 10 ME637H/IV 630 10 ME637H/IV 630 10 ME800H/IV 800 10 ME1007H/IV 1000 10 ME1257H/IV 1250 20 ME1607H/IV 1600 20 ME2007H/IV 2000 30 ME2507H/IV 2500 Rated current of current transformer ICT A Horizontal terminals Vertical terminals Ref. No. kg Ref. No. kg 250 400 630 800 1000 1250 1600 2000 2500 3200 758630 758688 758634 758636 758638 758640 758642 758644 758646 758648 44 44 44 45 45 46 52 52 76 89 758568 758633 758635 758637 758639 758641 758643 758645 758647 758649 47 47 47 48 50 53 62 62 90 109 250 400 630 800 1000 1250 1600 2000 2500 3200/2000 758650 758652 758654 758656 758658 758660 758662 758664 758666 758668 59 59 59 60 60 61 73 73 88 104 758651 758653 758655 758657 758659 758661 758663 758665 758667 758669 65 65 65 66 68 71 88 88 107 128 250 400 630 800 1000 1250 1600 2000 2500 758670 758672 758674 758676 758678 758680 758582 758684 758686 59 59 59 60 60 61 73 73 88 758671 758673 758675 758677 758679 758681 758683 758685 758687 65 65 65 66 68 71 88 88 107 ME07 - Order codes High performance range H Standard range S Circuit breaker type ME07 3-pole, up to 1000V AC Frame Type size 3-pole 10 10 10 10 10 10 20 20 40 50 60 70 ME637H ME637H ME637H ME800H ME1007H ME1257H ME1607H ME2007H ME3207H ME4007S ME5007S ME6307S Rated current of breaker Iu A Rated current of current transformer ICT A Vertical terminals Heightened arc chute Ref. No. kg 630 630 630 800 1000 1250 1600 2000 3200 4000 5000 6400 250 400 630 800 1000 1250 1600 2000 3200 4000 5000 6400 784161 784162 784163 784164 784165 784166 784167 784168 784169 784170 784171 784172 57 57 57 58 58 59 65 65 113 190 233 266 (extended breaking capacity) Circuit breaker 3-pole equipped with: • current transformer • electronic trip unit type bse 3-1 rms • handoperated mechanism type X2 • 11 auxiliary contacts 5 NO, 6 NC(1) (without current transformer and electronic trip unit) (1) For other trip unit types please refer to table on page 18 29 MET07 - Order codes Economy range N Disconnecting switch type MET07 3-pole, 4-pole, up to 415V AC Disconnecting switch equipped with • handoperated mechanism type X2 • 11 auxiliary contacts 5 NO, 6 NC (without current transformer and electronic trip unit) 30 Frame Type size Rated current of switch Iu A 3-pole 10 MET637N 630 10 MET800N 800 10 MET1007N 1000 10 MET1257N 1250 20 MET1607N 1600 20 MET2007N 2000 30 MET2507N 2500 40 MET3207N 3200 4-pole - Neutral conductor left 10 MET637N/IV 630 10 MET800N/IV 800 10 MET1007N/IV 1000 10 MET1257N/IV 1250 20 MET1607N/IV 1600 20 MET2007N/IV 2000 30 MET2507N/IV 2500 4-pole - Neutral conductor right 10 MET637N/IV 630 10 MET800N/IV 800 10 MET1007N/IV 1000 10 MET1257N/IV 1250 20 MET1607N/IV 1600 20 MET2007N/IV 2000 30 MET2507N/IV 2500 Horizontal terminals Vertical terminals Ref. No. kg Ref. No. kg 758000 758002 758004 758006 758008 758010 758012 758014 40 41 41 42 48 48 71 83 758001 758228 758005 758007 758009 758011 758013 758015 43 44 46 48 58 58 85 102 758984 758256 758222 758358 758315 758217 758969 45 46 46 47 69 69 83 758370 758375 758380 758426 758433 758452 759304 61 62 64 67 84 84 102 758360 758362 758364 758366 758368 758370 758372 45 46 46 47 69 69 83 758361 758363 758365 758367 758369 758371 758373 61 62 64 67 84 84 102 MET07 - Order codes Standard range S1 Disconnecting switch type MET07 3-pole, 4-pole, up to 500V AC Disconnecting switch equipped with • handoperated mechanism type X2 • 11 auxiliary contacts 5 NO, 6 NC (without current transformer and electronic trip unit) Frame Type size Rated current of breaker Iu A 3-pole 10 MET637S1 630 10 MET800S1 800 10 MET1007S1 1000 10 MET1257S1 1250 20 MET1607S1 1600 20 MET2007S1 2000 30 MET2507S1 2500 40 MET3207S1 3200 4-pole - Neutral conductor left 10 MET637S1/IV 630 10 MET800S1/IV 800 10 MET1007S1/IV 1000 10 MET1257S1/IV 1250 20 MET1607S1/IV 1600 20 MET2007S1/IV 2000 30 MET2507S1/IV 2500 40 MET3207S1/IV 3200/2000 4-pole - Neutral conductor right 10 MET637S1/IV 630 10 MET800S1/IV 800 10 MET1007S1/IV 1000 10 MET1257S1/IV 1250 20 MET1607S1/IV 1600 20 MET2007S1/IV 2000 30 MET2507S1/IV 2500 Horizontal terminals Vertical terminals Ref. No. kg Ref. No. kg 758016 758018 758020 758022 758024 758026 758028 758030 40 41 41 42 48 48 71 83 758017 758019 758021 758023 758025 758027 758029 758031 43 44 46 48 58 58 85 102 758268 758248 758214 758989 758307 758979 758459 758080 45 46 46 47 69 69 83 98 758983 758231 758973 758427 758988 758453 758125 758081 61 62 64 67 84 84 102 122 758374 758376 758378 758380 758382 758384 758386 45 46 46 47 69 69 83 758375 758377 758379 758381 758383 758385 758387 61 62 64 67 84 84 102 31 MET07 - Order codes High performance range H Disconnecting switch type MET07 3-pole, 4-pole, up to 500V AC Disconnecting switch equipped with • handoperated mechanism type X2 • 11 auxiliary contacts 5 NO, 6 NC (without current transformer and electronic trip unit) 32 Frame Type size Rated current of switch Iu A 3-pole 10 MET637H 630 10 MET800H 800 10 MET1007H 1000 10 MET1257H 1250 20 MET1607H 1600 20 MET2007H 2000 30 MET2507H 2500 40 MET3207H 3200 4-pole - Neutral conductor left 10 MET637H/IV 630 10 MET800H/IV 800 10 MET1007H/IV 1000 10 MET1257H/IV 1250 20 MET1607H/IV 1600 20 MET2007H/IV 2000 30 MET2507H/IV 2500 40 MET3207H/IV 3200/2000 4-pole - Neutral conductor right 10 MET637H/IV 630 10 MET800H/IV 800 10 MET1007H/IV 1000 10 MET1257H/IV 1250 20 MET1607H/IV 1600 20 MET2007H/IV 2000 30 MET2507H/IV 2500 Horizontal terminals Vertical terminals Ref. No. kg Ref. No. kg 758036 758038 758040 758042 758044 758046 758048 758050 40 41 41 42 48 48 71 83 758037 758039 758041 758043 758045 758047 758049 758051 43 44 46 48 58 58 85 102 758985 758240 758977 758342 758299 758975 758132 758098 45 46 46 47 69 69 83 98 758257 758223 758631 758316 758986 758181 758965 758099 61 62 64 67 84 84 102 122 758388 758390 758392 758394 758396 758398 758400 45 46 46 47 69 69 83 758389 758391 758393 758395 758397 758399 758401 61 62 64 67 84 84 102 MET07 - Order codes Standard range S1/S Disconnecting switch type MET07 3-pole, 4-pole, up to 690V AC Disconnecting switch equipped with • handoperated mechanism type X2 • 11 auxiliary contacts 5 NO, 6 NC (without current transformer and electronic trip unit) Frame Type size Rated current of breaker Iu A 3-pole 10 MET637S1 630 10 MET800S1 800 10 MET1007S1 1000 10 MET1257S1 1250 20 MET1607S1 1600 20 MET2007S1 2000 30 MET2507S1 2500 40 MET3207S1 3200 50 MET4007S 4000 60 MET5007S 5000 6400 70 MET6307S(1) 4-pole - Neutral conductor left 10 MET637S1/IV 630 10 MET800S1/IV 800 10 MET1007S1/IV 1000 10 MET1257S1/IV 1250 20 MET1607S1/IV 1600 20 MET2007S1/IV 2000 30 MET2507S1/IV 2500 40 MET3207S1/IV 3200/2000 50 MET4007S/IV 4000 4-pole - Neutral conductor right 10 MET637S1/IV 630 10 MET800S1/IV 800 10 MET1007S1/IV 1000 10 MET1257S1/iV 1250 20 MET1607S1/IV 1600 20 MET2007S1/IV 2000 30 MET2507S1/IV 2500 Horizontal terminals Vertical terminals Ref. No. kg Ref. No. kg 759306 759307 758474 758476 758478 759308 759309 758484 758032 758034 758518 40 41 41 42 48 48 71 83 138 165 200 758471 758473 758475 758477 758479 758481 758483 758485 – – – 43 44 46 48 58 58 85 103 – – – 758488 758491 758492 759310 759311 758498 758500 759312 758082 45 46 46 47 69 69 83 98 165 758489 758490 758493 758495 758497 758499 758501 758503 – 61 62 64 67 84 84 102 122 – 758504 758506 758508 758510 758512 758514 758516 45 46 46 47 69 69 83 758505 758507 758509 758511 758513 758515 758517 61 62 64 67 84 84 102 (1) Only available with withdrawable technique. 33 MET07 - Order codes High performance range H Disconnecting switch type MET07 3-pole, 4-pole, up to 690V AC Disconnecting switch equipped with • handoperated mechanism type X2 • 11 auxiliary contacts 5 NO, 6 NC (without current transformer and electronic trip unit) 34 Frame Type size Rated current of switch Iu A 3-pole 10 MET637H 630 10 MET800H 800 10 MET1007H 1000 10 MET1257H 1250 20 MET1607H 1600 20 MET2007H 2000 30 MET2507H 2500 40 MET3207H 3200 4-pole - Neutral conductor left 10 MET637H/IV 630 10 MET800H/IV 800 10 MET1007H/IV 1000 10 MET1257H/IV 1250 20 MET1607H/IV 1600 20 MET2007H/IV 2000 30 MET2507H/IV 2500 40 MET3207H/IV 3200/2000 4-pole - Neutral conductor right 10 MET637H/IV 630 10 MET800H/IV 800 10 MET1007H/IV 1000 10 MET1257H/IV 1250 20 MET1607H/IV 1600 20 MET2007H/IV 2000 30 MET2507H/IV 2500 Horizontal terminals Vertical terminals Ref. No. kg Ref. No. kg 758520 758522 758524 758526 758528 758530 758532 758534 40 41 41 42 48 48 71 83 758521 758523 758525 758527 758529 758531 758533 758535 43 44 46 48 58 58 85 102 758536 758538 758540 758542 758544 758546 758548 758550 45 46 46 47 69 69 83 98 758537 758539 758541 758543 758545 758547 758549 758551 61 62 64 67 84 84 102 122 758552 758554 758556 758558 758560 758562 758564 45 46 46 47 69 69 83 758553 758555 758557 758559 758561 758563 758565 61 62 64 67 84 84 102 MET07 - Order codes High performance range H Standard range S Disconnecting switch type MET07 3-pole, up to 1000V AC Frame Type size 3-pole 10 10 10 10 20 20 30 40 50 60 70 MET637H MET800H MET1007H MET1257H MET1607H MET2007H MET2507H MET3207H MET4007S(1) MET5007S(1) MET6307S(1) Rated current of switch Horizontal terminals Heightened arc chute Iu A Ref. No. kg 630 800 1000 1250 1600 2000 2500 3200 4000 5000 6400 784173 784174 784175 784176 784177 784178 784184 784179 784180 784181 784182 53 54 54 55 61 61 96 107 183 223 261 Disconnecting switch equipped with • handoperated mechanism type X2 • 11 auxiliary contacts 5 NO, 6 NC (without current transformer and electronic trip unit) (1) On request 35 MEG07 / MEGT07 - Order codes Circuit breaker type MEG07 Up to 1500V DC Frame Type size 10 20 40 10 50 60 20 70 MEG1257 MEG2007 MEG3207 MEG3207/10 MEG4007 MEG5007 MEG5007/20 MEG6307 Rated current of breaker Iu A 1250 2000 3200 3200 4000 5000 5000 6400 Horizontal terminals Ref. No. Up to 1200V 784130 784131 784132 784133 784134 784135 784136 784137 Horizontal terminals kg 45 52 86 84 154 182 178 221 Ref. No. Up to 1500V 784138 784139 784140 784141 784142 784143 kg 51 58 99 172 207 245 Two pole types for DC 1200V on request. Circuit breaker equipped with: • handoperated mechanism type X2 • external overcurrent release • shunt trip 230V AC • 11 auxiliary contacts 5 NO, 6 NC Disconnecting switch type MEGT07 Up to 1500V DC Frame Type size Disconnecting switch equipped with: • handoperated mechanism type X2 • 11 auxiliary contacts 5 NO, 6 NC (without external overcurrent release, shunt trip 230V AC) 10 20 40 10 50 60 20 70 MEGT1257 MEGT2007 MEGT3207 MEGT3207/10 MEGT4007 MEGT5007 MEGT5007/20 MEGT6307 Rated current of switch Iu A 1250 2000 3200 3200 4000 5000 5000 6400 Two pole types for DC 1200V on request. 36 Horizontal terminals Ref. No. Up to 1200V 784144 784145 784146 784147 784148 784149 784150 784151 Horizontal terminals kg 43 49 84 84 149 178 178 216 Ref. No. Up to 1500V 784152 784153 784154 784155 784156 784157 kg 49 55 96 167 202 241 ME07 - Order codes Drives Type x2 Manual operated mechanism with storage operation by manual ON/OFF button Type xv Manual operated machnism with storage, closing coil 42V, AC 50/60Hz 110V, AC 50/60Hz 220V, AC 50/60Hz 230V, AC 50/60Hz 240V, AC 50/60Hz 24V, DC 48V, DC 60V, DC 110V, DC 125V, DC 220V, DC Type fv1 All type fv with automatic control unit Motor operated mechanism with storage Separate command for charging and closing 42V, AC 50/60Hz 110V, AC 50/60Hz 220V, AC 50/60Hz 230V, AC 50/60Hz 240V, AC 50/60Hz 24V, DC 48V, DC 60V, DC 110V, DC 125V, DC 220V, DC Type fv2 Automatic charging after circuit breaker is opened 42V, AC 50/60Hz 110V, AC 50/60Hz 220V, AC 50/60Hz 230V, AC 50/60Hz 240V, AC 50/60Hz 24V, DC 48V, DC 60V, DC 110V, DC 125V, DC 220V, DC Ref. No. Standard 758730 758731 758732 758733 758734 758735 758736 758737 758738 758739 758740 758741 758742 758743 758744 758745 758746 758747 758748 758749 758750 758751 758752 758753 758754 758755 758756 758757 758758 758759 758760 758761 758762 37 ME07 - Order codes Drives (continued) Type fv3.1 Automatic charging after circuit breaker is closed, with manual first charging 42V, AC 50/60Hz 110V, AC 50/60Hz 220V, AC 50/60Hz 230V, AC 50/60Hz 240V, AC 50/60Hz 24V, DC 48V, DC 60V, DC 110V, DC 125V, DC 220V, DC Type fv3.2 Automatic charging after circuit breaker is opened or closed, with automatic first charging 42V, AC 50/60Hz 110V, AC 50/60Hz 220V, AC 50/60Hz 230V, AC 50/60Hz 240V, AC 50/60Hz 24V, DC 48V, DC 60V, DC 110V, DC 125V, DC 220V, DC Type fv4 Automatic closing when spring is charged 42V, AC 50/60Hz 110V, AC 50/60Hz 220V, AC 50/60Hz 230V, AC 50/60Hz 240V, AC 50/60Hz 24V, DC 48V, DC 60V, DC 110V, DC 125V, DC 220V, DC 38 Ref. No. 758763 758764 758765 758766 758767 758768 758769 758770 758771 758772 758773 758774 758775 758776 758777 758778 758779 758780 758781 758782 758783 758784 758785 758786 758787 758788 758789 758790 758791 758792 758793 758794 758795 ME07 - Order codes Electronic trip unit for AC Type bse 3-x rms bse 3-1 rms bse 3-2 rms bse 3-3 rms-24D bse 3-3 rms-125A bse 3-3 rms-230A bse 3-3.1 rms-24D bse 3-3.1 rms-125A bse 3-3.1 rms-230A bse 3-4 rms-24D bse 3-5 rms-24D bse 3-6 rms-24D bse 3-7 rms-24D Type bse 4-x rms(1) bse 4-1 rms bse 4-2 rms bse 4-3 rms-24D bse 4-3 rms-125A bse 4-3 rms-230A bse 4-3.1 rms-24D bse 4-3.1 rms-125A bse 4-3.1 rms-230A bse 4-4 rms-24D bse 4-5 rms-24D bse 4-6 rms-24D bse 4-7 rms-24D Auxiliary Voltage n.a. n.a. 24V DC 60-125V AC 125-230V AC 24V DC 60-125V AC 125-230V AC 24V DC 24V DC 24V DC 24V DC Aux. Switches 5s+6ö 5s+6ö 5s+5ö 5s+5ö 5s+5ö 4s+4ö 4s+4ö 4s+4ö 4s+4ö 4s+4ö 3s+3ö 3s+3ö Ref. no. bse3-1 rms-XX bse3-2 rms-XX bse3-3 rms-24D-XX bse3-3 rms-125A-XX bse3-3 rms-230A-XX bse3-3.1 rms-24D-XX bse3-3.1 rms-125A-XX bse3-3.1 rms-230A-XX bse3-4 rms-24D-XX bse3-5 rms-24D-XX bse3-6 rms-24D-XX bse3-7 rms-24D-XX n.a. n.a. 24V DC 60-125V AC 125-230V AC 24V DC 60-125V AC 125-230V AC 24V DC 24V DC 24V DC 24V DC 5s+6ö 5s+6ö 5s+5ö 5s+5ö 5s+5ö 4s+4ö 4s+4ö 4s+4ö 4s+4ö 4s+4ö 3s+3ö 3s+3ö bse4-1 rms-XX bse4-2 rms-XX bse4-3 rms-24D-XX bse4-3 rms-125A-XX bse4-3 rms-230A-XX bse4-3.1 rms-24D-XX bse4-3.1 rms-125A-XX bse4-3.1 rms-230A-XX bse4-4 rms-24D-XX bse4-5 rms-24D-XX bse4-6 rms-24D-XX bse4-7 rms-24D-XX Selection Code Frame size 10 10 10 10 10 10 20 20 30 40 50 60 70 Overcurrent release for DC Current transformer 250A 400A 630A 800A 1000A 1250A 1600A 2000A 2500A 3200A 4000A 5000A 6400A 3-pole bse 3-x rms 02 04 06 08 10 12 16 20 25 32 40 50 64 4-pole(1) bse 4-x rms 02 04 06 08 10 12 16 20 25 32 (63% protection) 40 - Overcurrent release for MEG 07 up to 1500V DC Rated current Ie 630-1250A 1600-3600A 1600-3600A Adjusted setting values 800/1200/1800A 1600/2000/3000A 2500/3200/3600A (continuously) Ref. No. 784158 784159 784160 Note - The MEG 07 must be provided with a shunt trip or undervoltage trip connected to the micro switch of the overcurrent release. Ordering details of shunt trip and undervoltage trip see next page. (1) 100% protection for N-pole, 63% and 50% protection on request. 39 ME07 - Order codes Auxiliary trips Accessories for auxiliary trips 40 Shunt trip type a 42V, AC 50/60Hz 110V, AC 50/60Hz 220V, AC 50/60Hz 230V, AC 50/60Hz 240V, AC 50/60Hz 24V, DC 48V, DC 60V, DC 110V, DC 125V, DC 220V, DC Shunt trip type r 42V, AC 50/60Hz 110V, AC 50/60Hz 220V, AC 50/60Hz 230V, AC 50/60Hz 240V, AC 50/60Hz 24V, DC 48V, DC 60V, DC 110V, DC 125V, DC 220V, DC Time delay unit type c For undervoltage trip (undervoltage trip 220V DC required) Rated operating voltage: AC 50/60Hz, 230V, 220V DC AC 50/60Hz, 110V, with external transformer AC 50/60Hz, 380V, with external transformer AC 50/60Hz, 400V, with external transformer AC 50/60Hz, 440V, with external transformer Capacitor trip unit type n1 Internal version, no shunt trip type a necessary Operating range 0.85 ... 1.1 Uc External version, shunt trip type a 220V DC required Operating range 0.0 ... 1.1 Uc Ref. No. 758818 758819 758820 758821 758822 758823 758824 758825 758826 758827 758828 758829 758830 758831 758832 758833 758834 758835 758836 758837 758838 758839 758843 758844 758845 758846 758847 758848 758849 ME07 - Order codes Indication switches Locking facilities Accessories Type Trip indication switch type m5 For b+s-channel, 1 self resetting NO switch pulse actuation, quick make contact about 15 to 20 ms if spring system is charged, otherwise continuous contact (trip unit type bse 3/4-1 and bse 3/4-2 rms only) Indication switch type m3 “Spring energy system charged” for hand operated mechanism. With motor operated mechanism and automatic control unit indication always supplied, not available with microswitch controlled mechanism Indication switch type m4 “Breaker ready for closure”. Indication: Breaker OFF, spring energy system charged, undervoltage trip if available energised for hand and motor operated mechanism, standard with microswitch controlled mechanism. Position locking devices for hand and motor operated mechanism With cylindrical lock Type y1 ON and OFF push-button locked key removable in both positions Type y2 ON push-button locked key removable in both positions Type y3 ON push-button locked key removable in both positions Type y7 ON and OFF push-button locked key removable when locked Type y8 ON push-button locked key removable when locked Type y9 ON push-button locked key removable when locked For 3 padlocks Type y4 ON and OFF push-button locked Type y5 ON push-button locked Type y6 ON push-button locked Sealing cover type p Protection against unauthorized actuation of ON and OFF push-button Type Clear cover for trip unit type k For trip unit bse 3/4-x rms Door adjustment frame type ü Compensation of tolerances between door cutout and front cover Sealing kit type d Mounting kit to achieve IP54 in door cutout, for pumping handle and trip unit cover Door interlock type q Prevents opening of door when circuit breaker is closed (fixed version only) Angular spacer For rear mounting in combination with vertical termination (2 pieces required) Bowden wire interlock type g1 Mounting kit for mechanical interlock of 2 circuit breakers (fixed version), supplementary provide electrical interlock Ceramic inserts For arc chutes to reduce clearance distances (only for range S1 and H 500V) Frame sizes 10 ... 30 Frame size 40 Test set type P107 for electronic trip unit type bse3/4-X Test set type P107 rms for electronic trip unit type bse3/4-X rms Ref. No. 758850 kg 0.15 758851 0.15 758852 0.15 758853 – 758854 – On request – 758855 – 758856 – On request – 758857 758858 On request – – – 758859 – Ref. No. 564243 kg – 758860 – 758860 0.3 758862 – 758863 – 758864 758840 758841 758349 75999 – – – – 41 ME07 - Order codes Withdrawable technique Cradle 3-pole, 4-pole Cradle provided with personnel protection by positively activated shutter, positive mechanical indication of functional position of breaker. ME637 to 3207: Integrated telescopic extension rails, padlocking facility against insertion of cranking handle, 3 socket connectors = 48 contacts for control circuit connection. In version “v” and “k” the terminals are accessable from the front. ME4007 to 6307: 48 control circuit contacts Cradle for circuit breaker type 3-pole ME367 to 1007 S1,N ME637 to 1257 H,S1,N ME1607 H, S1, N ME2007 H, S1, N ME2507 H, S1, N ME3207 H, S1, N ME637 to 1007 S1,N ME637 to 1257 H,S1,N ME1607 H, S1, N ME2007 H, S1, N ME2507 H, S1, N ME3207 H, S1, N ME4007 S ME5007 S ME6307 S ME637 to 1007 S1,N ME637 to 1257 H,S1,N ME1607 H, S1, N ME2007 H, S1, N ME2507 H, S1, N ME3207 H, S1, N 4-pole ME637 to 1007 S1, N ME637 to 1257 H,S1,N ME1607 H, S1, N ME2007 H, S1, N ME2507 H, S1, N ME3207 H, S1, N ME637 to 1007 S1,N ME637 to 1257 H,S1,N ME1607 H, S1, N ME2007 H, S1, N ME2507 H, S1, N ME3207 H, S1, N ME4007 S ME637 to 1007 S1,N ME637 to 1257 H,S1,N ME1607 H, S1, N ME2007 H, S1, N ME2507 H, S1, N ME3207 H, S1, N Cradle type Short- Termination circuit capacity kA Ref. No. kg T10v1 T10v2 T20v1 T20v2 T30v T40v T10w1 T10w2 T20w1 T20w2 T30w T40w T50 T60 T70 T10k1 T10k2 T20k1 T20k2 T30k T40k 105 176 220 220 220 220 105 176 220 220 220 220 220 220 220 105 176 220 220 220 220 Upper and lower vertical Upper and lower vertical Upper and lower vertical Upper and lower vertical Upper and lower vertical Upper and lower vertical Upper and lower horizontal Upper and lower horizontal Upper and lower horizontal Upper and lower horizontal Upper and lower horizontal Upper and lower horizontal Upper and lower horizontal Upper and lower horizontal Upper and lower horizontal Upper horizontal, lower vertical Upper horizontal, lower vertical Upper horizontal, lower vertical Upper horizontal, lower vertical Upper horizontal, lower vertical Upper horizontal, lower vertical 759305 758241 758242 758243 758244 758245 758250 758251 758252 758253 758254 758255 759544 759545 759546 758260 758261 758262 758263 758264 758265 40 40 47 47 55 80 40 40 47 47 55 80 80 65 80 40 40 47 47 55 80 T10v1/IV T10v2/IV T20v1/IV T20v2/IV T30v/IV T40v/IV T10w/IV T10w2/IV T20w1/IV T20w2/IV T30w/IV T40w/IV T50w/IV T10k1/IV T10k2/IV T20k1/IV T20k2/IV T30k/IV T40k/IV 105 176 220 220 220 220 105 176 220 220 220 220 220 105 176 220 220 220 220 Upper and lower vertical Upper and lower vertical Upper and lower vertical Upper and lower vertical Upper and lower vertical Upper and lower vertical Upper and lower horizontal Upper and lower horizontal Upper and lower horizontal Upper and lower horizontal Upper and lower horizontal Upper and lower horizontal Upper and lower horizontal Upper horizontal, lower vertical Upper horizontal, lower vertical Upper horizontal, lower vertical Upper horizontal, lower vertical Upper horizontal, lower vertical Upper horizontal, lower vertical 758270 758271 758272 758273 758274 759546 758280 758281 758282 758283 758284 758285 758286 758290 758291 758292 758293 758294 758295 48 48 55 55 58 92 48 48 55 55 58 92 65 48 48 55 55 58 92 Type ME5007S/IV, 5000A withdrawable breaker on request. 42 ME07 - Order codes Withdrawable technique Accessories for cradle Accessories Position indication switch Alternatively for indication of disconnected-, test- and connected position Frame sizes 10...40 1 switch 1CO 2 switches 2 CO 3 switches 3 CO 4 switches 4 CO 5 switches 5 CO 6 switches 6 CO Frame sizes 50...70 1 switch 2 NO, 2 NC 2 switches 4 NO, 4 NC 3 switches 6 NO, 6 NC 4 switches 8 NO, 8 NC (only frame sizes 50...60) Door interlocks Prevents door opening when circuit breaker is in ON and TEST position Frame sizes 10...40 Type lly Door (hinged left side) defeatable Type lln Door (hinged left side) not defeatable Type lry Door (hinged right side) defeatable Type lrn Door (hinged right side) not defeatable Frame sizes 50...70 Type ly Door defeatable Type ln Door not defeatable Locking facility type wi Cradle provided with cylindrical lock against insertion of cranking handle (frame sizes 50...70) Locking facility type we Mechanical interlock against insertion of cranking handle when circuit breaker is in ON position (frame sizes 50...70) 758302 758303 758304 759549 759306 759550 759551 759552 759553 759554 758308 758309 758310 758311 760323 760324 758312 758313 Accessories for circuit breaker Bowden wire interlock type g2 Mounting kit for mechanical interlock of 2 circuit breakers Supplementary provide an electrical interlock Frame size 10...40 Frame size 50...70 Extension rail For cradle frame sizes 50...70 758314 758325 760326 43 ME07 - Order codes Replacement parts Contacts Set of main contacts (1) Set of arcing contacts (1) applicable up to 690V AC and 750V DC Set of arcing contacts (1) applicable up to 1000V AC 1200V/1500V DC Arc chutes Suitable for circuit breaker ME637 to 1257 H, S1 ME1607 to 2507 H, S1 ME2507 H, S1 ME3207 H, S1 ME3207 H, S1/IV Neutral pole ME4007 S ME5007 S ME6307 S ME637 to1257 H, S1 ME1607 to 2507 H, S1 ME3207 H, S1 ME3207 H, S1/IV Neutral pole ME4007 S ME5007 to 6307 S ME637 to ME1257/H, MEG1257 ME1607 to ME2007H, MEG2007 ME3207H, MEG3207 ME4007S, MEG4007 MEG50007S MEG6307S Suitable for circuit breaker Arc chute without ceramic ME637 to 1257 H, S1, N inserts, applicable up to 500V AC ME1607 to 2007 H, S1, N ME2507 H, S1, N ME3207 H, S1, N ME3207 H, S1/IV Neutral pole Arc chute with ceramic ME637 to 1257 H, S1 inserts, applicable up to 690V AC ME1607 to 2007 H, S1 ME2507 H, S1 ME3207 H, S1 ME3207 H, S1/IV Neutral pole Arc chute ME4007 S, ME4007S/IV applicable up to 690V AC ME5007... 6307S Arc chute adaptor ME637 to ME1257H, MEG1257 applicable up to 1000V AC, ME1607 to ME2007H, MEG2007 1200V/1500V DC ME3207H, MEG3207 ME4007S, MEG4007 MEG5007 MEG6307 Arc chute heightend ME637 to ME1257H, MEG1257 applicable up to 1000V AC, ME1607 to ME2007H, MEG2007 1200V/1500V DC ME3207H, MEG3207 ME4007, MEG4007 MEG5007S MEG6307S Sets per pole 1 1 1 2 1 3 4 4 1 2 4 2 3 4 1 1 2 3 4 4 Ref. No. kg On request On request On request On request On request On request On request On request On request On request On request On request On request On request Please refer to spare part catalogue 1.5 2.1 2.9 4.2 2.1 0.6 0.6 0.2 0.2 0.2 0.2 0.2 0.2 0.2 Pieces / Ref. No. pole 1 760608 1 760609 1 760610 2 760609 1 760609 1 760575 1 760576 1 760577 2 760576 1 760576 3 758347 4 758347 1 Please refer to 1 spare part 2 catalogue 3 4 4 1 Please refer to 1 spare part 2 catalogue 3 4 4 kg (1) Set consists all fitting parts, e.g. fixed and movable contacts, contact springs and screws. 44 2.4 2.6 3.7 2.6 2.6 2.6 2.8 3.9 2.8 2.8 2.0 2.0 Notes 45 ME07 - Trip curves Type ME637 to ME6307 Trip units type bse 3 - 1 rms to bse 3 - 5 rms bse 4 - 1 rms to bse 4 - 5 rms ICT = primary current of the CT Long time delay b Ib = 0.40 to 1 x ICT Short time delay s Is = 1.5 to 14 x ICT ICT = 250 to 1250A ICT = 1600 to 2500A Is = 1.5 to 8 x ICT Is = 1.5 to 5 x ICT ICT = 3200A Is = 1.5 to 4 x ICT ICT = 4000A Is = 1.5 to 3 x ICT ICT = 5000A Is = 1.5 to 3 x ICT ICT = 6400A Time delay for s-channel ts = 30 to 300 ms class 35 class 30 class 25 Seconds Ground fault g (only bse 3/4 - 4 rms and bse 3/4 - 5 rms) tg = 100 to 300 ms ICT = 250 to 6400A Ig = 0.2 to 0.8 x ICT class 40 Minutes Instantaneous k (switchable on/off) ICT = 250 . . 1250A IK = 18 x ICT IK = 10 x ICT ICT = 1600 . . 2500A IK = 7 x ICT ICT = 3200A IK = 10 x ICT ICT = 4000A IK = 10 x ICT ICT = 5000A IK = 10 x ICT ICT = 6400A Dynamical high speed short time trip unit ks, except ME4007 to ME6307 Ks = value according to frame size (ME07 H) (see technical values) class 20 class 15 class 10 class 5 Values for b-channel 1.5 2 3 4 5 6 7.2 8 5 164 74 30 17 10 7 5 4 10 328 148 60 34 20 14 10 8 15 492 222 90 51 30 21 15 12 20 656 296 120 68 40 28 20 16 25 820 368 150 85 50 35 25 20 30 35 40 984 1148 1272 440 510 578 180 210 228 102 116 126 60 70 80 42 49 56 30 35 40 24 28 31 Trip Time X x current setting (Ib) Tripping class All times in seconds bse 3-1 rms and bse 4-2 rms: class 20 only bse 4-1 rms and bse 4-2 rms: class 20 only Phase current for b, s, k ks Sum of currents for g All curves from cold conditions. 46 ME07 - Trip curves Type ME637 to ME6307 Trip units type bse 3 - 6 rms to bse 3 - 7 rms bse 4 - 6 rms to bse 4 - 7 rms ICT = primary current of the CT Long time delay b Ib = 0.45 to 1 x ICT Ib = 0.55 to 1 x ICT bse 3-6 / 4-6 rms bse 3-7 / 4-7 rms Short time delay s Is = 1.5 to 14 x ICT ICT = 250 to 1250A Is = 1.5 to 8 x ICT ICT = 1600 to 2500A Is = 1.5 to 5 x ICT ICT = 3200A Is = 1.5 to 4 x ICT ICT = 4000A Is = 1.5 to 3 x ICT ICT = 5000A Is = 1.5 to 3 x ICT ICT = 6400A Time delay for s-channel ts = 0 . . 300 ms Ground fault g tg = 100 to 300 ms Ig = 0.2 to 0.8 x ICT class 35 class 30 class 25 class 20 class 15 Seconds Minutes Instantaneous k (switchable on/off) IK = 4 to 18 x ICT ICT = 250 to 1250A IK = 4 to 10 x ICT ICT = 1600 to 2500A IK = 4 to 7 x ICT ICT = 3200A IK = 4 to 10 x ICT ICT = 4000A IK = 4 to 10 x ICT ICT = 5000A IK = 4 to 10 x ICT ICT = 6400A Dynamical high speed short time trip unit ks, except ME4007 to ME6307 ks = value according to frame size (see table technical values) class 10 ICT = 250 to 6400A class 5 Values for b-channel 5 10 15 20 1.2 371 742 1113 1484 1.5 164 328 492 656 2 74 148 222 296 3 30 60 90 120 4 17 34 51 68 5 10 20 30 40 6 7 14 21 28 7.2 5 10 15 20 8 4 8 12 16 25 30 1855 2226 820 984 368 440 150 180 85 102 50 60 35 42 25 30 20 24 35 2597 1148 510 210 116 70 49 35 28 Trip Time X x current setting (Ib) Tripping class All times in seconds Phase current for b, s, k ks Sum of currents for g All curves from cold conditions. 47 ME07 - Wiring diagrams Basic connections Definitions The power circuit and the control part is presented as a typical circuit diagram. The overall control part is a combination of numbered basic diagrams for drives, trips and indicators. The number of the complete diagram can be derived by using the key numbers of the basic plan. Diagram key Key positions Range/breaker No. of poles/ mounting arrangement Basic breaker bse- overcurrent trip 1 2 34 . / . . 56 . . 78 . . 9 . 10 . 11 . 13 15 12 14 . . . . A ... Z • 0 ... 9 • A ... Z • Operating mechanism 00 ... ZZ • Trip device 00 ... ZZ • Auxiliary switch 0 ... Z • Indication switch on the drive 0 ... Z • Position indication switch on cradle 0 ... Z • Reserve 0 ... Z • Example: Complete diagram A / 1V Circuit breaker type ME, ME637 ... ME6307 3-pole/withdrawable technique Overcurrent trip type bse 3-1 ms with m5 indication switch for bs-channel fv 1 motor operated mechanism Charging via push-button Closing via push-button Automatic control unit r - undervoltage trip a1. shunt trip a2. shunt trip Auxiliary switch 3NO, 3NC Indication switch m 3 for drive Position indicating switch Reserve 48 1 35 T 1 1A 0000 ME07 - Wiring diagrams Basic connections Definitions Key no. Abbre- Current Designation and application viation Key position 1 and 2 - Breaker/range A Circuit breaker type ME637N to ME3207N, frame size 10 to 40 Circuit breaker type ME637S1 to ME3207S1, frame size 10 to 40 Circuit breaker type ME4007S to ME6307S, frame size 50 to 70 Circuit breaker type ME637H to ME3207H, frame size 10 to 40 Circuit breaker type ME637N/IV to ME2507N/IV, frame size 10/IV to 40/IV Circuit breaker type ME637S1/IV to ME3207S1/IV, frame size 10/IV to 40/IV Circuit breaker type ME4007S/IV, frame size 50/IV Circuit breaker type ME637H/IV to ME3207H/IV, frame size 10/IV to 40/IV Circuit breaker type MEG1257 to ME6307, frame size 10 to 70 Key position 3 - No. of poles/mounting arrangement 0 Circuit breaker 3-pole stationary mounting with/without electronic trip unit 3-pole, frame size 10 to 60 1 Circuit breaker 3-pole withdrawable version with/without electronic trip unit 3-pole, frame size 10 to 40 2 Circuit breaker 4-pole stationary mounting with/without electronic trip unit 3-pole, frame size 10 to 50 3 Circuit breaker 4-pole withdrawable version with/without electronic trip unit 3-pole, frame size 10 to 40 4 Circuit breaker 4-pole stationary mounting with electronic trip unit 4-pole, frame size 10 to 40 5 Circuit breaker 4-pole withdrawable version with electronic trip unit 4-pole, frame size 10 to 40 6 Circuit breaker 3-pole withdrawable version without electronic trip unit 3-pole, frame size 50 to 70 7 Circuit breaker 4-pole withdrawable version with/without electronic trip unit 3-pole, frame size 50 8 Circuit breaker 4-pole withdrawable version with electronic trip unit 4-pole, frame size 50 G DC - circuit breaker, stationary mounting Key position 4 - Electronic trip unit A Circuit breaker without electronic trip unit (Disconnecting switch) U Circuit breaker with electronic trip unit type bse 3-1 rms/bse 4-1 rms V Circuit breaker with electronic trip unit type bse 3-1 rms/bse 4-1 rms and trip indication bs-channel m5 W Circuit breaker with electronic trip unit type bse 3-2 rms/bse 4-2 rms X Circuit breaker with electronic trip unit type bse 3-2 rms/bse 4-2 rms and trip indication bs-channel m5 S Circuit breaker with electronic trip unit type bse 3-3 rms/bse 4-3 rms T Circuit breaker with electronic trip unit type bse 3-3.1 rms/bse 4-3.1 rms L Circuit breaker with electronic trip unit type bse 3-4 rms/bse 4-4 rms N Circuit breaker with electronic trip unit type bse 3-5 rms/bse 4-5 rms P Circuit breaker with electronic trip unit type bse 3-6 rms/bse 4-6 rms R Circuit breaker with electronic trip unit type bse 3-7 rms/bse 4-7 rms Key position 4 - DC overcurrent release A Circuit breaker without overcurrent release (Disconnecting switch) 1 Circuit breaker with overcurrent release 49 ME07 - Wiring diagrams Basic connections Definitions Key no. Abbre- Current viation Key position 5 and 6 - Operating mechanism 10 x2 1Z xv 1Y xv AC D0 E0 F0 M0 N0 O0 PO Q0 R0 D1 E1 F1 M1 N1 O1 P1 Q1 R1 D2 E2 F2 M2 N2 O2 P2 Q2 R2 D3 E3 F3 M3 N3 O3 P3 Q3 R3 – – – – – – – – – X – X A5 B5 C5 G5 H5 I5 J5 K5 L5 A6 B6 C6 G6 H6 I6 J6 K6 L6 A7 B7 C7 G7 H7 I7 J7 K7 L7 A8 B8 C8 G8 H8 I8 J8 K8 L8 A9 B9 C9 G9 H9 I9 J9 K9 L9 – X – A0 B0 C0 G0 H0 I0 J0 K0 L0 A1 B1 C1 G1 H1 I1 J1 K1 L1 A2 B2 C2 G2 H2 I2 J2 K2 L2 A3 B3 C3 G3 H3 I3 J3 K3 L3 A4 B4 C4 G4 H4 I4 J4 K4 L4 – X X X – X – S0 S1 S2 S3 S4 S5 S6 S7 DC f, su, v - AC f, su, v - DC ≤ 60V f, su, v - DC > 60V f, su - AC, v - AC f, su - AC, v - DC f, su - DC ≤ 60V, v - DC f, su - DC > 60V, v - DC f, su - DC ≤ 60V, v - AC f, su - DC > 60V, v - AC fv 2 f, su, v - AC f, su, v - DC < 60V f, su, v - DC > 60V f, su - AC, v - AC f, su - AC, v - DC f, su - DC ≤ 60V, v - DC f, su - DC > 60V, v - DC f, su - DC ≤ 60V, v - AC f, su - DC > 60V, v - AC fv 3.1 f, su, v - AC f, su, v - DC ≤ 60V f, su, v - DC > 60V f, su - AC, v - AC f, su - AC, v - DC f, su - DC ≤ 60V, V - DC f, su - DC > 60V, v - DC f, su - DC ≤ 60V, v - AC f, su - DC > 60V, v - AC fv 3.2 f, su, v - AC f, su, v - DC ≤ 60V f, su, v - DC > 60V f, su - AC, v - AC f, su - AC, v - DC f, su - DC ≤ 60V, v - DC f, su - DC > 60V, v - DC f, su - DC ≤ 60V, v - AC f, su - DC > 60V, v - AC fv 4 f, su, v - AC f, su, v - DC ≤ 60V f, su, v - DC > 60V f, su - AC, v - AC f, su - AC, v - DC f, su - DC ≤ 60V, v - DC f, su - DC > 60V, v - DC f, su - DC ≤ 60V, v - AC f, su - DC > 60V, v - AC signal contact untied potential signal contact tied potential ME637/III to 2507/III, ME4007S/III to 6307S/III ME637/IV to 4007/IV; ME3207/III fv 1 bse 3-7/4-7 rms D5 E5 F5 M5 N5 O5 P5 Q5 R5 D6 E6 F6 M6 N6 O6 P6 Q6 R6 D7 E7 F7 M7 N7 O7 P7 Q7 R7 D8 E8 F8 M8 N8 O8 P8 Q8 R8 – – – – – – – – – X – – v - AC, hand operated v - DC, hand operated f, v - AC f, v - DC f - AC, v - DC f - DC, v - AC f, v - AC f, v - DC f = Motor for operating mechanism 50 Designation and application Hand operated mechanism with storage Charging mechanically, closing by push-button Hand operated mechanism Charging mechanically Closing by push-button or electrically with closing coil Hand operated mechanism Charging mechanically Closing by-push button or electrically with closing coil Motor operated mechanism with storage and automatic control unit Separate command for pre-charging and closing Closing by push-button or electrically with closing coil Motor operated mechanism with storage and automatic control unit Automatic pre-charging after OFF Closing by push-button or electrically with closing coil Motor operated mechanism with storage and automatic control unit Automatic pre-charging after ON with manual first-charging Closing by push-button or electrically with closing coil Motor operated mechanism with storage and automatic control unit Automatic pre-charging after ON and automatic first-charging Closing by push-button or electrically with closing coil Motor operated mechanism with storage and automatic control unit Automatic ON after pre-charging Indication “Spring energy system charged” not available Operating mechanism Indication “Spring energy system charged” Frame size Frame size 10-30 Frame size 10-30 Frame size 10-30 Frame size 10-30 Frame size 10-30 Frame size 10-30 Frame size 40-60 Frame size 40-60 su = automatic control unit v = closing coil ME07 - Wiring diagrams Basic connections Definitions Key no. Abbre- Current Designation and application viation Key position 7 and 8 - Auxiliary trips 00 Without auxiliary trip for hand- or motor-operated mechanism 21 a AC 1. Shunt trip for hand- or motor-operated mechanism 22 a DC 1. Shunt trip for hand- or motor-operated mechanism 23 a AC 1. Shunt trip for hand- or motor-operated mechanism AC 2. Shunt trip for hand- or motor-operated mechanism 24 a DC 1. Shunt trip for hand- or motor-operated mechanism DC 2. Shunt trip for hand- or motor-operated mechanism 25 a AC 1. Shunt trip for hand- or motor-operated mechanism a DC 2. Shunt trip for hand- or motor-operated mechanism 26 a DC 1. Shunt trip for hand- or motor-operated mechanism a AC 2. Shunt trip for hand- or motor-operated mechanism 31 a AC 1. Shunt trip for hand- or motor-operated mechanism r AC Undervoltage trip for hand- or motor-operated mechanism 71 r AC Undervoltage trip for hand- or motor-operated mechanism 72 r DC Undervoltage trip for hand- or motor-operated mechanism 73 c AC Electrical delayed undervoltage trip without transformer A0 n2 AC/DC 2. Shunt trip with capacitor trip unit All possible combinations of shunt and undervoltage trips on request Key position 9 - Auxiliary contacts Key no. Frame size Breaker type Plug no. bse type Aux. contacts Z 10-40 fixed/withdr. X1/X2 3-1/3-2 5NO 6NC X 10-40 fixed/withdr. X1/X2 3-3 5NO 5NC V 10-40 fixed/withdr. X1/X2 3-3.1/3-4/3-5 4NO 4NC U 10-40 fixed/withdr. X1/X2 3-6 3NO 4NC C 50-60 fixed X1/X2 3-1/3-2 5NO 6NC D 50-60 fixed X1/X2 3-3 5NO 5NC E 50-60 fixed X1/X2 3-3.1/3-4/3-5 4NO 4NC F 50-60 fixed X1/X2 3-6 3NO 4NC G 50-70 withdr. X20 3-1/3-2 5NO 6NC H 50-70 withdr. X20 3-3 5NO 5NC J 50-70 withdr. X20 3-3.1/3-4/3-5 4NO 4NC K 50-70 withdr. X20 3-6 3NO 4NC Key position 10 - Indication switch on operating mechanism 0 without signalling 1 m3 Signal “Spring energy storage system charged” for hand- and motor-operated mechanism 2 m4 Signal “Breaker ready for closure for hand- and motor-operated mechanism 3 m3+m4 Key number 1 + 2 Key position 11 - Position indication switch on cradle - ME637 to ME3207 00 without signalling 11 1 indication switch 1CO - signal connected 12 1 indication switch 1CO - signal test 13 1 indication switch 1CO - signal disconnected 1A 3 indication switches 1CO - signal connected - test- disconnected (1 in each position) 1Y 6 indication switches 1CO - signal connected - test- disconnected (2 in each position) Key position 11 - Position indication switch on cradle - ME4007 to ME6307 00 without signalling 31 1 indication switch 2NC, 2NO - signal connected 32 1 indication switch 2NC, 2NO - signal test 33 1 indication switch 2NC, 2NO - signal disconnected 3A 3 indication switches 2NC, 2NO - signal connected - test- disconnected (1 in each position) 51 ME07 - Wiring diagrams ME 637...3207, ME 4007...ME 6307 Key position 4 Electronic trip unit type bse 3-1 rms / bse 4-1 rms U Tripping Circuit breaker Key position 4 Electronic trip unit type bse 3-1 rms / bse 4-1 rms 52 V ME07 - Wiring diagrams ME 637...3207, ME 4007...ME 6307 Key position 4 Electronic trip unit type bse 3-2 rms / bse 4-2 rms Key position 4 Electronic trip unit type bse 3-2 rms / bse 4-2 rms W X 53 ME07 - Wiring diagrams ME 637...3207, ME 4007...ME 6307 Key position 4 Electronic trip unit type bse 3-3 rms / bse 4-3 rms Key position 4 Electronic trip unit type bse 3-3.1 rms / bse 4-3.1 rms 54 S T ME07 - Wiring diagrams ME 637...3207, ME4007...ME6307 Key position 4 Electronic trip unit type bse 3-4 rms / bse 4-4 rms Key position 4 Electronic trip unit type bse 3-5 rms / bse 4-5 rms L N 55 ME07 - Wiring diagrams ME 637...3207, ME 4007...ME 6307 Key position 4 Electronic trip unit type bse 3-6 rms / bse 4-6 rms Key position 4 Electronic trip unit type bse 3-7 rms / bse 4-7 rms 56 P R ME07 - Wiring diagrams ME 637...3207 Key positions 5 and 6 Operating mechanism Fig. A/FV1 Fig. A ... E Motor operated stored energy operating mechanism 1 Bridge B4 - untied potential contact make connection from terminal 38 to 40 2 Rectifier omitted at DC ( protection circuitry) 3 Rectifier for type ME 3207 3-pole and type ME 2507 4-pole, otherwise motor connection directly 4 RC-circuitry at AC, diode at DC 5 Bridge B3 - for separate voltage for activation magnet, make connection terminal 31 and terminal 33 and connect pushbutton S21 to corresponding voltage 6 For DC only 7 For <= DC 60V connect the contacts in parallel i.e. link the terminals 34-37 and 35-36 These items are being considered by the manufacturer on corresponding request. 5