Services Practical advice Maximum lengths of busways in the TN system Maximum length in metres of busways in the TN system(1) protected against indirect contacts by circuit breakers Correction factor to be applied to the lengths given 400 V networks(3) Phase-to-phase (2) m = Sphases Spe 1 2 3 4 Copper cable Aluminium cable 1 0.62 0.67 0.41 0.50 0.31 0.40 0.25 P25M Three-phase network in 400 V, copper cable, Sph = Spe , Ul = 50 V, in the TN system. Sphases Calibre (A) mm2 0.16 0.24 0.4 1.5 2.5 4 5 (2 x 2.5) 0.6 730 1 426 710 1.6 255 425 681 851 2.4 170 284 454 568 4 102 170 272 340 6 68 113 181 227 10 42 71 113 142 16 27 44 71 89 20 21 35 56 71 25 17 28 45 56 B curve C60, C120 and NG125 Three-phase network in 400 V, copper cable, Sph = Spe , Ul = 50 V, in the TN system. Sphases Rating (A) mm2 2 3 4 6 10 13 1.5 613 409 307 204 123 94 2.5 4 6 10 16 25 35 50 16 77 681 511 341 204 157 128 1090 818 545 327 252 204 818 491 377 307 818 629 511 818 20 61 102 164 245 409 654 25 49 82 131 196 327 523 818 32 38 64 102 153 256 409 639 894 40 31 51 82 123 204 327 511 716 50 25 41 65 98 164 262 409 572 818 63 19 32 52 78 130 208 325 454 649 80 15 28 41 61 102 164 258 358 511 100 12 20 33 49 82 131 204 288 409 125 10 25 25 41 65 98 164 262 409 572 818 32 19 32 51 77 128 204 319 447 639 40 15 26 41 61 102 164 256 358 511 50 12 20 33 49 82 131 204 286 409 63 10 16 26 39 65 104 162 227 325 80 8 13 20 31 51 82 128 179 258 100 6 10 16 25 41 65 102 143 204 125 5 16 26 39 65 105 164 229 311 C curve C60, C120 and NG125 Three-phase network in 400 V, copper cable, Sph = Spe , Ul = 50 V, in the TN system. Sphases Rating (A) mm2 2 3 4 1.5 307 204 153 2.5 511 341 256 4 818 545 409 6 818 613 10 16 25 35 50 6 10 102 61 13 47 16 38 20 31 170 102 79 64 51 273 164 126 102 82 409 245 189 153 123 681 409 315 256 654 503 409 786 639 894 204 327 511 716 8 13 20 33 52 82 114 156 (1)b IT system with distributed neutral, apply a coefficient of 0.50 b IT system with non-distributed neutral, apply a coefficient of 0.72 (2)b Sphases : phase conductor cross-section in mm2. b Spe : protective conductor cross-section in mm2. (3)b for phase-to-phase 237 V networks, also apply a coefficient of 0.57 b for single-phase 237 V networks (between phase and neutral), do not apply this additional coefficient. version: 3.1 92504E.indd Maximum lengths of busways in the TN system Services Practical advice D curve C60, C120 and NG125 K curve C60 Three-phase network in 400 V, copper cable, Sph = Spe , Ul = 50 V, in the TN system. Sphases Rating (A) mm2 1 2 3 1.5 438 219 146 2.5 730 365 243 4 584 389 6 876 584 10 974 16 25 35 50 4 6 110 73 10 44 13 34 16 27 20 22 37 183 292 456 639 913 146 234 365 511 730 183 122 73 56 46 292 195 117 90 73 58 438 292 175 135 110 88 730 487 192 225 779 467 359 730 562 786 25 18 29 47 70 117 187 292 409 584 32 14 23 37 55 91 146 228 319 456 40 11 18 29 44 73 117 183 258 365 50 9 15 23 35 58 93 146 204 292 63 7 12 19 28 46 74 116 162 232 80 5 9 14 21 35 58 88 123 178 100 4 7 12 18 29 47 73 102 146 125 2 4 7 10 16 26 41 57 78 MA curve C60, NG125 Three-phase network in 400 V, copper cable, Sph = Spe , Ul = 50 V, in the TN system. Sphases Rating (A) mm2 1,6 2,5 1.5 274 175 2.5 456 292 4 730 467 6 701 10 16 25 35 50 4 110 183 292 438 730 6,3 70 116 186 279 465 743 10 44 73 117 175 292 467 730 12,5 35 58 93 140 234 374 584 818 16 27 46 73 110 183 292 456 639 913 25 18 29 47 70 117 187 292 409 584 40 11 18 29 44 73 117 183 256 365 63 7 12 19 28 46 74 116 162 232 80 5 9 14 21 35 58 88 123 178 Conventional calculation method In most cases this method will be sufficient and results in limiting the length of the various electrical circuits B PE A A Imagn Id SPE L C Sph Principle This consists of applying Ohm’s law only to the feeder concerned by the fault, assuming that the voltage between the faulty phase and the PE (or PEN) continues to be greater than 80 % of nominal phase voltage. This coefficient globally takes account of all the upstream impedances. In LV, when the protective conductor is routed alongside the corresponding phase conductors, conductor reactance can be ignored compared with resistance: this approximation is considered acceptable up to cross-sections of 120 mm2. Beyond this value, resistance is increased as follows: Cross-section (mm2) Calculation of L max in the TN system using the conventional method 150 185 240 Resistance R + 15 % R + 20 % R + 25 % The maximum length of a circuit in the TN system is given by the following formula: L max = 0,8 x Uo x Sph ρ x (1 + m) x la In which: b L max : maximum length in metres b Uo: phase voltage: v 230 V for 230/400 V network b ρ: resistivity at normal operating temperature: v for copper: 22.5 103 Ω x mm2/m v for aluminium: 36 103 Ω x mm2/m b Ia is equal to the current (A): v for operation of the circuit breaker magnetic trip unit v ensuring fuse blowing within the specified time b m: Sph/Spe b Sph: phase cross-section in mm2 b Spe : protective conductor cross-section in mm2 92504E.indd version: 3.1