K119-90A World Class Switching Solutions for Energy Management Miniature High-Power latching Relay » 90A Max. switching capability » 90A: IEC 62055-31 UC2 compliant at 63A » 90A: VDE IEC 61810-1 Certified » RoHS compliant » Outline dimensions: (38.1 x 30.0 x 16.5)mm Contact Data Click here for glossary of terms Characteristics Rated load 90A 277Vac Insulation resistance Contact form 1A or 1B Dielectric strength: Contact material AgSnO2 Coil to contact 4,000 Vac for 1 min. Max. switching voltage 250Vac Across open contacts 2,000 Vac for 1 min. Max. switching current 90A Dielectric creepage 8mm Max. AC switching power 24,930VA Ambient temperature -40 to +85°C Electrical endurance 10,000 cycles Ambient humidity 98% RH, +40°C Mechanical endurance 100,000 cycles Vibration 1.5mm (DA) , 10 to 55Hz Set time <20ms Shock resistance: Release time <20ms Functional* 10G Destructive 100G Unit weight Approx. 65 g Click here for glossary of terms 1,000 MΩ (500Vdc) TerminationPCB Construction Dust protected * Unit may change state but is still functional. Coil Data Click here for glossary of terms Dual Coil (latching) Single Coil (latching) Standard Coil Consumption Pulse Duration Sensitive Standard Sensitive 1.5W 1.0W 3.0W 2.0W 100ms min. 100ms min. 100ms min. 100ms min. KG Technologies, Inc. / Phone: +1.888.513.1874 / Fax: +1.888.511.3989 / Email: info@kgtechnologies.net / Web: www.kgtechnologies.net 062015 K119-90A Page 2 of 4 Coil Data Nominal Coil Voltage Min. Operating Voltage Single Coil 9Vdc 6.3Vdc 54Ω 12Vdc 8.4Vdc 15Vdc 12Vdc 24Vdc 16.8Vdc 384Ω 48Vdc 33.6Vdc 1536Ω Dual Coil Single Coil Dual Coil 2 x 27Ω 80Ω 2 x 40Ω 96Ω 2 x 48Ω 145Ω 2 x 72.5Ω 150Ω 2 x 75Ω NA NA 2 x 192Ω 575Ω 2 x 287.5Ω 2 x 768Ω 2270Ω 2 x 1135Ω P– 1A T–90A Ordering Information Relay Series: K119 Terminal Style: A: See illustration on page 31 B: See illustration on page 31 C: See illustration on page 31 D: See illustration on page 31 E: See illustration on page 31 X: Custom design2 Coil Type: B – S D: Dual coil; see drawings for terminals DX: Sensitive dual coil; see drawings for terminals S: Single coil; see drawings for terminals SX: Sensitive single coil; see drawings for terminals Coil Voltage3: 9, 12, 24, 48Vdc Coil Polarity: P: Positive N: Negative Contact Form: 1A: Form 1A – NO 1B: Form 1B – NC Contact Material: T: AgSnO2 Contact Rating: 90A 012 Other standard terminal type drawings available upon request. For custom designs, please contact KG Technologies. Integrated shunts, flex-wire, copper extensions and brass terminals available. 3 Coil voltage should be indicated in three digit format (9Vdc = 009) 1 2 KG Technologies, Inc. / Phone: +1.888.513.1874 / Fax: +1.888.511.3989 / Email: info@kgtechnologies.net / Web: www.kgtechnologies.net 062015 D K119-90A Page 3 of 4 K119B Dimensional Drawings All dimensions in mm unless otherwise noted. For more information, please contact KG Technologies. 30.0 Outline Dimensions 4 4 38.1 3 3 3 16.5 2 2 2 1 REVISIONS REV 1 REVISIONS RE REV DESCRIPTION INITIALS DESCRIPTI REV DESCRIPTION 01 PROTOTYPE RELEASE 01 PROTOTYPE RELEASE 01 PROTOTYPE RELEASE 02 ADDED "E" STYLE DA CONFIG 27 02 TERMINAL ADDED CONFIGURATION "E" STYLE TERMINAL 02 TERMINAL ADDEDCONFIGURATION "E" STYLE DA 26 Standard Terminal Types K119A K119A K119A K119 A K119B K119B K119 B K119B K119 C K119C K119C K119C C D K119D K119D K119 K119D K119 E K119E K119E K119E B A ITEM QTY KG PART NUMBER ITEM QTY METRIC ENGINEER: DATE: MATERIAL: FINISH: KG Technologies, Inc. / Phone: +1.888.513.1874 / Fax: +1.888.511.3989 / KG DESCRIPTION PART NUMBER DESC BILL OF MATERIALS BILL OF MATERIALS BILL O ITEM QTY KG PART NUMBER METRIC KG METRIC TECHNOLOGIES INC KG TECHN DA OF PROPRIETARY PROPERTY NOTICE OF PR DA ENGINEER: NOTICE ENGINEER: THE INFORMATION CONTAINED HEREIN ISTHE THEINFORMATION PROPRIETARY PROPERTY CONTAINEDOFHEREIN ISTHE THEINFO PR 26-AUG-2013 26-AUG-2013 DATE: INC. THE POSSESOR 26-AUG-2013 KG TECHNOLOGIES, AGREES TO THE FOLLOWING: DATE: KG TECHT KG TECHNOLOGIES, INC. THE POSSESOR AGREES (a) TO MAINTAIN THIS DOCUMENTN/A IN CONFIDENCE (a) TO N/A MATERIAL: (a) TO MAINTAIN THIS DOCUMENT IN CONFIDEN MATERIAL: N/A(b) NOT TO COPY OR REPRODUCE IT (b) NO (b) NOT TO COPY OR REPRODUCE IT (c) NOT TO REVEAL OR PUBLISH IT IN WHOLE OR INTOPART (c) NOT (c) NOT REVEAL OR PUBLISH IT IN WHOLE OR N/A FINISH: RIGHTS RESERVED N/A (d) ALL RIGHTS RESERVED FINISH: (d) ALL N/A(d) ALL TOLERANCES CUSTOMER PART NUMBER: TOLERANCES CUST TOLERANCES CUSTOMER PART NUMBE DA 0-<3 3-<6 0.2 0 - < 3 0.2 3 - < 6 0.2 0 - < 3 30 - < 120 120 - < 400 0.4 30 - < 120 30 - < 120 0.4 0.2 3 - < 6 N/A 0.2 0.2 Email: info@kgtechnologies.net6 - < 30/ Web:0.3www.kgtechnologies.net TITLE: 30 0.3 6 - <DRAWING 30 0.36 - <DRAWING TITLE: 0.5 - < 400 120 062015 0.4 DRA 120 - < 400 0.5 TERM K119 STYLES 0.5 TERMINAL K119 K119-90A Page 4 of 4 Wiring Diagrams Dual Coil Dual Coil Connection T2 Positive Polarity T1 T3 T2 Negative Polarity T1 Single Coil T3 Single Coil Connection Positive Polarity T1 T3 Negative Polarity T1 T3 Application Notes Dual Coil – Positive Polarity: Place a negative connection on T2. Then apply a 50ms positive pulse to T1 to open the contacts or to T3 to close the contacts. Dual Coil – Negative Polarity: Place a positive connection on T2. Then apply a 50ms negative pulse to T1 to open the contacts or to T3 to close the contacts. Single Coil – Positive Polarity: Place a negative connection on T1. Then apply a 50ms positive pulse to T3 to close the contacts. Place a positive connection on T1. Then apply a 50ms negative pulse to T3 to open the contacts. Single Coil – Negative Polarity: Place a positive connection on T1. Then apply a 50ms negative pulse to T3 to close the contacts. Place a negative connection on T1. Then apply a 50ms positive pulse to T3 to open the contacts. Additional Application Notes 1: It is possible that during transit or final assembly the relay could change state. Therefore, it is recommended that all relays be set to the desired state via a power supply. 2: In order to maintain an “Open” or “Closed” state of the relay, the coil voltage should reach the rated voltage. The pulse width should be 50ms minimum to ensure a proper change of state. DO NOT energize both T1 and T3 at the same time on a Dual Coil or energize the coil for longer than 1 minute (damage to the coil could incur). 3: Relays without flex-wire cannot be tin-soldered. Moving or bending the terminals could cause damage to the internal structure of the relay. 4: For definitions of terms used in this data sheet, see glossary at www.kgtechnologies.net. Disclaimer: This data sheet is for reference only. All specifications are subject to change without prior notice. KG Technologies, Inc. cannot predict every possible application for our relays. While we do our best to make our relays as versatile as possible, we highly recommend contacting our engineering team if you have any questions. KG Technologies, Inc. is not responsible for malfunctioning relays when operated outside the specified parameters given in this data sheet. KG Technologies, Inc. / Phone: +1.888.513.1874 / Fax: +1.888.511.3989 / Email: info@kgtechnologies.net / Web: www.kgtechnologies.net 062015