Indication contacts - Schneider Electric

advertisement
Functions
and characteristics
Indication contacts
Indication contacts are available:
b in the standard version for relay
applications
b in a low-level version for control of PLCs
and electronic circuits.
M2C and M6C contacts may be
programmed via the Micrologic P and H
control units.
ON/OFF indication contacts (OF)
b rotary type changeover contacts directly driven by the mechanism for
Masterpact UR. These contacts trip when the minimum isolation distance between
the main circuit-breaker contacts is reached.
OF
UR
Supplied as standard
Breaking capacity (A)
p.f.: 0.3
AC12/DC12
3
Standard
V AC
PB100807-20
V DC
240/380
480
690
24/48
125
250
Low-level
V AC
V DC
PB100820-32
ON/OFF indication contacts
(OF) (rotary type).
24/48
240
380
24/48
125
250
Minimum load: 100 mA/24 V
10
10
6
10
10
3
Minimum load: 2 mA/15 V
6
6
3
6
6
3
“Fault-trip” indication contacts (SDE)
Circuit-breaker tripping due to a fault is signalled by:
b a red mechanical fault indicator (reset)
b one changeover contact (SDE).
Following tripping, the mechanical indicator must be reset before the circuit breaker
may be closed.
SDE
UR
Additional “fault-trip”
indication contacts (SDE).
Supplied as standard
Maximum number
Breaking capacity (A)
p.f.: 0.3
AC12/DC12
Standard
V AC
V DC
240/380
480
690
24/48
125
250
Low-level
V AC
V DC
24/48
240
380
24/48
125
250
1
2
Minimum load: 100 mA/24 V
5
5
3
3
0.3
0.15
Minimum load: 2 mA/15 V
3
3
3
3
0.3
0.15
“Fault-trip” indication contacts (SD UR)
Circuit-breaker tripping due to a Thomson (TEC) fault is signalled by a change over
contact (SDUR).
This contact is located inside the "UR Power" module.
Note: this contact is a non Latching contact. To keep the indication, it is necessay to connect on
external relay.
Characteristics
Minimum load
Breaking capacity (A)
SDUR
V AC
V DC
A-32
250
400
30
150
300
10 mA/5 V
10
5
8
0.3
0.15