Functions and characteristics Indication contacts Indication contacts are available: b in the standard version for relay applications b in a low-level version for control of PLCs and electronic circuits. M2C and M6C contacts may be programmed via the Micrologic P and H control units. ON/OFF indication contacts (OF) b rotary type changeover contacts directly driven by the mechanism for Masterpact UR. These contacts trip when the minimum isolation distance between the main circuit-breaker contacts is reached. OF UR Supplied as standard Breaking capacity (A) p.f.: 0.3 AC12/DC12 3 Standard V AC PB100807-20 V DC 240/380 480 690 24/48 125 250 Low-level V AC V DC PB100820-32 ON/OFF indication contacts (OF) (rotary type). 24/48 240 380 24/48 125 250 Minimum load: 100 mA/24 V 10 10 6 10 10 3 Minimum load: 2 mA/15 V 6 6 3 6 6 3 “Fault-trip” indication contacts (SDE) Circuit-breaker tripping due to a fault is signalled by: b a red mechanical fault indicator (reset) b one changeover contact (SDE). Following tripping, the mechanical indicator must be reset before the circuit breaker may be closed. SDE UR Additional “fault-trip” indication contacts (SDE). Supplied as standard Maximum number Breaking capacity (A) p.f.: 0.3 AC12/DC12 Standard V AC V DC 240/380 480 690 24/48 125 250 Low-level V AC V DC 24/48 240 380 24/48 125 250 1 2 Minimum load: 100 mA/24 V 5 5 3 3 0.3 0.15 Minimum load: 2 mA/15 V 3 3 3 3 0.3 0.15 “Fault-trip” indication contacts (SD UR) Circuit-breaker tripping due to a Thomson (TEC) fault is signalled by a change over contact (SDUR). This contact is located inside the "UR Power" module. Note: this contact is a non Latching contact. To keep the indication, it is necessay to connect on external relay. Characteristics Minimum load Breaking capacity (A) SDUR V AC V DC A-32 250 400 30 150 300 10 mA/5 V 10 5 8 0.3 0.15