® For Your Information ... APPLICATION NOTE #137 Wiring Lutron Occupant Sensors to Lutron Control Systems and Hardware Lutron Control System Power Pack Required? Number of sensors powered by system System expandable with power pack? Quick Reference Guide EcoSystemTM N 1 Y Digital microWATTTM N 1-3 Y MicroWATT® N 1-3 Y Use lighting zone controller; at least one must be connected before expansion RadioTouchTM SoftswitchTM N N* 1 1 Y Y Use with RTA-RX controller/RTA-SCI Use with seeTouchTM wallstation/OMX-AV/Panel CCI LCP128TM N* 1 Y Use with seeTouch wallstation/OMX-AV/Panel CCI GRAFIK 5000/6000/7000TM GRAFIK Eye® 3000/4000 HomeWorks® RadioRA® N* Y Y Y 1 0 0 0 Y Y Y Y Use Use Use Use Notes: Use Ecosystem Ballast/C5-BMF Use lighting zone controller; at least one must be connected before expansion with with with with seeTouch wallstation/OMX-AV GRX-AV CCI RA-SCI *Power Pack required for OMX-AV and Panel CCI controls Supporting Hardware OMX-AV GRX-AV Panel Contact Closure Interface seeTouchTM wallstation Contact Closure Interface Y Y Y N Y 0 0 0 1 0 Y Y Y Y Y Power Power Power Power Power pack pack pack pack pack must power occupant sensor** must power occupant sensor** must power occupant sensor** used to expand system** must power occupant sensor** **Power Packs are able to support a MAX of three occupant sensors each Wire Size Note: Use a minimum wire size of #18 AWG (1.0 mm2) for long wire runs (>2000 ft/610 m), #24 AWG (0.5 mm2) for medium wire runs (500 ft/152 m to 2000 ft/610 m), and #28 AWG (0.5 mm2) for short wire runs only (<500 ft/152 m). • 1 See individual product specifications for a complete wiring guide of Lutron occupant sensors to other Lutron Lighting Control Systems Need additional assistance? Call the Lutron Technical Support Center 1-800-523-9466. Please provide exact model number when calling. GRX-AV and OMX-AV Wiring Diagram: 3-Zone Example GRX-AV/OMX-AV ON 1 1 2 3 2 3 4 4 MUX LINK 5 6 7 C 8 1 2 3 INPUTS 4 5 1 2 3 4 5 C Note: All occupant sensors tied to individual inputs will work to control 1 scene only, not 3. OUTPUTS Hot 120/277/347 V 60 Hz 230 V 50/60 Hz Neutral Black White Red (+20-24 V ) Blue (signal) Black (common) Power Pack Note: Maximum 3 occupant sensors. Hot Red Red Note: Cap off BLUE signal and RED power wires to power pack if switching is not being used. 120/277/347 V 60 Hz 230 V 50/60 Hz Neutral Black Note: For -R model sensors use gray wire instead of blue as seen in installation manual. Red (+20-24 V ) Blue (signal) Black (common) Power Pack White Red Red Note: Maximum 3 occupant sensors. Hot 120/277/347 V 60 Hz 230 V 50/60 Hz Neutral Black Red (+20-24 V ) Blue (signal) Black (common) White Power Pack Red Red Note: Maximum 3 occupant sensors. Note: All of the signal (blue) wires are connected to “C”, with the +24 V wire of each zone connected to a contact closure input of the AV unit. All three occupant sensors per power pack are seen as one signal by the AV input in this drawing. 2 Need additional assistance? Call the Lutron Technical Support Center 1-800-523-9466. Please provide exact model number when calling. Creating Toggle Function with GRX-AV/OMX-AV (for use with -R model sensors only) Enables the ability to toggle between two scenes instead of standard occupant sensor ON/OFF operation. GRX-AV/OMX-AV ON 1 1 2 3 2 3 4 5 6 4 7 8 C 1 MUX LINK 2 3 4 5 1 INPUTS 2 3 4 5 Note: BLUE knob on occupant sensor must be turned fully clockwise for unit to function properly. C OUTPUTS Scene when occupied Scene when non-occupied Black Red (+20-24 V White ) Power Pack Black (common) Yellow/White (NO) Black/White (NC) 120/277/347 V 60 Hz 230 V 50 Hz Neutral Red Red Gray Blue Blue/White (common) Dry Contacts LOS-CDT-x000R-WH Creating Toggle Function with RadioTouchTM (for use with -R model sensors only) Note: Maximum of 3 sensors can be powered by the unit. RadioTouch RadioT ouc h RTA-RX-F-SC Radio Frequency 120/277 V 60 Hz RTA-RX-F-SC 16 A Max. TM Contr oller LISTED 243C Ind. Cont. Eq. Coopersburg, PA 18036 USA 1-800-523-9466 1-888-235-2910 CONFIGURACIONES REGLAGES SETTINGS Powered PWR Status STAT ProgramPROG 100Burn-in Hr/100% ON 0-10 V CCO 5 CCO Com CCO 3 CCO 4 CCO 2 9 10 11 12 13 14 15 16 P/N 500-10634 ® 8 CCO 1 6 7 + 5 _ 4 PS Sig 3 Cir Com 1 2 15 V 5 24 V 4 Occ Sig 3 Occ. Com 2 PELV (Class 2: USA) 1 © 2006 Lutron Electronics Co., Inc. Coopersburg, PA 18036 USA, Canada Mexico www.lutron.com ® Refer to the Installers Guide for more detailed instructions. Consulte la Guía de Instaladores para información más detallada. Référer au Guide d’installation pour plus de renseignements détaillés. RTA-RX-F-SC Black (common) Red (+20-24 V ) Blue/White (common) Yellow/White (NO) Gray Blue Black/White (NC) LOS-CDT-x000R-WH 3 Need additional assistance? Call the Lutron Technical Support Center 1-800-523-9466. Please provide exact model number when calling. Combined Emergency and Occupant Sensor Function with RadioTouchTM (for use with -R model sensors only) Note: Set Radio Touch “Receiver Switch Settings” DIP switch 2 to OFF for emergency mode. LUT-ELI-3PH RTA-RX-F-SC For use with Lutron GRAFIK Eye GP-, XP-, LP- Series panels and RadioTouch TM Controllers +V Input (24VDC or 24VFW ) Circuit Common Nor mally Closed Contacts Fire Alarm Control Panel Fire Alarm Control Panel Nor mally O pen Contacts Not Used Signal on RadioTouch C o nrot le r(s ) CCO 5 CCO Com CCO 4 CCO 2 CCO 3 11 12 13 14 15 16 Sense on Circuit Selector(s) Drain MUX MUX 0-10 V 9 10 P/N 500-10634 © 2006 Lutron Electronics Co., Inc. ® 8 CCO 1 6 7 + 15 V 5 _ 4 PS Sig 3 Cir Com 1 2 CAUTION! Read instruction manual for installation, operation, and maintenance instructions. 100 Hr/100% 5 24 V 4 Occ Sig 3 Occ. Com PELV (Class 2: USA) 2 This equipment has more than one power connection point. To reduce the risk of electrical shock disconnect both the branch circuit breakers or fuses before ser vicing. 3-Phase 100V~ to 347V~, 50/60 Hz sense lines 24VDC or 24VFW input ON 1 CAUTION! ® 12 11 10 9 8 6 5 4 3 Status Indicators Press and hold to test 7 Term inal conn ections are Class 2. 2 1 S1 Signal 24 V Common OFF during non-occupancy Blue/White (common) Black/White (NC) ON during occupancy Yellow/White (NO) Gray Blue LOS-CDT-x000R-WH 4 Test Refer to the Installers Guide for more detailed instructions. Consulte la Guía de Instaladores para información más detallada. Référer au Guide d’installation pour plus de renseignements détaillés. PROG STAT Emergency Lighting and Power Equipment 59VB Coopersburg, PA 18036 © 2003 Lutron Electronics Co., Inc. PWR LUT-ELI-3PH 3 Phase Detector ® Fire Alarm 1-800-523-9466 1-888-235-2910 CONFIGURACIONES REGLAGES SETTINGS Emergency Lighting Interface LISTED 243C Ind. Cont. Eq. Coopersburg, PA 18036 USA USA, Canada Mexico www.lutron.com 60 Hz ON= Phase(s) OK OFF= Phase(s) failure 120/277 V 16 A Max. TM TM RadioTouch RTA-RX-F-SC Need additional assistance? Call the Lutron Technical Support Center 1-800-523-9466. Please provide exact model number when calling. Lighting Zone Controller Interface (microWATT® and Digital microWATTTM): Single-Zone Example Lighting Zone Controller Digital Link Enlace Digital Lien Digital ADDR 7 6 5 4 10 11 12 13 14 15 ON 1 2 3 9 SHLD 8 EMERG 7 MUX 6 LNK COM OCC SIG OCC COM 5 MUX +15 V 4 +24 V 3 WC COM CIR COM 2 WC SIG PS SIG 1 PS COM 8 ® +24 V Notes: • At least 1 occupant sensor must be connected to the microWATT interface to ensure proper operation. • A maximum of 3 occupant sensors are able to be powered by the microWATT unit alone. • A maximum of 10 occupant sensor signal lines are permitted to be connected to one microWATT unit. Red (+20-24 V ) Blue (signal) Black (common) 6 7 8 CLASS 2 LOW VOL 9 10 Shield EMERG Link Com MUX MUX 5 OCC Com WC Com 4 OCC Signal Circuit Com 3 +15V PS Com 2 +24V PS Signal 1 WC Signal +24V P/N 500-9066 Rev. F 11 12 13 14 15 TAGE WIRING Note: Maximum 3 occupant sensors. Note: For -R model sensors use gray wire instead of blue as seen in installation manual. Hot 120/277/347 V 60 Hz 230 V 50/60 Hz Neutral Black White Red (+20-24 V ) Blue (signal) Black (common) Power Pack Note: Maximum 3 occupant sensors. Hot Red Red Note: Cap off BLUE signal and RED power wires to power pack if switching is not being used. 120/277/347 V 60 Hz 230 V 50/60 Hz Neutral Black Red (+20-24 V White ) Blue (signal) Black (common) Power Pack Lighting Load Red Red Manual switch off (optional) Note: Maximum 3 occupant sensors. 5 Need additional assistance? Call the Lutron Technical Support Center 1-800-523-9466. Please provide exact model number when calling. Multi Lighting Zone Controller System: Interfacing Peripheral Connections between Lighting Zone Controllers Lighting Zone Controller Digital Link Enlace Digital Lien Digital ADDR 7 6 10 5 9 4 8 11 12 13 14 15 1 ON 2 3 OCC COM 7 SHLD OCC SIG 6 EMERG +15 V 5 MUX +24 V 4 LNK COM WC SIG 3 MUX WC COM 2 PS COM PS SIG 1 CIR COM +24 V 8 ® Shield 9 10 EMERG 8 Link Com 7 MUX 6 CLASS 2 LOW VOL MUX 5 OCC Com WC Com 4 OCC Signal Circuit Com 3 +15V PS Com 2 +24V PS Signal 1 WC Signal +24V P/N 500-9066 Rev. F 11 12 13 14 15 T AGE WIRING White (common) Red (signal) Black (24V) Sensor signal and COM must be referenced between units Circuit COM tied together Digital Link Enlace Digital Lien Digital ADDR 10 7 OCC COM 9 6 OCC SIG 8 5 +15 V 7 4 +24 V 6 11 12 13 14 15 1 ON 2 3 WC SIG 5 SHLD WC COM 4 EMERG CIR COM 3 LNK COM PS COM 2 MUX PS SIG 1 MUX +24 V 8 ® White w/Black trace (common) Yellow (signal) Shield 9 10 EMERG 8 Link Com 7 MUX 6 CLASS 2 LOW VOL MUX 5 OCC Com WC Com 4 OCC Signal Circuit Com 3 +15V PS Com 2 +24V PS Signal 1 WC Signal +24V P/N 500-9066 Rev. F 11 12 13 14 15 Purple (+20-24 V ) T AGE WIRING Blue Red (+20-24 V ) Blue (signal) Black (common) Gray Orange microWATT Control Wallstation Note: Maximum 3 occupant sensors. 6 Need additional assistance? Call the Lutron Technical Support Center 1-800-523-9466. Please provide exact model number when calling. Controlling Zone with Dual Feeds: Power Booster Example Zone 1 and Zone 2 controlled by same occupant sensors Zone 1 and Zone 2 powered by different feed lines NEUTRAL Hot CU WIRE ONLY 4 3 2 1 HOT/LIVE 120-127 V 60 Hz 220-240 V 50/60 Hz SSA USA CLASS 2 IEC PELV Panel Feed 1 ZONE 3 Neutral ZONE 2 ZONE 1 GRX-3103 Control Unit Panel Feed 2 Hot 120-127 V 60 Hz 220-240 V 50/60 Hz Neutral Auxiliary Power Pack Red Red Red (+20-24 V ) Blue (signal) Black (common) Power Pack Black White Red Red NGRX-PB Zone 2 7 Zone 1 Need additional assistance? Call the Lutron Technical Support Center 1-800-523-9466. Please provide exact model number when calling. Fluorescent Dimming Ballast (FDB) with Occupant Sensors: Single-Zone Example Note: Power Packs can switch 20 A ballast current for 120/277 V versions. Fixture Ground Ground Neutral Hot Dimmed Note: For -R model sensors use gray wire instead of blue as seen in installation manual. Green White Black Orange Green White Black Orange Lutron FDB or ECO Dimming Ballast Black White Red (+20-24 V ) Blue (signal) Black (common) Power Pack Red Red Note: Maximum 3 occupant sensors. Dual Circuit Switching of FDBs (<20 A/Zone): Single-Zone Example Note: Power Packs can switch 20 A ballast current for 120/277 V versions. Ground Neutral Hot Dimmed Green Green White White Black Black Fixture Ground Lutron FDB or ECO Dimming Ballast Orange Orange Bank of Ballasts <20 A Ground Neutral Hot Dimmed Fixture Ground Green White Black Black Orange Orange Lutron FDB or ECO Dimming Ballast Bank of Ballasts <20 A Black Red Red Auxiliary Power Pack Red (+20-24 V ) Blue (signal) Black (common) White Power Pack Red Red Note: Maximum of three devices total (occupant sensors and auxiliary power packs) can be connected to a power pack. 8 Need additional assistance? Call the Lutron Technical Support Center 1-800-523-9466. Please provide exact model number when calling. Switching Dimmed Hot to FDB: Single-Zone Example, Ground Neutral 120/277 V Main Feed ® Green White Black Orange Wallstation Fixture Ground Lutron FDB or ECO Dimming Ballast Zone 1 Ballast Black White Power Pack Red (+20-24 V Blue (signal) Red Red ) Black (common) Note: For -R model sensors use gray wire instead of blue as seen in installation manual. Fluorescent Control Wallstation Switched Hot (Z1) Dimmed Hot (Z1) Black Yellow Red Green or Bare Ground White 9 Need additional assistance? Call the Lutron Technical Support Center 1-800-523-9466. Please provide exact model number when calling. Switching Dimmed Hot to FDB: Dual-Zone Example Ground Neutral 120/277 V Main Feed Fixture Ground Green White Black Orange Lutron FDB or ECO Dimming Ballast Zone 1 Ballast Black White Power Pack Red Red Green White Black Orange Fixture Ground Lutron FDB or ECO Dimming Ballast Zone 2 Ballast Red (+20-24 V ) Blue (signal) Black (common) Note: For -R model sensors use gray wire instead of blue as seen in installation manual. Switched Hot (Z1) Fluorescent Control Wallstation Black Dimmed Hot (Z1) Yellow Red Green or Bare Ground White Switched Hot (Z2) Fluorescent Control Wallstation Black Dimmed Hot (Z2) Yellow Red Green or Bare Ground White 10 Need additional assistance? Call the Lutron Technical Support Center 1-800-523-9466. Please provide exact model number when calling. EcosystemTM Ballast Interface: Single-Zone Example Note: All occupant sensors tied to ballasts will control a single zone, not 4. +20 V +20 V +20 V Common Common Common IR Occ Daylight Red Black Blue EcoSystem Ballast A Low Voltage Connections +20 V +20 V +20 V Common Common Common IR Occ Daylight EcoSystem Ballast B Single Occupant Sensor Reference Hot Note: For -R model sensors use gray wire instead of blue as seen in installation manual. 120/277/347 V 60 Hz 230 V 50/60 Hz Neutral Black Red (+20-24 V Blue (signal) Black (common) Note: Maximum 3 occupant sensors. 11 White ) Power Pack Red Red Note: Cap off BLUE signal and RED power wires to power pack if switching is not being used. Need additional assistance? Call the Lutron Technical Support Center 1-800-523-9466. Please provide exact model number when calling. Wiring to a seeTouchTM allstation: Single-Zone Example 3 #18 AWG (1.0 mm2) 3: Common 2: 24 V 1: Signal C B A Occupant Sensor Note: All occupant sensors tied to controller will work to control 1 zone only, not 4. Note: For -R model sensors use gray wire instead of blue as seen in installation manual. Notes: • A MAXIMUM of 1 occupant sensor can be powered by the seeTouch wallstation to ensure proper operation. • A MAXIMUM of 10 occupant sensor signal lines are permitted to be connected to one seeTouch wallstation. •Occupant sensors do NOT work with standard seeTouch controls. Hot 120/277/347 V 60 Hz 230 V 50/60 Hz Neutral Black Red (+20-24 V Blue (signal) Black (common) White ) Power Pack Red Red Note: Cap off BLUE signal wire. Cap off RED power wires to power pack if switching is not being used. Note: Maximum 3 occupant sensors. Wiring to a Contact Closure Input: LCP Controller Example LCP Controller Hot CCI A CCI B 120/277/347 V 60 Hz 230 V 50/60 Hz Neutral 1 23 4 Black PELV (Class #2: USA) White Power Pack Common Signal Red Red Common Signal Red (+20-24 V Blue (signal) Black (common) Sensor A 12 ) Sensor B Need additional assistance? Call the Lutron Technical Support Center 1-800-523-9466. Please provide exact model number when calling. Interfacing Wallbox Occupant Sensors with Wallbox Dimming Products: Maestro® Wallstation Example Black Dimmed Hot Red Hot Wall Sensor Switched Hot 120/277 V Green Neutral Notes: • LOS-SIR is a wallbox-mounted occupant sensor that is used to switch power to a load. • Dimmer will retain previous settings when power is returned (based off assumed normal operation of a Maestro wallstation control). • This is a simple solution to this type of situation. • Do NOT use LOS-SUS units to switch a dimming load. • Unit must be wired on live side of dimmer. Interfacing Low-Voltage Occupant Sensors with Wallbox Dimming Products Hot Black White Power Pack Red (+20-24 V Blue (signal) Black (common) ) Red 120 V 230 V Red 60 Hz 50 Hz Dimmed Hot Neutral Notes: • The dimmed hot signal is switched in this circuit versus the hot signal in the previous drawing. • This is a more complex method that allows for the use of versatile low-voltage occupant sensors in place of a wallbox unit. 13 Need additional assistance? Call the Lutron Technical Support Center 1-800-523-9466. Please provide exact model number when calling. Title 24 Circuits: LOS-SIR-M Manual ON/Auto OFF LOS-SIR-M Red Black Hot Wall Sensor Lutron Lighting Control (If not Title 24 Complaint) Switched Hot 120/277 V Dimmed Hot Green Neutral Neutral Title 24 Circuits: Sentry Switch Manual ON/Auto OFF Hot Black White Power Pack Red Red Lutron Lighting Control (If not Title 24 Complaint) 120/277/347 V 230 V 50 Hz Sentry Switch Red (+20-24 V Blue (signal) Black (common) ) Neutral Neutral Dimmed Hot 14 Need additional assistance? Call the Lutron Technical Support Center 1-800-523-9466. Please provide exact model number when calling. 60 Hz Chicago Code Violation Solution: No 277 V Wallstation “ON” sensor powered; automatic sense of occupancy Wallstation “OFF” sensor not powered; lights off Do NOT exceed 1 000 ft (305 m) of low voltage cable with three occupant sensors attached. in the Wall Note: Low voltage switched in the wall because code does not allow 277 V power in the wall; mainly concerning ballast applications. Low Voltage (24 V ) 277 V feed (in ceiling) Wall Switch (in wall) Black White Red (+20-24 V Blue (signal) Black (common) ) Power Pack Red Red To lighting load Note: Maximum 3 occupant sensors. 15 Need additional assistance? Call the Lutron Technical Support Center 1-800-523-9466. Please provide exact model number when calling. Worldwide Technical and Sales Assistance If you need assistance, call the toll-free Lutron Technical Support Center. Please provide exact model number when calling. 24 hours/day + 7 days/week North and South America U.S.A., Canada, Caribbean: 1.800.523.9466 Mexico: +1.888.235.2910 Central/South America: +1.610.282.6701 Lutron Electronics Co., Inc. 7200 Suter Road Coopersburg, PA 18036-1299 U.S.A. Phone: +(610) 282-3800 Fax: -(610) 282-3090 Lutron, GRAFIK Eye, GRAFIK 6000, Maestro, microWATT, Nova, and RadioRA are registered trademarks, and EcoSystem, Digital microWATT, RadioTouch, seeTouch, Softswitch and GRAFIK 5000/7000 are trademarks of Lutron Electronics Co., Inc. © 2007 Lutron Electronics, Co., Inc. Europe Technical support: +44.(0)20.7680.4481 Asia Northern China: 10.800.712.1536 Southern China: 10.800.120.1536 Hong Kong: 800.901.849 Japan: +81.3.5575.8411 Singapore: 800.120.4491 Taiwan: 00.801.137.737 Thailand: 001.800.120.665853 Other countries: +65.6220.4666 Visit us on the web at www.lutron.com 16 Lutron Electronics Co., Inc. 7200 Suter Road Coopersburg, PA 18036-1299 U.S.A. Made and printed in U.S.A. 05/07 P/N 048-166 Rev. B Need additional assistance? Call the Lutron Technical Support Center 1-800-523-9466. Please provide exact model number when calling.