For Your Information

advertisement
®
For Your Information ...
APPLICATION
NOTE
#137
Wiring Lutron Occupant Sensors to
Lutron Control Systems and Hardware
Lutron Control System
Power Pack Required?
Number of sensors
powered by system
System expandable
with power pack?
Quick Reference Guide
EcoSystemTM
N
1
Y
Digital microWATTTM
N
1-3
Y
MicroWATT®
N
1-3
Y
Use lighting zone controller; at least one must be
connected before expansion
RadioTouchTM
SoftswitchTM
N
N*
1
1
Y
Y
Use with RTA-RX controller/RTA-SCI
Use with seeTouchTM wallstation/OMX-AV/Panel CCI
LCP128TM
N*
1
Y
Use with seeTouch wallstation/OMX-AV/Panel CCI
GRAFIK 5000/6000/7000TM
GRAFIK Eye® 3000/4000
HomeWorks®
RadioRA®
N*
Y
Y
Y
1
0
0
0
Y
Y
Y
Y
Use
Use
Use
Use
Notes:
Use Ecosystem Ballast/C5-BMF
Use lighting zone controller; at least one must be
connected before expansion
with
with
with
with
seeTouch wallstation/OMX-AV
GRX-AV
CCI
RA-SCI
*Power Pack required for OMX-AV and Panel CCI controls
Supporting Hardware
OMX-AV
GRX-AV
Panel Contact Closure Interface
seeTouchTM wallstation
Contact Closure Interface
Y
Y
Y
N
Y
0
0
0
1
0
Y
Y
Y
Y
Y
Power
Power
Power
Power
Power
pack
pack
pack
pack
pack
must power occupant sensor**
must power occupant sensor**
must power occupant sensor**
used to expand system**
must power occupant sensor**
**Power Packs are able to support a MAX of three occupant sensors each
Wire Size Note:
Use a minimum wire size of #18 AWG (1.0 mm2) for long wire runs (>2000 ft/610 m), #24 AWG (0.5 mm2)
for medium wire runs (500 ft/152 m to 2000 ft/610 m), and #28 AWG (0.5 mm2) for short wire runs
only (<500 ft/152 m).
•
1
See individual product specifications for a complete wiring guide of Lutron occupant sensors to other Lutron
Lighting Control Systems
Need additional assistance? Call the Lutron Technical Support Center 1-800-523-9466.
Please provide exact model number when calling.
GRX-AV and OMX-AV Wiring Diagram: 3-Zone Example
GRX-AV/OMX-AV
ON
1
1
2
3
2
3
4
4
MUX LINK
5
6
7
C
8
1
2
3
INPUTS
4
5
1
2
3
4
5
C
Note: All occupant sensors tied
to individual inputs will work to
control 1 scene only, not 3.
OUTPUTS
Hot
120/277/347 V
60 Hz
230 V
50/60 Hz
Neutral
Black
White
Red (+20-24 V
)
Blue (signal)
Black (common)
Power
Pack
Note: Maximum 3 occupant sensors.
Hot
Red
Red
Note: Cap off BLUE signal and
RED power wires to power pack
if switching is not being used.
120/277/347 V
60 Hz
230 V
50/60 Hz
Neutral
Black
Note:
For -R model
sensors use
gray wire
instead of
blue as seen
in installation
manual.
Red (+20-24 V
)
Blue (signal)
Black (common)
Power
Pack
White
Red
Red
Note: Maximum 3 occupant sensors.
Hot
120/277/347 V
60 Hz
230 V
50/60 Hz
Neutral
Black
Red (+20-24 V
)
Blue (signal)
Black (common)
White
Power
Pack
Red
Red
Note: Maximum 3 occupant sensors.
Note: All of the signal (blue) wires are connected to “C”, with the +24 V
wire of each zone connected to
a contact closure input of the AV unit. All three occupant sensors per power pack are seen as one signal by
the AV input in this drawing.
2
Need additional assistance? Call the Lutron Technical Support Center 1-800-523-9466.
Please provide exact model number when calling.
Creating Toggle Function with GRX-AV/OMX-AV (for use with -R model sensors only)
Enables the ability to toggle between two
scenes instead of standard occupant sensor
ON/OFF operation.
GRX-AV/OMX-AV
ON
1
1
2
3
2
3
4
5
6
4
7
8
C
1
MUX LINK
2
3
4
5
1
INPUTS
2
3
4
5
Note: BLUE knob on occupant sensor must be
turned fully clockwise for unit to function
properly.
C
OUTPUTS
Scene when occupied
Scene when non-occupied
Black
Red (+20-24 V
White
)
Power
Pack
Black
(common)
Yellow/White (NO)
Black/White (NC)
120/277/347 V 60 Hz
230 V 50 Hz
Neutral
Red
Red
Gray Blue
Blue/White (common)
Dry
Contacts
LOS-CDT-x000R-WH
Creating Toggle Function with RadioTouchTM (for use with -R model sensors only)
Note: Maximum of 3 sensors can be powered
by the unit.
RadioTouch
RadioT
ouc h
RTA-RX-F-SC
Radio
Frequency
120/277 V
60 Hz
RTA-RX-F-SC
16 A Max.
TM
Contr oller
LISTED 243C
Ind. Cont. Eq.
Coopersburg, PA 18036 USA
1-800-523-9466
1-888-235-2910
CONFIGURACIONES
REGLAGES
SETTINGS
Powered PWR
Status
STAT
ProgramPROG
100Burn-in
Hr/100%
ON
0-10
V
CCO 5
CCO Com
CCO 3
CCO 4
CCO 2
9 10 11 12 13 14 15 16
P/N 500-10634
®
8
CCO 1
6 7
+
5
_
4
PS Sig
3
Cir Com
1 2
15 V
5
24 V
4
Occ Sig
3
Occ. Com
2
PELV (Class 2: USA)
1
© 2006 Lutron Electronics Co., Inc.
Coopersburg, PA 18036
USA, Canada
Mexico
www.lutron.com
®
Refer to the Installers Guide for more
detailed instructions.
Consulte la Guía de Instaladores para
información más detallada.
Référer au Guide d’installation pour plus
de renseignements détaillés.
RTA-RX-F-SC
Black (common)
Red (+20-24 V
)
Blue/White (common)
Yellow/White (NO)
Gray Blue
Black/White (NC)
LOS-CDT-x000R-WH
3
Need additional assistance? Call the Lutron Technical Support Center 1-800-523-9466.
Please provide exact model number when calling.
Combined Emergency and Occupant Sensor Function with RadioTouchTM
(for use with -R model sensors only)
Note: Set Radio Touch “Receiver Switch
Settings” DIP switch 2 to OFF for emergency
mode.
LUT-ELI-3PH
RTA-RX-F-SC
For use with Lutron GRAFIK Eye
GP-, XP-, LP- Series panels and
RadioTouch TM Controllers
+V Input (24VDC or 24VFW )
Circuit Common
Nor mally Closed Contacts
Fire Alarm Control Panel
Fire Alarm Control Panel
Nor mally O pen Contacts
Not Used
Signal on RadioTouch C o nrot le r(s )
CCO 5
CCO Com
CCO 4
CCO 2
CCO 3
11 12 13 14 15 16
Sense on Circuit Selector(s)
Drain
MUX
MUX
0-10
V
9 10
P/N 500-10634 © 2006 Lutron Electronics Co., Inc.
®
8
CCO 1
6 7
+
15 V
5
_
4
PS Sig
3
Cir Com
1 2
CAUTION!
Read instruction
manual for installation, operation, and
maintenance instructions.
100 Hr/100%
5
24 V
4
Occ Sig
3
Occ. Com
PELV (Class 2: USA)
2
This equipment has
more than one power connection point. To
reduce the risk of electrical shock
disconnect both the branch circuit breakers
or fuses before ser vicing.
3-Phase 100V~ to 347V~, 50/60 Hz
sense lines
24VDC or 24VFW input
ON
1
CAUTION!
®
12 11 10 9
8
6
5
4
3
Status Indicators
Press and hold to test
7
Term inal conn ections are Class 2.
2
1
S1
Signal
24 V
Common
OFF during non-occupancy
Blue/White (common)
Black/White (NC)
ON during occupancy
Yellow/White (NO)
Gray Blue
LOS-CDT-x000R-WH
4
Test
Refer to the Installers Guide for more detailed
instructions.
Consulte la Guía de Instaladores para información
más detallada.
Référer au Guide d’installation pour plus de
renseignements détaillés.
PROG
STAT
Emergency Lighting
and Power Equipment
59VB
Coopersburg, PA 18036
© 2003 Lutron Electronics Co., Inc.
PWR
LUT-ELI-3PH
3 Phase Detector
®
Fire Alarm
1-800-523-9466
1-888-235-2910
CONFIGURACIONES
REGLAGES
SETTINGS
Emergency Lighting Interface
LISTED 243C
Ind. Cont. Eq.
Coopersburg, PA 18036 USA
USA, Canada
Mexico
www.lutron.com
60 Hz
ON= Phase(s) OK
OFF= Phase(s) failure
120/277 V
16 A Max.
TM
TM
RadioTouch
RTA-RX-F-SC
Need additional assistance? Call the Lutron Technical Support Center 1-800-523-9466.
Please provide exact model number when calling.
Lighting Zone Controller Interface (microWATT® and Digital microWATTTM):
Single-Zone Example
Lighting Zone Controller
Digital Link
Enlace Digital
Lien Digital
ADDR
7
6
5
4
10
11 12 13 14 15
ON
1
2
3
9
SHLD
8
EMERG
7
MUX
6
LNK COM
OCC SIG
OCC COM
5
MUX
+15 V
4
+24 V
3
WC COM
CIR COM
2
WC SIG
PS SIG
1
PS COM
8
®
+24 V
Notes:
• At least 1 occupant sensor must be
connected to the microWATT interface to
ensure proper operation.
• A maximum of 3 occupant sensors are
able to be powered by the microWATT unit
alone.
• A maximum of 10 occupant sensor
signal lines are permitted to be connected
to one microWATT unit.
Red (+20-24 V
)
Blue (signal)
Black (common)
6
7 8
CLASS 2 LOW VOL
9 10
Shield
EMERG
Link Com
MUX
MUX
5
OCC Com
WC Com
4
OCC Signal
Circuit Com
3
+15V
PS Com
2
+24V
PS Signal
1
WC Signal
+24V
P/N 500-9066 Rev. F
11 12 13 14 15
TAGE WIRING
Note: Maximum 3 occupant sensors.
Note:
For -R model sensors
use gray wire instead of
blue as seen in
installation manual.
Hot
120/277/347 V
60 Hz
230 V
50/60 Hz
Neutral
Black
White
Red (+20-24 V
)
Blue (signal)
Black (common)
Power
Pack
Note: Maximum 3 occupant sensors.
Hot
Red
Red
Note: Cap off BLUE signal and
RED power wires to power pack
if switching is not being used.
120/277/347 V
60 Hz
230 V
50/60 Hz
Neutral
Black
Red (+20-24 V
White
)
Blue (signal)
Black (common)
Power
Pack
Lighting
Load
Red
Red
Manual
switch off
(optional)
Note: Maximum 3 occupant sensors.
5
Need additional assistance? Call the Lutron Technical Support Center 1-800-523-9466.
Please provide exact model number when calling.
Multi Lighting Zone Controller System: Interfacing Peripheral Connections
between Lighting Zone Controllers
Lighting Zone Controller
Digital Link
Enlace Digital
Lien Digital
ADDR
7
6
10
5
9
4
8
11 12 13 14 15
1
ON
2
3
OCC COM
7
SHLD
OCC SIG
6
EMERG
+15 V
5
MUX
+24 V
4
LNK COM
WC SIG
3
MUX
WC COM
2
PS COM
PS SIG
1
CIR COM
+24 V
8
®
Shield
9 10
EMERG
8
Link Com
7
MUX
6
CLASS 2 LOW VOL
MUX
5
OCC Com
WC Com
4
OCC Signal
Circuit Com
3
+15V
PS Com
2
+24V
PS Signal
1
WC Signal
+24V
P/N 500-9066 Rev. F
11 12 13 14 15
T AGE WIRING
White
(common)
Red
(signal)
Black
(24V)
Sensor signal and COM must be
referenced between units
Circuit COM tied together
Digital Link
Enlace Digital
Lien Digital
ADDR
10
7
OCC COM
9
6
OCC SIG
8
5
+15 V
7
4
+24 V
6
11 12 13 14 15
1
ON
2
3
WC SIG
5
SHLD
WC COM
4
EMERG
CIR COM
3
LNK COM
PS COM
2
MUX
PS SIG
1
MUX
+24 V
8
®
White w/Black
trace (common)
Yellow
(signal)
Shield
9 10
EMERG
8
Link Com
7
MUX
6
CLASS 2 LOW VOL
MUX
5
OCC Com
WC Com
4
OCC Signal
Circuit Com
3
+15V
PS Com
2
+24V
PS Signal
1
WC Signal
+24V
P/N 500-9066 Rev. F
11 12 13 14 15
Purple
(+20-24 V
)
T AGE WIRING
Blue
Red (+20-24 V
)
Blue (signal)
Black (common)
Gray
Orange
microWATT
Control
Wallstation
Note: Maximum 3 occupant sensors.
6
Need additional assistance? Call the Lutron Technical Support Center 1-800-523-9466.
Please provide exact model number when calling.
Controlling Zone with Dual Feeds: Power Booster Example
Zone 1 and Zone 2 controlled by same occupant sensors
Zone 1 and Zone 2 powered by different feed lines
NEUTRAL
Hot
CU WIRE ONLY
4
3
2
1
HOT/LIVE
120-127 V
60 Hz
220-240 V
50/60 Hz
SSA
USA CLASS 2
IEC PELV
Panel Feed 1
ZONE 3
Neutral
ZONE 2
ZONE 1
GRX-3103
Control Unit
Panel Feed 2
Hot
120-127 V
60 Hz
220-240 V
50/60 Hz
Neutral
Auxiliary
Power
Pack
Red
Red
Red (+20-24 V
)
Blue (signal)
Black (common)
Power
Pack
Black
White
Red
Red
NGRX-PB
Zone 2
7
Zone 1
Need additional assistance? Call the Lutron Technical Support Center 1-800-523-9466.
Please provide exact model number when calling.
Fluorescent Dimming Ballast (FDB) with Occupant Sensors:
Single-Zone Example
Note: Power Packs can switch 20 A ballast current for
120/277 V versions.
Fixture Ground
Ground
Neutral
Hot
Dimmed
Note:
For -R model
sensors use
gray wire
instead of blue
as seen in
installation
manual.
Green
White
Black
Orange
Green
White
Black
Orange
Lutron FDB or ECO
Dimming Ballast
Black
White
Red (+20-24 V
)
Blue (signal)
Black (common)
Power
Pack
Red
Red
Note: Maximum 3 occupant sensors.
Dual Circuit Switching of FDBs (<20 A/Zone): Single-Zone Example
Note: Power Packs can switch 20 A ballast current for
120/277 V versions.
Ground
Neutral
Hot
Dimmed
Green
Green
White
White
Black
Black
Fixture Ground
Lutron FDB or ECO
Dimming Ballast
Orange
Orange
Bank of Ballasts <20 A
Ground
Neutral
Hot
Dimmed
Fixture Ground
Green
White
Black
Black
Orange
Orange
Lutron FDB or ECO
Dimming Ballast
Bank of Ballasts <20 A
Black
Red
Red
Auxiliary
Power
Pack
Red (+20-24 V
)
Blue (signal)
Black
(common)
White
Power
Pack
Red
Red
Note: Maximum of three devices total
(occupant sensors and auxiliary power packs)
can be connected to a power pack.
8
Need additional assistance? Call the Lutron Technical Support Center 1-800-523-9466.
Please provide exact model number when calling.
Switching Dimmed Hot to FDB: Single-Zone Example,
Ground
Neutral
120/277 V
Main Feed
®
Green
White
Black
Orange
Wallstation
Fixture Ground
Lutron FDB or ECO
Dimming Ballast
Zone 1 Ballast
Black
White
Power
Pack
Red (+20-24 V
Blue (signal)
Red
Red
)
Black (common)
Note:
For -R model sensors
use gray wire instead
of blue as seen in
installation manual.
Fluorescent Control
Wallstation
Switched
Hot (Z1)
Dimmed
Hot (Z1)
Black
Yellow
Red
Green or
Bare
Ground
White
9
Need additional assistance? Call the Lutron Technical Support Center 1-800-523-9466.
Please provide exact model number when calling.
Switching Dimmed Hot to FDB: Dual-Zone Example
Ground
Neutral
120/277 V
Main Feed
Fixture Ground
Green
White
Black
Orange
Lutron FDB or ECO
Dimming Ballast
Zone 1 Ballast
Black
White
Power
Pack
Red
Red
Green
White
Black
Orange
Fixture Ground
Lutron FDB or ECO
Dimming Ballast
Zone 2 Ballast
Red (+20-24 V
)
Blue (signal)
Black (common)
Note:
For -R model
sensors use gray
wire instead of
blue as seen in
installation
manual.
Switched
Hot (Z1)
Fluorescent Control
Wallstation
Black
Dimmed
Hot (Z1)
Yellow
Red
Green or
Bare
Ground
White
Switched
Hot (Z2)
Fluorescent Control
Wallstation
Black
Dimmed
Hot (Z2)
Yellow
Red
Green or
Bare
Ground
White
10
Need additional assistance? Call the Lutron Technical Support Center 1-800-523-9466.
Please provide exact model number when calling.
EcosystemTM Ballast Interface: Single-Zone Example
Note: All occupant sensors
tied to ballasts will control a
single zone, not 4.
+20 V
+20 V
+20 V
Common
Common
Common
IR
Occ
Daylight
Red
Black
Blue
EcoSystem
Ballast A
Low Voltage Connections
+20 V
+20 V
+20 V
Common
Common
Common
IR
Occ
Daylight
EcoSystem
Ballast B
Single Occupant
Sensor Reference
Hot
Note:
For -R model
sensors use
gray wire
instead of
blue as seen
in installation
manual.
120/277/347 V
60 Hz
230 V
50/60 Hz
Neutral
Black
Red (+20-24 V
Blue (signal)
Black (common)
Note: Maximum 3 occupant sensors.
11
White
)
Power
Pack
Red
Red
Note: Cap off BLUE signal
and RED power wires to
power pack if switching is
not being used.
Need additional assistance? Call the Lutron Technical Support Center 1-800-523-9466.
Please provide exact model number when calling.
Wiring to a seeTouchTM allstation: Single-Zone Example
3 #18 AWG
(1.0 mm2)
3: Common
2: 24 V
1: Signal
C
B
A
Occupant Sensor
Note: All occupant sensors
tied to controller will work to
control 1 zone only,
not 4.
Note:
For -R model sensors use
gray wire instead of blue as
seen in installation manual.
Notes:
• A MAXIMUM of 1 occupant
sensor can be powered by the
seeTouch wallstation to ensure
proper operation.
• A MAXIMUM of 10 occupant
sensor signal lines are permitted to
be connected to one seeTouch
wallstation.
•Occupant sensors do NOT work
with standard seeTouch controls.
Hot
120/277/347 V
60 Hz
230 V
50/60 Hz
Neutral
Black
Red (+20-24 V
Blue (signal)
Black (common)
White
)
Power
Pack
Red
Red
Note: Cap off BLUE signal
wire. Cap off RED power
wires to power pack if
switching is not being used.
Note: Maximum 3 occupant sensors.
Wiring to a Contact Closure Input: LCP Controller Example
LCP Controller
Hot
CCI A
CCI B
120/277/347 V
60 Hz
230 V
50/60 Hz
Neutral
1 23 4
Black
PELV (Class #2: USA)
White
Power
Pack
Common
Signal
Red
Red
Common
Signal
Red (+20-24 V
Blue (signal)
Black (common)
Sensor A
12
)
Sensor B
Need additional assistance? Call the Lutron Technical Support Center 1-800-523-9466.
Please provide exact model number when calling.
Interfacing Wallbox Occupant Sensors with Wallbox Dimming Products:
Maestro® Wallstation Example
Black
Dimmed
Hot
Red
Hot
Wall
Sensor
Switched
Hot
120/277 V
Green
Neutral
Notes:
• LOS-SIR is a wallbox-mounted occupant sensor that is used to switch power to a load.
• Dimmer will retain previous settings when power is returned (based off assumed normal operation of a
Maestro wallstation control).
• This is a simple solution to this type of situation.
• Do NOT use LOS-SUS units to switch a dimming load.
• Unit must be wired on live side of dimmer.
Interfacing Low-Voltage Occupant Sensors with Wallbox Dimming Products
Hot
Black
White
Power
Pack
Red (+20-24 V
Blue (signal)
Black (common)
)
Red
120 V
230 V
Red
60 Hz
50 Hz
Dimmed
Hot
Neutral
Notes:
• The dimmed hot signal is switched in this circuit versus the hot signal in the previous drawing.
• This is a more complex method that allows for the use of versatile low-voltage occupant sensors in place of
a wallbox unit.
13
Need additional assistance? Call the Lutron Technical Support Center 1-800-523-9466.
Please provide exact model number when calling.
Title 24 Circuits: LOS-SIR-M Manual ON/Auto OFF
LOS-SIR-M
Red
Black
Hot
Wall
Sensor
Lutron
Lighting
Control
(If not
Title 24
Complaint)
Switched
Hot
120/277 V
Dimmed
Hot
Green
Neutral
Neutral
Title 24 Circuits: Sentry Switch Manual ON/Auto OFF
Hot
Black
White
Power
Pack
Red
Red
Lutron
Lighting
Control
(If not
Title 24
Complaint)
120/277/347 V
230 V
50 Hz
Sentry
Switch
Red (+20-24 V
Blue (signal)
Black (common)
)
Neutral
Neutral
Dimmed Hot
14
Need additional assistance? Call the Lutron Technical Support Center 1-800-523-9466.
Please provide exact model number when calling.
60 Hz
Chicago Code Violation Solution: No 277 V
Wallstation “ON” sensor powered;
automatic sense of
occupancy
Wallstation “OFF” sensor not powered;
lights off
Do NOT exceed 1 000 ft (305 m) of
low voltage cable with three
occupant sensors attached.
in the Wall
Note: Low voltage switched in the
wall because code does not allow
277 V
power in the wall; mainly
concerning ballast applications.
Low Voltage
(24 V )
277 V
feed
(in ceiling)
Wall Switch
(in wall)
Black
White
Red (+20-24 V
Blue (signal)
Black (common)
)
Power
Pack
Red
Red
To lighting load
Note: Maximum 3 occupant sensors.
15
Need additional assistance? Call the Lutron Technical Support Center 1-800-523-9466.
Please provide exact model number when calling.
Worldwide Technical and Sales Assistance
If you need assistance, call the toll-free
Lutron Technical Support Center.
Please provide exact model number when calling.
24 hours/day + 7 days/week
North and South America
U.S.A., Canada, Caribbean: 1.800.523.9466
Mexico: +1.888.235.2910
Central/South America: +1.610.282.6701
Lutron Electronics Co., Inc.
7200 Suter Road
Coopersburg, PA 18036-1299 U.S.A.
Phone: +(610) 282-3800
Fax:
-(610) 282-3090
Lutron, GRAFIK Eye, GRAFIK 6000, Maestro, microWATT,
Nova, and RadioRA are registered trademarks, and
EcoSystem, Digital microWATT, RadioTouch, seeTouch,
Softswitch and GRAFIK 5000/7000 are trademarks of Lutron
Electronics Co., Inc.
© 2007 Lutron Electronics, Co., Inc.
Europe
Technical support: +44.(0)20.7680.4481
Asia
Northern China: 10.800.712.1536
Southern China: 10.800.120.1536
Hong Kong: 800.901.849
Japan: +81.3.5575.8411
Singapore: 800.120.4491
Taiwan: 00.801.137.737
Thailand: 001.800.120.665853
Other countries: +65.6220.4666
Visit us on the web at www.lutron.com
16
Lutron Electronics Co., Inc.
7200 Suter Road
Coopersburg, PA 18036-1299 U.S.A.
Made and printed in U.S.A. 05/07 P/N 048-166 Rev. B
Need additional assistance? Call the Lutron Technical Support Center 1-800-523-9466.