Residual Current Devices Selection and Nuisance tripping Why’s and wherefore’s Gary Busbridge February 2014 The Residual Current Device ●The RCD is a device that disconnects a circuit whenever it detects that the electric current is not balanced between the energised conductor and the return neutral conductor. Schneider Electric - Division - Name – Date 2 Designed to Trip ●Should the primary means of protection, the insulation, fail, the RCD is designed to trip before… a set time and at a current so low as to prevent permanent injury or death from an electric shock. ●Tripping may be as low as half the related sensitivity but must trip at its rated sensitivity. Schneider Electric - Division - Name – Date 3 An RCD or a Safety Switch? ●Introduced into the market as an Earth Leakage Circuit Breaker. ●Heavily promoted to the installers and standards groups as a supplementary safety protection ●Entrepreneurial retailer in SA dubbed the unit as a Safety Switch so that he could penetrate the consumer market ●Standards and industry speak now refers to the units as RCD’s Schneider Electric - Division - Name – Date 4 “Normal” Residual Current ●A sustained residual current which is above the predetermined level. ●Using a real-life scenario, the leakage on a circuit made up of a fridge, freezer and electric kettle ●Each of these may have its own sustained residual current and when added together could be above the threshold of the RCD and.. as such will trip the breaker, ceasing the flow of that residual current. Schneider Electric - Division - Name – Date 5 The Residual Current Device A path to Earth thru tapware Human body becomes path to Earth Appliance becomes faulty RCD on socket or switchboard ●30mA and 300ms is the cutoff before heart fibrillation Schneider Electric - Division - Name – Date 6 The Residual Current Device A path to Earth thru tapware Human body becomes path to Earth Appliance becomes faulty RCD on socket or switchboard ●10mA and 40ms is the cutoff before muscular contraction Schneider Electric - Division - Name – Date 7 RCD’s & Protection ●The use of RCDs with a residual current not exceeding 30 mA, is recognized as providing additional protection. ●The use of RCDs is intended only to augment other measures of basic protection. Schneider Electric - Division - Name – Date 8 RCD’s & Protection ●RCDs do not provide protection against: Faults between live conductors Voltages imported into the installation earthing system through the supply neutral. ●The use of such devices is not recognized as a sole means of protection and does not obviate the need to apply the protective measures Schneider Electric - Division - Name – Date 9 Disturbances : nuisance tripping earth-leakage protection can operate incorrectly and cause: • Power outages, • production downtimes or data losses • Lighting outages • End-user dissatisfaction Schneider Electric - Division - Name – Date 10 “Abnormal” Residual Current ●Any residual current that flows after an initial surge or impulse and then automatically ceases is a non-sustained residual current. ●This is not associated with insulation breakdown and therefore not sustained, and… is largely due to lightning surges, reactive load switching and momentary flows to earth. Schneider Electric - Division - Name – Date 11 General principle of nuisance tripping ●Although not dangerous, a high frequency current is seen as a fault by the residual current circuitbreaker Schneider Electric - Division - Name – Date 12 Causes of the phenomenon ●It seems that electro-magnetic compatibility can be partly attributed to this recent phenomenon as.. manufacturers are including mains input filters in their electronic equipment and.. High frequency ballasts into fluorescent lighting. ●Manufacturers of these devices are capacitively coupling current to earth to reduce radio frequency signals emitted into the atmosphere. Schneider Electric - Division - Name – Date 13 Causes of the phenomenon ●The switch-on phase in appliances provide a brief period where the capacitors are passing more leakage to earth than usual or.. in the case of lighting using electronic starters, there is an ignition current of hundreds of amperes with a duration of a few milliseconds.. which result in large capacitive current flow to earth and a lot of harmonic noise for a similar period. Schneider Electric - Division - Name – Date 14 Causes of the phenomenon ●This current is not returning to earth through the RCD via the neutral but still causes the RCD to see a difference in the current out and current in. ●Often the difference exceeds the allowed threshold and hence it trips the breaker. Schneider Electric - Division - Name – Date 15 What does the Installer need to understand? ●The installer must understand the practical requirements of the circuits being installed and consider the effects of this residual current in relation to circuit protection. Schneider Electric - Division - Name – Date 16 The phenomenon and the effect on computers ●Any computer, whether new or old, may have a residual current of between 1 and 2mA. ●It would seem that the number of computers that may be connected to an RCD may be between 7 and 10. ●Public Schools Departments in Australia have limited the number of computers on one RCD to seven. Schneider Electric - Division - Name – Date 17 Microcomputers, servers, data centers ●Each PC amplifies the sensitivity of the RCD; the more PCs there are, the greater the risk of tripping during high-frequency interference 1.5 mA 30 mA 13 mA Schneider Electric - Division - Name – Date 18 The phenomenon and effect on lighting ●Between 0.3mA and 1mA can be expected on any electronic ballast for fluorescent lighting ●It would seem that the maximum number of fluorescent lamps with ballasts protected by one RCD should be limited to 15 and 20. ●Consideration should be given to battens with more than one fluorescent lamp fitted, as each tube carries its own ballast. Schneider Electric - Division - Name – Date 19 Very low voltage fluorescent lighting ●When banks of lighting units are turned off, the high-frequency oscillations will be seen as a fault 200 pF/m 100 kHz - 10 MHz Transformer Lighting unit 1 nF Schneider Electric - Division - Name – Date 20 Fluorescent lighting with electronic ballast ●Upwards of 20 lighting units, there is a risk of tripping due to the stray capacitances 10 -100 kHz Schneider Electric - Division - Name – Date 21 The Phenomenon and effect on other devices ●Similar principles should apply to other devices but the non-sustained residual current may vary.. and will need to be checked before determining the maximum number of devices to be protected by any one RCD. ●Be aware that even though the residual current on any device may not be sufficient to trip the RCD it may have an overall effect on the background leakage. Schneider Electric - Division - Name – Date 22 EarthEarth-leakage protection downstream a UPS ●Slow and damped oscillations may cause nuisance tripping N U n 100 V U n -100 V Schneider Electric - Division - Name – Date 23 Activating a capacitor bank ●Activating the capacitor bank causes an overvoltage with high-frequency oscillations, which can cause nuisance tripping I∆ I ∆ Schneider Electric - Division - Name – Date U U U 1000 V 24 Variable speed drives with frequency converters ●Square voltage modulated between 2 and 15 kHz according to the frequency of the motor: This presents no danger, but the personnel protection devices may trip 2-20 kHz EMC M Schneider Electric - Division - Name – Date 25 Lightning ●The lightning pulses flow to ground, and the RCD will trip 10 kA 50 µs Schneider Electric - Division - Name – Date 26 Quantified Effect 1mA 2mA 0.5mA 1mA 0.5mA 0.75mA 0.5mA 1mA 0.5mA 1.5mA Around 1mA Schneider Electric - Division - Name – Date 27 What does the Installer need to do? ●Be aware of the type of load being put on the circuit. ●Divide the circuits to prevent a surplus of load on any one circuit. ●Limit the number of ballasts in the lighting circuit. ●Use a selective type RCD (Class A Type Si) on those circuits that may be affected. (These types of RCD’s are specifically designed to be less sensitive to the effect of high frequency disturbances whilst at the same time ensuring personal safety.) Schneider Electric - Division - Name – Date 28 Si type RCDs 1 - Current transformer (toroid) 2 Signal processing devices 3 Electromech. actuator SN SI Transient filter - waveform types : 8/20 µs - 0,5µs 100 kHz Schneider Electric - Division - Name – Date Pulsed current detector HF filter Energy accumulator Trip signal check 29 Common Myths ●Testing instruments are required to check the activation of an RCD. WRONG! Field testing has verified that the Test button operation is sufficient ●RCD’s cannot be used to protect Cookers because of nuisance tripping WRONG! There is now sufficient evidence from Cooker manufacturers that this is not a problem ●RCD’s protect against active to neutral faults WRONG! Common misconception amongst home-owners Schneider Electric - Division - Name – Date 30 Common Myths ●The new rules for 3 circuits per RCD are sufficient RIGHT & WRONG! It’s safe enough to install in this manner but how do you fault find without having 1 circuit per RCD ●RCD’s have been added to lighting circuits and if more than one then shared across RCD’s for extra safety RIGHT & WRONG! It’s helps keep the ceiling cavity safe but it also ensures that if one RCD trips then there is still a chance that the light circuit on the other is still working. Elderly concern! Schneider Electric - Division - Name – Date 31 In Summary ●Being more aware of the practical requirements of the circuit being designed and installed.. ●May well be the nuisance value in the future.. and perhaps go a long way in negating the nuisance trip problems that installers and designers face today. Schneider Electric - Division - Name – Date 32