Most Widely Accepted and Trusted 0 ICC-ES Report ICC-ES | (800) 423-6587 | (562) 699-0543 | www.icc-es.org 000 ESR-1464 Issued/Reissued 01/2016 This report is subject to renewal 01/2017. DIVISION: 05 00 00—METALS SECTION: 05 40 00—COLD-FORMED METAL FRAMING DIVISION: 09 00 00—FINISHES SECTION: 09 22 16.13—NON-STRUCTURAL METAL STUD FRAMING REPORT HOLDER: CLARKDIETRICH BUILDING SYSTEMS 9100 CENTRE POINTE DRIVE, SUITE 210 WEST CHESTER, OHIO 45069 EVALUATION SUBJECT: TRAKLOC NONLOAD-BEARING WALL STEEL FRAMING SYSTEM Look for the trusted marks of Conformity! “2014 Recipient of Prestigious Western States Seismic Policy Council (WSSPC) Award in Excellence” ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed as an endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as to any finding or other matter in this report, or as to any product covered by the report. Copyright © 2016 ICC Evaluation Service, LLC. All rights reserved. A Subsidiary of ICC-ES Evaluation Report ESR-1464 Reissued January 2016 This report is subject to renewal January 2017 www.icc-es.org | (800) 423-6587 | (562) 699-0543 DIVISION: 05 00 00—METALS Section: 05 40 00—Cold-Formed Metal Framing DIVISION: 09 00 00—FINISHES Section: 09 22 16.13—Non-Structural Metal Stud Framing REPORT HOLDER: CLARKDIETRICH™ BUILDING SYSTEMS 9100 CENTRE POINTE DRIVE, SUITE 210 WEST CHESTER, OHIO 45069 (513) 870-1100 www.clarkdietrich.com EVALUATION SUBJECT: TRAKLOC NONLOAD-BEARING WALL STEEL FRAMING SYSTEM 1.0 EVALUATION SCOPE Compliance with the following codes: ® 2012 and 2009 International Building Code (IBC) 2013 Abu Dhabi International Building Code (ADIBC)† † The ADIBC is based on the 2009 IBC. 2009 IBC code sections referenced in this report are the same sections in the ADIBC. Property evaluated: Structural 2.0 USES The Trakloc nonload-bearing wall steel framing system is used for framing of interior nonload-bearing walls. 3.0 DESCRIPTION 3.1 General: The Trakloc nonload-bearing wall steel framing system is constructed from the Trakloc studs and tracks which are available in five depths and three material thicknesses as noted in Table 1. The studs and tracks have a snap-lock system that permits stud installation to the top and bottom tracks without the use of fasteners. The Trakloc studs are available as single-unit fixed-length studs and as two-part adjustable-length studs. The single-unit fixed-length studs have the designation xxxTLFxxx-xx. The adjustable-length stud is made up of two parts, the stud base (TSO) and the stud extension (TSE). The TSE is fitted into the TSO, allowing the length of the Trakloc stud to be adjusted in the field. When the two pieces are fitted together, the A Subsidiary of the International Code Council ® designation is xxxTLAxxx-xx as shown in Table 1. The extension length of the TSE must be limited to a maximum of 1/8 of the total wall span. The minimum overlap length is as noted in Table 1. Marks are placed on the TSO indicating the minimum lap (splice) length. The TSO is manufactured with and without punch-outs. The punchouts are 0.75 inch by 4.0 inches (19 mm by 102 mm) for TSOs with web depth of less than 3 inches (76 mm). For all other TSOs, the punch-outs are 1.5 inches by |4.0 inches (38 mm by 102 mm). Punch-outs are spaced 24 inches (610 mm) on center along the centerline of the TSO, with a minimum distance of 10 inches (254 mm) from the end of the member to the near edge of the punch-out, when provided. The fixed-length studs are fabricated from the TSO only. The tracks are channel-shaped with an inward ridge to snap-lock the studs to the track. See Figure 1 for stud and track configurations. See Figure 2 for punch-out configurations. 3.2 Material: The studs and tracks are formed from coils of galvanized steel complying with ASTM A653 SS, Grade 33. The uncoated minimum base-metal thickness is specified in Table 1. The galvanized coating is minimum G40 in accordance with ASTM A653. 4.0 DESIGN AND INSTALLATION Installation of the Trakloc nonload-bearing wall steel framing system must be in accordance with the applicable code, the approved construction documents and this report. If there is a conflict between this report and the documents submitted for approval, this report governs. The approved plans must be available on the jobsite at all times during installation. Load-span combinations must be limited to those shown in Table 2. 5.0 CONDITIONS OF USE The Trakloc described in alternative to Section 1.0 conditions: nonload-bearing wall steel framing system this report complies with, or is a suitable what is specified in, those codes indicated in of this report, subject to the following 5.1 The Trakloc nonload-bearing wall steel framing system is manufactured, identified and installed in accordance with this report, the approved plans, and the manufacturer’s published installation instructions. 5.2 The wall assemblies are limited to interior nonloadbearing installations where the superimposed axial load is zero pounds (zero Newtons). ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed as an endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as to any finding or other matter in this report, or as to any product covered by the report. 1000 Copyright © 2016 ICC Evaluation Service, LLC. All rights reserved. Page 1 of 4 ESR-1464 | Most Widely Accepted and Trusted Page 2 of 4 5.3 Design of the attachment of the wall to the surrounding structure is outside the scope of this report. 5.4 Calculations and drawings demonstrating compliance with this report must be submitted to the code official for each project. The calculations and construction documents must be prepared and sealed by a registered design professional where required by the statutes of the jurisdiction in which the project is to be constructed. 6.0 EVIDENCE SUBMITTED Data in accordance with the ICC-ES Acceptance Criteria for Cold-formed Steel Framing Members (AC46), dated June 2012. 7.0 IDENTIFICATION Each Trakloc stud and track must have a legible label or stamp, at a maximum spacing of 96 inches (2413 mm) on center, indicating the member designation; manufacturer’s name or initials (CD); and the evaluation report number (ESR-1464). 5.5 Trakloc studs and tracks are manufactured at the ClarkDietrich facility in Woodland, California and Bristol, Connecticut. TABLE 1—TRAKLOC STUDS AND TRACKS STUDS MEMBER DESIGNATION 250TLA125-18 5 (250TLF125-18) 250TLA125-24 5 (250TLF125-24) 250TLA125-30 5 (250TLF125-30) 350TLA125-18 5 (350TLF125-18) 350TLA125-24 5 (350TLF125-24) 350TLA125-30 5 (350TLF125-30) 362TLA125-18 5 (362TLF125-18) 362TLA125-24 5 (362TLF125-24) 362TLA125-30 5 (362TLF125-30) 550TLA125-30 5 (550TLF125-30) 600TLA125-30 5 (600TLF125-30) 1,2 WEIGHT (lb./ft.) DEPTH (in.) FLANGE (in.) LIP (in.) THICKNESS (mils) MINIMUM BASE-METAL 3 THICKNESS (in.) DESIGN THICKNESS (in.) MINIMUM OVERLAP 4 LENGTH (in.) 0.3476 2.500 1.250 0.288 18 0.0179 0.0188 8 0.4579 2.500 1.250 0.288 24 0.0237 0.0249 10 0.5704 2.500 1.250 0.288 30 0.0296 0.0312 8 0.4116 3.500 1.250 0.288 18 0.0179 0.0188 8 0.5426 3.500 1.250 0.288 24 0.0237 0.0249 10 0.6766 3.500 1.250 0.288 30 0.0296 0.0312 8 0.4196 3.625 1.250 0.288 18 0.0179 0.0188 8 0.5532 3.625 1.250 0.288 24 0.0237 0.0249 10 0.6899 3.625 1.250 0.288 30 0.0296 0.0312 8 0.8889 5.500 1.250 0.288 30 0.0296 0.0312 12 0.9420 6.000 1.250 0.288 30 0.0296 0.0312 12 18 24 30 18 24 30 18 24 30 30 30 0.0179 0.0237 0.0296 0.0179 0.0237 0.0296 0.0179 0.0237 0.0296 0.0296 0.0296 0.0188 0.0249 0.0312 0.0188 0.0249 0.0312 0.0188 0.0249 0.0312 0.0312 0.0312 ----------------------- TRACKS 250TTS137-18 0.3627 2.500 250TTS137-24 0.4571 2.500 250TTS137-30 0.5700 2.500 350TTS137-18 0.4273 3.500 350TTS137-24 0.5387 3.500 350TTS137-30 0.6720 3.500 362TTS137-18 0.4354 3.625 362TTS137-24 0.5489 3.625 362TTS137-30 0.6847 3.625 550TTS137-30 0.8756 5.500 600TTS137-30 0.9270 6.000 For SI: 1 inch = 25.4 mm, 1 lb/ft = 1.488 kg/m. 1 1.375 1.375 1.375 1.375 1.375 1.375 1.375 1.375 1.375 1.375 1.375 ----------------------- 2 Values based on stud base (TSO). Depth of studs measured from outside face to outside face of flanges of TSO. Depth of track measured from inside face to inside face of flanges. 3 Minimum thickness permitted for framing members delivered to the project site. 4 Not applicable to the single-unit fixed-length Trakloc stud. 5 The designation in parentheses is the nomenclature for the single-unit fixed-length Trakloc stud. 2 ESR-1464 | Most Widely Accepted and Trusted Page 3 of 4 1 TABLE 2—ALLOWABLE WALL HEIGHTS STUD SPACING L (in) /120 12 13'- 0" 250TLA125-18 16 11'- 3" 2 (250TLF125-18) 24 8'- 10" 12 15'- 3" 250TLA125-24 16 13'- 3" 2 (250TLF125-24) 24 10'- 10" 12 16'- 5" 250TLA125-30 16 14'- 11" 2 (250TLF125-30) 24 12'- 7" 12 15'- 7" 350TLA125-18 16 13'- 6" 2 (350TLF125-18) 24 9'- 0" 12 18'- 5" 350TLA125-24 16 16'- 0" 2 (350TLF125-24) 24 13'- 0" 12 21'- 4" 350TLA125-30 16 18'- 8" 2 (350TLF125-30) 24 15'- 3" 12 15'- 10" 362TLA125-18 16 13'- 6" 2 (362TLF125-18) 24 9'- 0" 12 18'- 10" 362TLA125-24 16 16'- 3" 2 (362TLF125-24) 24 13'-3" 12 21'- 11" 362TLA125-30 16 19'- 1" 2 (362TLF125-30) 24 15'- 7" 12 29'- 5" 550TLA125-30 16 25'- 6" 2 (550TLF125-30) 24 20'- 9" 12 30'- 11" 600TLA125-30 16 26'- 9" 2 (600TLF125-30) 24 21'- 10" For SI: 1 inch = 25.4 mm, 1 psf = 47.88 Pa. MEMBER DESIGNATION 1 5 psf L /240 11'- 1" 10'- 1" 8'- 10" 12'- 2" 11'- 0" 9'- 8" 13'- 0" 11'- 10" 10'- 4" 14'- 4" 13'- 1" 9'- 0" 15'- 9" 14'- 4" 12'- 6" 16'- 11" 15'- 4" 13'- 5" 14'- 9" 13'- 5" 9'- 0" 16'- 2" 14'- 8" 12'- 10" 17'- 5" 15'- 10" 13'- 9" 24'- 0" 21'- 10" 19'- 1" 25'- 8" 23'- 4" 20'- 5" L /360 9'- 8" 8'- 9" 7'- 8" 10'- 7" 9'- 8" 8'- 5" 11'- 5" 10'- 4" 9'- 0" 12'- 7" 11'- 5" 9'- 0" 13'- 9" 12'- 6" 10'- 11" 14'- 9" 13'- 5" 11'- 9" 12'- 11" 11'- 9" 9'- 0" 14'- 2" 12'- 10" 11'- 2" 15'- 2" 13'- 9" 12'- 1" 21'- 0" 19'- 1" 16'- 8" 22'- 5" 20'- 5" 17'- 10" TRANSVERSE LOAD 7.5 psf L L L /120 /240 /360 10'- 7" 9'- 8" 8'- 5" 8'- 10" 8'- 9" 7'- 8" 5'- 10" 5'- 10" 5'- 10" 12'- 6" 10'- 7" 9'- 3" 10'- 10" 9'- 8" 8'- 5" 8'- 10" 8'- 5" 7'- 4" 14'- 4" 11'- 5" 9'- 11" 12'- 7" 10'- 4" 9'- 0" 10'- 3" 9'- 0" 7'- 11" 12'- 0" 12'- 0" 10'- 11" 9'- 0" 9'- 0" 9'- 0" 6'- 0" 6'- 0" 6'- 0" 15'- 1" 13'- 9" 12'- 0" 13'- 0" 12'- 6" 10'- 11" 10'- 5" 10'- 5" 9'- 6" 17'- 7" 14'- 9" 12"- 11" 15'- 3" 13'- 5" 11'- 9" 12'- 5" 11'- 9" 10'- 3" 12'- 0" 12'- 0" 11'- 3" 9'- 0" 9'- 0" 9'- 0" 6'- 0" 6'- 0" 6'- 0" 15'- 4" 14'- 2" 12'- 4" 13'- 3" 12'- 10" 11'- 2" 10'- 5" 10'- 5" 9'- 9" 18'- 0" 15'- 2" 13'- 3" 15'- 7" 13'- 9" 12'- 1" 12'- 9" 12'- 1" 10'- 6" 24'- 0" 21'- 0" 18'- 4" 20'- 9" 19'- 1" 16'- 8" 15'- 11" 15'- 11" 14'- 6" 25'- 2" 22'- 5" 19'- 7" 21'- 10" 20'- 5" 17'- 10" 15'- 10" 15'- 10" 15'- 6" Spans are based on weak axis and maximum torsional bracing of 48 inches, and both flanges fully braced. The member in parentheses is the single-unit fixed-length Trakloc stud. 2 L /120 8'- 10" 6'- 7" 4'- 5" 10'- 10" 9'- 4" 7'- 7" 12'- 7" 10'- 10" 8'- 10" 9'- 0' 6'- 9" 4'- 6" 13'- 0" 11'- 3" 7'- 10" 15'- 3" 13'- 2" 10'- 9" 9'- 0" 6'- 9" 4'- 6" 13'- 3" 11'- 6" 7'- 10" 15'- 7" 13'- 6" 11'- 0" 20'- 9" 17'- 11" 11'- 11" 21'- 10" 17'- 10" 11'- 10" 10 psf L /240 8'- 9" 6'- 7" 4'- 5" 9'- 8" 8'- 9" 7'- 7" 10'- 4" 9'- 5" 8'- 2" 9'- 0" 6'- 9" 4'- 6" 12'- 6" 11'- 3" 7'- 10" 13'- 5" 12'- 2" 10'- 8" 9'- 0" 6'- 9" 4'- 6" 12'- 10" 11'- 6" 7'- 10" 13'- 9" 12'- 6" 10'- 11" 19'- 1" 17'- 4" 11'- 11" 20'- 5" 17'- 10" 11'- 10" L /360 7'- 8" 6'- 7" 4'- 5" 8'- 5" 7'- 8" 6'- 8" 9'- 0" 8'- 2" 7'- 2" 9'- 0" 6'- 9" 4'- 6" 10'- 11" 9'- 11" 7'- 10" 11'- 9" 10'- 8" 9'- 3" 9'- 0" 6'- 9" 4'- 6" 11'- 2" 10'- 2" 7'- 10" 12'- 1" 10'- 11" 9'- 7" 16'- 8" 15'- 1" 11'- 11" 17'-10" 16'- 2" 11'- 10" ESR-1464 | Most Widely Accepted and Trusted FIGURE 1—TRACKLOC MEMBERS FIGURE 2—HOLE CONFIGURATION Page 4 of 4 ICC-ES Evaluation Report ESR-1464 CBC Supplement Reissued January 2016 This report is subject to renewal January 2017. www.icc-es.org | (800) 423-6587 | (562) 699-0543 A Subsidiary of the International Code Council ® DIVISION: 05 00 00—METALS Section: 05 40 00—Cold-Formed Metal Framing DIVISION: 09 00 00—FINISHES Section: 09 22 16.13—Non-Structural Metal Stud Framing REPORT HOLDER: CLARKDIETRICH™ BUILDING SYSTEMS 9100 CENTRE POINTE DRIVE, SUITE 210 WEST CHESTER, OHIO 45069 (513) 870-1100 www.clarkdietrich.com EVALUATION SUBJECT: TRAKLOC NONLOAD-BEARING WALL STEEL FRAMING SYSTEM 1.0 REPORT PURPOSE AND SCOPE Purpose: The purpose of this evaluation report supplement is to indicate that the Trakloc Nonload Bearing Wall Steel Framing System, recognized in ICC-ES master report ESR-1464, has also been evaluated for compliance with Chapters 16, 16A, 17, 17A, 22, and 22A of the code noted below. Applicable code edition: 2010 California Building Code (CBC) 2.0 CONCLUSIONS The Trakloc nonload-bearing wall steel framing system, described in Sections 2.0 through 7.0 of the master evaluation report ESR-1464, complies with CBC Chapters 16, 16A, 17, 17A, 22, and 22A, provided the design and installation are in accordance with the International Building Code® provisions noted in the master report and the additional requirements of CBC Chapters 16, 16A, 17, 17A, 22, and 22A, as applicable. This supplement expires concurrently with the master report reissued January 2016. ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed as an endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as to any finding or other matter in this report, or as to any product covered by the report. 1000 Copyright © 2016 ICC Evaluation Service, LLC. All rights reserved. Page 1 of 1