Installation and Operation Instructions PS-50xx-NQ-xx-AB Series Please Read Instruction Carefully Before Installation! Product Specifications Supply Voltage Output Signal Accuracy (Non-linearity, Hysteresis, Repeatability) Stability Thermal Error -40 to 221°°F (-40 to 105°°C) Response Time Burst Pressure 8 - 30 VDC Proof Pressure 2-Wire, 4 – 20 mA (PS-50xx-NQ-MA-AB) Operating Temp. Range 2-Wire, 1 – 5 VDC (PS-50xx-NQ-D5-AB) 1 2-Wire, 2 – 10 VDC (PS-50xx-NQ-D1-AB) 2 Process Fitting 75 to 1000 psi: ± 0.5% of FS 15 to 60 psi: ± 1.00% of FS Case & Fitting ± 1% Full Scale < 0.50 % Full Scale EMC Compliance < 1ms Weight 3X Full Scale 1 Shipped with 249 Ohm, 1%, ¼ Watt Resistor 2 Shipped with 499 Ohm, 1%, ¼ Watt Resistor Part Number PS-5030-NQ-MA-AB PS-5030-NQ-D5-AB PS-5030-NQ-D1-AB PS-5040-NQ-MA-AB PS-5040-NQ-D5-AB PS-5040-NQ-D1-AB PS-5050-NQ-MA-AB PS-5050-NQ-D5-AB PS-5050-NQ-D1-AB PS-5060-NQ-MA-AB PS-5060-NQ-D5-AB PS-5060-NQ-D1-AB PS-5070-NQ-MA-AB PS-5070-NQ-D5-AB PS-5070-NQ-D1-AB PS-5080-NQ-MA-AB PS-5080-NQ-D5-AB PS-5080-NQ-D1-AB Pressure Ranges 0 to 15 PSI 0 to 15 PSI 0 to 15 PSI 0 to 50 PSI 0 to 50 PSI 0 to 50 PSI 0 to 100 PSI 0 to 100 PSI 0 to 100 PSI 0 to 200 PSI 0 to 200 PSI 0 to 200 PSI 0 to 500 PSI 0 to 500 PSI 0 to 500 PSI 0 to 1000 PSI 0 to 1000 PSI 0 to 1000 PSI Sensing Type Vented Gage Vented Gage Vented Gage Vented Gage Vented Gage Vented Gage Vented Gage Vented Gage Vented Gage Vented Gage Vented Gage Vented Gage Sealed Gage Sealed Gage Sealed Gage Sealed Gage Sealed Gage Sealed Gage 3X Full Scale -40 to 221°F (-40 to 105°C) ¼” – 18 NPT Male Thread 304L Stainless Steel 10 Volts / Meter < 0.206 lbs. (93 grams) Output 4 – 20 mA 1 – 5 VDC 2 – 10 VDC 4 – 20 mA 1 – 5 VDC 2 – 10 VDC 4 – 20 mA 1 – 5 VDC 2 – 10 VDC 4 – 20 mA 1 – 5 VDC 2 – 10 VDC 4 – 20 mA 1 – 5 VDC 2 – 10 VDC 4 – 20 mA 1 – 5 VDC 2 – 10 VDC General Information The PS-50xx-NQ-xx-AB Series units are a 2-wire, 4-20 mA gage pressure transmitter. The 4-20 mA current output will be proportional to the pressure applied and can be operated over the temperature range of –40 to 122°F (-40 to 105°C). The PS-50xx-NQ-D5-AB Series units are shipped from the factory with a 249 Ohm, 1%, ¼ watt resistor to convert the 4-20 mA output to a 1 to 5 VDC voltage output. The PS-50xx-NQ-D1-AB Series units are shipped from the factory with a 499 Ohm, 1%, ¼ watt resistor to convert the 4-20 mA output to a 2 to 10 VDC voltage output. Mounting Instructions The PS-50xx-NQ-xx-AB Series units are a compact, robust package made from a laser-welded stainless steel design that can be used in harsh and benign environments. The PS-50xx-NQ-xx-AB Series gage pressure transmitters are compatible with a wide range of gases and liquids such as air, water, wastewater, Hydrogen, Nitrogen, hydraulic fluid, steam, and many others. The PS-50xx-NQ-xx-AB Series gage pressure transmitters have a pressure port that is a ¼”-18 NPT male fitting made of 304L stainless steel. Each unit is approximately 2.60” long and weighs approximately 0.206 lbs (93 grams). The PS-50xx-NQ-xx-AB Series units come with a 2 conductor 18 AWG shielded cable 2’ in length for making all of the proper I0000496 Rev 2.Doc 2305 Pleasant View Rd. Middleton Industrial Park Middleton, WI 53562 PH: (608) 831-2585 FAX (608) 831-7407 www.workaci.com connections. Typically, standard pipe fittings and procedures should be used during installation. The torque speciation for mounting the gage pressure port is 2 T.F.F.T. (Turns From Finger Tight). However, for pressure ranges in excess of 500 psi, we recommend the use of a sealant such as Loctite Hydraulic SealantTM. ! Caution: - Wiring must comply with all applicable local and national electrical codes. - Do not run the gage pressure transmitter wiring in any conduit with mains power system wiring. Warning: - Remove power before wiring! Never connect or disconnect wiring with power applied. Wiring Instructions The PS-50xx-NQ-xx-AB Series gage pressure transmitter is a true 2-wire, 4 – 20 mA current output device. There are 3-wires that need to be connected from the pressure transmitter to the controller. The RED wire is the positive voltage, the WHITE wire is the 4 – 20 mA current loop output to the controller. The SHIELD wire should be connected to the system common or earth ground. These units are reverse polarity protected. ACI recommends the use of 18-22 AWG shielded cable for all installations. When using a shielded cable, be sure to connect the cable shield to the ground at the controller ONLY. Verify all wire connections are properly configured as per Figures #1 and #2 before initially powering the unit. Now verify that you are getting a pressure reading on your Building Automation System. PS-50xx-NQ-MA-AB Series DC Power Supply Automation Panel 24 VDC + 4 - 20 mA Input - Shield Red Wire (8 to 30 VDC) White Wire (4-20mA) Figure # 1 I0000496 Rev 2.Doc 2305 Pleasant View Rd. Middleton Industrial Park Middleton, WI 53562 PH: (608) 831-2585 FAX (608) 831-7407 www.workaci.com Common PS-50xx-NQ-D5-AB Series PS-50xx-NQ-D1-AB Series DC Power Supply Automation Panel 24 VDC + Analog Input - Signal Common 249 Ohm, 1%, 1/4 Watt Resistor (1 - 5 VDC) 499 Ohm, 1%, 1/4 Watt Resistor (2 - 10 VDC) Shield Red Wire (8 to 30 VDC) White Wire (4-20mA) Figure # 2 Troubleshooting No reading - Check that you have the correct power supply voltage at the unit. - Verify all wire connections are connected and that all of the wires are firmly in place. Erratic readings - Verify that all of the wires are terminated properly (No loose connections). - Check that the input power is clean. In areas of high RF interference or noise, shielded cable may be necessary to stabilize signal. Inaccurate readings - If you suspect that the transmitter is not reading within the specified tolerance please contact ACI for assistance. Gage Pressure Conversion Formulas To convert transmitter output signal to gage pressure. 4-20 mA to Pressure (4 mA = 0 psi and 20 mA = 500 psi) Example: 12mA transmitter signal output Multiplier = 16 mA (transmitter span) / 500 psi (pressure span) = 0.032 (12mA-4mA)/ 0.032 = 250 psi 1-5 VDC to Pressure (1 VDC = 0 psi and 5 VDC = 500 psi) Example: 3.0 VDC transmitter signal output Multiplier = 4 VDC (transmitter span) / 500 psi (pressure span) = 0.008 (3.0 VDC-1.0 VDC) / 0.008 = 250 psi 2-10 VDC to Pressure (2 VDC = 0 psi and 10 VDC = 500 psi) Example: 8 VDC transmitter signal output Multiplier = 8 VDC (transmitter span) / 500 psi (pressure span) = 0.016 (8 VDC – 2 VDC) / 0.016 = 375 psi WEEE Directive At the end of their useful life the packaging and product should be disposed of via a suitable recycle centre. Do not dispose of with household waste. Do not burn. I0000496 Rev 2.Doc 2305 Pleasant View Rd. Middleton Industrial Park Middleton, WI 53562 PH: (608) 831-2585 FAX (608) 831-7407 www.workaci.com