ACRI 210-240: Unitary Air-Conditioning and Air

advertisement
By Authority Of
THE UNITED STATES OF AMERICA
Legally Binding Document
By the Authority Vested By Part 5 of the United States Code § 552(a) and
Part 1 of the Code of Regulations § 51 the attached document has been duly
INCORPORATED BY REFERENCE and shall be considered legally
binding upon all citizens and residents of the United States of America.
HEED THIS NOTICE: Criminal penalties may apply for noncompliance.
e
Document Name: ACRI 210-240: Unitary Air-Conditioning and Air-Source
Heat Pump Equipment
CFR Section(s):
Standards Body:
10 CFR 431.96
Air Conditioning and Refrigeration Institute
Official Incorporator:
THE EXECUTIVE DIRECTOR
OFFICE OF THE FEDERAL REGISTER
WASHINGTON, D.C.
2003
STANDARD for
UNITARY AIR ..
CONDITIONING
AND AIR ..
SOURCE HEAT
PUMP
EQUIPMENT
AIR-CONDITIONING &
REFRIGERATION
INSTITUTE
Standard 210/240
4100 N. FAIRFAX DR.,STE. 200 • ARLINGTON, VIRGINIA 22203
I
IMPORTANT
SAFETY DISCLAIMER
(
ARl does not set safety standards and does not certify or guarantee the safety of any products, components or systems
designed, tested, rated, installed or operated in accordance with this standard/guideline. It is strongly recommended
that products be designed, constructed, assembled, installed and operated in accordance with nationally recognized
safety standards and code requirements appropriate for products covered by this standard/guideline.
ARl uses its best efforts to develop standards/guidelines employing state-of-the-art and accepted industry practices.
ARl does not certify or guarantee. that any tests conducted under its standards/guidelines will be non-hazardous or
free from risk.
ARI CERTIFICATION PROGRAM PROVISIONS
Scope of the Certification Program
The Certification Program includes all Unitary Air-Conditioning and Air-Source Unitary Heat Pump equipment rated
below 65,000 Btu/h [19,000 W] at ARl Standard Rating Conditions (Cooling).
Certified Ratings
The following Certification Program ratings are verified by test:
Unitary Air-Conditioners
A.
Air-cooled under 65,000 Btu/h [19,000 W]
1. ARl Standard Rating Cooling Capacity, Btu/h [W]
2.
Seasonal Energy Efficiency Ratio, SEER, Btu/(W·h)
B.
Water-cooled and evaporative-cooled under 65,000 Btu/h [19,000 W]
J.
ARl Standard Rating Cooling Capacity, Btu/h [W]
2. Energx Efficiency Ratio, EER, Btu/(W·h)
(
Air-Source Unitary Heat Pumps
Air-cooled under 65,000 Btu/h [19,000 W]
1.
ARI Standard Rating Cooling Capacity, Btu/h [W]
2.
Seasonal Energy Efficiency Ratio, SEER, Btu/(W·h)
3.
High Temperature Heating Standard Rating Capacity, Btu/h [W]
4.
Region IV Heating Seasonal Perfomlance Factor, HSPF, Minimum Design Heating Requirement,
Btu/(W·h)
Confolmance to the requirements of the Maximum Operating Conditions Test, Voltage Tolerance Test, LowTemperature Operation Test (Cooling), Insulation Effectiveness Test (Cooling), and Condensate Disposal Test
(Cooling), as outlined in Section 8, are also verified by test.
(
Note:
This standard supersedes ARl Standard 210/240-94.
P,;ce $20.00 (M) $40.00 (NM)
Plinted in U.S.A
~Pi;
• • • ".
©Copyright 2003, by Air~Conditioning and Reti"igeration Institute
Registered United States P<ltent and Trademark Office
TABLE OF CONTENTS
SECTION
PAGE
Section 1.
Purpose ..................................................................................................................... 1
Section 2.
Scope ........................................................................................................................ 1
Section 3.
Definitions ................................................................................................................ 1
Section 4.
Classifications .......................................................................................................... 2
Section 5.
Test Requirements ................................................................................................... 2
Section 6.
Rating Requirements ................................................................................................ 2
Section 7.
Minimum Data Requirements for Published Ratings ..................... ,...................... 10
Section 8.
Operating Requirements ........................................................................................ 10
Section 9.
Marking and Nameplate Data ................................................................................ 13
Section 10. Conformance Conditions ....................................................................................... 13
TABLES
Table 1.
Classification of Unitary Air-Conditioners .............................................................. 4
Table 2.
Classification of Air-Source Unitary Heat Pumps .................................................. 5
Table 3.
Conditions for Standard Rating Tests and Operating Requirement Tests for
Air-cooled Equipment Using Appendix C ............................................................... 6
Table 4.
Conditions for Standard Rating Tests for Air-cooled Variable Speed Equipment
Meeting the Requirements of Appendix C .............................................................. 7
Table 5.
Conditions for Standard Rating Tests and Operating Requirement Tests for
Water-cooled and Evaporative-cooled Equipment Using ASHRAE Standard 37 ... 8
Table 6.
Minimum External Pressure .................................................................................... 9
FIGURE
Figure 1.
Part-Load Factor Curve .......................................................................................... 11
APPENDICES
Appendix A.
References - Normative ............................................................. :..................... 14
Appendix B.
References - Informative ................................................................................. 14
Appendix C.
Unifonn Test Method for Measuring the Energy Consumption of Central
Air Conditioners - Normative .......................................................................... 15
Appendix D.
Prescriptive Methodology for the Cyclic Testing ofDucted Systems
Required by C4.1 and C4.2 - Normative ......................................................... 34
Appendix E.
Example of Calculating Integrated Part-Load Values(IPLV) - Normative .... 39
(
TABLE FOR APPENDICES
Table El.
Example IPLV Calculation ............................................................................. .41
FIGURES FOR APPENDICES
Figure Dl.
Tunnel Air Enthalpy Test Method Arrangement ............................................. 35
Figure D2.
Loop Air Enthalpy Test Method Arrangement ................................................ 36
Figure D3.
Calorimeter Air Enthalpy Test Method Arrangement ..................................... 37
Figure D4.
Room Air Enthalpy Test Method Arrangement ............................................... 38
Figure El.
Part-Load Factor Example ........................................................... :................... 40
(
(
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _~-_ _ _ ARI STANDARD 210/240-2003
UNITARY AIR-CONDITIONING
AND AIR-SOURCE HEAT PUMP EQUIPMENT
Section 1. Purpose
1.1
Pwpose, The purpose ofthis standard is to establish,
for Unitary Air-Conditioners and Air-SourceUnitary Heat
2.2.5
This standard does not apply to rating units
equipped with desuperheater/water heating devices in
operation.
.
Pumps: definitions; classifications; test requirements; rating
requirements; minimum data requirements for Published
Ratings; operating requirements; marking and nameplate
data; and conformance conditions.
1.1.1
Intent, This standard is intended for the
guidance of the industry, including manufacturers,
engineers, installers, contractors and users.
1.1.2
Review andAmendment, This' standard is
subject to review and amendment as technology
advances.
Section 2, Scope
2.1
Scope, This standard applies to factOly-made Unitary
Air-Conditioners and Air-Source Unitary Heat Pumps as
defined in Section 3,
2.1.1
Energy Source. This standard applies only
to electrically operated, vapor co.mpression
refrigeration systems.
2.2
Exclusions, This standard does not apply to the
rating and testing of individual assemblies, .such as
condensing units or coils, for separate use.
2.2.1
This standard does not apply to heat
operated air~conditioning/heat pump'equipment, o'r to
packaged tenninal ajr-conditioners/h~at pumps, or,to
room air-conditioners/heat pumps.
2.2,2
This standard does not apply to Unitary AirConditioners as defined in ARI Standard 340/360
with capacities of 65,000 Btu/h [19,000 Wl or
greater.
2.2.3
This standard does not apply to Air-Source
Unitary Heat Pumps as defined in ARl Standard
340/360 with cooling capacities of 65,000 Btu/h
[19,000 W] or greater, or to water-source heat
pumps, to ground water-'source heat pumps, and to
ground source closed-loop heat pumps,
2,2.4
This standard does not include water heating
heat pumps,
Section 3. Definitions
All terms in this document shall follow the standard industry
definitions in the current edition ofASHRAE Terminology of
Heating, Ventilation, Air- Conditioning and Rejl-igeration,
unless otherwise defined in this section.
Note: See Appendix C for definitions that apply to tile
testing and calculation procedures required by Appendix C,
3.1
Air-Source Unitmy Heat Pump. One or more
factOly-made assemblies which normally include an indoor
conditioning coil(s), compressor(s), and outdoor coil(s),
including means to provide a heating function. Vlhen such
equipment is provided in more than one assembly, the
separated assemblies shall be designed to be used together,
and the requirements of rating outlined in the standard are
based upon the use of matched assemblies,
3.1.1
Functions. They shall provide the function
of air heating with controlled temperature, and may
include the functions of air~cooling, air-circulating,
arr-cleaning, dehumidifying or humidifying.
3,2
Deg,-adation Coefficient (CD)' The measure of the
efficiency loss due to the cycling of the units as determined
in Appendices C and D.
3.3
Design Healing Requirement (DHR). This is the
amount of heating required to maintain a given indoor
temperature at a particular outdoor design temperature.
3.4
Energy Efficiency Ratio (EER), A ratio of the
cooling capacity in BLuth to the power input value in watts at
any given set of Rating Conditions expressed in BtuJ(W,h),
3.4_1
Standard Energy Efficiency Ratio, A ratio
of the capacity to power input value obtained at
Standard Rating Conditions,
3,5
Heating Seasonal Pelformance Factor (HSPF), The
total heating output of a heat pump, including supplementary
electric heat necessary to achieve building heating
requirements during its nonnal annual usage period for
heating divided by the total electric power during the same
period, as determined in Appendices C (Section C4,2) and
D, expressed in Btu/(W,h),
ARI STANDARD 2101240-2003 _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ __
3.6
Integrated Part-Load Value (IPLV). A single number
part-load efficiency figure of merit calculated per the
method described in this standard.
and the requirements of rating outlined in this st~ndard are
based upon the use of these assemblies in operation together.
(
Functions. Eithe;:r alone or in combination
with a heating plant, the functions are to provide air~
circulation, air-cleaning, cooling with controlled
temperature and dehumidification, and may
optionally include the function of heating andlor
humidifying.
3.12.1
3.7
Published Rating. A statement of the assigned values
of those perfonmance characteristics, under stated Rating
Conditions, by which a unit may be chosen to fit its
application. These values apply to all unitsoflike nominal
capacity and type (identification) produced by the same
manufacturer. As used herein, the tenm Published Rating
includes the rating of all perfonmance characteristics shown
on the unit or published in specificatio~s, advertisi!lg, or
other literature controlled by the manufacturer, at stated
. ..
Rating Conditions.
3.7.1
Application Rating. A rating b~~ed ~n tests
performed at Application Rating Conditions (other
.'.
than Standard Rating Conditions):
3.7.2
Standard Rating. A rating based on tests
perfonmed at Standard Rating Conditions.
3.8
Rating Conditions. Any set of operating conditions
under which a single level of performance results and which
causes only that level of perfonmance to occur.
3.8.1
Standard Rating Conditions.
Rating
Conditions used as the basis of comparison for
p~rfo~ance _characteristics.
3.9
Seasonal Energy Efficiency Ratio (SEER). The total
cooling of a central air-conditioner during -its normal usage
period for cooling (not to exceed 12 months) divided by the
total electric energy input during the same _period as
detennined in Appendices C (SectionC4.1) and D,
expressed in Btl.l/(W·h).
3.10 "Shall" or "Should". "Shall" or "should" shall be
interpreted as follows:
Shall. Where "shall" or "shall not" is used
for a provision specified, that provision is mandatory
if compliance with the standard is claimed. .
3.10.1
3.10.2 Should.
"Should" is used to indicate
provisions which are not mandatory but which are
desirable as good practice.
3.11 Standard Air. Air weighing 0.075 Ib/ft 3 [1.2 kg/ml]
which approximates dry air at 70°F [21°C] and at a
bar9metric pressure of29.92 inHg [101.3 kPa].
3.12 UnitaJY Air-Condilloner. One or more factory-made
assemblies which nonmally include an evaporator or cooling
coil(s), compressor(s), and condenser(s). Where such
equipment is provided in more than one assembly, the
separated assemblies are to be designed to be used together,
2
Section 4. Classifications
Equipment covered within the scope of this standard shall be
classified as shown in Tables 1 and 2.
Section 5. Test Requirements
All Standard Ratings ihall be verified by tests conducted in
accordance with ANSI/ASHRAE Standard 37 and with the
test methods and procedures as described in this standard
and its appendices.
Air-cooled units shall be tested in accordance with
Appendices C and D. Water-cooled and evaporative-cooled
units shall be tested in accordance with ANSI! ASHRAE
Standard 37.
Section 6. Rating Requirements
Standard Ratings.
Standard Ratings shall be
established at the Standard Rating Conditions specified in
.
6.1.3.
6.1
Air-cooled unit:? shall be rated at conditions specified in
Table 3 or Table 4.
Water-cooled and evaporative-cooled units shall be rated at
condi.tions specified in Table 5.
Standard Ratings relating to cooling or heating capacities
shall be net values, including the etIects of circulating-fan
heat, but not including supplementary heat. Power input
shall be the total power input to the compressor(s) and
fanes), plus controls and other items required as. part of the
system for normal operation.
Standard Ratings of units which do not have indoor aircirculating fans furnished as part of the model, i.e., split
systems with indoor coil alone, shall be established by
subtracting from the total cooling capacity 1,250 Btu/h per
1,000 clin [775 W/m 3/s], and by adding the same amount to
the heating capacity. Total power input for both heating and
cooling shall be increased by 365 W per 1,000 clin [226
W/mJ/s] of indoor air circulated.
(,
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _~_ _ _ARI STANDARD 210/240-2003
Standard Ratings of water-cooled units shall include a total
allowance for cooling tower fan motor and circulating water
pump motor power inputs to be added in the amount·of 10.0
W per 1,000 Btu/h [34.1 W per 1,000 W] cooling capacity.
6.1.1
Values of Standard Capacity Ralings.
These ratings shall be expressed only in terms of
B tu/h [WJ as shown:
6.1.3.3 Indoor-Coil Airflow Rate. All
Standard Ratings shall be determined at an
indoor-coil airflow rate as outlined below
All airflow rates shall be expressed in tenn~
of Standard Air. .
a.
.
Capacity Ratings,
Btu/h rW1
< 20,000 [5,9001
~ 20,000 and < 38,000
[5,900 up to 11,000]
~ 38,000 and < 65,000
[11,000 up to 19,000J
Multiples, Btu/h [W]
100 [30J
200 [60]
....
500 [150]
Equipment with indoor fans
intended for use with field
installed duct systems shall be
rated at the indoor-coil
airflow rate (not to exceed
37.5 SCFM per 1,000 Btulh
[0.06 m'ls per 1,000W] of
rated capacity) delivered
when operating against the
...
minimum ,external ,pressure
Standard me~sures of energy efficiency, whe'never
specified in 6.1.3.6 or at a
lower indoor-coil airflow rate
if so specified by . the
manufacturer.
6.1.2
Values of Measures of Energy Efficiency.
published, shall be expressed in multiples of the
nearest 0.05 Btu/(W·h) for EER, SEER and HSPF.
and in multiples of 0.1 for IPLV.
6.1.3
Standard Rating Tests. Tables 3, 4 and 5
indicate the test and test conditi()ns which are
required to determine values of standard capacity
ratings and values of measures of energy efficiency.
6.1.3.1 Assigned Degradation Factor. In
lieu. of conducting C and D tests or the
heating cycling test (as sho~ in Table 3),
an assigned value of 0.25.may be used for
either the cooling Of heailng D~gradation
Coefficient, Co, orboth. For units with two
compressor speeds, two ~ompressors' or
cylinder unloading, if the assigned CD is
used for one cooling mode, it must be used
for both cooling modes. If the assigned CD
is used for one heating mode, it must be
used forboth heating modes.
6.1.3.2 Electrical Conditions. Standard
Rating tests shall be performed. at the
nameplate rated voltage(s) and frequency.
For air-cooled equipment which is rated
with 208-230V dual nameplate voltages,
Standard Rating tests shall be performed at
230 V. For all other dual nameplate voltage
equipment covered by this standard, the
Standard Rating tests shall be performed at
both voltages or at the lower of the two
voltages if only a single Standard Rating is
to be published.
b.
Equipment witl) indoor fans
not intended for use with field
installed duet systems (free
discharge) shall be rated at
the indoor-coil airflow rate
delivered when operating at 0
in H 2 0 [0 Pal external
pressure as specified by the
manufacturer.
. c.' Equipment which does not
incorporate an indoor fan, but
is rated in combination with a
device employing a fan shall
be rated as described under
6.1.3.3 a. For equipment of
this class which is rated for
general use to be applied to a
variety of heating units, the
indoor-coil airflow rate shall
specified. by
the
be
manufacturer in' Standard
Ratings, not to exceed 37.5
SCFMIl ,000 Btu/h [0.06 m'ls
per 1,000 W] of rated
capacity or the airflow rate
obtained through the indoor
coil assembly when the
pressure
drop
across
the
indoor coil assembly and the
reconunended enclosures and
attachment means is not
greater than 0.30 in H 2 0 [75
PaJ, whichever is less.
3
ARI STANDARD 210/240-2003 _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ __
(
Table 1. Classification of Unitary Air-Conditioners
Types of Unitary Air-Conditioners
ARJ Type
Desianation
1,2
Ananaement
SP-A
SP-E
sP-W
Single Package
I FAN I COMP
EVAP
COND
I
..
.
....
Refrigeration
'" Chassis
,
."
.
.'
Year-Round
Single
Package
Remote
Condenser
RCH-A
RCH-E
RCH-W
I EVAP
SPY-A
SPY-E
SPY-W
FAN
HEAT
EVAP
RC-A
RC-E
RC-W
FAN
EVAP
COMP
.
RCY-A
RCY-E
RCY-W
Year-Round
Remote
Condenser
..
~
I COMP
COND
COMP
COND
I
I
I
I COND I
FAN
EVAP
HEAT
COMP
(
I COND I
.
Conderisi~g
"'Unit Coil
1"Alo~e
RCU-A-C
RCU-E-C
RCU-W-C
.
v
Condensing
Unit, Coil
And Blower
RCU-A-CB
RCU-E-CB
RCU-W-CB
Year-Round
Condensing
Unit, Coil and Blower
RCUY-A-CB
RCUY-E-CB
RCUY-W-CB
"
I EVAP I
I COND
: COMP
,
I
.
..
m
EVAP
I COND
I
COMP
FAN
EVAP
HEAT
I COND
I
COMP
'""
Notes:
1
2
A
suffix' of" -0" following any of the above classifications indicates equipment not intended for use with field-
installedduct systems (6,U.3b).
A suffix ofll_AI! indicates air-cooled condenser, "_Ell indicates
water-cooled condenser.
evaporative~cooled
condenser and !1-VlI! indicates
(
4
_ _ _ _ _ _ _ _ _ _ _ _ _ _-:-_ _ _ _ _ _ _-'-_ _ _ _,ARI STANDARD 210/240-2003
Table 2. Classification of Air-Source Unitary Heat Pumps
Types of Air-Source Unitary Heat Pumps
.
ARlType'
Designation
Arrangement
.
Heating and
Coolin o
Heating Only
.
HSP-A
Single Package
HOSP-A
FAN
INDOOR
COIL
HORC-A-CB
HRC-A-CB
Remote Outdoor Coil
Remote Outdoor Coil
With No Indoor Fan
BRC-A-C
Split System
BRCU-A-CB
BORC-A-C
COMP
OUTDOOR
COIL
FAN
INDOOR COIL
COMP
I OUTDOOR COIL I
I INDOOR COIL
I OUTDOOR COIL I
COMP
I
I COMP
BORCU-A-CB
I ;;:OOR COIL
I I OUTDOOR COIL
I INDOOR COIL
I
.
Split System
With No Indoor Fan
~-
... - ..
~
',._.
BRCU-A-C
.
BORCU-A-C
I COMP
I
I OUTDOOR COIL I
Note:
,
A suffix of 11_0 11 following any of the above classifications indicates equipment not intended for use with fieldinstalled duct systems (6.1.3.3 b.).
5
ARI STANDARD 210/240-2003 _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ __
(
Table 3. Conditions for Standard Rating Tests and Operating Requirement Tests for Aircooled Equipment Using Appendix C
INDOOR UNIT
OUTDOOR UNIT
Air Entering
Air Entering
TEST
Dry-Bulb
of
Standard Rating Conditions
!!AII
CoolinO' Steady State
80.0
Wet-Bulb
°C
26.7
of
Dry-Bulb
°C
of
Wet-Bulb
°C
of
°C
67.0
19.4
95.0
35.0
75.0
2
23.9
67.0
19.4
82.0
27.8
65.0
2
18.3
I
IlBI! Cooling Steady State
80.0
"C" Cooling Steady State Dry Coil
80.0
"D" Cooling Cyclic Dry Coil
80.0
Low Temperature Operation
Cooling
26.7
"
0
is
e-1
0
0
u
57.0
5
13.9
82.0
27.8
65.0
2
18.3
26.7
57.0
5
13.9
82.0
27.8
65.0
2
18.3
67.0
19.4
57.0
13.9
67.0
19.4
57.0 2
13.9
Insulation Efficiency
80.0
26.7
75.0
23.9
80.0
26.7
75.0 2
23.9
Condensate Disposal
80.0
26.7
75.0
23.9
80.0
26.7
75.0
2
23.9
Maximum Operating Conditions
80.0
26.7
67.0
19.4
115.0
46.1
75.0
2
23.9
26.7
(
,,'
Standard Rating Conditions
High Temperature Heating 3
Steady State
70.0
21.1
60.0
(max)
15.6
47.0
8.3
43.0
6.1
High Temperature Heating Cyclic
70.0
21.1
60.0
(max)
15.6
47.0
8.3
43.0
6.1
High Temperature Heating4
Steady State
70.0
21.1
60.0
(max)
15.6
62.0
16.7
56.5
13.6
Low Temperature Heating
Steady State
70.0
21.1
60.0
15.6
17.0
-8.3
15.0
-9.4
Frost Accumulation
70.0
21.1
15.6
35.0
1.7
33.0
0.6
Maximum Operating Conditions
80.0
26.7
- 75.0
23.9
65.0
18.3
0
is~
-<
<L1
;r:
(max)
60.0
(max)
-
Notes:
I
Same conditions used for Voltage Tolerance Tests.
2
The wet-bulb temperature condition ~s not required when testing air-cooled condensers which do not evaporate
condensate.
3
Same conditions used for Voltage Tolerance Tests (Heating-only units).
4
For two speed, two compressor or units with compressor unloading capability.
Wet-bulb temperature sufficiently low that no condensate forms on evaporator.
,
6
(
~_ _ _ _ _ _ _~_ _ _ _ _ _ _ _ _ _ _ _ _,--_ _ _~ARI
STANDARD 2101240-2003
Table 4. Conditions for Standard Rating Tests for Air-cooled Variable Speed Equipment
Meetin~ the Requirements of Appendix C
',"
TEST
,
lNDOORCOIL
OUTDOOR COIL
AlRENTERING
AIR ENTERING
Dry-Bulb
OF
Wet-Bulb
°C
of
Dry Bulb
°C
of
Wet Bulb
°C
of
°C
"A" Cooling Steady State
At Maximum (k=2) Compressor Speed
80,0
26,7
67,0
19.4
95.0
35,0
75,0 '
23.9
!lB-2" Cooling Steady State
At Maximum (k=2) Compressor Speed
80.0
26.7
67,0
19A
82.0
27.8
65.0 '
18.3
!lB_11t Cooling Steady State
80,0
26,7
67,0
19,4
82.0
27.8
65,0 '
18.3
Low Ambient Cooling Steady State
At Minimum (k= 1) Compressor Speed
80.0
26,7
67,0
19,4
67,0
19A
53.5 '
11.9
Dry Coil Cooling Steady State
At Minimum (k=l) Compressor Speed
80.0
26.7
57.0
4
13.9
67.0
19.4
535 '
11.9
Cyclic Cooling Dry Coil 4
At Minimum (k= 1) Compressor Speed
80.0
26.7
57.0
4
13.9
67.0
19.4
53.5 '
Intennediate Cooling Steady State
At Intermediate (k=i) Compressor Speed
80.0
Standard Rating:Heatini;
At Nominal 2 (k=n) Compressor Speed
70.0
21.1
60.0
(max)
15.6
47.0
8.3
43.0
6. i
Max Temperature Heating
At Minimum (k= 1)Compressor Speed
70.0
21.1
60.0
15.6
62.0
16.7
56.5
13.6
Cyclic Heating 4
At Minimum (k= 1) Compressor Speed
70.0
21.1
60.0
15.6
62.0
16.7
56.5
13.6
High Temperature Heating
At Maximum (k=2) Compressor Speed
70.0
21.1
60.0
15.6
47.0
8.3
43.0
6.1
High Temperature Heating
At Minimum (k= I) Compressor Speed
70.0
21.1
60.0
15.6
47.0
8.3
43.0
6.1
Frost Accumulation 3
At Maximum (k=2) and!or Intermediate
(k""j) Compressor Speed
70.0
21.1
60.0
15.6
35.0
1.7
33.0
0.6
70.0
21.1
60.0
15.6
17.0
-8.3
15.0
-9.4
At Minimum (k= I) Compressor Speed
J 1.9
"
"
"
"
26.7
67.0
19.4
87.0
30.6
69.0'
20.6
"
,
Low Temperature Heating
At Maximum (k=2) Compressor Speed
All tests are pClfon11ed at the outdoor fan speed and indoor blower speed intended for oonna! operalion.
k = Compressor speed
Notes:
, Not maintained if no condensate rejected to outdoor coil.
2
Optional test used to detennine the DHR. The nominal speed is the lesser of the cooling and heating maximum speeds.
Optional equations may be used in lieu of the maximum speed test. The lntennediate speed is the same as the cooling lntennediate speed.
Wet·bulb temperature sufficiently low that no condensate fOll11S on evaporator.
,
,
7
ARI STANDARD 210/240-2003 _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ __
Table 5. Conditions for Standard Rating Tests and Operating Requirement Tests for Water-cooled(
and Evaporative-cooled Equipment Using ASHRAE Standard 37
INDOOR SECTION
TEST
OUTDOOR SECTION
Air Entering
Standard Rating
Conditions
°C
Dry-Bulb
Wet-Bulb
Dry-Bulb
of
Evaporative-cooled
OF
°C
OF
°C
Water-cooled
Air Entering
Make-up Water 3
Wet-Bulb
-",-.,
of
°C
of
°c
Condenser Inlet
of
Condenser
Outlet
°c
of
°C
29.4
95.0
35.0
80.0
26.7
67.0
19.4
95.0
35.0
75.0
23.9
85.0
29.4
85.0
67.0
19.4
57.0
13.9
67.0
19.4
57.0
13.9
67.0
19.4
-
-
70.0
21.1
80.0
26.7
75.0
23.9
80.0
26.7
75.0
23.9
85.0
29.4
-
-
80.0
26.7
80.0
26.7
75.0
23.9
80.0
26.7
75.0
23.9
85.0
29.4
-
-
80.0
26.7
80.0
26.7
67.0
19.4
100.0 37.8
80.0
26.7
90.0
32.2
90.0
100.0
37.8
26.7
67.0
19.4
80.0
67.0
19.4
77.0
25.0
75.0' 23.9
Cooling!
Low
.
Temperature
Operating
Cooling
0
Insulation
2i
Efficiency
""'00
U
Condensate
Disposal
Maximum
Operating
Conditions
Part-Load
32.2
(
80.0
26.7
-
-
Conditions
(IPLV)
.
Notes:
I
Same conditions used for Voltage Tolerance Tests
Water tlow rate as detennined from Standard Rating Conditions.
3
Water in basin shall not overflow.
,
Indoor-coil airflow i"ates and pressures as
referred to here.inapply to the airflow rate
experienced when the unit is cooling and
dehumidifying under the conditions
specified in this section. This airflow rate,
except as noted in 6.1.3.3 band 8.4, shall be
employed in all other tests prescribed herein
without regard to resulting external static
pressure. _Heating only units shall use the
airflow rate experienced when the unit is
operating under the High Temperature
Heating Standard Rating Conditions Test.
6.1.3.4 Outdoor-Coil Airjlo}v Rate. All Standard
Ratings shall be detennined at the outdoor-coil
airflow rate specified by the manufacturer' where the
fan drive is adjustable. Where the fan drive is
non-adjustable, they shall be detennined .at the
outdoor-coil airflow rate inherent in the equipment
when operated with all offue resistance' elements
associated with inlets, louvers, and any ductwork and
attachments considered by the manufacturer as
.
nonnal installation practice. Once established, the
outdoor coil air circuit of the equipment shall remain
unchanged throughout all tests prescribed herein.
6.1.3.5 Requirements for Separated Assemblies.
All Standard Ratings for equipment in which the
outdoor section is separated from the indoor section,
as in Types RC, RCY, RCU, RCUY, HRC, HORC,
HRCU and HORCU (shown in Section 4), shall be
detennined with at least 25 ft [7.6 m] of
interconnection tubing on each line of the size
recommended by the manufacturer. Such equipment
in which the interconnection tubing is furnished as an
integral part of the machine not recommended for·
cutting to length shall be tested with the complete
length of tubing furnished, or with 25 ft [7.6 m] of
tuhbing, whichev~r is grbeater. hAtlllebastl 0 ft [3.0 mlof
t e mterconnectlOn tu mg s a e exposed to the
outside conditions. The line sizes, insulation, and
details of installation shall be in accordance with the
manufacturer!s published recorrunendation.
C
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _'--_ _ _~ARI STANDARD 210/240-2003
6.1.3.6 lvlinimum External Pressure. Indoor airmoving equipment intended for use with field
installed duct systems shall be designed to operate
against, and tested at not less than, the minimum
external pressure shown in Table 6 when delivering
the rated capacity and airflow rate specified in
6:1.3.3.
--.
Indoor air-moving equipment not intended for' use'
with field installed duct systems (free discharge) shall
be tested at 0 in H 2 0 [0 Pal external pressure.
6.2.1
Part~Load Rating Conditions.
Test
conditions for part-load ratings shall be per Table 5.
Any water flow required for system function shall be
at water flow rates established at (full load) Standard
Rating Conditions.
Capacity reduction means may be adjusted to obtain
the specified step of unloading.
No manual
adjustment of indoor and outdoor airflow rates from
those of the Standard Rating Conditions shall be
made. However, automatic adjustment of, airflow
rates by system function is permissible.
Table 6. Minimum External Pressure
Minimum
Standard Capacity
Ratings 1
-
-
- MBtu/h
External
Resistance
-- ---.
kW
inH,O
Pa
;; 28
;; 8.2
0.10
25
> 28 and;; 42
> 8.2 and;; 12.4
0.15
37
> 42 and < 65
> 12.4 and ;;-19.0
0.20 -
50
6.2.2
Integrated Part-Load Value (IPLV). For
equipment covered by this standard, the IPLV shall
be calculated as follows:
a.
Determine the capacity and EER at the
conditions specified in Table 5 -
b.
Detennine the Part-Load Factor (PLF)
from Figure I, "Part-Load Factor
Curve,!! at each rating point (see
Appendix E)
c.
I Cooling capacity for units with cooling fi.mction;
High Temperature Heating Capacity for heating-only
.units
Use the following equation to calculate
IPLV:
-
IPLV
Interpreting this requir~merit, it is understood th'at'tlle
most restrictive filters, supplementary heating coils,
and other equipment specified as part of the unit be in
place and timt the net external pressure specified
above is available.
6.1..3.7 lvloisture Removal Determination. Indoor
'a'ir moisture removed shall be detennined at Standard
Rating Conditions (cooling) for units tested in
accordance with both ANSI/ASHRAE Standard 37
and Appendix C. The expression of the removal rate
shall be based upon the net cooling capacity,
including an allowance of I ,250 Btu/h per 1,000 cfrn
[775 W/m2/s] fan heat lor blowerless equipment.
6.2
Part-Load Rating. Only systems which are capable
of capacity reduction shall be rated at 100% and at each step
of capacity reduction provided by the refrigeration system(s)
as published by the manufacturer. These rating points shall
be used to calculate the IPLV (see 6.2.2).
where:
PLF
Part-load
factor
determined from
Figure 1
n
Superscript 1
Total number of
capacity steps
~
100%
capacity
and EER at part-
load
Subscript 2, 3 etc.
Rating
Conditions
Specific capacity
and EER at partload steps per 6.2
9
ARI STANDARD 210/240-2003 _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ __
4,
6.3
Application Ratings. Ratings at conditions of
temperature or airflow rate other than those specified in
6.1.3 and 6.2.1 may be published as Application Ratings,
and shall be based on data determined by the methods
prescribed in 6.1. Application Ratings in the defrost region
shall include net capacity and COP based upon a complete
defrost cycle.
6.4
Publication of Ratings. Wherever Application
Ratings are published or printed, they shall inClude, or be
accompanied by the Standard Ratings plus the IPLV (where
applicable), clearly designated as such, including a statement
of the conditions at which the ratings apply.
Capacity Designation.
The capacity
designation used in: published specifications,
literature or advertising, controlled by the
manufacturer, for equipment rated under tlllS
standard, shall be expressed only in Btu/h [W] at the
Standard Rating Conditions specified in 6.1.3 plus
part-load Rating Conditions specified in 6.2.1 and in
the terms described in 6.1.1 and 6.1.2. Horsepower,
tons or other units shall not be used as capacity
designation.
Region IV Heating Seasonal Perfonnance
Factor, HSPF, minimum design p.eating
requirement
(
7.2
Latent Capacity Designation. The moisture removal
designation shall be published in the manufacturer's
specifications and literature. The value shall be expressed
consistently in either gross or net in one or more of the
following forms:
. .
a.
b.
c.
Sensible capacity/total capacity ratio and total
capacity
Latent capacity and total capacity
Sensible capacity and total capacity
6.4.1
Tolerances. To comply with this standard, measured
test results shall not be less than 95% of Published Ratings
for performance ratios and capacities.
7.3
Rating Claims. All claims to ratings within the scope
of this standard shall include the statement "Rated in
accordance with ARl Standard 210/240". All claims to
ratings outside the scope of this standard shall include the
statement: "Outside the scope of ARl Standard 2 I 01240".
Wherever Application Ratings are published or printed, they
shall include a statement of the conditions at which the
ratings apply.
Section 8. Operating Requirements
6.5
(Note: Products covered by the National Appliance Energy
Conservation Act (NAECA) shall be rated in accordance
with 10 CFR 430, Section 24 m (I) (i) and (ii).)
Section 7. Minimum Data Requirements for
Published Ratings
7.1
Minimum Data Requirements/or Published Ratings.
As a minimum, Published Ratings shall consist of the
following information:
(
8.1
Operating Requirements. Unitary equipment shall
comply with the provisions of this section such that any
production unit will meet the requirements detailed herein.
8.2
Maximum Operating Conditions Test. Unitary
equipment shall pass the following maximum operating
conditions test with an indoor-coil airflow rate as
determined under 6.1.3.3.
8.2.1
Temperature Conditions.
Temperature
conditions shall be maintained as shown in Tables 3,
4 or 5.
8.2.2
a.
For Unitary Air-Conditoners (air-cooled)
1.
2.
b.
ARI Standard Rating cooling capacity
Seasonal Energy Efficiency Ratio, SEER
For Unitary Air-Conditioners (water-cooled and
evaporative-cooled)
Voltages. The test shall be run at the Range
A minimum utilization voltage from ARl Standard
110, Table 1, based upon the unit's nameplate rated
voJtage(s). This voltage shall be supplied at the unit's
service connection and.at rated frequency.
8.2.3
Procedure.
The equipment shall be
operated for one hour at the temperature conditions
and voltage specified.
I.
2.
c.
ARl Standard Rating cooling capacity
Energy Efficiency Ratio, EER
For all Air-Source Unitary Heat Pumps
1.
2.
3.
ARl Standard Rating cooling capacity
Seasonal Energy Efficiency Ratio, SEER
High temperature heating Standard Rating
capacity
8.2.4
Requirements. The equipment shall operate
continuously without interruption for any reason for
one hour.
8.2.4.1 Units
with
water-cooled
condensers shall be capable of operation
under these maximum conditions at a water-
(
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _-'--_ _ _ _,ARI STANDARD 210/240-2003
Note: The curve is based on following equation:
PLF = AD + (Al xQ)+(A2xQ')+(A3xQ')+(A4xQ')+(A5xQ')+(A6xQ')
where: PLF = Part-Load Factor
Q = Percent of full-load capacity at part-load rating
conditions.
AO = -0.12773917 X 10-'
Al = - 0.27648713 x 10-'
A2 =
0.50672449 x 10-'
A3 = -0,25966636 x 10-'
A4 =
0.69875354 x 10-'
A5 = -0.76859712 x 10-'
A6 =
0.28918272 x 10- 10
Figure 1. Part-Load Factor Curve
11
ARI STANDARD 210/240-2003 _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ __
pressure drop not to exceed 15.0 psi [103
kPa], measured across the unit.
8.3.4
8.3.4.1 During both tests, the equipment
shall operate without failure of any of its
parts.
8.3
Voltage Tolerance Test. Unitary equipment shall
pass the following voltage tolerance test with a cooling coil
airflow rate as determined under 6.1.3.3.
8.3.4.2 The equipment shall operate
continuously without interruption for any
reason for the one hour period preceding the
power intemlption.
8.3.1
Temperature Conditions.
Temperature
conditions shall be maintained at the standard cooling
(and/or standard heating, as required) steady state
conditions as shown in Table 3, Table 4 or Table 5.
8.3.2
8.3.4.3 The unit shall resume continuous
operation within two hours of restoration of
power and shall then operate continuously
for one half hour. Operation and resetting
of safety devices prior to establishment of
continuous operation is permitted.
Voltages.
8.3.2.1 Tests shall be run at the Range B.
minimum and maximum utilization voltages
from ARl Standard 110, Table I, based
upon the unitls narneplate rated voltage(s).
These voltages shall be supplied at the unit's
service cormection and at rated frequency.
A lower minimum or a higher maximum
voltage shall be used, if listed on the
nameplate.
(
Requirements.
8.4 Low-Temperature Operation Test (Cooling) (Not.
required for heating-only units). Unitary equipment shall
pass the following low-temperature operation test when
operating with initial airflow rates as determined in 6.1.3.3
and 6.1.3.4 and with controls and dampers set to produce the
maximum tendency to frost or ice the evaporator provided
such settings ar:e not contrary to the manufacturer1s
instructions to the user.
1
8.3.2.2 The power supplied to single phase
equipment shall be adjusted just prior to the
shut-down period (8.3.3.2) so that the
resulting voltage at the unit's service
cOlll1ection is 86%
nameplate rated
voltage when the compressor motor is on
locked-rotor.
(For 200V or 208V
nameplate rated equipment the restart
voltage shall be set at 180V when the
compressor motor is on locked rotor). Open
circuit voltage for three-phase equipment
shall not be greater than 90% of nameplate
rated voltage.
of
8.3.2.3 Within one minute after" the
equipment has resumed continuous
operation (8.3.4.3), the voltage shall be
restored to the values specified in 8.3.2.1.
8.3.3
(
Temperature
Conditions shall be maintained as shown in Table 3
or Table 5.
8.4.1
Te,rnperalure Conditions.
8.4.2
Procedure. The test shall be continuous
with the unit on the cooling cycle, for not less than
four hours after estahlishment of ihe specified
temperature conditions. The unit will be pennitted to
start and stop under control of an automatic limit
device, if provided.
8.4.3
Requirements.
8.4.3.1 During the entire test, the
equipment shall operate without damage or
failure of any of its parts.
Procedure.
8.3.3.1 The equipment shall be operated
for one hour at the temperature conditions
and voltage(s) specified.
8.4.3.2 During the entire test, the air
quantity shall not drop more than 25% from
that determined under the Standard Rating
test.
8.3.3.2 All power to the equipment shall
be shut off for a period sufficient to cause
the compressor to stop (not to exceed five
.
seconds) and then restored.
8.4.3.. 3 During the test and during the
defrosting period after tbe completion of the
test, all ice or meltage must be caught and
removed by the drain provisions.
8.5 Insulation Effectiveness Test. (Cooling) (not required
for healing-only unit.s). Unitary equipment shall pass the
following insulation effectiveness test when operating with
airflow rates as determined in 6.1.3.3 and 6.1.3.4 with
1 ')
(
_ _ _ _ _ _ _ _ _ _ _ _ _ _---c:--_ _ _ _ _ _'--_ _ _ _ ARI STANDARD 210/240-2003
controls~ fans, dampers, and grilles set to produce the
maximum tendency to sweat l provided such settings are not
contrary to the manufacturer1s instructions to the user.
Section 9. Marking and Nameplate Data
9.1
lYJarking and Nameplate Data. As a minimum, the
nameplate shall display the manufacturer's name, model
designation, and electrical characteristics.
8.5.1
Temperature Conditions.
Temperature
conditions shall be maintained as shown in Table 3 or
Table 5.
Nameplate voltages for 60 Hertz systems shall include one
or more of the equipment nameplate voltage ratings shown
in Table I of ARl Standard 110. Nameplate voltages for 50
Hertz systems shall include one or more of the utilization
voltages shown in Table I of lEe Standard Publication
60038.
8.5.2
Procedure. After establishment of the
specified temperature conditions, the unit shali be
operated continuously for a period of four hours.
8.5.3
Requirements.
During the test, no
condensed water shali drop, run, or blow off from the
unit casing.
Section 10. Conformance Conditions
8.6
Condensate Disposal Test (Cooling)* (not required
for heating-only units). Unitary equipment which rejects
condensate to the condenser air shall. pas's the following
condensate disposal test when operating with airflow rates as
determined in 6.1.3.3 and 6.1.3.4 and with controls and
dampers set to produce condensate at the maximum rate,
proyided such settings are not contrary to the manufacturer's
instructions to the user.
10.1 Conformance. While conformance with this standard
is voluntary, conformance shall not be claimed or implied
for products or equipment within its Purpose (Section 1) and
Scope (Section 2) unless such claims meet all of the
requirements of this standard.
*
This test may be nm concurrently with the Insulation
Effectiveness Test (8.5).
8.6.1
Temperature Conditions.
Temperature
conditions shall be maintained as shown in Table 3 or
.,.
Table 5.
,.
" . c · ; " " .,;
8.6.2
Procedure. After establishment of the
specified temperature conditions, the equipment shall
be started with its condensate collection pan filled to
the overflowing point and shall be operated
continuously for four hours after the condensate level
has reached eqUilibrium.
8.6.3
Requirements. During the test, there shall
be no dripping, running-off, or blowing-off of
moisture from the unit casing.
8.7
Tolerances. The conditions for the tests outlined in
Section 8 are average values subject to tolerances of± 1.0oP
[± 0.6°C] for air wet-bulb and dry-bulb temperatures,
± 1.0% of the reading for voltages.
13
ARI STANDARD 210/240-2003 _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ __
APPENDIX A. REFERENCES - NORMATIVE
(
AI.4
ARl Standard 340/360-2000, Commercial
and Industrial Unilmy Air-Conditioning and Heat
Pump Equipment, 2000, Air-Conditioning and
Refrigeration Institute, 4100 North Fairfax Drive,
Suite 200, Arlington, VA 22203, U.S.A.
Al
Listed here are all standards, handbooks and other
publications essential to the fonnation and implementation
of the standard. All references in this appendix are
considered as part of this standard.
A1.l
ANSIIASHRAE Standard 37-1988,Meihods
a/Testing/or Rating Unitary Air-Conditioning and
Heat Pump Equipment, 1988, American Society of
Heating, Refrigerating and Air-Conditioning
Engineers, Inc., 1791 Tullie Circle N.E., Atlanta, GA
30329, U.S.A.
A1.5
ASHRAE Terminology of Heating,
Ventilation, Air-Conditioning and Refrigeration,
Second Edition, 1991, American Society of Heating,
Refrigerating and Air-Conditioning Engineers, Inc.,
1791 Tullie Circle, N.E., Atlanta, GA 30329, U.S.A.
A1.6
IEC Standard Publication 60038, lEC
Standard
Voltages,
1983,
International
Electrotechnical Commission, 3, rue de Varembe,
P.O. Box13l, 12.11 Geneva 20; Switzerland.
A1.2
ANSI/ASHRAE Standard 41.1-1986 (RA
2001), Standard Method for Temperature
Measurement, 2001, American Society of Heating,
Refrigerating and Air-Conditioning Engineers, Inc., .
1791 Tullie Circle, N.E., Atlanta, GA 30329, U.S.A.
A1.3
ARl Standard 110-2002, Air-Conditioning
and Refrigerating Equipment Nameplate Voltages,
Air-Conditioning and Refrigeration Institute, 2002,
4100 North Fairfax Drive, Suite 200, Arlington, VA
22203, U.S.A.
(
APPENDIX B. REFERENCES - INFORMATIVE
None.
(
14
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ ARI STANDARD 210/240-2003
APPENDIX C. *UNIFORM TEST METHOD FOR
MEASURING THE ENERGY CONSUMPTION OF
CENTRAL AIR·CONDITIONERS . NORMATIVE
APP~:o.!UA .Yt 1(,.
'r.\.."l::5t
;Y!!::thOd ib"
CO!l.Stl1:r.J'tri,',~{·iU (:,f
G(\ n cij
-ci tlj':V:~T~;
C',,,,::,,,,,,,
~1~~~~~
/ ...1.;19
"f~";;';:i:i:Si'lf, ,;0:,4"i'l1g-"f ::l\;l~nS' ch;; (l,:';nQu:nl.-
Dr tcdin; :;;: B)':;U':; J>l~::fnn::;\~d by ¢, \,mit b\"er '"
f:'h'~'r::rX:
at i.b'h:\ I!~:-::lrldi.cg
1:;;;.,<;~)( ,~j)olihg,
A~1 •.'l
Tr:$t:I~,,:g
.~~~i~::~~<;~;r~~<J ";;~~it;:~~~
.I BSi-
;c_~
hdb
tf.!mJ::"~,~t-um
'if;:.;t
_'$
t,~,
~
C :,:;::.d D
c:,,)cr~1l~
"':tH~::1
15
ARI STANDARD 210/240-2003, _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ __
(
(
(
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _~_ _ _ _ _ ARI STANDARD 210/240-2003
LpM" t~' . r;:lx,n:,[.!Jre :;:5: C1?nttitil,~J~;,}
'The LP'N 1'£'mpc'''j.{;.lf!~ ~ri::lttl\hHl! be Gcmnw;«\:tt
tit, i.l dry-b~db temp;;~nl,"iJ .:r.tf;'rh~ th:- ')tU!kijf pqnkm m" ~h# tt:~it 0;' i'l ? and ;l Wt~t-hufh
.J..3.2.1A
)
19~~ff:ti f~i~';~;~~:,~~;;i~~i,r~~£~1
17
ARI STANDARD 210/240-2003, _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ __
(
.AA.I~lA
Illr lal;;,(.'i U'lt.;;,
(
(
, 0
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _-C-_--::-___,ARI STANDARD 210/240-2003
~d~~,~,·;~~;e;;~~~!fii0~fJ~Ji~;~::~ti;
!::
:'0.D:ll!tl!nle:r:tf. ci,~,Jl .u~"q r.~ ui;~'::.
~h4; 1.vo),:
~!~~~:~l~
;f~;~}~~r~~~~~}~~~~~E~I~~~
wjn~~JjrC';, tIlt! 't;..::st ~b~H S.:':"..rt 'TI,;~jt dunttlrm 1s
I)hf~~~h.:dt hocr.1!\,:,t';ati tl."ilts. ciefrost $nr,u.ld"lY,i
;rt'~':<"l;:r.1u!"'2 ·dtttin.g :rhf~ om:~llt1.tf teSt J?;'.nr.:.cL
:\.,L2.2 Test tn.stnmw:~l:~{ik};i:
1~~~t~~~dJ1f:.~:~t;:~3r~~r~S£~Jff~
§~§~g
dv$.
t!<$C
spt."-.!iroen cllJ'f;.1.1~h· a !::h...4(rt, }jlE.::'u,m:,
TIle e·!.h'tt.1j$~ sld<: -cf tb::. air iJ.(lW r;:u; ;:l::SSt1,rhlg' t:b.1:jl;1~ {:(mrains .u,t;:~ e:m:aJ.::tt f.ar.!. ',\-+U1S;:i'trH?
"(ri!;:!:{(nS Vl V~!)! 1::4, c~'n;;H:;f-t:l :';0. cilt..1.l.n clw :ci~
;:,J'c~d axrJJ:rr.~ re5i:>t.~n(!11: W,iii' J1m'} raw, T:}11.:
~Jd:\a~zc si~c}:s cl.:t!',~left,Qi~11l-'t65h~ tf....m. I'tlOW
tlr 1!!i J(r!.l;titE{i t!~rtlUg,tl. U;'.¢(:h1uil1<Jnm.?:tFpl1.rziUS
MC 'then btjck· to t.bt~ tm~~: SP!tChM:1 ituJ:"(.. The
.'5tat'!!::: p~~.;;nu~ ~}:::r<I:;& U:~e n~r;th';5.",~ht ~'~b~{y
,).t"¢S$u:-e. rulCi tM StaLIC
pt"f~S#l1rl;
tn'(m.!J·..rrt:~
~;:1!::!nts,M t.l>~ :;lfJ~le,:hr~\',shaU be tn'&as~-ed
~,l..r;:;h mi:mCl1::'lk"!;.t::n~ which '~"iH r~..,clt en I!ITOr!
wKi&Ji. (:ire ,no lr;'l~U'::-':-:' th,!c :'! LO ::ret'cei,~.t i)(
1:neL:;':1'H:4 y~uQ.!: Md h"7.\"lrlg ;~:t;.:L'1'iJ~::t.m tc..'!.JI:
~!~dl~~l~ tf~~.~;~'~~~~;!~~~u?;;~~J):5.~~!~~:~~t~~:
'mt!ri$i'.:rlf.::trf,11~ trillS;';' he
::tken
:a.('
the
nl~w:l~'
4tk~'~;.·1~ :~~~;~e~:t:~~l=!l~r~:~lil~~·d~~$~~;~j
~2;~f;~~~~' :!H~~~~~f1~:':idi,~:i~f"
19
ARI STANDARD 210/240-2003 _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ __
(
(
Cait.."l.:lt·:ti:<.)rI.·it It'!l' pfi:rjSn"l1~;'::J;;e_fal;:t:pn,
of"
,el~J:li"'t:-'
eft1.
""0r,~~E~;a;i~:i~i~;
~:':/:'~~~r:;:~:~\l;~~~, stdl indu'qll" rhf:,fdUnw..
<>.t~:!~iL!.;:~;~~~{~~~~~~!;;:i,~;~:~!~I:,\~W~,£~dl:~.,
the ,_~l'?ctr;\c.ii·· f'O'j!':i!' Lttpt:i:' to .aU
,t\i'z:t:sJ.rrom ';'.r.St: C
n,11.!""t:he ;~j,t!t;;t:r.lc~~ 11~""{F~ {w5ltt.~h.\,):J:t) tr9u;, tf:t$t
~'p:plk~'blt,
C:{)f:::l'XtH!':1t:s '<U'ni C(lftt,i"f.Jh;
(
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _~_ _ _ _ ARI STANDARD 210/240-2003
~,'~~,
!.>':
~~~"I
,and I l{1f,
('-<!UiHl()1"':';
f " WhiCh
]f.
des.c:-l-i)(,;lj by
r}f' ,•• )
(1)
~_Q'~~r~r:\ v ~
N
-
..
1".)/h,iV
21
ARI STANDARD 210/240-2003 _ _ _~_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ __
(
A>.:' •.L.3..5 Calcuh\:,ti ',::-:'i;l
r,.r. ",Biug: t.he vahlt;;, fer
in
Btu\;.iw,a~,:·
t!:;:m-s
QiT;l
IV
<i~'t6cle.nC'y ,,":!tlO5 He
P8r:::E'tlru-
8quatlrm$.~
'.i
can b" C3kull",u'ed b,Y
where
J~.lA
t"lo:i:ci,.oo for
,,,,,l~,'~~"'j,, . ,. i.l
SEE,£{
[(IF
~~~l'~~lt~:
1.11': mQci9 'of Ol')';:,D:UOiE $t:h~ct~d :~) ce:x:rmint
t.:'c, svO!~\ciY~i;;ul:l,e \;apT.icit.ies Q>/(93), o.,,,,~"iS2!;
~~~f;{,g;;:$"~~;':(;~d k"~ll~k~:Y, ~~~I'~~~t:\~~~~
B i.s outl:iner.:l
in.S".j:c~iG(n
A2.'Ht
AS.J .. U $ec:s0.r..ttl i!:!l-ergJ. ;'f,/icie11!;.'Y rGtiIJ, /Qr
"rir-,g(111:rr.-e un.its with Z'il;Qii?"capc.cz~y compr"s>
sors, (Reser.'e\i)
?:"~ I f ?2}
32
~!};J;~;ti~~!t~~;~f:~1r~0~;'{~~~~~'l~~~;£~~
Bmci·e.ncy
(
q,;,."Ji:BZ1
67
whi:rl'! Gnerndent~ A, E, an~ C sh(d.l bit i;:vak:tlL~~-ti using t11!: foikw;ng t;i,Ue,ulicltio"l ;;t~P$:
Cl)l'.r.ml':es$tm;, the sf;i.k~onal enen-v
r-atl{; (S:f:ER}: shu.l1 ':::* dBfin,';),Q, ,S::iii'fqnow$~
SEER '"'
Onc\~ th~
eql'l....tion fm'
Q,/ "'iJl~}
.!:ms ,been
d*::.-enr.:ineo. :ht' temp-e"~<:~lJr'~ \vhtJre
q~,": r=..131iT) can br.. .ihunc. This t.emp-t'l:',at:.m::
,....,lH~:,£ til;:: nurnber of
h(J!J.r,~
in til1'; fh u"n';';:"'?,r,·
3tT}~ ~~}:~t/~'l!lj t~~icl:~~~:f;'~~~b;>;';'~;~aL'
g;$(~rli~eth:~~~)'J~fa~1:pZ~iRZd1;ls~\5.~~3~t'~~i3;
'd,Ii!: eX.-ceGtir..Ytl th::i.t t..:..)tJ, (Jwand:i~$
~1~e&~1h:;i~;:~ftS (~';;r~~}~~~ :~~tb!lfr~\Ir.I~~;~~d~;~~
ctrmprr.-s.i\(rr spe~!,d (k ::.":.ii and thi; f<.<r.np(O:ro.t.u:re
;''1'",) :is deter:::n:n>eG by:
Case III !S the $M}I: a& ::l'pedfi,rid in }·.5J,,;3.·L
R:t~(~jl~~;tSb~"~;~~~)~(;r{:y ·~t; :(~~1ci~~~
pre~->cribe-d
in A5 ..L3,
Sc<;:'S<)nal energy er:i,l..'Ler,cy .rOJi1~ /nr
.'itpU,Hypi~ ,(u.u:d,(~ss $ysiem,!;", j~ tl! :;pllt-·typ:,::
AS,I.]
Q,,/".I(T)
<a!'.d E.:;'~· 1i>1) slwJl Of: calc\dar.eri by the fol.klw,
ing equadt)',:re:
;;l~~,fi~"~ ~;.s~~~~b;,S~IJt lS~~j e~~j'~~~bin~:
non set of Indot/T ~oi Is to be u;;,ed with e common Q\'JtnQo:r unit.
AS,..:! Ca.lcuic.tion. of H;;a:jng Siif!'${mc.i Per',
tormc.J'I,c:e Factors (F.fSP,F)
/},~" .~~:~-:_~"' ~{S2)
x
(,~2 ~
T)
Case II I!,'. wnen the comPTe'S_;,;;o)" 0y,;:rat:e's ai!.-
aoy in tenn,~d'jatt; I)" '.' '- 0) $D0eci ::'elw~~un the
:~~~~l:~~f~:(\~~~'=b~iJiR~':~;~1t~~1;:d~ .~!,.~~~~(~
the fol'lo~vin,g i;){lU41rion:;:
{t,~"(T,>
"" HI.. (1')
'"
N'~ :;:~~~!~)i =if;:~:~~I)
r:
{{If
A.ir-
Sou-mi.' th iis.
Mi":
The te-s~i:m: data 2.:ld re;:,tlJ:.S 'r-eouired to cal~
cul.ate th.&. her:..ting s~-a:s(!l't;;l.i peririnnnnc<l f~c­
tar iHSPF:, in Btu's p-e1' watt~~1:r, .shall inducie
tht} foUnwing:
m H(~:;.!:ting cap::1<::iticR fBtuh.; f:o't:n che in·
dom: a:~!' f.;ntnalpy method n'n t.he High
T¢lnpera~t);r~~ Te:s::s, ;:n:d tht: 1',01,.'1.1 herlt·
Lng dont; (Btu'.sl ro,r the cyci.ic ilnd f:rost
e.ccumillati.on tests. ,
Q",(.17) cr Q,u(52).
QH{l7).
Q ~!It { 4-7).
C}D'!:J·{35),
("
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ ARI STANDARD 210/240-2003
un
Eb:;riclI! power inpt:; to .nil
!.~omM
p\mQ;Jt.~
S"J;ll?
teSt:"
th\~ ~,e~Hiy
(watt:):: f'il'
:l.lH)
ttll:
{wct.!'i<:>:ll
{W~tt#h(rli':i.! f,x [.hl';
w.~i!\!m1d:":ticn t!.li:·C,
E.::,{4/J
Cit
t . ,(.\i).
:.l~:;2.,?e
cydi.i: ~tlrl frost
(v)
1:il.l11~
Outdoor wet b''ulh \If di!lV poi.nt,
ibdoor· c'n' bulb and
Indoor wet hulh.
Datil as spedtlt;d in T{!bfe .5 of 'ASH~
'H..-v: 'St,mdn rd 3-7 ·b8
. Wh{!'re tr& he~H'ing, capacities Q~,~i4ii,
Q",~D21 and Q,)l1} and the ina.cor aIr fitw: rate
aT: ~talc~l~~~d .~S.j~ti!!,e e9)1:!th:.n$:~1)(:cifi,.eil i~
SC:ctlVn I"J.4.ana 1.8;·.) 01 ,ASHP..-"Ji: stjna~ru
31·88._, The.total hej.ting tiotJe, Qc';,,:1"47), ~lhd
q("m:.~~j,5)a!'e taic,~l:<lted U,&[rig' thi: 'eqllf'lt.ilm:s'
below.
Unh,s not 'having iU-, injoo.r f;l'fl ;)$ part or
the mm]":l Le;~,ted, :i,hall ~dd .1.2;)0. Htuh p-I?J"
l~OOO SCF'_M -,;f indGIJr,a,ir h;md,led 'to, the
me:itsun~rj cap<l.dty'i.o (Jbtain thc:, !,oLal 'he~\dng
{;d,Pad'O,Y,QJ17), Q1)47L Or q,).-6:rr. ahd ~dd
·365 'watw, per.l.00u·SCFi\I oj' inJoor air han~led tot-he meimm;d p()werto obcaintn: total
pG_,:,,'cr InpU~r E,j.1 i;, £",,14T., (,If E,p;2;, ,W (h~
umt.
,The cqeffirif.!lt::; of !),erfOm!;1DCe (COP)
(or tno;l, High Ter:lpCI':1.till"-: Te,:;;tici CO.P ~Ai2)
Of COPJ~7); 'and. Low Tt-mper:J.lw'e 'Te~t,
COP .,(l7)! ill'!} <!:l.lC\liated as- the.' ro.t;;Q ',of
th(:, heating c:;J.pacity in Btuh to th~
-r::r.od:~1.c,~ '.of ::t,U3' :lI1,(( the 'p0.'-.\'e:~ inplH.-; to
~,!l!? :nwJol""_ fan ln' W!ltts' irn(l' ~h~ :,powr..r
,In.pu.ts t,?, t~0 nm~;'!l,ning eq\lipm'~_r:it ('om.
pGMtltS ilncmdine: all control:i} ,in W_:lq;:.
Units I'i'hich (jo~ not. h:w_idn'door ':.tir (',irclifll.t-in-g f[(n~ fiitn.ii;h~d as: D:lft -M t.he
model shdl h;~... (! ttli.~;r tct,:d het~{._i:r•.:; ,d~)l1e
(Q-l:f.(i.T1r, Md en.-;:ftW '!'li.~d, ~~y~(47,ril1 om,
com.ph:te cyell'; adju$-'t(,,:d for t:)~~ {'fft::r.'~ of
,1}iJ'cui:1til1g_, ,lnGot1r' .air '~quipment pow(:r.
FoT' ur-it.'!_ t6,~~,d ,'wltlii.i!lt Qr. indo'Or f~:! os
part of tri(' ,model, ()cy~(47) sht!ll be itl~
c.rea~r.d ~Y,~ _qU!lntity of h(."H equ.a! to the
prodtlc~ '(If 1250 Bttlh p~r l;iJ()(} BefM,
~h~ length Df the_ OnHpel'lOd of .he test I:ycle
holt::-:;, nnd the l1ow, rate _df,1.ndoor ,tir
io uni't~ .of 1,uOa 3CF:\--L The
to.t:'11 t>nergy usagei E'~y,'-(4.7)1 shjIl h\~ the-,
:Sum 1)( the 'enCrgy w~aire reauhed for a.ir
circubtion d~:~in:i t.b.€ test- 't)'dr. ":me{ tbil
erH\l'gy met! hy the n~mil.jning eqni'pme-tit
C'-omponi!1),:s, {inclt.lding.-all, co_rm'ol$) tbl'ir,l"
the test'r;y-ch 'Cnits, not, h~Ying- an indoi)r
[an as-pan vi' the' !1'KFk,J ti:-5t~ci. shaH ::et: ;,he
l:iI,
clr~u!:necl
ene-nt)" r~q'.l\r2d for jnrloo~ ,air cll'!~\lJ;JtlQn:
e-qun: -t" the:;q\l~nt:q' given. by thf' prodllct
of 30t5 watt!' pe'r -1000 l"SCr?YI, i:he leng~h of
ule_Q!I_pcl'iod ('j( the tes't' cvde in hours, and
t-he:ri1t~ of ir"qoor air circ~l,lat{:d 10 tml-ts of
1000 ~CnL
(lir HSPf, ;~~ ~,~:termjl1~d abovoJ,: .:.haJl beo,'1!'HJIdpi.i.'la by un ,*nh,ulcement fac,l;()f F,;;,:' W -::om·
?ens-r:u: ,Cof inlp,r,()\·,ed pcriOrmanc0. ["yi; ITit'a~'
"-ycl,,t,S -in ~ L'lAlOllr perlcd <l nd snou1d ':>e- c",I,
c!.lbted us, (oHows;
UldO(if';lir tlmr ratetSCY}!i and'·~xter·
Ml re.sisr.&nc~; to ind,)'OI' ,air "iiO'w Gnthes
()fw;.ii.i;f W,C')
Alf. ,'.(.::lil pii'.r.:.t\!r:(~ i.f\
Outdoor drY
with
in- ~he, '.FiQ~t ,.'\cc'timu:Jati-,nr. Test. 1h;:;
l\mor r:: i;" dfJPtY~lds I)n ~he n,umber ~)f defl'ost
e~)'rH7\
(IV)
8ri.~ .~q'.lippe-c!
l.ln~d'
E,,,(1)2).
EOH{3S).
!li:l!
For air"sotJfcC liniw that
"de11,lll.nd defb)st c:.mtjij( :5Y5U:ms:'. the v,aiue
f.:r<J-'l ;; 0:./;;) 1.;,_' ~;'!"~I' ~n~iir;"'k
F-, ;t;#;p~~;:j(t~i:rl1.'~;~~~:~:~n~~~\;1;:;ii
i
3 . ,; <;0,
{,~b 1\,',:;, ,,':J'r.q";j1'Q
,3, ,51',
~:::~~{;\lfi~~~~~~~~r~1il~~;~~~i~
W~mH\lnlitJlI.7 r\\~il);(tb/!li)~
'Sf):1
~\>h'.;:re;
F.(,'J,~~(!,mJt,d dl;iro:ft<:rE'j\\ ! w",d '.1,:, .11~1!h,t1i"ir t,)
'l~;.d I' t.hr;.}'"l; khkh i;nir.S:6'lhed by th~
~q\ra~-ion;
!-I2Hf;
,Y,:: !~E:;~~J~;i~~;ig~;;;~';:;;:';:~;,::::'
For u~niTE tl?-::;ced ,withou_:-indoor tnm:, the
vt\lue di;H:rrrJ,ined,f~'( Q,').'::c{35) hi;'iow shall. bE:
Ir'!tre';\.sed 'by a quantity ;,i[; hear. ',,:'qual !iO lhe
produCt ,0[12.5_0 Htuh"per'JPOO $CF~t ~he
Jemg-th (!f -time, in hci,u.r:s dunng--Jhe·_.Fro,st Atcumulatit:oti l~\ thfu:,ihen: \-;:en~ jndno~ _;;t,il'
r;;clrc~la,Ul)¥, an~ ,th~ jwerag¢ ,-Hi)'.? nr~ 01' in,'dqilr :I.lr. Clfculated -lD ,lHllts. DfJOO,(? ,ScF)\t
T~e _total" ~iv:.rgy, u~~g¢,J£,'}j;./3f..1, __:Erw-l:l be
the .sum (lthe en-erg:\-' JJ.sag{~ required for in,
door-1dr c.ircula,tion Juring the t€Rpe:riod a-od
the en-e:-gy uSl?d by the :rtlmainin_g !:qu,j?tn8J'!.t
componer-,t'ii, during the tea. period., {.}nits nOi
having 'an ir!a(Jor fatl as P>.'llt ,of the h1{iOel
te~,te-d, shaH s~t the:li:,n~rgy fI.!quire,d irJ'r indCh'}'f
,:,ir d.rcuhHlcn !;\j1l3! to the qU:'lnti'ry give:-1 by
the _orociuct Df 365 \'{~ltts PI:,!" 10.00 SCF!vL ,the
!,ength. of time iii bours dl.l'fUW-- the. FrI)'St A,;*
cumub,xlotl Ti..,::,t that thl~re, -was indoo!,-flit tit·
(;tljating-, ;:Ind dIe" ,l.'\'erarre' no\\' nw~ 61' ;,ndu,")t
(1.ir'ci.r(;ula.ted In: u:n,it;:; 91'.11)00 SC.FM,
wile!'e'
T,i{;} '" '!?r::·9_db,t~'I~'p~1'it\:r~
~i:;Vf ~1)lr,rh(1 11!1'l".(n
or :lit >llw:--(it1g lit~ lTI·
T.'in::: \)r;:;';mlh ""mr.(:r... t;!r~ 9!.air l~:.\'(i::r, ',~~bdw
,~lii;'Fi,~ttim~',I!i_
'
Th!;: cvdk duo:i':ldUUOh coefih:k!1t sJl:ill
he. t.1;eul:lted .15 '(611()\Vs:
_
CD-
Cl)
J
_co p,!~A 47)
·'C'PH\"J,
"7·I
(~e_
1 IiLP
wb,cre
Co::::th,~-¢.,.dkd(';r.,_d:ltil)ll (';Ul.:tliC;'!ilt ~oalta~1
to the
n~ar~$,
.ut
"
CO:'F"r.(fi) as dOOned abo-'?'-~
cCtP,;(,!'i)
,~definl!Q i~¢vl)
Hf.,F is ,:J1'f.> 'hea\.l'Jlg 16ad
ioHows:
i~;;()Jr yilC!liat{1J :lS
Ii LF _ Q,,.(47)
The aduul hen't,ing clone d\lrlng the
Cyelle Te*'t, Q~~44i), s.h"n, be detel:mim;d
usi~g_ the i:()ll'pwj.n~ eql:aHon:
~rbf:r~
f>OXYXCt>,X r
[V,iX(HW,)]
Q~~'c(47)
(1)
Q,,(47)X,
Q-,~<Hi') :IS
defined ~bo';l!
Q,)'H7) 'as defllle<! ab«"e
T",DU:\llkm,;,t l!m" if1:::'.!!~) !¢f'ou-,:w:nplm;
c~·c1~.<.\)'F~j.stjl:Il'f.of ClI.l~ \~,"ir.pr~-\o'S(lt'''pn'' \l!n~
Cm".l?re~Or "ll;!" U<.l,c:
V", tb~
flo,'"
.-hu:ni; Ih~ on<i:led~~o ~,\!c'Jb:~to ;tl
ii~l:crd~:lc~, wi(h ::i!ctititl j"B..3 N' ,1t.::;HR.... E St!\n·
(:.l,t,f"
lilv; O:1e
,sard ~:;:BS ill j:!f!,1.
C~. '" :;~a,"i:'.ific 'I,IM1 ill ·~f)!l5tar.t, )i(,~sS'Gr~ 1)[
m~>:tu:li D(:-'~
jlr·'·;,·J(\e.r
c:lImd (.Ie d('I :~:r .. Wtu(jb·f"
\l.r"'-:-;p~l,'!,Iw. ?-'~II1;n(' M :l:t'\I'~~:;f nllxt'!m M ,r,'l ,,;aJue
d'ty·'bltlo 1f'ntP;:,itllr~: (l\;'''ll~(!jl'.'!' n!\F.l. ~mi
prP.$$U:~ ns.:;-i ;u ttl~ d~'N7i'!m2.(;()ll oi th~ indGor
o.lt ;'],),11' flite \i~J,'jb)'
11'.,:::: Humiil~~y mIlO tib;to).
and
r 'lhr:f'),
,equa~jdn:
w,hich is ,deBcrioed by the
" -,'
lt1:mdndoor'Is!i oil) ,
J
p= ,
. . .IT.,(I)-T,,!tl.jdt
"time l!)d~(.\r f,~,\\ nil),
,
" '
A6.2..1 Cak;)Jation of the heatin.E seasonai
Derfonnance factor fHSP'F'1 for alrsoun:e he,at pumps' with s,l'ngle,spt:tJd
compn:$liors.
for e'l:ch dimste region Hiited i'n §.ection
1\$',2-.4, a.1d for desig:n hf.'k~iing requirenkntS
l~qu~l-to b\)th r.he-':.tanda,rd11.erl minimum and
maxirnum de.sign hea.ting requirements de·
ftned be,iow, ciliculatB the 11.sPF detin,erl <IS;
'HSfF
where'
'I"'IU)"""Dh;~i);m)' !~;:;fl~l:n!.iit1' Qr <'ltr tJIi-Crh!~ d;e ill>
dditr ,;oll,irl !Ii, tlmf r/'i,
T.:H/ ... brr·,()Hlll 1-('m!--'~r~u:(I).' 01' air j~:;\'mg '{he jndilur ~oil r'~~1 i'l\. tim .. 'I ",
"nr
TN' B1'TI
\ 'I'
The Mt, he:Ltbg, Q'OgV (35) in Btu'-s
dum:. (hwlr.lg the te$t pe!'iod sh.all' be deu.\r~
mined ushi~ the follOWing eq.lt..::.tio!:l:
..
. Th~ -rj-:c-lk" ciJefficie..'l~ of oel'fO!:m:l'nc~1
CO p~!I~(·17) (5' n~lr.-uiat:ed. as the r:rr..!o l)( the
Wtal ~f;!lfing done_ {Q~n(41}) in Beu';:! to
tbe prodtu:t.af 3.-413_ Btufw:lt't~hour'J.nd the
toui.energy us:J.g~ (Bo)'~(47)) in watt nours.
The',ne!. heatlng I.:~~pjcity, Q1)~:~·(;35'~ ,Bt.uh" is
the, t{)tal.net heating, done over thr~ test period
(j'nduding any .i!r!!djt, for the indoor fan heat-!
?lvld_ed by the total length ,of :he- t~st period.
lil hours:,
(-/
''
~Thcse
items have: be:::n correw::d in accorrbnce with!! k,l(e!' fl'wr. rhe
De:ptmment of Energy, dared Decl!mb.'~r 7.1930,
23
ARI STANDARD 210/240-2003_,--_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ __
(
Xi
-,}: "" Jl~',;l;.",:;; ~l-) -'1£;,:;';
,
\.
VI
'sb{:'!i'$
:q"qn
;;';f:;;:;~)~c;Jrr!~~:v~~:23~F'~~~~:j~~rd
wi~h
j~"t .
:L
It".,..
C"\:Im-
s1ng1i:!. i!tjtt\,pF.::!!'{J),'!
(
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _'--_ _ _ _,ARJ STANDARD 210/240-2003
(.t~~',~~;; 1T)
"
tU!(
T~')
--r"
iBl~,\ ':t/J ~~(n--~\
r
! +~--..,,--.-". i~i>:;')
.T,::iIJ i
F:-
-£-:;'(17))
X,(T;-~171.
f.i::.~;(11)
I
:t:"-'-~'\ 't;-}? 1.
;1
(z.;-',
~~\62)--
r.B:.,-~on
I
(1.;'(-1.7))
Cr:.'diiiq~')~ ..".8:'>(.'t7·,\)
1
!"'"-, on
i
7>:..\0 F'
U)};;;~,{3.5}-,Q~>o-t{1j;'})
tTi}:""1i
\
X.'tTr-l:'; .
;Ki
;,t..'S;:z."::1 Htc!.:!:.a $e.cs:>;mc,l ,C>itrhrrrm,ru:,: {de.:,(,;
~:3~~;;~~~~H!~~'~~ci) Wf~.Jl tr~pl~·,:J:Zpf!C;ly I:.om_
A,5~~2.A
fi.,\;I!1.i~"',.g
si:c:.:wna,i
per8~r,T.:?:'I'IX"I,I /;:;!cf-c!'~
~;'i~;·i~ ~£t~t!i~;~~_:~~f::~dc~~~~:::.;~;;~_~;
hi\':at;~.\g $eQ'..'l3~,tlCJ ,},'f:r;_~tr:;·,4..!:1ct 1.:ll:t01':
ti; ci;:,-fir~:ed
(,h;)t'F.
hy :.1'ttJ !()llc·..."n;r <:-qu0.tk,n:
HS/-',t;·
25
ARI STANDARD 2101240-2003 _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ __
(
r/~~:.-'t(J7)
1
i"'"
'j"
ll
<,; if'~{
T.3.':~$ r-,D: T..~17 iT
1Q;;-'lH'
i
f
I
r;
i
11
ll'(Tf),%~,~a;
11;
I'
1'0;
r
1'i-:5 'l'br;
(
G'Zl\'}il~; -:r.t..'tJ·<,Ti,::f'1·v~
h;
'rf>l"J!'
<£':'-!':(:! -;);- t::-~ Ct 7J)
i< £ ~!',i'~-17
'I
q.o~-: (~:.1)
(,41;,--'
.1.2.... ·0'7)
fQ, ;
;!:'-I(
Tr~'''''"'::'{l.~;
,". -,
(
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _--'_ _ _ _ _,ARI STANDARD 210/240-2003
AS.:3.2
C:iku!ation· of r;epresental'ive :re~
gion;a] .annual perfonnance',factors
(.A.PF,H) COT-each .region and-lor each
stanqa:rdi,z.ed deS.liJP
heating
f~'
quiremen.t,
(OLlld
(Q •.'(9SF))
+
(AP}, )_
(HLll,)(DE1l1) (C)
' ( C LE,) ( Q..' (goP))
BB7fii--
+(HLH,)(DHR) (C)
ESPl'
1.Q,,)(SSF'11 ;) o~f.n~<:I 111 A~U.
:WHflf il' <i"~i\n<:e in .'\;5.2::t
!c~ h ci ... lin;ct h: A~.:!;:Z.
where.
A5.4
Calcul'a:'ion.s _of Seosan;al 'E11e'rg:/ ,1i'fft"
Ci~,!Cl'}' Rati?/or 1l;"ct!,zr ~ou"cr Uhit,c;
~:I,o hlC!; ProuweBott1. He.cwh£ 'a:nd Cool"
,in..g-,
lR;eservedl
"
Uil.f.Rl r~Qth~~~.~;~~ntdY:1'. h"JilinflIQ.IoC' ho~d for ell:ch
~C'Ki(ln .iI,$ i.lt~..rm,m-ti! ;'/'> ~~lllf1 ,l;iU.• 5,.
A.:5.5 Calculation, {)j'Seating Seasonal P~t'·
!$!f:R ~-l~b:/;'":::~~~;J:3~t ~~ej~n'l'. ,.nie. u dm'f'
/Qrmch'CI)".- Fa,ctor {or.",Wanr SOUl'c-e
!HSPFI \~, tnt' h~"t;nli, ~tat>i).",) p.erl{,r.n~Il~j)" fll,~Ulr H
Units ,Y/hid: ProuideBo-tA Heating an-d
d~t,.r.Tmill1'd ill ~~1~11 ,0\5.2'- (or d~h r:<:gi!1l1'lI.nG
Coolins-. "('Reserved)
(<lr J:,loch ill»nd ... n:li-:.,.ci d.,His:n I;'~.ilti.l)t rI!QIlH:t·
lTI~.11-1 wl~h.~tI t.lli.:h .rt,i."19n.
A5.€ Cab::,u'iatJ.on. 'I,if AnniH:i Pcrform.aM~
Fo.cttJr Far Waler Source Unit.$ Wh'hh
whe,re- the t'l<gions <lore' Hsted "in se.::tio.n AS.2.S ,
IC'LHJ(I l~,:h~ repl'1!"~~ni.!i""_<'Mlj'l1~ l~.Ioe I"Hld ['II" r'A~~
h;""li;l:;-I<.lnd !lQWI"'" r~gJ!ln.,H <i~t~r.11!iM'<l iJrl't'~·
j
and, the. stsnd~rdized' aesign heating requh'e~
m.r:nts, within -the regi_ons are det-ermin>e-d in
sections, .&.5.2, a:no .'"\6.2,6.
Pro-,I;[d~' Bath Beotin.g and Coolinf-.
(Reserved}
.
27
»
.)
:-2
o
(j)
-tJ:i at '~Y-j huLl:.;:d:' (}f h_"i'.n;;k-tOfH'd' In:)urg H1
t, (-:'",pn f,;<, Lure b:1.n,~ :'1'-:(.1 ~_;'f:'; j.jJ1,i~.,.tl ___.fl::~.~"~.~,iI-J~\l,I_~~
-of Uw_ SJ>iHf1 -t{il.~
C-(1rr,tH_>,;,;~.',,"{,;:t .1.hl
f;OmrreH!:10t"
-'i'i'.';'ut OfH~f'~tlH-r;)
~lnd
tJnJ t:R
'"
!2
....'"o
~
fA:d -er:ttneF~ ft:Yr eyc'l! -L' dt',),-"eoi t -tl'i1i'1;:-;g:
pert,; ttln::
ciInqi;:
t
(t:,('j1:~t
t
<"3b_ftt:) f.'v~~d
f~ ,<1n'Ji:)
'ft0dt:
erjnd i t.:L:;n
f'ah-rmlh!:~
~
f;P:);"l\
1
2.
i, S
t~~i 'I:
condit:1.on]
1
7 .'
£'I;.)-cci f.i
fid
"
U
')
. , .. ,
TrH;!O(u: d.:'V-hull) flj f
b:7;ln-o~-ta lute; F\nh ns-tHif 'i-e t
ni1t6rJn~r· •.••..- ...-.•....'
>
~
, ..
2.0
£i
,
It1doot --\1Ht'---IHI.lh -61r
t-,V-r_~p_8e~t\H;g- ( 'f(~b ninlH:'-:i. t;
{':r.'tc~t t'n(l-~ •• ~ ... ~ ..' . -~ ~ • ~ ...-..
t\ft:g:.t~ tHrii lst~ 3"0 SHe Rtt-er
G;.J'!Hjee,jjt~'or·
{{t.1t-tHJ':!.
CfrS L'.:i t imt-e to
i rfc·lh:~_s -W.ci t Ui~ ~
NI:i-Z'Z1-f¢ f}ruin~un;1 dn)~%~ f
NN LO-l]fra '1
{\ t r- ClDH I
p~n'·{;_~i-it of
'"
rretlfUn1;J-•••. ". ~.
2.. ti
EIHctrn:-;al vt'llta:(-[t1 lhput$
tt) tht:: t.t:st uidt~, -petC"ifmt.
-; .:-D
shllll t"I-t. Ii!) t!tjtj~ _-e:.tCVf~d
ti~h\~f$iI."i\t\ln::+ \Jhi~;'h :nt-;¥ultH
th,H: Vi'llue
(')t
h"l;':nj'~-:,,~~
thE ~x:l~·Ltu-jb
lt1 th<] fJ,n"idBL"C.1b-11 (}{ cn-n-l:.ki-\=
fHite hV the- j n<lOOl' cG-} 1 .'.it t:18' dr"I-h,.i Ib Ca!!iDe'ro:.tOH'
"~~Hl,:tt-iitff fo!" thlC' lljr' f):t<ter!i)\';J the ind00t' p6rtJ(}f~ f,r
!'rH! Jnit.
tti
-I II to
,
B!)
.
n,,>
.
6 "_ ..
L(f
J9
H4
f;'i
H9
1'0
,
, 1-.1 ·1
7 'I
.. -~!l'~
:(
..
9() 'co >~H .
'l S 1:0 £rs ,
1
to 1 04
no
I
OJ ;J
!l ?
~n
f! 2
9 ",,
10 -,"
N
o
o
w
i,
~rieqrt:t-!!!
(Vn 'ftl f{j:~ i-on
of a\,'U-l"'H\~fi
d-yy,-blllh aIr
i
F'iih r;i&n,hn i {; :
.•.• "' • , ..- ••
i. U
hd fi
t(l 1+rt',{1 n~;t'.!
-e~·n)H}eya t;ift~.e
r;;~1-t~.d.nt.l·
VeJ>Htu¥'0
b i:1 fOi
Fo:~hr-t~n!lu-i t j
<l
~'jut,th':mt
tbm-
P0fKI{;U(L'
fzh:q ::o<!;s
l\~S t
{.~Fl'tiFl- h t i. rfq
t.(~ 1 ('} t ,H) 1;: ~~
o
»
;0
o
r:nntltt:H:HI
ti\!$';t
~
Z
)'1
61
'... .1l-O,ll"
c
0 -' ;~
.0 )Al
,-(lfJ 'I
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _~_ _ _ARI STANDARD 210/240-2003
'-4
c...1
....; ;,C
G,:...,;
c- m
U
."W
,....
I:: ":'
= ti
~.J ~
''.;..:;
(:
c
C
..,..;~.
,.;1- ....
--.:l,,-:tt"'"'
I
_~-:;.c:
I
I
..,.,. .j?
..w ::;-
I
oeS"i
JJ :0
J
OC:p....,~
>t!: 4.
,,04
C_
,1'\
.
.
I
Ij
~
'!
I \
c
/11'""-/
_ _ _,..Ll
/
.... yl
C.A.
oopr~ /J
l.
/
-~I'!
-"'--------1./
00. t.J<.!
~,p
f
,
"""
I
6.:'
~
:
~
::
~
,~
5t
:. :- ~ ~, :;
-'
o
C
.:g!~~~~:
o
'"
C;O'C:Q:::::':c_
ggg-g~,g
OOi~Nd\b~¢.
J
I t I I I t
\It
:::
,,;,~
."Jr.,";;
C
'!
.::: ~
,__ r::: ?
£';':: g.£
E,:;!'~'~E'Z?
·::uc='':~';5
29
ARI STANDARD 210/240-2003, _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ __
,.W
,~
,1.1.
:
I>
""-,' ,,;;,
.....
~'
."""""'f"
.-"
~' ~~
,#,~,
~
...",.,...:.,-
.1)
""
--
~
'~.'
'"
;
-
'....7"
:::t
~,~
,<:;
~
."",
11'\
~"tl
-
~.
'"
~A
~
'"
"....e' '"~
i~.'~
'C- ....
•
j{~
~
..
Jf ,",
d,:
'i.
t;I>
~
. .,..
,.,.
,,"
,"'_
o
\.
"" ~
....
t -e' -[
'""
~(
..t
J;I
~~
,.J.'
,104
~
,,,,,~"';;
....
~!,
.
....
: ._
'i't
......-:
t~ 'J::
""'
....
<
~
'''!'''
-:
,~
,'<"(
'M
"C
""',
.\1-
~ >~
:ioOl ,..:J
''[~,,:,,
'"
,'0:;;
...
.'<. ' .....
• >
'~
...
w.:.,-:
.... '"
'"~ ""'-.;0 x'
~
(c;
."
"
t<~
""•
;;_.
0;.
I~ ""
.~,
¢
.
....
'''~
,'>
to<
--.
,..
." .;;,•.
~~.
.,....
.;;,'" i;:'* ":
'_.
""' ...
'-1 ... $:
""'"
...
~
-~
';'
~
,0.,'-"'.'
-)1)'
;-
e
""' ,W
,...
.~
}~
,,,",, :t'(..
¥ ,,:':t
(
;;"
'<:,-.:i
i".",",
,
•,t:
~
",,''It
',-' '\>'
"""'i:::
go'!:'•
U
,I
,0
~o
'<~
;;!
.,;.' ~
-.
,.
'0
~
.. ''!
•.
'C .:
~
-.
,1\'
"" '"'"':. iI:
-'0
j:...'" -:>-
..
M
'f! ::
'"
......
,,""
"''''Ir
i!C
-~
fj
_~!-
-~
'5
.. i;
"~ '
,... .,...o
':
:,...
,
~
~z
.~
';&l
>'"
'l>
"-
:!>.
u
,,'"
.-;!>
"...... ,-:;
.~
~ '~
.! .,'"
tz;;::1 t ,..
.. '!
,~,:>- e·e '5_ "~
..
,*
",,'
fr'
-
,,",~,
. • ':(;,.(#
-!O!.~
.t.
-!)
.: ;
'I;)
'M-
... . .
... ;;
,"'~
'~
<r;;
"•
""
'I::
~
>
.. .,•
¢
'..
-...
~,
...
~
,....
-~
.\0<
:>
~
~
;::
'"
~,....(
!:e
-
•
l:;" 'N
-'"
••
k
_..,
'<"" ....
•
""'''':'
~:
~
...
.. <::
,0"'"
-'"
'::-
--.
'0(
;:.
',\-
~ :~
.!. ',"
~
.... t:r .("..,
""
i<t
r::'§,'~
"
-<:::
"
e-:
.-...
;:I
~.
~,
,
"C
..
e... ,.=: , •
).0
~
... ,;C
~
-M;t
•.:> ,""' v
...........;::;
-
...
~
,"
... :£ g
.! ',",
"" ......
(':i
r
"
...." .;;:•
'~.'
o-e "".
0
"· •"
·.
'","
•
'"
;to
(
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _----'_-_ _ _,ARI STANDARD 2101240·2003
i
;;;:;
.....
<
>:
.!"
'0
~ ~
".0
o
"
~
-"
"-
::
<
,,
~ ;:
~
.
'il"';:
,s
~
~-5
'E..E
t
~
•
~
il'_g
t-o,~
-e_
~
"
"
o
Q
u:.&:.
-,u0 g,,,,,,o
~
,"
-
...
o
~
.
~
l
~ oS
~
...
~
..:
, I
I •
..
.
..
.
o
~
~>
.~
g •
.
•" •
•0
•
o
~#
~ u
-.•
•e:::
~
L
.:1;;
u
::.
31
»
.J
J
2:!
AfUL5 ,t\cltwr hnMing lund -hOlH~I~, an~{-r(J tHHLragf-onnfhtJnUnif INHi hour{{
t.fiLHn.1
i'{it'
(f)
-l
lh,! th}!tes Stnk'-l'tl
»
Z
o
»
;0
o
toaQ
'"
o
~
2500
N
2600
""o
N
o
o
w
VI
15(}O
Ala.s!:'lt
I
TS(}
II
1250
1750
2250
tIL
IV
V
2750
VI
27 50
ThtS, trwf} I? ,_~~_a~~lm,H{ at~~mlf~, lV(::H!f~~:_ Vitt.~t p{ !lie IJfl!I~\f<$~-,iJ(i~ '!JUl. 'is" 'if!~(tS~~~,lnfi "hi{li~}1
-, -':~enilra1ut:it--:~J~xJ ·c-rXH-e-qug:lilt{:j'ib-t'.jUf} 'a!:ttif;lt~~ i~ _nm\imHmUtiS:.:t~tJ\l;\lt;i. p;!ftfCnldffr' )(l tlii! flu"cki?"S
Ila~;r::-U ~~lH_i ',..,.
"rex:rJtor.ieh:-
aSCi)
111.11
(I' . nL!!
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _~_ _ _ _ARI STANDARD 210/240-2003
S~andardDesignHeatingRequlr~m~nt.s (Btuh)
A6.2.6
A6.3
ABA
',;;,oop
25,000.
.;' •.50,000
,10,000
30iOO~
60,000
100,000
15,000
35,000
70,000
~10.,
20,000
40,000
80,000
130,000
000
Repre·s.entxtive Cooling Load Hour·s (CLRR) for Each Heating
Load Bours R.agi.on
Region
Cl.RR
EJ..BR
I
240;0
750
n
1800
1250
III
1200
1750
IV
1300
2250
V
400
2750
VI
200
2750
Grcund Water Te~perature Map
IF~ 00<::. ~la!ro'Fl!ord ':u..;t7_7S:'.&pl's
~G~~l-C
-iltll
(Reserved)
ARI STANDARD 210/240-2003 _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ __
APPENDIX D. PRESCRIPTIVE METHODOLOGY
FOR THE CYCLIC TESTING OF DUCTED SYSTEMS
REQUIRED BY C4.1 AND C4.2 - NORMATIVE
For the purpose of unifonnity in the cyclic test requirements
of Appendix C, the following test apparatus and conditions
shall be met:
D 1 The test apparatus is a physical arrangement of
dampers, damper boxes, mixers, themlopiJe and ducts all
properly seaJed and insulated. See Figures D 1 tluough D4
for typical test apparatus. The arrangement and size(s) of
the components may be altered to meet the physical
requirements of the unit to be tested.
D2
Dampers and their boxes shall be located outside of
the ANSI/ASHRAE Standard 37 pressure measurement
locations in the inlet air and. outlet air ducts.
D3
The entire test apparatus shall not have a leakage rate
which exceeds 20 cfm [0.01 m'ls] when a negative pressure
of 1.0 in H20 [0.25 k1'a] is maintained at the 'apparatus exit
air location.
D4
The apparatus shall be insulated to have "U" value
not to exceed 0.04 Btu/(h·ft2 °F) total.
D5
The air mixer and a 40% maximum open area
perforated screen shall be located in the outlet air portion of
the apparatus upstream of the outlet damper. Themixer(s)
shall be as described in Al'iSI/ASHRAE Standard 41.1. The
mixing device shall achieve a maximum temperature spread
of 1.5°F [0.8 0c] across the device. An inlet air mixer is not
required.
(
D7
The dampers shall be capable of being completely
opened or completely closed within a time period not to
exceed 10 seconds for each action. Airflow tluough the
equipment being tested should stop within 3 seconds after
the airflow measuring device is de-energized. The air
pressure difference (6P) at the nozzle shall be witmn 2% of
steady state 61' within 15 seconds from the time the air
measuring device is re~energized.
D8
Test set up, temperature and electrical measureme~t~
must be identical for nc" and "UI! tests in order to obtain
minimum eITor in CD_ Electrical measurements shall be
taken with an integrating type meter per ANSIIASHR..A.E
Standard 37 having an accuracy for all ranges experienced
during the cyclic test.
D9
Prior to taking test data, the unit shall be operated at
least one hour after achieving dry coil conditions. The drain
pan shall be drained and the drain opening plugged. The
drain pan shall be completely dry in order to maximize
repeatability and reproducibility of test results.
(
DJO For coil only units not employing an enclosure, the
coil shall be tested with an enclosure constructed of 1.0 in
[25 rum 1fiberglass ductboard with a density of61b/ftJ [100
kg/m3] or an equivalent llR" value. For units with enclosur~s
or cabinets, no extra insulating or sealing shall be employed.
D6
The temperature difference between inlet air and
outlet air shall be measured by a thennopile. The
thennopile shall be constructed of 24 gauge thermocouple
wire with 16 junctions at each end. At each junction point
the wire insulation shall be stripped for a length of 1.0 in
[25 rum]. The junction of the wires shall have no more than
two bonded turns.
(
ROOM
CONDHIONING
ROOM
APPARATUS
!
'----, IIII IIII EI===::31
~t=-'·r'-'- t: ·'u=, 1=·,· .::;-;=:=L--,::::j _==1=:- EI====::311111!t1111 ~
INDOOR SIDE./ TEST ROOM
....
IoIf.ASURING
INSTRUMENTS :-:
n
MANOMETER
\~
OUTDOOR SIDE
TEST ROOM
,-
-11 ~
~::U~AT'07
AIR
fLOW
MEASURING
APPARATUS
I·
iNSULATED
AIR fLOW M€ASURl~
APPARATUS
. '. .
J
K
i /.:>~ r:HII ._.'i IIII if==;:;b:::::::;::jj
:fl~
I "
-
.
,-,'
-,
t
;-- \
TEMPERATUIl~E.'
~_
t
CONDITIONING
APPARATUS
"t4;;;:....~,.: ; J!
,':
-.' / ... ill [11 1- I I
I'
'--.-[~~~~~~ }~ !'. ""i IIIJ#ID~~
TEMPERATURE MEASUAm rt \
UiSTRUU[HTS ••X-....!
.
MANOMETER
'NSULATION
-11 G
I
--
rt~t~t~?~'T'J
--
f=~~~~l-MIXEir-'
I
!
TEMPERATURE MEASURING
mSTRUMEN1S
r- "
1
1=;:::'::;:11
-
t.MXER
INSULATION
roo.
AIR rr..Gf I.NO
!!mWU.P'( rLGI HE:l'fO) IS OPTtGW. 00"
SPLIT s'(S"l'tHS. (BEl: APPmOtXC4.1)
»
~
~c~~~- ~==========tt==~
ll·=· ., LIQUID
L_
A1'rACwmn'S "lO mIT
'I111U'I':AAttflU!: HEASURE1i1'liT fOR Wit HInt
AIR I!NTUA1.P,( ~ ala!> NiO
LICtJIO rt.CM liETER fOR RURIGDAHl'
--- r-
(fJ
-l
FLOW
r- METER
»z
o
»
;u
o
'"
o
.
~
N
o
~
Figure D1. Tunnel Air Enthalpy Test Method Arrangement
o
o
w
',-.'
'-
'"
.'
';i,
"".,,,
~OOM
5i
CONDITIONING
APPARATUS
en
~
z
o
INDOOR SIDE
TEST ROOM
I
MANOMETER
AIR
WINDOW DOOR
'--..,:
/'
/ ..... \
(
I
I
!!
r. : ! I I
1:
II
::'-11
1
III
)'. )..
~
jr---.::,
~
I
,
I !
\
111- }
.
-
(
lWIPER
l
1...
::: -" ! I
~:, 'II
C- 7C -"1'-1I II
_/L-
L--~EMP£RATURE
MEASURING
INSTRUMENTS
INSULATION
TC GRID
ROOM CONDITIONING
APPARATUS
.
--
-
OUTDOOR SIDE
TEST
ROOM
--
TCG71
~!,
. I
,
I
I
'NSULATlON~
.'
TEST UNIT
rf'
~
-
-~t==:.i=
~-
~----=il
~
---"
.
MANOMETER
TEMPERATURE
iNSTRUMENTS
,,~
'l"rl'1$?'!:M'\lItI.:
'to WIT f'Ol "IP. rt.CIf »0
~ rat USt Wlnt
"u mnw..n
~
stos
.
,
NI)
LlQUlD rt.CIf Htrta f'a\ RUltlot:AA.HT
nmW\LPY rLCtf I'It'llDl 15 OPT100P0L (loI
SPLIT 8'tS'l'tltS. (sn M'HmIX C4.1 )
~IOUID
MEASURING
INSTRUMENTS
o
o
w
r- MEASURING
.'
,~~
o
N
TEMPERATURE
} - - MEASURING
INSTRUMENTS
IL-J
-
.P-
--
f
~
~
f
FLOW
MEASURING
APPARATuS
MlXER ____
'"
o
N
1111111111-=
AIR
MlXER1
=
llAMPER~
.'. .
lliSUlAT17'\
II ~J
I
\
,-
r- 1\
INSULATED
FlOW MEASUt=:L
APPARATUS
-
o
f
t
'-----,
»
;0
~
_L::F
Figure D2. Loop Air Enthalpy Test Method Arrangement
FLOW
METER
....
ROOM
CONDiTiONING
APPARAT.US
t ' .
r
1111111I1 EI=====~I
./-\
t
r.========'
r-
'--.:...,::::=t'
INSULATED
AIR FLOW MEA5~~
" '\ W1NO",~
OOOR P I
:!
I
\ ',-C '; .\J ,--.,i·~q' ._}i
\
I .,.
:'i, -:'- ""'-~
/"."
-__
"1'-.
'I'
r---'t
h
:
..,
I I"
I 1'::============:;-,
'I I
I, II
~~
f---INSUlATION
..
-:~.::-:..
rZ>: DAMPER
=:::=;-, ______~
~
="l======·. •.=
,
~======l"~~d-:'"rFE="ob,I =:hldl
-
INDOOR SIDE
TEST ROOM
..
fiT===e===~A~P;PA~R~A;,:T="U~Si==;f;=ll
,"
.
.
'.
TE"'P£RATuRE
TC
MEASURING
INSTRUMENTS
'.
GRID"
"'X1,,)(."O:)(:1
I =~~!!I!l:J11 -MIXER
,F
...-: ":'.:
TEMPERATURE
r--MEASURING
, ,_; , . ,.INSTRUMENTS
..
ltJ
A1"l'AOHI:H'rS. "ro llUT rat LIOJID rLCJf
Ht"n;R f'C:M NnIGlDWn' J:H:n\I\LIY rt.CW
HImm IS OPTIaw:. Q\I ·4fLIT SY8"lI!:HS.
(am ~IX·C4.-1 I
INSULATED
--
ENCLOSURE -c-
»
..
2:!
INSULATION.
,
(j)
-l
»
z
CJ
»
;u
CJ
N
~
o
N
....
o
N
Figure 03. CalorimeterAir Ehthalpy Test Method Arrangement
o
o
w
»
,,: ;
ROOM
AIR flOW .... EASURING
en
APPARATlIS
APf'AAATUS
AWARATUS
2:!
ROOM CONOITIONING
CONDITIONING
~
z
o
»
;U
o
N
~
o
...
N
o
N
o
o
w
1t---11""'l ATiON
--
--
"j,'" ,
DAMPER
INSULATION
~:;;~;:;:;~~UG~F:'::;';:~;'~M:'E~A~S'UR'HG
INSTRuMENTS
':.:0
,
I
MeASURING INSTRUMENTS
-
TEMPERATuRE
MEASURING
INSTRUMENTS
TEST
UNIT
DAMPER
Figure D4. Roo':nAir Enthalpy Test Method Arrangement
A~
'to WIT P'OII. AIR
rt.(Jf I!9)
'tF.IIPaAWRE ~ fOR ~E WI'm
AIR. ENlllALPY 1'$ll~ alOE NIO
LIQ,JIO f't...GI' KETf::R FOR REnUGD'WlI'
Dn1W.P:t' rLGf I'I£'tlIOO IS 0Pl'1cw.t. 00
SPLIT SYSTWS. (SEE At>Pf.N)IXC4.1)
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _-'-_ _ _ _ ARI STANDARD21 0/240-2003
APPENDIX E. EXAMPLE OF CALCULATING
INTEGRATED PART-LOAD VALUES (IPLV) - NORMATIVE
El
Pwpose and Scope.
E3
Calculation Example for a Four Capacity Step
System.
E1.l
Purpose. This appendix shows example
calculations for detennining Integrated Part-Load
Values (IPLV).
E3.1
Assume equipment has four capacity steps as
follows:
E1.2
Scope. This appendix is for equipment
covered by this standard.
E2
I
2
3
4
General Equation and Definitions of Terms.
IPLV = (PLF, _PLF, ) (EER': EER, )
E3.2
100% (full load)
75% of full load
50% of full load
25% of full load
Obtain part-load factors from Figure EI.
EI
E3.3 . Obtain EER at each capacity step per 6.2 of
this standard.
+ (PLF, _ PLF) (EER'; EERl )
E3.4
with:
+ ........... .
Calculate IPLV using the general equation
n
+ (PLF" )(EER" )
where:
=4
PLF, = 1.0
PLF, = 0.9
PLF) = 0.4
PLF4 = 0.1
EER, = 8.9
EER,
7.7
EER)
7.1
EERt
5.0
Enter the above values in Equation E I:
PLF
Part-load
factor
determined' from Figure
EI
n
Total number of capacity
steps
Subscript I
100% capacity and EER
at part- load Rating
Conditions
+ (OA-O.I)
C
I
;5.0)
+ 0.1 x 5.0
SUbscript 2,3, etc. =
Specific capacity and
EER at part-load steps
per 6,2 of this standard
(0.1 x 8.3) + (0.5 x 7.4)
+ (0.3 x 6.0) + 0.5
0.83 + 3.70 + 1.80 + 0,5
IPLV
6.8 Btu/(Wh)
To further illustrate the calculation process,
see the example in Table EI.
39
ARI STANDARD 210/240-2003, _ _ _- - - - -_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ __
/
\
I
..
1.0
..,.
.e'
r--
,;'
0, 9
I
0,a
I
I
il
0,7
0,6
j
T
0,;
I
.
0.4
I
.
I
0,3
I
)
0,<
i
I
/
0.1
o
-'"
i/
(
I
V
.
o
60
so
PERCENT CIF FULL-LOAD CAPACITY AT
PART-LOAD GC.NDlTlClNS
Note:
The curve is b.nsed on fDH-Owjng equation:
PLF - AO + (AI x 0) +(A2 x 0')+ (A3 X 0') +(A4 X ct) + (AS X 0') +(A6x Q')
where: PLF - Part-Load Factor
Q ""Percenl of full-load capacity at part-load rating
conditions,
-0.12773917 x 10-'
x 10-'
A2 = 0.50671449 x 10 -,
A3 - -0,25966636 x 10-'
A4 0.69875354 x 10-'
AS
-O,7{)859712 x 10-'
A6 0.28918272 x 10 - ",
AO
~
Al - -0,17648713·
£
(
Figure E1. Part -Load Factor Example
40
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _--'--_ _ _ _ ARI STANDARD210/240-2003
I-P Units
Using infonnation from E3:
Table E1. Example IPLV Calculation
PLF 3
Step
% Full
Load
Cap.'
1
100%
1.0
Capacity
2
3
4
75%
50%
25%
0%
0.9
0.4
0.1
0.0
Mfi·s.
PartLoad
EER
8.9
Avg.
PartLoad
EER
2
=
8.3
=
7.4
=
6.0
=
5.0 [
PLF Diff.
(1.0 - 0.9) =
0.1
7.7
7.1
5.0
Avg. EER x
PLF Diff. =
Weighted
Avg.
8J xO.l
=
0.83
7.4 x 0.5
=
3.70
6.0 x 0.3
=
L80
=
0.50
(0.9 - 0.4)
0.5
=
(0.4 - 0.1)
OJ
=
5.0[xO.l
=
Single number
IPLV
-~---
(0.1 - 0.0)
0.1
6.83
4
Notes:
[ For the range between 0% capacity and the last capacity step, use EER of the last capacity step for the
average EER.
2 The 100% capacity and EER are to be determined at the part-load Rating Conditions.
J Part-load factor from Figure El.
4 Rounded to 6.8 Btu/(W·h).
41
(
(
(,
Download