MTS9000A 2.0m Integrated Cabinet

advertisement
MTS9000A 2.0m Integrated Cabinet
Introduction
Huawei MTS9000A is a new generation telecom energy
solution which realizes site power to be a network element
to ensure maximum site level cost saving, easy O&M and
seamless evolution in future.
MTS9000A integrated cabinet is especially designed for
outdoor site with power, telecom equipment and battery in
one cabinet. The cabinet is designed with sandwich panel,
European standard lock, multiple anti-theft components and
plentiful optional thermal control devices for equipment
compartment and battery compartment to provide safe and
suitable working environment.
MTS9000A 2.0m integrated cabinet could provide inner
equipment room 22U, battery room for 2 group of 12V
100Ah/150Ah/190Ah.
Features
 High reliability cooling devices with -48V DC input
 High heat isolation performance lead to OPEX saving
 Super anti-theft, European standard lock and enhanced fence
 Fast deployment, assembled in 30 minutes
 Compact figure, easy land acquisition
Application Scenarios
 Outdoor site
 Power cabinet
 Transmission cabinet
 Data communication cabinet
Specification
Cabinet
Cooling
Dimension
(includes door and
plinth)
815mm (W)×900mm (D)×2030mm (H)
Base station
815 mm (H) × 735 mm (D) ×150 mm (H)
Cooling mode
Equipment and battery separate cooling
Maintenance
Front operation & maintenance
Weight
<200kg
Panel material
Sandwich panel
Security lock
European standard
Protection level
IP55 (direct ventilation battery cabinet : IP44)
Equipment cooling
Heat exchanger
Heat exchanger
DV①
Intelligent heat exchanger
Input voltage
-48V
-48V
-48V
-48V & 220V
Cooling capacity
80W/K
150W/K
250W/K
1500W
Battery cooling
TEC
DV
TEC
DV
TEC
A/C②
Ditto
Input voltage
-48V
-48V
-48V
-48V
-48V
-48V
Ditto
Cooling capacity
200W
300W
200W
300W
200W
500W
Ditto
Heating power
400W
---
400W
---
400W
---
---
Heating capacity
>400W
---
>400W
---
>400W
---
---
Heating box
(optional)
500W
Operating
temperature
-40℃~+45℃ (heat exchanger / TEC)
-40℃~+55℃ (A/C / intelligent heat exchanger)
-10℃~+45℃ (DV)
Storage &
temperature
-40℃~+70℃
Operation humidity
5%~100% (DV: 5%~95%)
Lighting
-48V LED
Sensors (optional)
Smoke, water, door switch, temperature & humidity, etc
Environment
monitor
Cable distribution
unit
EMUA ③ (optional)
Voltage
12V
Capacity
100Ah / 150Ah / 190Ah (2 groups)
Environment
Others
Battery
(optional)
①DV:
③To
DDF/ODF (optional)
②A/C: air conditioner
direct ventilation
monitor site environment, EMUA should be configured if not choose Huawei power system.