true front access

advertisement
12-1029
DCS
UPS
TRUE
FRONT
ACCESS
HIGH RATE MAX
UPS
UPS
UPS
UPS
12-410 MRXF
12-615 MRXF
12-700 MRXF
12-1000 MRXF
Valve Regulated Lead Acid
A
(VRLA) Battery Series
Design For UPS Standby Power Applications
FEATURES & BENEFITS
APPLICATIONS
z
Data Centers
z
Network Operations Centers
z
Industrial Process Control Facilities
z
z
12 years design life @ 20oC
Eurobat Classifiication: Long Life
True Front Acce
ess threaded copper alloy
inserts, for reduce
ed maintenance and
increased safety
z
z
z
z
Internet Housing Sites
z
Semiconductor Manufacturing
z
Banks & Financial Markets
z
P
Power
G
Generation
ti Plants
Pl t
Terminal versatility - ease of diagnostic
readings
di
with
ith C&D
D Ohmic
Oh i Ri
Ring®
®
z
z
Hospitals & Testing Laboratories
z
Emergency 911 Response Centers
z
z
z
Innovative front terminal design maximizing
energy density with direct connect extrusion
fusion weld technology
z
Reduced heads
space driving higher energy
density, in cabinet or rack applications
z
Absorbent Glass Mat (AGM)
technology for efficient gas
recombination of over 99%
Flame-arresting, one-way
pressure-relief vent for safety
and long life
Complies with UL 1778,924,1989
and 94 V-0. BS6290-4, IEC-896-2
UL-recognized component
Multicell design for ease of
installation and maintenance
z
z
Removable han
ndles for ease of installation
Thermally welde
ed case-to-cover bond to
ensure a leak-pro
oof seal
z
z
Flame-retardantt polypropylene case and
cover compliant with
w
UL94 V-0 with an
Oxygen Limiting Index of greater than 28
z
Not restricted for air transport Complies with IATA/ICAO Special
Provision A67
Not restricted for surface transport –
Classified as non-hazardous material
as related to DOT-CFR Title 49 parts
171-189
3 Year Full Warranty (refer to
warranty card, 41-9027)
z
z
Not restricted for water transport –
Classified as non-hazardous material
IMDG Amendment 27
TECHNICAL DATA
Model
Voltage
UPS 12-410 MRXF
UPS 12-615 MRXF
UPS 12-700 MRXF
UPS 12-1000MRXF
12
12
12
12
AH
20 hr*
109
172
201
254
*True 20 hr rate to 1.75 VPC in Ampere-hours
5
701.1
1027.1
1117.8
1520.0
wer Discharge Ratings - Watts Per Cell @ 77oF (25oC)
Constant Pow
Operrating Time (in minutes) to 1.67 Volts per Cell
10
15
20
30
40
50
60
514.6
410.0
0
339.5
256.0
203.1
169.8
146.6
771.8
615.0
0
513.8
392.5
318.8
271.3
237.8
866.0
700.0
0
583.0
453.0
368.1
313.3
274.7
823.7
616.2
491.2
412.0
356.9
1210.0
1000. 0
90
105.1
171.5
199.3
256.7
INTRODUCING A UPS FRONT ACCES
SS BATTERY WITH TRUE FRONT
ACCESS TERMINALS
z
Direct welded front facing terminals
- Uses proven Extrusion Fusion welding processs for high reliability
- Provides most efficient current path for excelle
ent high rate performance
- No bolted on “L” brackets which try to make a top
t terminals battery into a front
terminal
i lb
battery
- One less bolted connection that requires
maintenance, builds up resistance, and can
lead to poor string performance
z
Designed as a UPS battery from the
ground up to efficiently handle high rate
discharges
- Not a converted telecom front access battery
z
Raised Terminals for ease of maintenance
and access to C&D Ohmic Ring®
C&D Ohmic Ring®
C&D Ohmic Ring®
z
Large surface area for direct access to
s
terminals for accurate ohmic measurements
C&D Ohmic Ring®
- No more taking readings from bus bars or
hardware which can lead to substantial errors
z
Provides consistent and accurate
measuring location
- No guessing to what point was the base line
reading taken from
z
z
Ideally sized for use with standard
monitor
i
probes
b on fully
f ll installed
i
ll d systems
The Ohmic Ring design is the only terminal
configuration in which micro-ohm connection
resistances can be taken as required by
standard maintenance programs.
Probe
The True Front Access UPS Battery - The Better UPS Battery Solution
Eliminate hard to service top terminal batteries with
w a full front access solution
Higher watts per cell allows a reduction of a paralllel string for most common UPS configurations,
providing a reduced footprint solution
z
Maintenance is significantly easier and safer with
h all required service points front accessible reducing both time and cost of periodic servicing
g
z
As a 12V battery design, the UPS12-410 MRXF, UP
PS12-615 MRXF , UPS12-700 MRXF and UPS12-1000
MRXF easily
il integrate
i t
t with
ith existing
i ti battery
b tt
monitori
it ing
i equipment.
i
t
z
z
SPECIFICATIONS
Operating Temperature Range
with temperature compensation
0oF (-40oC) to +160oF (71oC)
Discharge: -40
Charge: -10oF (-23oC) to +140oF (60oC)
Nominal Operating Temperature Range
t +80oF (27oC)
+74oF (23oC) to
Recommended Maximum Charging
g g
Current Limit
C/5 amperes @ 20hr rate
V
average per 12V unit @ 77°F (25°C)
13.5 to 13.8 VDC
dation:13.65V per unit)
(Recommend
0.5% RMS or 1.5% P-P of float charge voltage recommended for best results.
Max voltage allowed = 1.4% RMS (4% P-P) Max current allowed = C/20
Float Charging Voltage
Maximum AC Ripple (Charger)
Self Discharge
Battery can be
e stored up to 6 months at 77°F (25°C) before a freshening
charge is requ
uired. Batteries stored at temperatures greater than 77°F (25°C)
will require rec
charge sooner than batteries stored at lower temperatures.
See C&D broc
chure 41-7272, Self-Discharge and I nventory Control for details.
Terminal: Inserted - Inter-unit
connector provided
per alloy insert terminal to accept:
Threaded copp
M6 bolt (UPS 12-410 MRXF)
M8 bolt (UPS 12-615 MRXF, UPS 12-700 MRXF, UPS 12-1000 MRXF)
Terminal Hardware
Initial Torque
107 in.-lbs ( 12
2 N-m) for UPS 12-410 MRXF
160 in.-lbs. ( 18
1 N-m) for UPS 12-615 MRXF, UPS 12-700 MRXF, UPS 12-1000 MRXF
Am pere Hours
Am pere Hours
Voltage Capacity 20 Hour Rate C
Capacity 10 Hour Rate
Per Unit
@ 68°F (20°C) to
@ 77°F (25°C) to
1.80EPV per cell
1.75EPV per cell
Battery
Model
UPS 12-410 MRXF
UPS 12-615 MRXF
UPS 12-700 MRXF
UPS 12-1000 MRXF
12V
12V
12V
12V
Battery
Model
UPS
UPS
UPS
UPS
12-410 MRXF
12-615 MRXF
12-700 MRXF
12-1000 MRXF
109
172
201
254
100
160
185
234
Hioki
Impedance
(mOhms)
Midttronics
Cond. (Mhos)
2 37
2.37
1.91
1.84
1.47
2000
2500
2700
3700
IEC Short
Circuit
Current (A)
IEC
Resistance
(m Ohm s)
Weight
( kg)
2860
3700
4400
5540
4.4
3.4
2.8
2.3
37.1
55.2
64.9
85.2
Maximum
Short Circuit
Terminal
Current
Discharge Current
(AMPS @0.1 sec)
Rating (AMPS)
4900
800
6500
800
7900
800
10100
1000
* Per IEEE 1188-2005, Internal ohmic values are useful as a trending tool. To use these readings effectively, accurate
baseline readings should be taken after about six months of battery operation. Internal ohmic readings taken without
the benefit of baseline data may be difficult to interpret and
d of limited value. Values are provided are for reference only.
Dimensions
Top
View
Front
View
Side
View
A
UPS
UPS
UPS
UPS
Model
12-410 MRXF
12-615 MRXF
12-700MRXF
12-1000MRXF
in
18.6
20.3
20.3
20.3
mm
473.1
516.9
516.9
516.9
B
in
20.1
22.0
22.0
22.0
mm
510.5
558.5
558.5
558.5
C
in
19.6
21.5
21.5
21.5
mm
498.3
546.5
546.5
546.5
D
in
18
8.5
20
0.2
20
0.2
20
0.2
mm
469.5
512.2
512.2
512.2
E
in
8.5
10.6
12.2
12.2
mm
215.2
268.9
310.8
310.8
F
in
9.1
11.0
12.7
12.7
G
mm
231.4
278.7
322.1
322.1
in
4.3
4.9
4.9
6.1
mm
109.0
125.0
125.0
154.3
H
in
4.3
4.9
4.9
6.0
mm
108.0
123.4
123.4
152.7
*All dimensions in inches and (millimeters). All dimensions are for reference only.
o
Contact a C&D Representative for complete dimensions information.
Detail of Terminal
UPS 12
12-410
410 MRXF
UPS 12-6
615 MRXF
UPS 12-7
700 MRXF
UPS 12-1000 MRXF
UPS 12- 410 MRXF
Constant Power Discharge Ratin
ngs - Watts Per Cell @ 77oF (25oC)
Operating Time to End Point
P
Voltage ( in minutes)
End Point
Volts/CeIl
1.75
1.70
1 67
1.67
1.65
5
10
15
20
30
40
45
50
60
90
660.1
690.8
701 1
701.1
709.7
484.4
507.0
514 6
514.6
520.8
386.0
404.0
410 0
410.0
415.0
321.2
334.4
339 5
339.5
344.1
244.0
2
2
252.0
2 0
256
256.0
2
260.0
195.3
200.5
203 1
203.1
205.7
178.3
182.6
184 8
184.8
186.9
164.3
167.9
169 8
169.8
171.6
142.7
145.3
146 6
146.6
147.9
102.4
104.2
105 1
105.1
106.0
Constant Current Discharge Ratings
R
- Amperes @ 77oF (25oC)
Operating Time to End
d Point Voltage ( in hours)
End Point
Volts/CeIl
1 85
1.85
1.80
1.75
1
2
3
5
8
10
12
20
24
72
67
71
73
38 4
38.4
40.5
41.5
27 7
27.7
29.2
29.8
18 5
18.5
19.4
19.8
12.0
12
0
12.6
12.8
97
9.7
10.2
10.4
82
8.2
8.6
8.8
5 07
5.07
5.34
5.46
4 28
4.28
4.50
4.61
1 50
1.50
1.58
1.61
UPS 12- 615 MRXF
Constant Power Discharge Ratings - Watts Per Cell @ 77oF (25oC)
Operating Time to End Point Voltage ( in minutes)
End Point
Volts/CeIl
1.75
1.70
1.67
1.65
5
10
15
20
30
40
45
50
60
90
973.6
1010.4
1027.1
1035.4
731.7
759.3
771.8
778.1
583.0
605.0
615.0
620.0
494.2
508.0
513.8
516.8
386.0
3
3
391.0
3
392.5
3
393.5
313.6
317.4
318.8
319.5
288.0
291.4
292.8
293.4
266.9
269.9
271.3
271.8
234.0
236.5
237.8
238.2
169.0
170.7
171.5
172.0
Constant Current Discharge Ratings
R
- Amperes @ 77oF (25oC)
Operating Time to End
d Point Voltage ( in hours)
End Point
Volts/CeIl
1.85
1 80
1.80
1.75
1
2
3
5
8
10
12
20
24
72
109
118
120
61.8
65 8
65.8
67.0
44.0
46 7
46.7
47.5
28.7
30 4
30.4
30.9
19.0
20 1
20.1
20.3
15.5
16 3
16.3
16.5
13.1
13 8
13.8
13.9
8.10
8 47
8.47
8.61
6.81
7 12
7.12
7.26
2.38
2 49
2.49
2.54
Note: Batteries to be mounted with 0.5 in. (1.25 cm) spacing minimum and free
e air ventilation. Specifications subject to change without notification.
Above ratings do not include interunit connector voltage drops.
UPS 12-700 MRXF
Constant Power Discharge Ratin
ngs - Watts Per Cell @ 77oF (25oC)
Operating Time to End Point Voltage ( in minutes)
End Point
Volts/CeIl
1.75
1.70
1.67
1.65
5
10
15
20
30
40
45
50
60
90
1020.6
1083.8
1117.8
1134.0
780.0
839.6
866.0
878.5
630.0
669.0
700.0
703.0
544.1
570.2
583.0
590.1
437.0
4
4
449.0
4
453.0
4
457.0
358.7
365.5
368.1
370.3
330.8
336.0
338.1
339.7
307.7
311.6
313.3
314.5
271.5
273.5
274.7
275.2
196.5
198.6
199.3
199.7
Constant Current Discharge Ratings
R
- Amperes @ 77oF (25oC)
Operating Time to End
d Point Voltage ( in hours)
End Point
Volts/CeIl
1.85
1.80
1.75
1
2
3
5
8
10
12
20
24
72
121
130
134
71.4
75.1
76.6
51.1
53.9
54.6
33.5
35.2
35.7
22.1
23.2
23.6
18.0
18.8
19.2
15.2
15.9
16.2
9.48
9.88
10.07
8.01
8.34
8.51
2.80
2.92
2.98
UPS 12-1000
12 1000 MRXF
Constant Power Discharge Ratin
ngs - Watts Per Cell @ 77oF (25oC)
Operating Time to End Point Voltage ( in minutes)
End Point
Volts/CeIl
1.75
1.70
1.67
1 65
1.65
5
10
15
20
30
40
45
50
60
90
1379.8
1469.0
1520.0
1541 9
1541.9
1098.4
1169.4
1210.0
1227 5
1227.5
907.8
966.4
1000.0
1014 4
1014.4
763.7
801.7
823.7
834 1
834.1
589.7
5
6
606.1
6
616.2
6 3
622
622.3
472.2
484.4
491.2
495 5
495.5
431.2
442.0
447.7
451 4
451.4
397.5
407.1
412.0
415 2
415.2
345.3
353.2
356.9
359 4
359.4
250.1
254.7
256.7
257 9
257.9
Constant Current Discharge Ratings
R
- Amperes @ 77oF (25oC)
Operating Time to End
d Point Voltage ( in hours)
End Point
Volts/CeIl
1.85
1 80
1.80
1.75
1
2
3
5
8
10
12
20
24
72
168
181
188
96.1
102.0
102
0
104.1
67.9
71 3
71.3
72.1
43.2
45 0
45.0
45.4
28.1
29 3
29.3
29.7
22.9
23 9
23.9
24.3
19.4
20 2
20.2
20.6
12.05
12 50
12.50
12.70
10.18
10 60
10.60
10.70
3.56
3 71
3.71
3.75
Note: Batteries to be mounted with 0.5 in. (1.25 cm) spacing minimum and free air ven
ntilation. Specifications subject to change without notification.
Above ratings do not include interunit connector voltage drops.
Shanghai C&D Battery Co., Ltd.
No.55 Liandu Road, Spark Development Zone,
Shanghai P.R.C
Service Hotline:86 - 400 - 678 - 3721
www.cdtechno.com.cn & www.cdtechno.com
Any data, descriptio
ons or specifications presented herein are subject to revision by C&D Technologies, Inc. without
notice. While such information is believed to be accurate as indicated herein, C&D Technologies, Inc. makes no
warranty and hereb
by disclaims all warranties, express or implied, with regard to the accuracy or completeness of
such information. Further, because the product(s) featured herein may be used under conditions beyond its control,
C&D Technologies
Technologies, Inc.
Inc hereby disclaims all warranties
warranties, either express or implied
implied, concerning the fitness or
suitability of such prroduct(s) for any particular use or in any specific application or arising from any course of dealing
or usage of trade. The
T user is solely responsible for determining the suitability of the product(s) featured herein for
user’s intended purpose and in user’s specific application.
0212-MRXF-E