12-1029 DCS UPS TRUE FRONT ACCESS HIGH RATE MAX UPS UPS UPS UPS 12-410 MRXF 12-615 MRXF 12-700 MRXF 12-1000 MRXF Valve Regulated Lead Acid A (VRLA) Battery Series Design For UPS Standby Power Applications FEATURES & BENEFITS APPLICATIONS z Data Centers z Network Operations Centers z Industrial Process Control Facilities z z 12 years design life @ 20oC Eurobat Classifiication: Long Life True Front Acce ess threaded copper alloy inserts, for reduce ed maintenance and increased safety z z z z Internet Housing Sites z Semiconductor Manufacturing z Banks & Financial Markets z P Power G Generation ti Plants Pl t Terminal versatility - ease of diagnostic readings di with ith C&D D Ohmic Oh i Ri Ring® ® z z Hospitals & Testing Laboratories z Emergency 911 Response Centers z z z Innovative front terminal design maximizing energy density with direct connect extrusion fusion weld technology z Reduced heads space driving higher energy density, in cabinet or rack applications z Absorbent Glass Mat (AGM) technology for efficient gas recombination of over 99% Flame-arresting, one-way pressure-relief vent for safety and long life Complies with UL 1778,924,1989 and 94 V-0. BS6290-4, IEC-896-2 UL-recognized component Multicell design for ease of installation and maintenance z z Removable han ndles for ease of installation Thermally welde ed case-to-cover bond to ensure a leak-pro oof seal z z Flame-retardantt polypropylene case and cover compliant with w UL94 V-0 with an Oxygen Limiting Index of greater than 28 z Not restricted for air transport Complies with IATA/ICAO Special Provision A67 Not restricted for surface transport – Classified as non-hazardous material as related to DOT-CFR Title 49 parts 171-189 3 Year Full Warranty (refer to warranty card, 41-9027) z z Not restricted for water transport – Classified as non-hazardous material IMDG Amendment 27 TECHNICAL DATA Model Voltage UPS 12-410 MRXF UPS 12-615 MRXF UPS 12-700 MRXF UPS 12-1000MRXF 12 12 12 12 AH 20 hr* 109 172 201 254 *True 20 hr rate to 1.75 VPC in Ampere-hours 5 701.1 1027.1 1117.8 1520.0 wer Discharge Ratings - Watts Per Cell @ 77oF (25oC) Constant Pow Operrating Time (in minutes) to 1.67 Volts per Cell 10 15 20 30 40 50 60 514.6 410.0 0 339.5 256.0 203.1 169.8 146.6 771.8 615.0 0 513.8 392.5 318.8 271.3 237.8 866.0 700.0 0 583.0 453.0 368.1 313.3 274.7 823.7 616.2 491.2 412.0 356.9 1210.0 1000. 0 90 105.1 171.5 199.3 256.7 INTRODUCING A UPS FRONT ACCES SS BATTERY WITH TRUE FRONT ACCESS TERMINALS z Direct welded front facing terminals - Uses proven Extrusion Fusion welding processs for high reliability - Provides most efficient current path for excelle ent high rate performance - No bolted on “L” brackets which try to make a top t terminals battery into a front terminal i lb battery - One less bolted connection that requires maintenance, builds up resistance, and can lead to poor string performance z Designed as a UPS battery from the ground up to efficiently handle high rate discharges - Not a converted telecom front access battery z Raised Terminals for ease of maintenance and access to C&D Ohmic Ring® C&D Ohmic Ring® C&D Ohmic Ring® z Large surface area for direct access to s terminals for accurate ohmic measurements C&D Ohmic Ring® - No more taking readings from bus bars or hardware which can lead to substantial errors z Provides consistent and accurate measuring location - No guessing to what point was the base line reading taken from z z Ideally sized for use with standard monitor i probes b on fully f ll installed i ll d systems The Ohmic Ring design is the only terminal configuration in which micro-ohm connection resistances can be taken as required by standard maintenance programs. Probe The True Front Access UPS Battery - The Better UPS Battery Solution Eliminate hard to service top terminal batteries with w a full front access solution Higher watts per cell allows a reduction of a paralllel string for most common UPS configurations, providing a reduced footprint solution z Maintenance is significantly easier and safer with h all required service points front accessible reducing both time and cost of periodic servicing g z As a 12V battery design, the UPS12-410 MRXF, UP PS12-615 MRXF , UPS12-700 MRXF and UPS12-1000 MRXF easily il integrate i t t with ith existing i ti battery b tt monitori it ing i equipment. i t z z SPECIFICATIONS Operating Temperature Range with temperature compensation 0oF (-40oC) to +160oF (71oC) Discharge: -40 Charge: -10oF (-23oC) to +140oF (60oC) Nominal Operating Temperature Range t +80oF (27oC) +74oF (23oC) to Recommended Maximum Charging g g Current Limit C/5 amperes @ 20hr rate V average per 12V unit @ 77°F (25°C) 13.5 to 13.8 VDC dation:13.65V per unit) (Recommend 0.5% RMS or 1.5% P-P of float charge voltage recommended for best results. Max voltage allowed = 1.4% RMS (4% P-P) Max current allowed = C/20 Float Charging Voltage Maximum AC Ripple (Charger) Self Discharge Battery can be e stored up to 6 months at 77°F (25°C) before a freshening charge is requ uired. Batteries stored at temperatures greater than 77°F (25°C) will require rec charge sooner than batteries stored at lower temperatures. See C&D broc chure 41-7272, Self-Discharge and I nventory Control for details. Terminal: Inserted - Inter-unit connector provided per alloy insert terminal to accept: Threaded copp M6 bolt (UPS 12-410 MRXF) M8 bolt (UPS 12-615 MRXF, UPS 12-700 MRXF, UPS 12-1000 MRXF) Terminal Hardware Initial Torque 107 in.-lbs ( 12 2 N-m) for UPS 12-410 MRXF 160 in.-lbs. ( 18 1 N-m) for UPS 12-615 MRXF, UPS 12-700 MRXF, UPS 12-1000 MRXF Am pere Hours Am pere Hours Voltage Capacity 20 Hour Rate C Capacity 10 Hour Rate Per Unit @ 68°F (20°C) to @ 77°F (25°C) to 1.80EPV per cell 1.75EPV per cell Battery Model UPS 12-410 MRXF UPS 12-615 MRXF UPS 12-700 MRXF UPS 12-1000 MRXF 12V 12V 12V 12V Battery Model UPS UPS UPS UPS 12-410 MRXF 12-615 MRXF 12-700 MRXF 12-1000 MRXF 109 172 201 254 100 160 185 234 Hioki Impedance (mOhms) Midttronics Cond. (Mhos) 2 37 2.37 1.91 1.84 1.47 2000 2500 2700 3700 IEC Short Circuit Current (A) IEC Resistance (m Ohm s) Weight ( kg) 2860 3700 4400 5540 4.4 3.4 2.8 2.3 37.1 55.2 64.9 85.2 Maximum Short Circuit Terminal Current Discharge Current (AMPS @0.1 sec) Rating (AMPS) 4900 800 6500 800 7900 800 10100 1000 * Per IEEE 1188-2005, Internal ohmic values are useful as a trending tool. To use these readings effectively, accurate baseline readings should be taken after about six months of battery operation. Internal ohmic readings taken without the benefit of baseline data may be difficult to interpret and d of limited value. Values are provided are for reference only. Dimensions Top View Front View Side View A UPS UPS UPS UPS Model 12-410 MRXF 12-615 MRXF 12-700MRXF 12-1000MRXF in 18.6 20.3 20.3 20.3 mm 473.1 516.9 516.9 516.9 B in 20.1 22.0 22.0 22.0 mm 510.5 558.5 558.5 558.5 C in 19.6 21.5 21.5 21.5 mm 498.3 546.5 546.5 546.5 D in 18 8.5 20 0.2 20 0.2 20 0.2 mm 469.5 512.2 512.2 512.2 E in 8.5 10.6 12.2 12.2 mm 215.2 268.9 310.8 310.8 F in 9.1 11.0 12.7 12.7 G mm 231.4 278.7 322.1 322.1 in 4.3 4.9 4.9 6.1 mm 109.0 125.0 125.0 154.3 H in 4.3 4.9 4.9 6.0 mm 108.0 123.4 123.4 152.7 *All dimensions in inches and (millimeters). All dimensions are for reference only. o Contact a C&D Representative for complete dimensions information. Detail of Terminal UPS 12 12-410 410 MRXF UPS 12-6 615 MRXF UPS 12-7 700 MRXF UPS 12-1000 MRXF UPS 12- 410 MRXF Constant Power Discharge Ratin ngs - Watts Per Cell @ 77oF (25oC) Operating Time to End Point P Voltage ( in minutes) End Point Volts/CeIl 1.75 1.70 1 67 1.67 1.65 5 10 15 20 30 40 45 50 60 90 660.1 690.8 701 1 701.1 709.7 484.4 507.0 514 6 514.6 520.8 386.0 404.0 410 0 410.0 415.0 321.2 334.4 339 5 339.5 344.1 244.0 2 2 252.0 2 0 256 256.0 2 260.0 195.3 200.5 203 1 203.1 205.7 178.3 182.6 184 8 184.8 186.9 164.3 167.9 169 8 169.8 171.6 142.7 145.3 146 6 146.6 147.9 102.4 104.2 105 1 105.1 106.0 Constant Current Discharge Ratings R - Amperes @ 77oF (25oC) Operating Time to End d Point Voltage ( in hours) End Point Volts/CeIl 1 85 1.85 1.80 1.75 1 2 3 5 8 10 12 20 24 72 67 71 73 38 4 38.4 40.5 41.5 27 7 27.7 29.2 29.8 18 5 18.5 19.4 19.8 12.0 12 0 12.6 12.8 97 9.7 10.2 10.4 82 8.2 8.6 8.8 5 07 5.07 5.34 5.46 4 28 4.28 4.50 4.61 1 50 1.50 1.58 1.61 UPS 12- 615 MRXF Constant Power Discharge Ratings - Watts Per Cell @ 77oF (25oC) Operating Time to End Point Voltage ( in minutes) End Point Volts/CeIl 1.75 1.70 1.67 1.65 5 10 15 20 30 40 45 50 60 90 973.6 1010.4 1027.1 1035.4 731.7 759.3 771.8 778.1 583.0 605.0 615.0 620.0 494.2 508.0 513.8 516.8 386.0 3 3 391.0 3 392.5 3 393.5 313.6 317.4 318.8 319.5 288.0 291.4 292.8 293.4 266.9 269.9 271.3 271.8 234.0 236.5 237.8 238.2 169.0 170.7 171.5 172.0 Constant Current Discharge Ratings R - Amperes @ 77oF (25oC) Operating Time to End d Point Voltage ( in hours) End Point Volts/CeIl 1.85 1 80 1.80 1.75 1 2 3 5 8 10 12 20 24 72 109 118 120 61.8 65 8 65.8 67.0 44.0 46 7 46.7 47.5 28.7 30 4 30.4 30.9 19.0 20 1 20.1 20.3 15.5 16 3 16.3 16.5 13.1 13 8 13.8 13.9 8.10 8 47 8.47 8.61 6.81 7 12 7.12 7.26 2.38 2 49 2.49 2.54 Note: Batteries to be mounted with 0.5 in. (1.25 cm) spacing minimum and free e air ventilation. Specifications subject to change without notification. Above ratings do not include interunit connector voltage drops. UPS 12-700 MRXF Constant Power Discharge Ratin ngs - Watts Per Cell @ 77oF (25oC) Operating Time to End Point Voltage ( in minutes) End Point Volts/CeIl 1.75 1.70 1.67 1.65 5 10 15 20 30 40 45 50 60 90 1020.6 1083.8 1117.8 1134.0 780.0 839.6 866.0 878.5 630.0 669.0 700.0 703.0 544.1 570.2 583.0 590.1 437.0 4 4 449.0 4 453.0 4 457.0 358.7 365.5 368.1 370.3 330.8 336.0 338.1 339.7 307.7 311.6 313.3 314.5 271.5 273.5 274.7 275.2 196.5 198.6 199.3 199.7 Constant Current Discharge Ratings R - Amperes @ 77oF (25oC) Operating Time to End d Point Voltage ( in hours) End Point Volts/CeIl 1.85 1.80 1.75 1 2 3 5 8 10 12 20 24 72 121 130 134 71.4 75.1 76.6 51.1 53.9 54.6 33.5 35.2 35.7 22.1 23.2 23.6 18.0 18.8 19.2 15.2 15.9 16.2 9.48 9.88 10.07 8.01 8.34 8.51 2.80 2.92 2.98 UPS 12-1000 12 1000 MRXF Constant Power Discharge Ratin ngs - Watts Per Cell @ 77oF (25oC) Operating Time to End Point Voltage ( in minutes) End Point Volts/CeIl 1.75 1.70 1.67 1 65 1.65 5 10 15 20 30 40 45 50 60 90 1379.8 1469.0 1520.0 1541 9 1541.9 1098.4 1169.4 1210.0 1227 5 1227.5 907.8 966.4 1000.0 1014 4 1014.4 763.7 801.7 823.7 834 1 834.1 589.7 5 6 606.1 6 616.2 6 3 622 622.3 472.2 484.4 491.2 495 5 495.5 431.2 442.0 447.7 451 4 451.4 397.5 407.1 412.0 415 2 415.2 345.3 353.2 356.9 359 4 359.4 250.1 254.7 256.7 257 9 257.9 Constant Current Discharge Ratings R - Amperes @ 77oF (25oC) Operating Time to End d Point Voltage ( in hours) End Point Volts/CeIl 1.85 1 80 1.80 1.75 1 2 3 5 8 10 12 20 24 72 168 181 188 96.1 102.0 102 0 104.1 67.9 71 3 71.3 72.1 43.2 45 0 45.0 45.4 28.1 29 3 29.3 29.7 22.9 23 9 23.9 24.3 19.4 20 2 20.2 20.6 12.05 12 50 12.50 12.70 10.18 10 60 10.60 10.70 3.56 3 71 3.71 3.75 Note: Batteries to be mounted with 0.5 in. (1.25 cm) spacing minimum and free air ven ntilation. Specifications subject to change without notification. Above ratings do not include interunit connector voltage drops. Shanghai C&D Battery Co., Ltd. No.55 Liandu Road, Spark Development Zone, Shanghai P.R.C Service Hotline:86 - 400 - 678 - 3721 www.cdtechno.com.cn & www.cdtechno.com Any data, descriptio ons or specifications presented herein are subject to revision by C&D Technologies, Inc. without notice. While such information is believed to be accurate as indicated herein, C&D Technologies, Inc. makes no warranty and hereb by disclaims all warranties, express or implied, with regard to the accuracy or completeness of such information. Further, because the product(s) featured herein may be used under conditions beyond its control, C&D Technologies Technologies, Inc. Inc hereby disclaims all warranties warranties, either express or implied implied, concerning the fitness or suitability of such prroduct(s) for any particular use or in any specific application or arising from any course of dealing or usage of trade. The T user is solely responsible for determining the suitability of the product(s) featured herein for user’s intended purpose and in user’s specific application. 0212-MRXF-E