Safety instructions
VEGAPULS PSWL61.
KX***H***
CSA 14.2719243
CL I, DIV 2, GP ABCD; CL II, DIV 2, GP FG;
CL III
Document ID: 49581
Contents
1 Area of applicability.................................................................................................................. 3
2 General information.................................................................................................................. 3
3 Technical data........................................................................................................................... 3
4 Application conditions............................................................................................................. 3
5 Protection against static electricity........................................................................................ 3
6 Use of an overvoltage arrester................................................................................................ 4
7 Material resistance................................................................................................................... 4
8Grounding.................................................................................................................................. 4
9 Special features........................................................................................................................ 4
49581-EN-150324
Please note:
These safety instructions are part of the documentation:
•
•
2
38061 - VEGAPULS WL 61 - 4 … 20 mA/HART - two-wire
49580 - Certificate of Conformity CSA 14.2719243
VEGAPULS PSWL61.KX***H***
1
Area of applicability
2
General information
These safety instructions apply to the radar sensor VEGAPULS WL 61 series VEGAPULS PSWL61.
KX***H*** according to Certificate of Conformity CSA 14.2719243 (certificate number on the type
label) and for all instruments with the number of the safety instruction (49581) on the type label.
The level measuring instrument VEGAPULS PSWL61.KX***H*** is based on radar technology and
is used to detect the distance between product surface and sensor by means of high frequency,
electromagnetic waves in the GHz range. The electronics uses the running time of the signals
reflected by the product surface to calculate the distance to the product surface.
The VEGAPULS PSWL61.KX***H*** consist of an electronics housing, a process connection element and a sensor, an antenna.
The measured products can be combustible liquids, gases, mist or vapour.
The VEGAPULS PSWL61.KX***H*** are suitable for use in hazardous atmospheres of all combustible materials of Class I Division 2 Groups A, B, C, D and Class II Division II Groups F, G and Class
III.
The operating instructions as well as the applicable, national HazLoc mounting regulations and
standards for electrical equipment must be observed.
The installation of explosion-endangered systems must always be carried out by qualified personnel
trained in explosion protection and being familiar with national regulations.
Sensors installed in hazardous locations must be operated inside the specified electrical, thermal
and mechanical parameters given within this document.
Modification of the sensor can affect explosion protection and must be carreid out by staff authorized to perform such work by the manufacturer.
3
Technical data
Electrical data
VEGAPULS PSWL61.KX***H***
Power supply and signal circuit: (cores
brown [+], blue [-])
4
•
U = 9.6 … 36 V DC
Application conditions
The max. permissible ambient temperatures depending on the temperature classes are specified in
the below table.
Temperature class
Temperature on the sensor
Ambient temperature on the electronics
T6, T5, T4, T3, T2, T1
-20 … +50 °C
-20 … +50 °C
49581-EN-150324
The prerequisites for operation in the absence of explosive mixtures can be found in the manufacturer specifications.
5
Protection against static electricity
VEGAPULS PSWL61.KX***H***
3
The VEGAPULS PSWL61.KX***H*** in the version with chargeable plastic parts, are provided with
a caution label on the housing referring to the safety measures that must be taken in case electrostatic charging occurs during operation.
Caution: Plastic parts! Danger of electrostatic charge!
•
•
•
Avoid friction
No dry cleaning
Installation: The VEGAPULS PSWL61.KX***H*** must be constructed/installed in such a way
that:
–– electrostatic charges are ruled out during operation, maintenance and cleaning
–– process related electrostatic charges, e. g. by measuring media flowing past, are ruled out
6
Use of an overvoltage arrester
7
Material resistance
If necessary, the VEGAPULS PSWL61.KX***H*** can be connected to an overvoltage arrester, e. g.
type B62-36G or B62-30W from VEGA.
VEGAPULS PSWL61.KX***H*** should only be used in media against which the wetted materials
are sufficiently resistant.
8Grounding
For the VEGAPULS PSWL61.KX***H*** in the version with mounting strap, the strap must be electrostatically (contact resistance ≤ 1 MΩ) grounded.
9
Option:
•
•
•
Special features
The housing corresponds to the mechanical strain level "low".
The instrument must be installed and operated in a way that ensures there is no danger of ignition from electrostatic charging.
Mount VEGAPULS WL 61 in a way that adequately ensures that the sensor will not touch the
vessel wall due to the movements of other vessel installations and flow conditions in the vessel.
49581-EN-150324
4
VEGAPULS PSWL61.KX***H***
49581-EN-150324
Notes
VEGAPULS PSWL61.KX***H***
5
Notes
49581-EN-150324
6
VEGAPULS PSWL61.KX***H***
49581-EN-150324
Notes
VEGAPULS PSWL61.KX***H***
7
All statements concerning scope of delivery, application, practical use and operating conditions of the sensors and processing systems correspond to the information
available at the time of printing.
Subject to change without prior notice
© VEGA Grieshaber KG, Schiltach/Germany 2015
VEGA Grieshaber KG
Am Hohenstein 113
77761 Schiltach
Germany
Phone +49 7836 50-0
Fax +49 7836 50-201
E-mail: info.de@vega.com
www.vega.com
49581-EN-150324
Printing date:
Download