OF, SD, MX + OF, MN C60 Electrical auxiliaries IEC They remotely trip or indicate circuit breakers or supplementary protectors. Compliance with electrical auxiliaries standards b b b b b b For UL 489 circuit breaker File #217688. For CSA C22.2 No. 5.2 circuit breakers File #179014. For UL 1077 Supplementary Protectors File #E90509. For CSA C22.2 No. 235-M04 Supplementary Protectors File #179014. For IEC 60947-2 and IEC 60947-5-1 circuit-breakers. CE Marked. Possible electrical auxiliary combinations Auxiliaries are mounted to the left of the circuit breaker and/or the supplementary protectors for a total width of 2.13 in (54 mm) max. : b they are fixed using clips (no tools) b a maximum of 3 indication auxiliaries (OF), (SD) on the same device b a maximum of 2 tripping auxiliaries (MX + OF) or (MN) on the same device. 2.13 in. (54 mm): 6 modules of 0.354 in. (9 mm) max. SD Alarm Switch + OF auxiliary Switch PB100992-35 PB100993-35 PB100994-35 PB100995-35 + PB100977A_SE releases auxiliaries contact + MX + OF Shunt trip and auxiliary switch + MN Undervoltage release C60 Supplementary protectors or C60 circuit breaker Connection for copper cables UL 486A file #E216919 b Terminal pads for: v two #16 AWG (1.5 mm2) cables, or one #14 AWG (2.5 mm2) cable v torque 9 Ib.in. Type Control voltage Va Vc Width in modules 0.354 in. (9 mm) Cat. no. UL/CSA 1 26925 1 26928 12 to 24 48 110 to 130 2 2 2 27118 27110 27109 24 48 - 2 2 2 2 27108 27106 27107 27105 OF auxiliary switch SD alarm switch MX + OF shunt trip 24 48 110 to 277 MN undervoltage release Instantaneous version: 3.2 24 48 120 220 to 240 90081E.indd OF, SD, MX + OF, MN C60 Electrical auxiliaries IEC Remote tripping Remote tripping is possible by means of a shunt trip (MX+OF) or undervoltage release (MN). A tripped device is indicated by a red indicator flag on the front panel. MX + OF shunt trip DB100993-35 b When energized, trips the associated device: v equipped with an O + F switch that indicates the “open” or “closed” position of the device v realize a self-interrupting allowing the control circuit to remain on. u> 14 12 C2 DB112939 08603083 Wiring diagrams C1 DB100992-35 MN Undervoltage Release b When the voltage drops to 70–35% of the supply voltage, the associated device trips and is prevented from reclosing until the supply voltage is restored: v uses emergency stop via push button v uses safety feature on circuit supplying several machines preventing uncontrolled restarting of the motors. u< 08603146a 08603084 Wiring diagrams u< D1 D2 D1 D2 L or + N or - 90081E.indd version: 3.2 OF, SD, MX + OF, MN C60 Electrical auxiliaries IEC Remote Indication Operation test button on the front panel of the auxiliary (OF) and alarm switches (SD) allows simulation of the OF and SD functions without operating the device. OF auxiliary switch b Indicates the “open” or “closed” position of the device. DB112940 08603086 PB100994-35 Wiring diagrams 14 12 11 SD Alarm Switch b Indicates the “tripped-on-fault” position of the device with a red indicator flag on the front panel. DB112941 08603085 PB100995-35 Wiring diagrams 92 94 91 OF and SD position contact depending on status of combinated circuit breaker: C60 Position Switch OF Switch SD version: 3.2 ON OFF Trip 11/14 11/12 91/94 91/92 b b b ON OFF OFF ON OFF ON OFF ON OFF ON ON OFF 90081E.indd OF, SD, MX + OF, MN C60 Electrical auxiliaries IEC MN, MX + OF releases technical data Releases Cat. no. Nominal line voltage (V) (10, -20%) Alternating current (a) Direct current (c) Operating frequency 50/60 Hz Min. cut-in voltage (V) Min. tripping voltage (V) Holding current (A) Power consumption (VA) Min. voltage dip time (ms) Releases MN 27105 220 to 240 b 27106 48 b b b 187 40.8 40.8 Between 0.35 and 0.70 Un 0.014 0.03 3.3 1.6 30 8 0.02 1.1 8 MX+OF 27109 120 b 240 b 277 b b b b 60.5 60.5 Inrush current (A) Inrush power (VA) Min. control impulse duration (ms) Power circuit breaking time (ms) 0.4 44 8 18 0.8 184 OF contact rated operational current Ie (A) See the auxiliary contact table Nominal line voltage (V) (+10, -20%) Alternating current (a) Direct current (c) Operating frequency 50/60 Hz Min. cut-out voltage (V) 48 b 110 b 125 b 60.5 60.5 60.5 1 277 0.3 38 0.3 45 27107 120 b 27108 24 b b b 102 20.4 20.4 0.011 1.3 8 0.04 1 10 0.02 0.5 10 27110 48 b b 26.4 1 48 8 18 48 b 27118 12 b 26.4 6.6 0.7 33.6 2.5 30 8 18 24 b 24 b b 24 b 6.6 6.6 7.7 185 5.6 135 OF, SD auxiliary contacts technical data b b v v Degree of protection: IP20. Rating of auxiliary contact short-circuit protection device: circuit breaker: C60 - 2P - C curve - 6 A - limitation class 3 fuse: 6 A, 500 V, type Gg, 10.3 x 38 mm. Contact rated operational current Ie (A) to IEC 60947-5 Auxiliary contacts Cat. no. Rated operational voltage Ue (V) a Cat. AC12 c Cat. DC12 277 V 220 to 240 V 12 to 24 V 48 V 60 V 130 V OF, SD 26925 / 26928 3 6 6 2 1.5 1 Common technical data of auxiliary contacts and releases Common technical data Operating temperature when live (°C) -25°C to +50°C Storage temperature -40°C to +85°C DB110258 Dimensions MN, MX+OF 90081E.indd version: 3.2 OF, SD