OF, SD, MX + OF, MN C60

advertisement
OF, SD, MX + OF, MN
C60
Electrical auxiliaries
IEC
They remotely trip or indicate circuit breakers or
supplementary protectors.
Compliance with electrical auxiliaries standards
b
b
b
b
b
b
For UL 489 circuit breaker File #217688.
For CSA C22.2 No. 5.2 circuit breakers File #179014.
For UL 1077 Supplementary Protectors File #E90509.
For CSA C22.2 No. 235-M04 Supplementary Protectors File #179014.
For IEC 60947-2 and IEC 60947-5-1 circuit-breakers.
CE Marked.
Possible electrical auxiliary combinations
Auxiliaries are mounted to the left of the circuit breaker and/or the supplementary
protectors for a total width of 2.13 in (54 mm) max. :
b they are fixed using clips (no tools)
b a maximum of 3 indication auxiliaries (OF), (SD) on the same device
b a maximum of 2 tripping auxiliaries (MX + OF) or (MN) on the same device.
2.13 in. (54 mm): 6 modules of 0.354 in. (9 mm) max.
SD Alarm
Switch
+
OF auxiliary
Switch
PB100992-35
PB100993-35
PB100994-35
PB100995-35
+
PB100977A_SE
releases
auxiliaries contact
+
MX + OF Shunt
trip and
auxiliary switch
+
MN
Undervoltage
release
C60
Supplementary
protectors
or C60
circuit breaker
Connection for copper cables UL 486A file #E216919
b Terminal pads for:
v two #16 AWG (1.5 mm2) cables, or one #14 AWG (2.5 mm2) cable
v torque 9 Ib.in.
Type
Control voltage
Va
Vc
Width in
modules
0.354 in.
(9 mm)
Cat. no.
UL/CSA
1
26925
1
26928
12 to 24
48
110 to 130
2
2
2
27118
27110
27109
24
48
-
2
2
2
2
27108
27106
27107
27105
OF auxiliary switch
SD alarm switch
MX + OF shunt trip
24
48
110 to 277
MN undervoltage release
Instantaneous
version: 3.2
24
48
120
220 to 240
90081E.indd
OF, SD, MX + OF, MN
C60
Electrical auxiliaries
IEC
Remote tripping
Remote tripping is possible by means of a shunt trip (MX+OF) or undervoltage
release (MN). A tripped device is indicated by a red indicator flag on the front panel.
MX + OF shunt trip
DB100993-35
b When energized, trips the associated device:
v equipped with an O + F switch that indicates the “open” or “closed” position of the
device
v realize a self-interrupting allowing the control circuit to remain on.
u>
14 12 C2
DB112939
08603083
Wiring diagrams
C1
DB100992-35
MN Undervoltage Release
b When the voltage drops to 70–35% of the supply voltage, the associated device
trips and is prevented from reclosing until the supply voltage is restored:
v uses emergency stop via push button
v uses safety feature on circuit supplying several machines preventing uncontrolled
restarting of the motors.
u<
08603146a
08603084
Wiring diagrams
u<
D1
D2
D1
D2
L or +
N or -
90081E.indd
version: 3.2
OF, SD, MX + OF, MN
C60
Electrical auxiliaries
IEC
Remote Indication
Operation test button on the front panel of the auxiliary (OF) and alarm switches (SD)
allows simulation of the OF and SD functions without operating the device.
OF auxiliary switch
b Indicates the “open” or “closed” position of the device.
DB112940
08603086
PB100994-35
Wiring diagrams
14 12 11
SD Alarm Switch
b Indicates the “tripped-on-fault” position of the device with a red indicator flag on
the front panel.
DB112941
08603085
PB100995-35
Wiring diagrams
92 94 91
OF and SD position contact depending on status
of combinated circuit breaker:
C60 Position
Switch
OF
Switch
SD
version: 3.2
ON
OFF
Trip
11/14
11/12
91/94
91/92
b
b
b
ON
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
ON
ON
OFF
90081E.indd
OF, SD, MX + OF, MN
C60
Electrical auxiliaries
IEC
MN, MX + OF releases technical data
Releases
Cat. no.
Nominal line voltage (V) (10, -20%)
Alternating current (a)
Direct current (c)
Operating frequency
50/60 Hz
Min. cut-in voltage (V)
Min. tripping voltage (V)
Holding current (A)
Power consumption (VA)
Min. voltage dip time (ms)
Releases
MN
27105
220 to 240
b
27106
48
b
b
b
187
40.8
40.8
Between 0.35 and 0.70 Un
0.014
0.03
3.3
1.6
30
8
0.02
1.1
8
MX+OF
27109
120
b
240
b
277
b
b
b
b
60.5
60.5
Inrush current (A)
Inrush power (VA)
Min. control impulse duration (ms)
Power circuit breaking time (ms)
0.4
44
8
18
0.8
184
OF contact rated operational current Ie (A)
See the auxiliary contact table
Nominal line voltage (V) (+10, -20%)
Alternating current (a)
Direct current (c)
Operating frequency
50/60 Hz
Min. cut-out voltage (V)
48
b
110
b
125
b
60.5
60.5
60.5
1
277
0.3
38
0.3
45
27107
120
b
27108
24
b
b
b
102
20.4
20.4
0.011
1.3
8
0.04
1
10
0.02
0.5
10
27110
48
b
b
26.4
1
48
8
18
48
b
27118
12
b
26.4
6.6
0.7
33.6
2.5
30
8
18
24
b
24
b
b
24
b
6.6
6.6
7.7
185
5.6
135
OF, SD auxiliary contacts technical data
b
b
v
v
Degree of protection: IP20.
Rating of auxiliary contact short-circuit protection device:
circuit breaker: C60 - 2P - C curve - 6 A - limitation class 3
fuse: 6 A, 500 V, type Gg, 10.3 x 38 mm.
Contact rated operational current Ie (A) to IEC 60947-5
Auxiliary contacts
Cat. no.
Rated operational
voltage Ue (V)
a
Cat. AC12
c
Cat. DC12
277 V
220 to 240 V
12 to 24 V
48 V
60 V
130 V
OF, SD
26925 / 26928
3
6
6
2
1.5
1
Common technical data of auxiliary contacts
and releases
Common technical data
Operating temperature when live (°C)
-25°C to +50°C
Storage temperature
-40°C to +85°C
DB110258
Dimensions
MN, MX+OF
90081E.indd
version: 3.2
OF, SD
Download