Technical Note Wiring Configurations for Using Relay Modules with 500N Series Smoke Detectors Using a 405-05 Relay Module with 4-Wire 500N Series Smoke Detectors ESL 405-05 polarity reversal relay modules are designed for use with ESL smoke detectors that have built-in sounders. On alarm, the module applies reverse polarity to the detectors activated by the bell or programmable output. Applying reverse polarity causes the sounders on detectors not in alarm to activate. Listed Burglar/Fire Alarm Control Panel Smoke Power + - Bell or Pgm Output + - * Shown with CleanMe Enabled ESL 405-05 Polarity Reversal Relay White/Red Red Black White/Black Contact NO Gray C Contact + - Power White * NO C * - + Power NO C NC ESL 541NCSXT Power Supervision Relay ESL 541NCSXTE Fire Alarm Zone 24-Hour Normally Open EOL Resistor Using a 405-03/405-01 Relay Module with 4-Wire 500N Series Smoke Detectors ESL 405-03/405-01 polarity reversal relay modules are designed for use with ESL smoke detectors that have built-in sounders. On alarm, the module disconnects the detectors from their normal power supply and applies reverse polarity from the notification appliance circuit. Applying reverse polarity causes the sounders on detectors not in alarm to activate. Listed Burglar/Fire Alarm Control Panel + 1 2 - 3 4 + 5 6 Smoke Power Bell Output * Shown with CleanMe Enabled ESL 405-03 Polarity Reversal Relay Contact NO C Contact + - Power - ESL 204-12/24V Power Supervision Relay * NO C + - * Power NC 7 8 C ESL 541NCSXT NO ESL 541NCSRH 541NCSRXT Fire Alarm Zone 24-Hour Normally Open EOL Resistor WARNING ! The 405 relay modules may not be compatible with all power supervision relays. When using this device on 4-wire circuits, use the ESL 204 series power supervision relay at the end-of-line. An ESL smoke detector with a sounder that incorporates an end-of-line/sensitivity relay output may also be used. ESL 08/02 Using a 405-03/405-01 Relay Module with 2-Wire 500N Series Smoke Detectors ESL 405-03/405-01 polarity reversal relay modules are designed for use with ESL smoke detectors that have built-in sounders. On alarm, the module disconnects the detectors from their normal power supply and applies reverse polarity from the notification appliance circuit. Applying reverse polarity causes the sounders on detectors not in alarm to activate. * Shown with CleanMe Enabled Listed Burglar/Fire Alarm Control Panel ESL 405-01 Polarity Reversal Relay Fire Alarm Zone 24-Hour Normally Open + 1 2 - 3 4 + 5 6 Bell Output EOL Resistor + Note: Polarity in Bell Output is shown in alarm condition. 7 8 - Power * + - * Power NC C ESL 521NCSXT ESL 521NCSRXT NO Note: The 405-03, 405-01, and 405-05 modules can be used with 4-wire 500N detectors, but only the 405-03 and the 405-01 can be used with 2-wire 500N detectors.