Reverse Polarity Signaling Module - Surveillance

advertisement
Reverse Polarity Signaling Module
D185
en
Installation Instructions
Reverse Polarity Signaling Module
Notices | en
3
Notices
1
These instructions cover the installation of the D185 Reverse Polarity Signaling Module in a
fire system supervised by a fire alarm control panel (FACP) or a combination Burglary/Fire
control panel.
Before installing the module, become familiar with the Installation and Operation Guide for the
control panel you are using.
Install, test and maintain the module according to these instructions, NFPA 72, local codes,
and the authority having jurisdiction (AHJ). Failure to follow these instructions can result in
failure of a detector to initiate an alarm event. Bosch Security Systems, Inc. is not responsible
for improperly installed, tested or maintained devices.
!
Warning!
Follow these instructions to avoid personal injury and damage to equipment.
NFPA 72 requires that you perform a complete system wide functional test following any
modifications, repair, upgrades or adjustments made to the system’s components, hardware,
wiring, programming and software/firmware.
2
Description
The D185 Reverse Polarity Signaling Module connects a control panel with either a single set
or a pair of leased telephone company (telco) lines in NFPA 72 remote station applications.
The module’s three input terminals accept alarm, trouble, or supervisory input from the
control panel, and the module transmits this information to a monitoring station after a built-in
20±5 sec) delay. This module operates with either a 12 VDC or 24 VDC supply. All circuits are
power limited.
The module can be used with the Bosch Security Systems, Inc. control panels indicated in the
following table. You can also use the module with non-Bosch, UL Listed control panels where
it is referenced as compatible in the control panel's installation instructions.
Control panels
Compatible relays
See section:
Active:
FPD-7024 panel
D275, PAM-4
Wiring to an FPD-7024 FACP,
page 7
G Series (GV2 and higher)
D275, PAM-4
panels
Wiring to a G Series control
panel, page 8
1
Legacy:
D7024 panel
See control panel documentation on the Bosch website
(http://www.boschsecurity.com)
G Series (prior to GV2)
panels2
D9412, D7412, and D7212**
panels
DS9400 panel*
Bosch Security Systems, Inc.
Installation Instructions
2013.05 | 03 | F.01U.034.781
4
en | Notices
Reverse Polarity Signaling Module
Control panels
1
Compatible relays
See section:
G Series (GV2 or higher) = GV4 (D9412GV4, D7412GV4, and D7212GV4**), GV3
(D9412GV3, D7412GV3, and D7212GV3**), and GV2 (D9412GV2, D7412GV2, and
D7212GV2**) panels
2
G Series (prior to GV2) = D9412G, D7412G, and D7212G** panels
* Legacy products were investigated to comply only to UL864 8th edition
** indicates products which are not UL listed for commercial fire applications
Figure 2.1: D185 reverse polarity signaling module
1 Input terminals
10 Connects to telco line for sending
supervisory signals
2 Earth Ground
11 Connects to telco line for sending
alarm\trouble signals
3 Common
12 Connects to telco line for sending
alarm\trouble signals
4 Connects to control panel Aux or
13 Not used
external power supply (12 VDC or
24 VDC)
5 Connects to Trouble Relay on control
panel
14 Connects to end-of-line (EOL)
supervisory relay (such as, D275,
PAM‑4)
6 Connects to Supervisory Relay on
15 Alarm signal adjuster
control panel
7 Connects to Alarm Relay on the control
16 Supevisory signal adjuster
panel
8 Output terminals
17 Alarm Test LED
9 Connects to telco line for sending
18 Alarm Test switch
supervisory signals
2013.05 | 03 | F.01U.034.781
Installation Instructions
Bosch Security Systems, Inc.
Reverse Polarity Signaling Module
3
Notices | en
5
Operation
Under normal conditions, the module sends a steady 10 mA of current to the alarm telco
outputs and 14 mA of current to the supervisory output which connects to a monitoring
station. In an alarm or supervisory condition, the module reverses the output current polarity
and signals a trouble condition by interrupting the output voltage and current.
Input
Output
Alarm
Supevisory
Trouble
Alarm
Supervisory
No Current
No Current
No Current
Normal
Normal
No Current
No Current
Active High
No Current
Normal
No Current
Active High
No Current
No Current
Reversed Polarity
No Current
Active High
Active High
No Current
Reversed Polarity
Active High
No Current
No Current
Reversed Polarity
Normal
Active High
Active High
No Current
Reversed Polarity Reversed Polarity
Active High
Active High
Active High
Reversed Polarity Reversed Polarity
Table 3.1: Input and output states
3.1
Alarm and trouble responses (alarm output telco lines)
The module responds to an alarm input from the control panel by reversing the alarm telco
output polarity. The module responds to a trouble input from the control panel by interrupting
the current to the alarm telco outputs
If the control panel sends an alarm during a trouble signal, the module overrides the trouble
telco output and responds with an alarm telco output (reversed polarity).
3.2
Supervisory response (supervisory output telco lines)
The module responds to a supervisory signal input by reversing the polarity of the supervisory
telco outputs. A second set of telco lines must be connected.
3.3
Alarm test
The Alarm Test Switch (Item 18 in Figure 1 on page 2) disables module output during testing
that triggers a trouble output from the module during testing. Generally, this switch is off but
during an Alarm Test, you must move the switch to the ON position. Turning on the Alarm Test
Switch lights the Alarm Test LED (Item 17 in Figure 1).
4
Installation
Notice!
Install the module within 20 ft (6 m) of the control panel with a minimum of 22 AWG
(0.34 mm2) wire. Ensure all wiring is in conduit.
Install the D185 in a system by:
Bosch Security Systems, Inc.
Installation Instructions
2013.05 | 03 | F.01U.034.781
6
en | Notices
Reverse Polarity Signaling Module
Danger!
Inform the operator and the local AHJ before installing this module in an existing system.
Disconnect all power to the control panel before installing this module.
1.
Removing power from the control panel
Before making or removing any connections to the FACP, remove the standby battery
power.
Remove AC power from the system at the dedicated 120 VAC breaker.
2.
Mounting the module
The module mounts on a snap-track and installs with a supplied screw in the control
panel enclosure.
3.
Connecting the module
The module has twelve screw terminal connection points, six on the left side for inputs
and six on the right side for outputs (see the D185 reverse polarity signaling module
figure in Description, page 3 and the Wiring, page 6 section).
Caution!
!
Connect input power only to the PWR Terminals.
4.
Restoring power to the control panel
Restore AC power to the system at the dedicated 120 VAC breaker.
Reconnect the standby battery power.
5.
Adjusting the amount of output current
To adjust the amount of output current required on the telco output, use a screwdriver to
rotate the alarm signal adjuster.
5
Wiring
An external 12 VDC or 24 VDC power supply listed for fire signaling units or commercial or
residential burglary units can be used.
The external power supply must be UL1481 or UL864 Listed, regulated, and power‑limited.
Install the control panel and external power supply in the same room no more than 20 ft (6 m)
apart. The interconnecting wires between the control panel and external power supply must
be in conduit.
The power source for both the auxiliary power supply and the control panel must be from the
same dedicated AC branch circuit.
2013.05 | 03 | F.01U.034.781
Installation Instructions
Bosch Security Systems, Inc.
Reverse Polarity Signaling Module
Notices | en
5.1
Wiring to an FPD-7024 FACP
5.1.1
Wiring for power supplied by the FACP
7
Figure 5.1: Wiring an FPD-7024 FACP to supply 12 VDC power to the D185
1 FPD-7024 FACP
11 Negative (-) connection from power
supply to D185
2 D185 module
12 EOL supervision relay
3 Positive (+) power to Relay 3 (NC3)
13 Relay leads
4 Relay 3 (COM3) to trouble trigger
14 2.2 kΩ EOL resistor
5 Positive (+) power to Relay 2 (NO2)
15 D275 +12 VDC input (red wire)
6 Relay 2 (COM2) to supervisory trigger
16 Positive (+24 VDC) power connection
from FACP to EOL supervision relay
7 Earth Ground
17 D185 supervisory zone connection to
EOL supervision relay
8 Positive (+) power to Relay 1 (NC1)
18 Telco connection for supervisory signal
9 Relay 1 (COM1) to alarm trigger
19 Telco connection for alarm\trouble
signals
10 Positive (+) power connection from
FACP to D185 and EOL supervision
relay
Bosch Security Systems, Inc.
Installation Instructions
2013.05 | 03 | F.01U.034.781
8
en | Notices
5.1.2
Reverse Polarity Signaling Module
Wiring for power supplied by an external power supply
Figure 5.2: Wiring an FPD-7024 FACP to a D185 with power supplied by an external power supply
1 FPD-7024 FACP
10 External power supply
2 D185 module
11 Positive (+) connection from power
supply to FACP relays, EOL
supervision relay, and D185
3 Positive (+) power to Relay 3 (NC3)
12 Negative (-) connection from power
supply to D185
4 Relay 3 (COM3) to trouble trigger
13 EOL supervision relay
5 Positive (+) power to Relay 2 (NO2)
14 Relay leads
6 Relay 2 (COM2) to supervisory trigger
15 2.2 kΩ EOL resistor
7 Positive (+) power to Relay 1 (NC1)
16 D185 supervisory zone connection to
EOL supervision relay
8 Relay 1 (COM1) to alarm trigger
17 Telco connection for supervisory signal
9 Earth Ground
18 Telco connection for alarm\trouble
signals
5.2
Wiring to a G Series control panel
2013.05 | 03 | F.01U.034.781
Installation Instructions
Bosch Security Systems, Inc.
Reverse Polarity Signaling Module
5.2.1
Notices | en
9
Wiring for power supplied by the control panel
Figure 5.3: Wiring G Series panels to supply power to a D185
1 D185 module
10 D185 SUPV TRIG connection to D130
2 G Series panel
11 G Series Relay A connection to D185
ALRM TRIG
3 EOL supervision relay
12 D185 SUPV ZONE connection to the
EOL supervision relay
4 D130 relay
13 G Series Relay C connection to EOL
supervision relay
5 If using 24 VDC, cut the wire
14 Connection to one relay lead of the
EOL supervision relay to an on‑board
point on the control panel
6 Earth Ground
15 Connection to the other relay lead of
the EOL supervision relay to an
on‑board point on the control panel
7 Common connection between control
panel, D130 relay, and D185 module
control panel
8 +12 VDC aux power from control panel
17 Telco connection for supervisory signal
9 G Series Relay B connection to D185
18 Telco connection for alarm\trouble
TRBL TRIG
Bosch Security Systems, Inc.
16 1 kΩ EOL resistor as specified for the
signals
Installation Instructions
2013.05 | 03 | F.01U.034.781
10
en | Notices
5.2.2
Reverse Polarity Signaling Module
Wiring for power supplied by an external power supply
Figure 5.4: Wiring G Series panels to a D185 with power supplied by an external power supply
1 D185 module
11 D185 supervisory trigger connection to
D130 relay
2 G Series panel
12 G Series Relay A connection to D185
ALRM TRIG
3 External power supply
13 D185 supervisory zone connection to
the EOL supervision relay
4 EOL supervision relay
14 G-series Relay C connection to the
D130 relay
5 D130 relay
15 Connection to one relay lead of the
EOL supervision relay to an on‑board
point on the control panel
6 If using 24 VDC, cut the wire
16 Connection to the other relay lead of
the EOL supervision relay to an
on‑board point on the control panel
7 Earth Ground
17 1 kΩ EOL resistor as specified for the
control panel
8 Common connection for external
power supply, control panel, EOL
18 Telco connection for alarm\trouble
signals
supervision relay, and D185 module
9 Positive (+) connection from power
19 Telco connection for supervisory signal
supply to EOL supervision relay
+12 VDC or +24 VDC input and D185
PWR + terminal
2013.05 | 03 | F.01U.034.781
Installation Instructions
Bosch Security Systems, Inc.
Reverse Polarity Signaling Module
Notices | en
11
10 G Series Relay B connection to D185
TRBL TRIG
6
Programming
6.1
Programming an FPD-7024 FACP
Relay 1 steady activation on alarm, Relay 2 steady activation on supervisory, and Relay 3
steady activation on trouble.
For programming details, see the control panel’s Installation and Operation Guide (IOG).
6.2
Programming a G Series control panel
Relay A steady activation on alarm, Relay B steady activation on trouble, and Relay C steady
activation on supervisory.
For programming details, see the control panel’s Program Entry Guide (PEG).
7
Specifications
Electrical
12 V
Power Inputs (for
standby battery
calculations)
Start up voltage
11 VDC
Minimum voltage
10.2 VDC
Maximum voltage
–
–
Alarm*
Supervisory
Trouble
245 mA
120 mA
Alarm current draw
300 mA
143 mA
Minimum
Maximum
Voltage
10.2 VDC
30 VDC
Current
2.25 mA
8.1 mA
Voltage
10.2 VDC
30 VDC
Current
2.25 mA
8.1 mA
Voltage
10.2 VDC
30 VDC
Current
2.25 mA
8.1 mA
Minimum
Maximum
0 mA
35 mA
Minimum
Maximum
Current
2.5 mA
15 mA
Nominal
10 mA
Supervisory Zone (current sink)
Telco Output Current
Adjustment Range
30 VDC
Idle current draw
Inputs
–
24 V
* The alarm activation delay is 20±5 sec
Bosch Security Systems, Inc.
Installation Instructions
2013.05 | 03 | F.01U.034.781
12
en | Notices
Reverse Polarity Signaling Module
Environmental
Environment
Indoor, dry
Relative Humidity
<93%, non‑condensing
Temperature
+32°F to +120°F (0°C to +49°C)
2013.05 | 03 | F.01U.034.781
Installation Instructions
Bosch Security Systems, Inc.
Bosch Security Systems, Inc.
130 Perinton Parkway
Fairport, NY 14450
USA
www.boschsecurity.com
© Bosch Security Systems, Inc., 2013
Download