Reverse Polarity Signaling Module D185 en Installation Instructions Reverse Polarity Signaling Module Notices | en 3 Notices 1 These instructions cover the installation of the D185 Reverse Polarity Signaling Module in a fire system supervised by a fire alarm control panel (FACP) or a combination Burglary/Fire control panel. Before installing the module, become familiar with the Installation and Operation Guide for the control panel you are using. Install, test and maintain the module according to these instructions, NFPA 72, local codes, and the authority having jurisdiction (AHJ). Failure to follow these instructions can result in failure of a detector to initiate an alarm event. Bosch Security Systems, Inc. is not responsible for improperly installed, tested or maintained devices. ! Warning! Follow these instructions to avoid personal injury and damage to equipment. NFPA 72 requires that you perform a complete system wide functional test following any modifications, repair, upgrades or adjustments made to the system’s components, hardware, wiring, programming and software/firmware. 2 Description The D185 Reverse Polarity Signaling Module connects a control panel with either a single set or a pair of leased telephone company (telco) lines in NFPA 72 remote station applications. The module’s three input terminals accept alarm, trouble, or supervisory input from the control panel, and the module transmits this information to a monitoring station after a built-in 20±5 sec) delay. This module operates with either a 12 VDC or 24 VDC supply. All circuits are power limited. The module can be used with the Bosch Security Systems, Inc. control panels indicated in the following table. You can also use the module with non-Bosch, UL Listed control panels where it is referenced as compatible in the control panel's installation instructions. Control panels Compatible relays See section: Active: FPD-7024 panel D275, PAM-4 Wiring to an FPD-7024 FACP, page 7 G Series (GV2 and higher) D275, PAM-4 panels Wiring to a G Series control panel, page 8 1 Legacy: D7024 panel See control panel documentation on the Bosch website (http://www.boschsecurity.com) G Series (prior to GV2) panels2 D9412, D7412, and D7212** panels DS9400 panel* Bosch Security Systems, Inc. Installation Instructions 2013.05 | 03 | F.01U.034.781 4 en | Notices Reverse Polarity Signaling Module Control panels 1 Compatible relays See section: G Series (GV2 or higher) = GV4 (D9412GV4, D7412GV4, and D7212GV4**), GV3 (D9412GV3, D7412GV3, and D7212GV3**), and GV2 (D9412GV2, D7412GV2, and D7212GV2**) panels 2 G Series (prior to GV2) = D9412G, D7412G, and D7212G** panels * Legacy products were investigated to comply only to UL864 8th edition ** indicates products which are not UL listed for commercial fire applications Figure 2.1: D185 reverse polarity signaling module 1 Input terminals 10 Connects to telco line for sending supervisory signals 2 Earth Ground 11 Connects to telco line for sending alarm\trouble signals 3 Common 12 Connects to telco line for sending alarm\trouble signals 4 Connects to control panel Aux or 13 Not used external power supply (12 VDC or 24 VDC) 5 Connects to Trouble Relay on control panel 14 Connects to end-of-line (EOL) supervisory relay (such as, D275, PAM‑4) 6 Connects to Supervisory Relay on 15 Alarm signal adjuster control panel 7 Connects to Alarm Relay on the control 16 Supevisory signal adjuster panel 8 Output terminals 17 Alarm Test LED 9 Connects to telco line for sending 18 Alarm Test switch supervisory signals 2013.05 | 03 | F.01U.034.781 Installation Instructions Bosch Security Systems, Inc. Reverse Polarity Signaling Module 3 Notices | en 5 Operation Under normal conditions, the module sends a steady 10 mA of current to the alarm telco outputs and 14 mA of current to the supervisory output which connects to a monitoring station. In an alarm or supervisory condition, the module reverses the output current polarity and signals a trouble condition by interrupting the output voltage and current. Input Output Alarm Supevisory Trouble Alarm Supervisory No Current No Current No Current Normal Normal No Current No Current Active High No Current Normal No Current Active High No Current No Current Reversed Polarity No Current Active High Active High No Current Reversed Polarity Active High No Current No Current Reversed Polarity Normal Active High Active High No Current Reversed Polarity Reversed Polarity Active High Active High Active High Reversed Polarity Reversed Polarity Table 3.1: Input and output states 3.1 Alarm and trouble responses (alarm output telco lines) The module responds to an alarm input from the control panel by reversing the alarm telco output polarity. The module responds to a trouble input from the control panel by interrupting the current to the alarm telco outputs If the control panel sends an alarm during a trouble signal, the module overrides the trouble telco output and responds with an alarm telco output (reversed polarity). 3.2 Supervisory response (supervisory output telco lines) The module responds to a supervisory signal input by reversing the polarity of the supervisory telco outputs. A second set of telco lines must be connected. 3.3 Alarm test The Alarm Test Switch (Item 18 in Figure 1 on page 2) disables module output during testing that triggers a trouble output from the module during testing. Generally, this switch is off but during an Alarm Test, you must move the switch to the ON position. Turning on the Alarm Test Switch lights the Alarm Test LED (Item 17 in Figure 1). 4 Installation Notice! Install the module within 20 ft (6 m) of the control panel with a minimum of 22 AWG (0.34 mm2) wire. Ensure all wiring is in conduit. Install the D185 in a system by: Bosch Security Systems, Inc. Installation Instructions 2013.05 | 03 | F.01U.034.781 6 en | Notices Reverse Polarity Signaling Module Danger! Inform the operator and the local AHJ before installing this module in an existing system. Disconnect all power to the control panel before installing this module. 1. Removing power from the control panel Before making or removing any connections to the FACP, remove the standby battery power. Remove AC power from the system at the dedicated 120 VAC breaker. 2. Mounting the module The module mounts on a snap-track and installs with a supplied screw in the control panel enclosure. 3. Connecting the module The module has twelve screw terminal connection points, six on the left side for inputs and six on the right side for outputs (see the D185 reverse polarity signaling module figure in Description, page 3 and the Wiring, page 6 section). Caution! ! Connect input power only to the PWR Terminals. 4. Restoring power to the control panel Restore AC power to the system at the dedicated 120 VAC breaker. Reconnect the standby battery power. 5. Adjusting the amount of output current To adjust the amount of output current required on the telco output, use a screwdriver to rotate the alarm signal adjuster. 5 Wiring An external 12 VDC or 24 VDC power supply listed for fire signaling units or commercial or residential burglary units can be used. The external power supply must be UL1481 or UL864 Listed, regulated, and power‑limited. Install the control panel and external power supply in the same room no more than 20 ft (6 m) apart. The interconnecting wires between the control panel and external power supply must be in conduit. The power source for both the auxiliary power supply and the control panel must be from the same dedicated AC branch circuit. 2013.05 | 03 | F.01U.034.781 Installation Instructions Bosch Security Systems, Inc. Reverse Polarity Signaling Module Notices | en 5.1 Wiring to an FPD-7024 FACP 5.1.1 Wiring for power supplied by the FACP 7 Figure 5.1: Wiring an FPD-7024 FACP to supply 12 VDC power to the D185 1 FPD-7024 FACP 11 Negative (-) connection from power supply to D185 2 D185 module 12 EOL supervision relay 3 Positive (+) power to Relay 3 (NC3) 13 Relay leads 4 Relay 3 (COM3) to trouble trigger 14 2.2 kΩ EOL resistor 5 Positive (+) power to Relay 2 (NO2) 15 D275 +12 VDC input (red wire) 6 Relay 2 (COM2) to supervisory trigger 16 Positive (+24 VDC) power connection from FACP to EOL supervision relay 7 Earth Ground 17 D185 supervisory zone connection to EOL supervision relay 8 Positive (+) power to Relay 1 (NC1) 18 Telco connection for supervisory signal 9 Relay 1 (COM1) to alarm trigger 19 Telco connection for alarm\trouble signals 10 Positive (+) power connection from FACP to D185 and EOL supervision relay Bosch Security Systems, Inc. Installation Instructions 2013.05 | 03 | F.01U.034.781 8 en | Notices 5.1.2 Reverse Polarity Signaling Module Wiring for power supplied by an external power supply Figure 5.2: Wiring an FPD-7024 FACP to a D185 with power supplied by an external power supply 1 FPD-7024 FACP 10 External power supply 2 D185 module 11 Positive (+) connection from power supply to FACP relays, EOL supervision relay, and D185 3 Positive (+) power to Relay 3 (NC3) 12 Negative (-) connection from power supply to D185 4 Relay 3 (COM3) to trouble trigger 13 EOL supervision relay 5 Positive (+) power to Relay 2 (NO2) 14 Relay leads 6 Relay 2 (COM2) to supervisory trigger 15 2.2 kΩ EOL resistor 7 Positive (+) power to Relay 1 (NC1) 16 D185 supervisory zone connection to EOL supervision relay 8 Relay 1 (COM1) to alarm trigger 17 Telco connection for supervisory signal 9 Earth Ground 18 Telco connection for alarm\trouble signals 5.2 Wiring to a G Series control panel 2013.05 | 03 | F.01U.034.781 Installation Instructions Bosch Security Systems, Inc. Reverse Polarity Signaling Module 5.2.1 Notices | en 9 Wiring for power supplied by the control panel Figure 5.3: Wiring G Series panels to supply power to a D185 1 D185 module 10 D185 SUPV TRIG connection to D130 2 G Series panel 11 G Series Relay A connection to D185 ALRM TRIG 3 EOL supervision relay 12 D185 SUPV ZONE connection to the EOL supervision relay 4 D130 relay 13 G Series Relay C connection to EOL supervision relay 5 If using 24 VDC, cut the wire 14 Connection to one relay lead of the EOL supervision relay to an on‑board point on the control panel 6 Earth Ground 15 Connection to the other relay lead of the EOL supervision relay to an on‑board point on the control panel 7 Common connection between control panel, D130 relay, and D185 module control panel 8 +12 VDC aux power from control panel 17 Telco connection for supervisory signal 9 G Series Relay B connection to D185 18 Telco connection for alarm\trouble TRBL TRIG Bosch Security Systems, Inc. 16 1 kΩ EOL resistor as specified for the signals Installation Instructions 2013.05 | 03 | F.01U.034.781 10 en | Notices 5.2.2 Reverse Polarity Signaling Module Wiring for power supplied by an external power supply Figure 5.4: Wiring G Series panels to a D185 with power supplied by an external power supply 1 D185 module 11 D185 supervisory trigger connection to D130 relay 2 G Series panel 12 G Series Relay A connection to D185 ALRM TRIG 3 External power supply 13 D185 supervisory zone connection to the EOL supervision relay 4 EOL supervision relay 14 G-series Relay C connection to the D130 relay 5 D130 relay 15 Connection to one relay lead of the EOL supervision relay to an on‑board point on the control panel 6 If using 24 VDC, cut the wire 16 Connection to the other relay lead of the EOL supervision relay to an on‑board point on the control panel 7 Earth Ground 17 1 kΩ EOL resistor as specified for the control panel 8 Common connection for external power supply, control panel, EOL 18 Telco connection for alarm\trouble signals supervision relay, and D185 module 9 Positive (+) connection from power 19 Telco connection for supervisory signal supply to EOL supervision relay +12 VDC or +24 VDC input and D185 PWR + terminal 2013.05 | 03 | F.01U.034.781 Installation Instructions Bosch Security Systems, Inc. Reverse Polarity Signaling Module Notices | en 11 10 G Series Relay B connection to D185 TRBL TRIG 6 Programming 6.1 Programming an FPD-7024 FACP Relay 1 steady activation on alarm, Relay 2 steady activation on supervisory, and Relay 3 steady activation on trouble. For programming details, see the control panel’s Installation and Operation Guide (IOG). 6.2 Programming a G Series control panel Relay A steady activation on alarm, Relay B steady activation on trouble, and Relay C steady activation on supervisory. For programming details, see the control panel’s Program Entry Guide (PEG). 7 Specifications Electrical 12 V Power Inputs (for standby battery calculations) Start up voltage 11 VDC Minimum voltage 10.2 VDC Maximum voltage – – Alarm* Supervisory Trouble 245 mA 120 mA Alarm current draw 300 mA 143 mA Minimum Maximum Voltage 10.2 VDC 30 VDC Current 2.25 mA 8.1 mA Voltage 10.2 VDC 30 VDC Current 2.25 mA 8.1 mA Voltage 10.2 VDC 30 VDC Current 2.25 mA 8.1 mA Minimum Maximum 0 mA 35 mA Minimum Maximum Current 2.5 mA 15 mA Nominal 10 mA Supervisory Zone (current sink) Telco Output Current Adjustment Range 30 VDC Idle current draw Inputs – 24 V * The alarm activation delay is 20±5 sec Bosch Security Systems, Inc. Installation Instructions 2013.05 | 03 | F.01U.034.781 12 en | Notices Reverse Polarity Signaling Module Environmental Environment Indoor, dry Relative Humidity <93%, non‑condensing Temperature +32°F to +120°F (0°C to +49°C) 2013.05 | 03 | F.01U.034.781 Installation Instructions Bosch Security Systems, Inc. Bosch Security Systems, Inc. 130 Perinton Parkway Fairport, NY 14450 USA www.boschsecurity.com © Bosch Security Systems, Inc., 2013