CHENNAI INSTITUTE OF TECHNOLOGY Kundrathur to Sriperumbudur Highway, Kundrathur,Nandhambakkam Post, Pudupedu, Chennai– 600 069. DEPARTMENTOF ELECTRONICS AND COMMUNICATION ENGINEERING LABORATORY MANUAL EE 6461Electrical Engineering and Control System Laboratory LIST OF EXPERIMENTS 1. Open circuit and load characteristics of separately excited and self excited D.C.Generator. 2. Load test on DC shunt motor. 3. Swinburne’s test and speed control of DC shunt motor. 4. Load test on single phase transformer and open circuit and short circuit test on single phase transformer 5. Regulation of three phase alternator by EMF and MMF methods. 6. Load test on three phase induction motor. 7. No load and blocked rotor tests on three phase induction motor (Determination of equivalent circuit parameters and predetermination of performance characteristics at various loads) 8. Study of D.C. motor and induction motor starters. 9. Digital simulation of linear systems. 10. Stability analysis of linear system using MATLAB. 11. Study the effect of P, PI, PID controllers using MATLAB. 12. Design of lead and lag compensator. 13. Transfer function of separately excited D.C. generator. 14. Transfer function of armature and field controlled DC motor 2 Ex. No: 1A Date: OCC AND LOAD CHARACTERISTICS OF SEPARATELY EXCITED D.C GENERATOR Aim: To conduct no load and load test on separately excited generators and to obtain the characteristics Exercise 1. Obtain the open circuit characteristics (OCC) of a separately excited D.C generator and determine critical resistance. 2. Draw the external and internal characteristics of a separately excited D.C generator and compute full load regulation. Apparatus Required: Sl.no Name of the component Specification Quantity Name plate details: Motor Generator Fuse rating calculation for field and armature: No load test 10 % of rated current (full load current) Load test 125 % of rated current (full load current) Precautions 1. Motor side field rheostat should be kept at minimum resistance position. 2. Generator side field rheostat should be kept at maximum resistance position. 3. Starter should be in off position before switching on the supply. 4. The DPST switch must be kept open. 3 CIRCUIT DIAGRAM FOR OPEN CIRCUIT ON SEPARATELY EXCITED DC GENERATOR Procedure for open circuit test 1. Connections are given as per the circuit diagram. 2. The motor is started with the help of THREE POINT starter. 3. Adjust the motor speed to rated speed by adjusting motor field rheostat when the generator is disconnected from the load by DPST switch 2. 4. By varying the generator field rheostat gradually, the open circuit voltage [Eo] and corresponding field current (If) are tabulated up to 125 % of rated voltage of generator. 5. The motor is switched off by using DPST switch 1 after bringing all the rheostats to initial position. Tabulation for Open Circuit Test on Separately Excited D.C Generator: Sl.no Open circuit Field voltage in current in Volts [Eo] Amps [If] CIRCUIT DIAGRAM FOR LOAD TEST ON SEPARATELY EXCITED DC SHUNT GENERATOR 4 Procedure for Load test: 1. Connections are given as per the circuit diagram 2. The prime mover is started with the help of three point starter and it is made to run at rated speed when the generator is disconnected from the load by DPST switch 2. 3. By varying the generator field rheostat gradually, the rated voltage [Eg] is obtained. 4. The ammeter and voltmeter readings are observed at no load condition. 5. The ammeter and voltmeter readings are observed for different loads up to the rated current by closing the DPST switch 2. 6. After tabulating all the readings the load is brought to its initial position. 7. The motor is switched off by using DPST switch 1 after bringing all the rheostats to initial position. Tabulation for Load Test: Sl.no Armature current [Ia] in Amps Load voltage [VL] in Volts Load current [IL] in Amps Armature drop Ia Ra In volts Generated emf [Eg = VL+IaRa] In volts 5 Circuit diagram for find the generator armature resistance [Ra] Procedure for find armature resistance Ra: 1. Connections arte given as per circuit diagram 2. Check loading rheostat must be at maximum resistance position. 3. Close the DPST switch and vary the loading rheostat for various values in steps and noted the corresponding voltmeter and ammeter reading. 4. Open the DPST switch after loading rheostat begins its initial position. Tabulation for Finding Armature Resistance: Open circuit voltage in Volts [Eo] Model graph Open circuit characteristics Eo Vs If If Field current [If] in amps Armature current I Ra = Va/ Ia Internal (Eg Vs Ia) and External (VL Vs IL) characteristics Load voltage in Volts [VL] Armature voltage Va Generated emf in Volts [Eg] Sl.no Eg Vs Ia VL Vs IL Load current [IL] in amps Armature current [Ia] in amps Result: 6 Ex. No: 1B Date: OCC AND LOAD CHARACTERISTICS OF SELF EXCITED D.C SHUNT GENERATOR Aim: To conduct no load and load test on self excited generators and obtain the characteristics Exercise 1. Obtain the open circuit characteristics (OCC) of a self excited D.C generator and determine critical resistance. Draw the external and internal characteristics of a self excited D.C generator and compute full load regulation. 2. Apparatus Required: Sl.no Name of the component Specification Quantity Name plate details: Motor Generator Fuse rating calculation for field and armature: No load test 10 % of rated current (full load current) Load test 125 % of rated current (full load current) Formula used: Generated voltage Eg = VL + Ia Ra Precautions 1. Motor side field rheostat should be kept at minimum resistance position. 2. Generator side field rheostat should be kept at maximum resistance position. 3. Starter should be in off position before switching on the supply. 4. The DPST switch must be kept open. 7 CIRCUIT DIAGRAM FOR OPEN CIRCUIT TEST ON SELF EXCITED DC SHUNT GENERATOR Procedure for open circuit test 1. Connections are given as per the circuit diagram. 2. The motor is started with the help of THREE POINT starter. 3. Adjust the motor speed to rated speed by adjusting motor field rheostat when the generator is disconnected from the load by DPST switch 2. 4. By varying the generator field rheostat gradually, the open circuit voltage [Eo] and corresponding field current (If) are tabulated up to 125 % of rated voltage of generator. 5. The motor is switched off by using DPST switch 1 after bringing all the rheostats to initial position. CIRCUIT DIAGRAM FOR LOAD TEST ON SELF EXCITED DC SHUNT GENERATOR Procedure for Load test: 1. Connections are given as per the circuit diagram 2 The prime mover is started with the help of three point starter and it is made to run at rated speed when the generator is disconnected from the load by DPST switch 2. 3. By varying the generator field rheostat gradually, the rated voltage [Eg] is obtained. 4. The ammeter and voltmeter readings are observed at no load condition. 5. The ammeter and voltmeter readings are observed for different loads up to the rated current by closing the DPST switch 2. 8 6. 7. After tabulating all the readings the load is brought to its initial position. The motor is switched off by using DPST switch 1 after bringing all the rheostats to initial position. Tabulation for Open Circuit Test on Separately Excited D.C Shunt Generator: Sl.no Open circuit Field voltage in current in Volts [Eo] Amps [If] Tabulation for Load Test: Sl.no Armature current [Ia] in Amps Load voltage [VL] in Volts Load current [IL] in Amps Armature drop Ia Ra In volts Generated emf [Eg = VL+IaRa] In volts Circuit diagram for find the generator armature resistance [Ra] Procedure for find armature resistance Ra: 1. Connections are given as per circuit diagram 2. Check loading rheostat must be at maximum resistance position. 3. Close the DPST switch and vary the loading rheostat for various values in steps and noted the corresponding voltmeter and ammeter reading. 4. Open the DPST switch after loading rheostat begins its initial position. 9 Tabulation for Finding Armature Resistance: Sl.no Armature voltage Va Armature current I Ra = Va/ Ia Open circuit voltage in Volts [Eo] Model graph Open circuit characteristics Eo Vs If If Load voltage in Volts [VL] Generated emf in Volts [Eg] Field current [If] in amps Internal (Eg Vs Ia) and External (VL Vs IL) characteristics Eg Vs Ia VL Vs IL Load current [IL] in amps Armature current [Ia] in amps Result: 10 Ex. No: 2 Date: LOAD CHARACTERISTICS OF DC SHUNT MOTOR Aim: To conduct load test on DC shunt motor and compound motor and draw the characteristic curves Exercise Draw the following characteristic curves for DC shunt motor i. Output Vs η% ii. Output Vs T iii. Output Vs N iv. Output Vs IL v. Torque Vs N Apparatus Required: Sl.no Name of the component type Range - Quantity Name plate details: MOTOR Fuse rating calculation for field and armature: Load test 125 % of rated current Formulae Used: t (i) Torque = ( S1 ~ S 2 ) 9.81 ( R ) in N-M 2 S1, S2 – spring balance readings in Kg R- Break drum radius in m (ii) Input power = V x I in Watts (iii) Output power = 2NT / 60 in Watts N – Speed of the motor in RPM (iv) Percentage of efficiency = (Output power /Input power) x 100. CIRCUIT DIAGRAM FOR LOAD TEST ON DC SHUNT MOTOR 11 Precautions Starter should be in off position before switching on the supply. The DPST switch must be kept open. The motor field rheostat must be kept at minimum resistance position There should be no load on the motor at the time of starting. Before connecting the meters check the polarity and zero error. Procedure for DC shunt motor Connections are given as per the circuit diagram. Observe the precaution and using three-point starter the motor is started to run at the rated speed by adjusting the field rheostat if necessary. The meter readings are noted at no load condition. By using break drum with spring balance arrangement the motor is loaded and the corresponding readings are noted up to the rated current. After observation of all the readings the load is released gradually The motor is switched off by using DPST switch. TABULATION FOR LOAD TEST ON DC SHUNT MOTOR Radius of the brake drum (R) = Sl No Load Load speed Voltage current in in I rpm Volts Amps in m Thickness of the belt (t) = in m Spring balance Reading In kg S1 S2 Input Output Power Torque Power Efficiency in in NM in in % Watts S1S2 Watts 12 MODEL GRAPH (A) Electrical characteristics in % IL T % N T in N-m Speed in rpm IL in Amps Output power in watts Speed (N) in rpm (B) Mechanical characteristics T Vs N Torque ( T ) in N-m (C) Torque, Speed Vs Load current 13 Speed (N) in rpm Torque (T) in N-m IL Vs N IL Vs T Load current (IL) in Amps Model calculation: Graph: Output Vs η% Output Vs T Output Vs N Output Vs IL Torque Vs N Result: Ex. No: 3 Date: SWINBURNE’S TEST AND SPEED CONTROL OF DC SHUNT MOTOR Aim To conduct Swinburne’s test and predetermine the performance characteristics of DC machine and speed control of DC motor Exercise 1. Predetermine efficiency at various load current while operating as a motor and generator and plot a graph output Vs η% 2. Draw the following curves for a. If Vs N at Va = 0.8 Va and 1Va b. Va Vs N at 0.8 If and If Apparatus Required: Sl.no Name of the component type Range Quantity 14 Name plate details: Motor Speed Type Field Armature Fuse rating calculation: CIRCUIT DIAGRAM TO FIND THE CONSTANT LOSS Precaution: 15 Starter should be in off position before switching on the supply. The DPST switch must be kept open. The motor field rheostat must be kept at minimum resistance position The motor armature rheostat must be kept at maximum resistance position. Before connecting the meters check the polarity and zero error. Procedure Connections are given as per the circuit diagram. Observe the precaution and switch ON the supply. By adjusting the field rheostat get the motor speed to rated speed A. Armature Control Method Keep the Field Current Constant By adjusting armature rheostat the speed and armature voltage are noted. Repeat the same procedure for various positions. B. Field Control Method Keep the armature voltage constant. By adjusting the field rheostat various field currents and voltage are noted. Repeat the same procedure for various positions Tabulation for Armature Control Method Field current I1 Armature Speed N in RPM voltage Va Field current I2 Armature Speed N in voltage Va RPM Tabulation for Field Control Method Armature Voltage V1 Field Current If In AMPS Speed N in RPM Armature Voltage V2 Field Current If In AMPS Speed N in RPM 16 Result: Ex. No: 4 Date: OC AND SC TESTS ON SINGLE PHASE TRANSFORMER Aim: To conduct open circuit and short circuit test and to predetermine the efficiency of the transformer at desired load and power factor and to calculate the regulation at different power factor Exercise 1. Determine the equivalent circuit of the transformer. 2. Predetermine the efficiency at different load at UPF and 0.8 Power factor lagging. 3. Predetermine the full load regulation at different power factor. 4. Draw the following curves a. Output Vs η% b. Power factor Vs %Regulation Apparatus Required: Sl.no Name of the component type Range Quantity - Name plate details: Transformer 17 Fuse calculation for transformer (O.C and S.C test): Primary current IP = KVA rating of the transformer /primary voltage. Secondary current IS =KVA rating of transformer / secondary voltage. O.C test 10 % of rated primary current S.C test 125 % of rated secondary current Formulae Used: Open circuit test: Woc 1. No load power factor (cos 0 ) Voc I oc WOC = open circuit power in watts VOC = open circuit voltage in volts IOC = open circuit current in amps VOC 2. No load working component resistance (RO); RO in ohms I OC Coso VOC 3. No load magnetizing component (XO); X O in ohms I OC Sino Short circuit test: V 4. Equivalent impedance referred to HV side (Z02); Z O 2 SC in ohms. I SC W 5. Equivalent resistance referred to HV side (R02); RO 2 SC2 in ohms I SC 6. Equivalent reactance referred to HV side (X02); X O 2 Z O 2 RO 2 in ohms 2 2 V2 V1 R 8. Equivalent resistance referred to LV side (R01); RO1 O22 in ohms K X 9. Equivalent reactance referred to LV side (X01); X O1 O22 in ohms K Efficiency and regulation 10. Output power = ( X KVA Cos ) in watts 11. Chopper loss = ( X 2 WSC ) in watts 7. Transformation ratio (K); K 12. Total loss WT = (Cu loss Iron loss ) in watts Output power 100 in % Output power Total loss X I SC [ RO 2 Cos X O 2 Sin 100 in % 14. Regulation = V2O 13. Efficiency = 18 Precautions: 1. Auto transformer should be kept at zero volt position. 2. At the time of starting the experiment DPST switch kept open and transformer should be no load. 3. High voltage and low voltage sides of the transformer should be properly used as primary or secondary respective to experiments. Procedure (for Open circuit Test) Connections are given as per the circuit diagram. Ensuring the precautions the supply is switched on by closing DPST switch. Auto transformer is adjusted to energize the transformer with primary voltage on LV side. Voltmeter, ammeter and wattmeter readings are noted at no load condition. Auto transformer is gradually decreased to its initial position. Switch off the supply by DPST. Procedure (for Short CKT Test) Connections are given as per the circuit diagram. Ensuring the precautions the supply is switched on by closing DPST switch. Auto transformer is adjusted to energize the transformer with primary current on the HV side. Voltmeter, ammeter and wattmeter readings are noted at no load condition. Auto transformer is gradually decreased to its initial position. Switch off the supply by DPST. Circuit diagram for open circuit test of 1 transformer Circuit diagram for short circuit test of 1 transformer 19 Tabulation for OC Test multiplication factor: Open circuit Open circuit power Open circuit Sl. primary current (Woc) in Watts primary voltage no (IOC) (VOC) in Volts Observed Actual In Amps Tabulation for SC Test Short circuit Sl. primary current No (ISC) In Amps multiplication factor: Short circuit power Short circuit (Wsc) in Watts primary voltage (VSC) in Volts Observed Actual Predetermination of efficiency: Core (or) Iron loss (Wi) = Rated Short circuit current = Fraction of load/ Load factor (X) Short circuit current (ISC X) in Amps 0.4 0.6 Short circuit Secondary Current in Amps Watts, KVA rating of Transformer = Amps Short Circuit power (WSC) = Output power ( X KVA Cos ) in watts 0.2 Open circuit Secondary voltage in volts 0.8 1 . . Copper Efficiency Total loss loss W Wi WSC o / p X 100 ( X 2 WSC ) T o / p WT in watts in watts in % 20 ¼ ½ ¾ 1 Tabulation to predetermine % Voltage regulation: ISC = RO2= XO2= Fractio n of load (X) Value of Cos 1 0. 8 0. 6 0. 4 V2O= % of Regulation X I SC [ RO 2 Cos X O 2 Sin 100 V2O 0.8 0.6 0.4 0.2 Value of Sin 0. 2 1 0. 8 0. 6 0.4 0.2 1 Lag Lead Lag Lead Lag Lead Lag Lead ¼ ½ ¾ 1 Model graph 1) Efficiency 2) Regulation 21 Result: EXPT NO: 4.b Date : LOAD TEST ON A SINGLE PHASE TRANSFORMER AIM: To conduct a direct load test on the given single phase transformer and to determine the efficiency and regulation at different load conditions. NAME PLATE DETAILS: KVA rating = Rated H.V side Voltage = Rated L.V side Voltage = INSTRUMENTS AND EQUIPMENTS REQUIRED: S.No Equipment Type 1. 2. 3. 4. 5. Range Quantity THEORY: Direct load test is conducted to determine the efficiency characteristics and regulation characteristics of the given transformer. An ideal transformer is supposed to give constant secondary voltage irrespective of the load current. But, practically the secondary voltage decreases as the transformer is loaded due to primary 22 and secondary impedance drops. Since these drops are dependent on load current, this variation in terminal voltage is found using direct loading. PRECAUTIONS: 1. Remove the fuse carriers before wiring and start wiring as per the circuit diagram. 2. Fuse Calculations: This being a load test, the required fuse ratings are 120% of rated current on L.V side. PROCEDURE: 1. The circuit connections are made as per the circuit diagram as shown in figure. 2. Keeping the autotransformer in its minimum position and the DPST switch in open position, the main supply is switched ON. 3. By slowly and carefully operating the Auto transformer the rated voltage (115V) is applied to the L.V side of the transformer. 4. Under this no-load condition one set of readings namely VH.V, IH.V, WH.Vs, VL.V, WL.V, are recorded in the tabular column. 5. The DPST switch on the load side is now closed and the load is increased in gradual steps and at each step all meter readings are noted down in the tabular column. CIRCUIT DIAGRAM: 6. The procedure is continued until the current on the H.V side is equal to its full load value. 7. After the experiment is completed, the load is decreased to its minimum, the auto transformer is brought back to its original position and then the main supply is switched OFF. CALCULATIONS:- 23 I. EFFICIENCY CALCULATION: i . The efficiency of the transformer for each set of reading is calculated and tabulated using the expression, Output % X 100 Input where, The output of the transformer = VH.V * IH.V on the H.V side The input of the transformer = WL.V = Wattmeter reading on the L.V side ii . A Graph is plotted between the percentage efficiency and the output, taking % efficiency on Y-axis and the output on X-axis, as shown in figure. II . REGULATION CALCULATIONS: i . The regulation is calculated and tabulated for each set of readings using the expression , % Re gulation VH .V ( Nolaad) VH .V (load) VH .V ( Noload) X 100 where, VH.V(No-load) - is the no-load voltage on the H.V side . VH.V(Load) - is the actual voltage on the H.V side under load condition . ii . A Graph is plotted b= ween the percentage regulation and the output taking % regulation on Y-axis and the output on X- axis as shown in figure. TABULAR COLUMN: Input Out put (%) VL.V IL.V WL.V (W) VH.V (V) IH.V (A) %REG WH.V (watts) 24 MODEL CALCULATION: MODEL GRAPH: RESULT: - 25 Ex. No: 5 Date: Predetermination of Regulation of Three Phase Alternator by EMF and MMF Methods AIM: To predetermine the regulation of three phase alternator by EMF and MMF method and also to draw the vector diagrams. Name plate details: 3 Alternator DC Shunt Motor Fuse rating: 125 % of current (Full load current) For dc shunt motor. For alternator Apparatus required: s. no Name of the apparatus Formulae used: Emf method: Armature resistance Ra Synchronous impedance Zs Synchronous impedance Xs Open circuit voltage Eo Open circuit voltage Eo Open circuit voltage Eo Percentage regulation Precaution: Type Range Quantity = 1.6 Rdc where - Rdc is the resistance in DC supply. = Open circuit voltage (E1 (ph))/short circuit current (Isc) = (Zs2-Ra2) = ((Vrated cos + Ia Ra) 2 + (Vrated sin +IaXs)2)(For lagging power factor) = ((Vrated cos + Ia Ra)2+(Vrated sin - IaXs)2) (For leading power factor) = ((Vrated cos + Ia Ra)2+( IaXs)2) (For unity power factor) = (Eo-Vrated /Vrated)*100(For both EMF and MMF methods) 26 i. ii. iii. The motor field rheostat should be kept in the minimum resistance position. The alternator field potential divider should be in the maximum voltage position. Initially all switches are in open position. Procedure for both emf and MMF method: 1. 2. 3. 4. Note down the nameplate details of motor and alternator. Connections are made as per the circuit diagram. Give the supply by closing the dust switch. Using the three point starter, start the motor to run at the synchronous speed by varying the motor filed rheostat. 5. Conduct an open circuit test by varying the potential divider for various values of field current and tabulate the corresponding open circuit voltage readings. 6. Conduct a short circuit test by closing the TPST switch and adjust the potential divider to set the rated armature current, tabulate the corresponding field current. 7. Conduct a stator resistance test by giving connection as per the circuit diagram and tabulate the voltage and current readings for various resistive loads. Procedure to draw the graph for EMF method: 1. Draw the open circuit characteristics curve (generator voltage per phase Vs field current) 2. Draw the short circuit characteristics curve (short circuit current Vs field current) 3. From the graph find the open circuit voltage per phase (E1 (ph)) for the rated short circuit current (Isc). 4. By using respective formulae find the Zs, Xs, Eo and percentage regulation. Open circuit test: S.NO Field current(If) Amps Open circuit line voltage (VOL) Volts Open circuit phase voltage (Vo(ph)) Volts 27 28 Short circuit test: S.No Field current(If) Amps Short Circuit Current (120 to 150 % of rated current ) (Isc) Amps Tabulation to find out the armature resistance (ra): S.No Armature current (I) Amps Armature voltage (V) Volts Armature Resistance Ra=V/I Ohms Procedure to draw the graph for MMF method: 1. 2. 3. 4. Draw the open circuit characteristics curve (generator voltage per phase Vs field current) Draw the short circuit characteristics curve (short circuit current Vs field current) Draw the line OL to represent If’ which gives the rated generated voltage (V). Draw the line LA at an angle (90Φ) to represent If” which gives the rated full load current.(Isc) on short circuit [(90Φ) for lagging power factor and (90- Φ) for leading power factor]. 5. Join the points O and A and find the field current (If) measuring the distance OA that gives the open circuit voltage (E0) from the open circuit characteristics. 6. Find the percentage regulation by using suitable formula. Procedure to draw the vector diagram: 1. Draw the line OA that represents the rated voltage V. 2. Draw the line OB to represent the rated current Ia, which makes an angle Φ (it may lags/leads in phase) with the voltage. 3. Draw the line AC to represent IRa drop, which is parallel to current axis (OB) 4. Draw the perpendicular line CD with the line AC (IRa drop) to represent IXs drop. 5. Join the points D and A to represent the IZs drop. 6. Join the points O and D and measure the length OD by voltage scale to find open circuit voltage Eo. 7. Find the percentage regulation by using suitable using formulae. RESULTANT TABULATION FOR REGULATION OF THREE PHASE ALTERNATOR BY EMF AND MMF METHODS 29 MODEL CALCULATION: S.N o Power factor 1. 0.2 2. 0.4 3. 0.6 4. 0.8 5. 1.0 EMF method Lagging Leading MMF method unity Lagging Leading unity RESULT Ex. No:6 Date: Load Test on Three - Phase Induction Motor(Squirrel cage) Aim: To conduct the load test on three phase squirrel cage induction motor and to draw the performance characteristics curves. Name plate details: 3 Induction Motor Auto Transformer Fuse rating: 30 125% of rated current (Full load current) Apparatus required: S.No Name of the Apparatus Type Range qty 1. 2. 3 4 Formulae used: 1. Torque 2. Output power 3. Input power 4. Percentage of efficiency 5. Percentage of slip 6. Power factor (cos ) = (S1S2) (R+t/2) x 9, 81 N-m. S1, S2 – spring balance readings in Kg. R – Radius of the brake d5rum in m. T – Thickness of the belt in m. = 2NT/60 Watts N – Rotor speed in rpm. T – Torque in N-m. = (W1+W2) Watts W1, W2 – Wattmeter readings in watts. = (Output power/Input power) x 100% = (Ns – N)/Ns x 100% Ns – Synchronous speed in rpm. N – Speed of the motor in rpm. = (W1+W2)/3 VLIL. Circuit diagram i. The motor should be started without any load PROCEDURE: 31 1. 2. 3. 4. 5. 6. Note down the name plate details of motor. Connections are made as per the circuit diagram. The TPSTS is closed and the motor is started using On Line starter to run at rated speed. At no load the speed, current, voltage and power are noted. By applying the load, for various values of current the above-mentioned readings are noted. The load is later released and the motor is switched off and the graph is drawn. OBSERVATION: Circumference of the brake drum = Thickness of the belt = MODELGRAPH: The graph drawn for Output power Vs speed Output power Vs line current Output power vs. Torque Output power Vs power factor Output power Vs Efficiency Output power Vs %slip. Mechanical Characteristics Speed in rpm Torque Vs Speed Torque in N-m Electrical Characteristics 32 T in N-m IL Cos N in rpm S % Sli p % in NT m N in rpm Cos Out put Power in Watts TABULATION FOR LOAD TEST ON THREE PHASE SQUIRREL CAGE INDUCTION MOTOR Multiplication factor: ………….. S. no Load current (IL) Amps Load voltage (VL) Volts Input power (W1) Input power (W2) Observed Actual Observe d Actual Watts Watts Watts Watts Speed of the motor (N) rpm Spring balance reading S 1 S 2 S1 ~S 2 K g Kg Kg Torqu e (T) (s1~s 2) (R) (9.81) Output power 2NT/ 60 Efficienc y () o/p / i/p x 100 Slip (S) (Ns-N) / Ns x 100 N-m Watts % % MODEL CALCULATION: 33 Power factor (cos) i/p / VLIL RESULT: Ex. No: 7 Date: NO LOAD TEST AND BLOCKED ROTOR TEST ON THREE PHASE SQUIRREL CAGE INDUCTION MOTOR Aim: To conduct the No Load test and Blocked rotor on three phase squirrel cage induction Motor and to predetermine the performance characteristics at various loaded conditions. Name plate details: 3 INDUTION MOTOR AUTO TRANSFORMERS Fuse Rating calculation: No Load: 10% of rated current (Full load current) Load: 125% of rated current (Full load current) Apparatus required: S .No Name of the Type Range Apparatus 1 2 3 Qty 34 4. 5. Formulae used: Open circuit test: No load power factor ( Cos o) Working component current (IW) Magnetizing current (Im) No Load resistance (Ro) No load reactance (Xo) = Po / Vo Io = Io(ph) x Cos o = Io (ph) x Sin o = Vo / Io (ph) Cos o in = Vo / Io (ph) Sin o in Where: Vo – No load voltage per phase in volts Io – no load current per phase in amps Po – no load power per phase in watts Short circuit test: Motor equivalent impedance referred to stator (Zsc (ph)) = Vsc(ph) / Isc (ph) in Motor equivalent resistance referred to stator (Rsc(ph)) = Psc(ph) / I2sc (ph) in Motor equivalent reactance referred to stator (Xsc(ph)) = (Zsc(ph)2 / Rsc (ph)2 )in ROTOR resistance referred to stator (R2’ (ph)) = Rsc(ph) – R1 in Rotor reactance referred to stator (X2’ (ph)) = Xsc(ph) / 2 = X1 in Equivalent load resistance (RL’) = R2’ (1/s – 1) in Where: R1 – stator resistance per phase X1 – stator reactance per phase R1= R (ac) = 1.6 x R (dc) = R2’ (1/s-1) in Slip (S) = (Ns-N) / Ns Ns – Synchronous speed in rpm N- Speed of the motor in rpm Circuit diagram of No load test of 3 induction motor 35 Circuit diagram of Blocked Rotor test of 3 induction motor Procedure: Note down the name plate details of motor 1. For no-load or open circuit test by adjusting autotransformer, apply rated voltage and note down the ammeter and wattmeter readings .In this test rotor is free to rotate. 2. For short circuit or blocked rotor test by adjusting autotransformer, apply rated current and note down the voltmeter and wattmeter readings. In this test rotor is blocked. 3. After that make the connection to measure the stator resistance as per the circuit Diagram 4. By adding the load through the loading rheostat note down the ammeter, voltmeter reading for various values of load Tabulation for No load test on three phase squirrel cage induction Speed of the induction motor: ………….. Type of the stator connection: …………… Multiplication factor: ……….. No load power . No No load Current (Io) No Load Voltage (Vo) Amps Volts W1 W2 Observed Actual Observed Actual Watts Watts Watts Watts Total No Load Power Po = (W1+W2) Watts No load power / phase Po(ph) = (Po/3) Watts No load Current / Phase Io (ph) No load Voltage / phase Vo (ph) Amps Volts 36 Tabulation for blocked rotor test on three phase squirrel cage induction Type of the stator connection: …………… Multiplication factor: ……….. No Short Circuit Current (Isc) Short Circuit Voltage (Vsc) Amps Volts Short Circuit power W1 W2 Observed Actual Observed Actual Watts Watts Watts Watts Total Short Circuit Power Po = (W1+W2) Watts Short Circuit power / phase Psc (ph) = (Psc/3) Watts Short Circuit Current / Phase Isc (ph) Short Circuit Voltage / phase Vsc (ph) Amps Volts Measurement of armature resistance Tabulation to find out the stator resistance (r1) 37 S No Stator current (I) Stator Voltage (V) Amps Volts Stator Resistance Rs = V/I Ohms MODEL CALCULATION: Equivalent circuit of 1 induction motor P R1 X1 I1 I2 R2’ X2’ Io 230 V, 1, 50Hz AC Supply Ro Xo RL’ = R2’ (1/s-1) N RESULT: 38 Expt. No: 8 Date: TRANSFER FUNCTION OF SEPERATELY EXCITED DC GENERATOR AIM: To determine the transfer function of separately excited dc generator. INSTRUMENTS & EQUIPMENTS REQUIRED: S. No 1 Name of the Equipment Range Type No of Quantity 2. 3. 4. 5. NAME PLATE DETAILS: D.C.GENERATOR: D.C.MOTOR: Rated voltage: Rated voltage: Rated Current: Rated Current: Rated Speed: Rated Speed: Power Rating: Power Rating: EXCITATION: Voltage: Current: 39 CIRCUIT DIAGRAM: THEORY: The transfer function for DC generator is defined as ratio of Laplace Transform Of output V1(t) to Laplace Transform of Input Vf(t). Transfer function = V1(t) / Vf(t) The KVL to field circuit is Vf(t) = If(t)Rf + Lf (dIf(t) /dt) ………………… 1 The armature induced emf Ea(t) is Ea(t) If(t) = Kf If(t) ………………… 2 where Kf is proportionality constant The KVL to armature circuit is given by 40 Ea(t) = Ia(t) (Ra +RL) +La (dIa /dt) ………………… 3 V1(t) = Ia(t) RL ………………… 4 The load voltage Ia(t) = IL(t) Taking Laplace transform for equations 1,2,3 & 4 we get Vf(s) = If(s) Rf + sLf If(s) ………………… 5 Ea(s) = Kf If(s) ………………… 6 Ea(s) = Ia(s) (Ra +RL) + sLa Ia(s) ………………… 7 V1(s) = Ia(s) RL ………………… 8 From the above equations we get Ea(s) = Kf Vf(s) / (Rf + sLf ) ………………… 9 From 7 & 9 Kf Vf(s) / (Rf + sLf ) = Ia(s) (Ra +RL) + sLa Ia(s) ………………… 10 From equation 10 Ia(s) = {Kf Vf(s) / (Rf + sLf ) [(Ra +RL) + sLa ]} ………………… 11 V1(s) = {Kf Vf(s) R1 / (Rf + sLf ) [(Ra +RL) + sLa ]} V1(s) / Vf(s) = {Kf R1 / (Rf + sLf ) [(Ra +RL) + sLa ]} G(s) = V1(s) / Vf(s) = {Kf R1 / (Rf + sLf ) [(Ra +RL) + sLa ………………… 12 G(s) = V1(s) / Vf(s) = { (Kf RL / Lf La ) / (s + Rf / Lf) (s + (Ra +RL) /La )} Where Lf / Rf = field time constant, La / Ra = armature time constant La / (Ra +RL) = total time constant The above equation is known as the load transfer function of separately excited D.C generator. PRECAUTIONS: (Not to be included in the Record) 41 1. Remove the fuse carriers before wiring and Start wiring as per the circuit diagram. 2. Check the positions of the various rheostats as specified. 3. The SPST switch is kept open at the time of starting the experiments. 4. Fuse calculations: As this is a no-load test the required fuse ratings are 20% of the rated current. 5. Replace the fuse carriers with appropriate fuse wires after the circuit connections are checked by the staff-in-charge. PROCEDURE: (To Find K) 1. The circuit connections are made as per the circuit diagram in the shown figure 4.1. 2. Keeping the motor field rheostat in its minimum position, generator field rheostat in maximum position and the starter in its OFF position, the main supply is switched ON to the circuit. 3. The motor is started using the 3-point starter by slowly and carefully moving the starter handle from its OFF to ON position. 4. The motor is brought to its rated speed by adjusting its rheostat and checked with the help of a tachometer. 5. With the SPST switch open, the residual voltage is noted. 6. Now the SPST switch is closed and the generator field rheostat is gradually decreased in steps and at each step the field current (If) and the corresponding induced EMF (Eg) are recorded in the tabular column. This procedure is continued until the generator voltage reaches 120% of its rated value. 7. After the experiment is completed the various rheostats are brought back to their original position in sequence and then main supply is switched OFF. CIRCUIT DIAGRAM: 42 Procedure: (To Find Ra & La) 1. The circuit connections are made as per the circuit diagram shown in figure 4.2. 2. Keeping autotransformer in minimum position, Main is switched ON. 3. Slowly adjust the variac and apply a small voltage (say 20V) to the armature winding. 4. Note down voltmeter, ammeter and wattmeter readings. 5. Bring the variac to minimum position and switch OFF the main supply. Procedure: (To Find Rf & Lf) 1. The circuit connections are made as per the circuit diagram shown in figure 4.3. 2. Keeping autotransformer in minimum position, Main is switched ON. 3. Slowly adjust the variac and apply a small voltage (say 60V) to the field winding. 4. Note down voltmeter, ammeter and wattmeter readings. 5. Bring the variac to minimum position and switch OFF the main supply. CALCULATION: 1. The open circuit characteristic is drawn to scale as shown in model graph. 2. A tangent is drawn to the linear portion of this OCC. 3. The slope of tangent is found using the relation Kf = Ea / If 4. The inductance and resistance of the field winding are calculated as follows: 43 W1=If2Rf Rf =W1 / If2 Zf=Vf / If Xf = (Zf2 – Rf2)1/2 Lf = Xf / 2пf 5. The inductance of the armature winding is calculated using the equation W2=Ia2Ra Ra =W2 / Ia2 Za=Va / Ia Xa = (Za2 – Ra2)1/2 La = Xa / 2пf 6. The transfer function of the given separately excited D.C shunt generator is then evaluated by substituting the values Kf, Rf, Lf, Ra & La in the standard equations For no Load TABULAR COLUMN : Tabulation 1: OCC test S.NO If (A) Eg (V) 44 Tabulation 2: To find Rf and Lf Sl.No. W1 If Vf W2 Ia Va Tabulation 3: To find Ra and La Sl.No. Model Graph MODEL CALCULATION: RESULT: Thus the Transfer Function of Separately Excited D.C Shunt Generator is determined & is given by 1. G(s)NL = 2. G(s)L = Ex. No : 9A Date: TRANSFER FUNCTION OF ARMATURE CONTROLLED DC SERVO MOTOR Aim: To derive the transfer function of the given DC Servomotor and experimentally determine the transfer function parameters Apparatus required: Sl no Apparatus Name Type/ Range Quantity 45 Name plate details: Voltage Current Speed H.P Load 220 V 19 A 1500 RPM 5 hp Brake drum Fuse calculation: 125 % of full load current Formula used: 1) Transfer function G(s) KT θ(s) E a (s) s[(R a sL a )(Js f o ) K T K b ] Where: KT – Torque constant calculated from graph (T Vs Ia) Ra – Armature Resistance in La – Inductance of Armature in H fo – Viscous friction coefficient In N-M / rad /sec J – Equivalent moment of inertia of motor and load referred to motor shaft (Kg-m2) Kb – Is the back EMF constant. 2) Inertia constant: J 2 J Vav * I av 60 t1t2 In Kg/m2 N av * N 2 t1 t 2 46 Where: T1 – Time for fall of speed from N1 to N2 in no load condition T2 – Time for fall of speed from N1 to N2 in load condition V V I I Vav 1 2 , I av 1 2 2 2 N N2 N av 1 N N1 N 2 2 3) Frictional coefficient of motor and load N N 2 f o * J * 1 2 2 In N-M / rad /sec 60 Where: 2N av 60 2 2 2 4) Back EMF constant Kb V I a Ra Kb 2N 60 Where: V- Applied voltage in volts Ia – Armature current in A Ra – Armature Resistance in N – Rated speed in RPM Theory: Armature control method is used when speed below the no load speed are required. As the supplied voltage is normally constant, the voltage across the armature is varied by inserting a variable rheostat in series with the armature circuit as shown. As controlled resistance is increased, potential difference across the armature is decreased. For load of constant speed approximately proportional to the potential difference across the armature. Derivation of transfer function of armature controlled DC servo motor: Consider the armature controlled d.c. servo motor shown in fig. below In this system, Ra = resistance of armature (Ω). La = Inductance of the Armature Winding (H). ia= = Armature Current(A). if = Field Current (A). ea = Applied Armature Voltage(V). eb = Back EMF (volts). TM = torque developed by armature (Nm). 47 θ = angular displacement of motor shaft (rad). J = equivalent moment of inertia of motor and load referred to motor shaft (Kg-m2) fo = equivalent viscous friction coefficient of motor and load referred to motor Shaft (N m/( rad/s)) If (costant) La Ra + TM ea - ia θ In servo applications, the d.c motors are generally used in the linear range of the magnetization curve. Therefore, the air gap flux Φ is proportional to field current Φ= Kfif where, Kf, is a constant. The torque TM developed by the motor is proportional to the product of the armature current and air gap flux, TM = K1Kf if ia where, K1, is a constant. In the armature controlled d.c motor, the field current is kept constant, so that TM = kTia where, KT, is motor torque constant. The motor back emf being proportional to speed is given as dθ eb K b dt where, Kb, is the back emf constant. The differential equation of the armature circuit is di La a R a ia eb ea dt The torque equation is d 2θ dθ J 2 f0 TM K T i a dt dt Taking the Laplace transform and assuming zero initial conditions, we get Eb(s) = Kb s θ(s) (Las+Ra) Ia(s) = Ea(s) - Eb(s) (Js2+fos) θ(s) = TM(s) = KTIa(s) 48 The transfer function of the system is obtained as KT θ(s) G(s) E a (s) s[(R a sL a )(Js f o ) K T K b ] Assumptions: The field current is constant. The flux which is proportional to the field current is also constant. The torque generated is proportional to the product of flux and the armature current Tm ΦIa T Ia Tm = KtIa Where Kt is the motor torque constant Back EMF of the motor is proportional to the speed and the flux Eb Φ. Precautions: 1) At the time of starting the motor should be at no load condition 2) Armature rheostat must be kept at maximum resistance position 3) Field rheostat must be kept at minimum resistance position Procedure: 1) To find inertia constant [J] Connections are made as per the circuit diagram The DPST switch is switched ON. It is in the initial position at the time of starting. After observing the precautions, switch on the DPST. Adjust the field side rheostat and the armature side rheostat and allow the motor to run at rated speed N1. Open the DPST and observe the speed of the motor note the time taken for the speed to fall down to any three values of the speed N2. Adjust the rheostat to initial position and switch of the DPST. Open the DPST and bring 2-2 position and immediately note down the reading Repeat the steps 2, 3, 4. Observe that the speed falls rapidly for the same values of speed noted in steps note down the time taken, voltage and current. Switch off the dc supply. Inertia Constant is calculated using formula J 2 Vav * I av 60 t1t2 N av * N 2 t1 t 2 2) To Find Torque Constant [KT] 1. Connections are given as per the circuit diagram. 49 2. The DPST is switched on. 3. Adjust the armature side rheostat and keep in fixed position so that the value of Ia is maintained constant through the experiment. 4. Note down If, Va, Ia in table. 5. Adjust the field rheostat and note down the Va, Ia, If and Speed. 6. Graph is drawn between the torque and If. KT = T/If 3) To fined Back EMF constant [Kb] The connections are given as per the circuit diagram The D.C supply is given by closing the DPST switch Run the motor at its rated speed by adjusting armature rheostat At rated speed the readings of applied voltage and armature current were noted down V I a Ra Back MEF constant is calculated using the formula K b 2N 60 4) To find armature resistance [Ra] Connections are made as per the circuit diagram The resistive should be in off position at the time of starting. Adjust the load, for each values of load, note down the ammeter, voltmeter readings. Armature resistance is calculated by using the formula 5) To find field impedance [Zf] 1. Connections are made as per the circuit diagram 2. Vary the auto transformer and note down the corresponding ammeter and voltmeter readings. 3. Calculate the value of Zf = Vf /If and find the mean of Zf. Circuit diagram for calculating inertia constant J 50 Tabulation to find Torque constant [J] Sl no Armature current Ia in Amps Field current If in Amps Spring balance reading S1 in Kg S2 in Kg S1~ S2 in Kg Torque T = t 9.81* S1 ~ S 2 R 2 in NM Circuit diagram for find armature resistance Ra Circuit diagram for find Impedance Za 51 Tabulation to find Back EMF constant [Kb] Armature Voltage Va in Volts Armature current Ia in Amps Speed in RPM Back EMF Constant V I a Ra Kb 2N 60 Tabulation to find Armature Resistance [Ra] Armature Armature Armature Voltage Va in current Ia in resistance Ra Volts Amps = V * I in Ω Tabulation to Find Armature Resistance [Za] Armature Armature Armature Voltage Va in Current Ia in Impedance Za Volts Amps = V / I in Ω 52 Model graph Torque Vs Ia T in N-M T Ia KT T I a T Ia in Amps Result: Ex. No : 9B Date: TRANSFER FUNCTION OF FIELD CONTROLLED DC SERVO MOTOR Aim: To derive the transfer function of the given D.C Servomotor and experimentally determine the transfer function parameters Apparatus required: Sl No. Apparatus Name Type/ Range Quantity Name plate details: Voltage Current Speed H.P Load Fuse calculation: 125 % of full load current 53 Formula used: 1) Transfer function Km θ(s) E f (s) s(τ f s 1)(τ me s 1) Where: Km = KT’/Rff – Motor Gain Constant τf = Lf/Rf –Time Constant of Field Circuit τme = J/f – Mechanical Time Constant. lf – inductance of field winding in H Rf – Resistance of field winding in J – Equivalent of inertia of motor and load referred to motor shaft (kg-m2). f – Equivalent viscous friction coefficient of motor and load referred to motor shaft Nm rad/s 2) Inertia constant: J 2 Vav * I av 60 t1t2 In Kg/m2 N av * N 2 t1 t 2 Where: T1 – Time for fall of speed from N1 to N2 in no load condition T2 – Time for fall of speed from N1 to N2 in load condition V1 V2 I I , Vav I av 1 2 2 2 N N2 N av 1 N N1 N 2 2 3) Frictional coefficient of motor and load 2 2 2 N N 2 f o * J * 1 2 2 In N-M / rad /sec 60 Where: 2N av 60 J Derivations of transfer function of Field Controlled D C motor: In this system Rf - Field Winding Resistance (Ω) Lf -Field Winding Inductance (H). e- Field control voltage. (V). if - Field Current(A). TM - Torque Developed By Motor (Nm). J- Equivalent of inertia of motor and load referred to motor shaft (kg-m2). f- Equivalent viscous friction coefficient of motor and load referred to motor shaft Nm rad/s 54 θ - Angular displacement of motor shaft (rad). Rf ef ia( constant) TM Lf If θ J,f In this field controlled motor, the armature current is fed from a constant current source. Therefore TM = K1Kfiaif = KT’ if where KT’ is a constant. The equation for the field circuit is di Lf f R f if ef dt The torque equation is d 2θ dθ J 2 f TM K T ' I f (s) dt dt Taking the Laplace transform and assuming zero initial conditions we get (Lfs + Rf) If(s) = Ef(s) (Js2+fs) θ(s) = TM(s) = KT’ If(s) From the above equations, the transfer function of the motor is obtained as Km θ(s) E f (s) s(τ f s 1)(τ me s 1) where Km = KT’/Rff – motor gain constant τf = lf/Rf –time constant of field circuit τme = J/f – mechanical time constant. Theory: The speed of the dc motor is directly proportional to the armature voltage and inversely proportional to the flux. In the field controlled dc motor, armature voltage is kept constant and the speed is varied by varying the flux of the machine. Precautions: The DPST is kept open initially. The field rheostat is kept at maximum position. Procedure: 55 1) To find inertia constant [J] Connections are made as per the circuit diagram The DPST switch is switched ON. It is in the initial position at the time of starting. After observing the precautions, switch on the DPST. Adjust the field side rheostat and the armature side rheostat and allow the motor to run at rated speed N1. Open the DPST and observe the speed of the motor note the time taken for the speed to fall down to any three values of the speed N2. Adjust the rheostat to initial position and switch of the DPST. Open the DPST and bring 2-2 position and immediately note down the reading Repeat the steps 2, 3, 4. Observe that the speed falls rapidly for the same values of speed noted in steps note down the time taken, voltage and current. Switch off the dc supply. 2 V * I 60 t t Inertia Constant is calculated using formula J av av 1 2 N av * N 2 t1 t 2 2) To Find Torque Constant [KT] 7. Connections are given as per the circuit diagram. 8. The DPST is switched on. 9. Adjust the armature side rheostat and keep in fixed position so that the value of Ia is maintained constant through the experiment. 10. Note down If, Va, Ia in table. 11. Adjust the field rheostat and note down the Va, Ia, If and Speed. 12. Graph is drawn between the torque and If. KT = T/If 3) To find armature resistance [Rf] Connections are made as per the circuit diagram The resistive should be in off position at the time of starting. Adjust the load, for each values of load, note down the ammeter, voltmeter readings. Armature resistance is calculated by using the formula Rf= V/I 4) To find field impedance [Lf] 1. Connections are made as per the circuit diagram 2. Vary the auto transformer and note down the corresponding ammeter and voltmeter readings. 3. Calculate the value of Zf = Vf /If and find the mean of Zf. 56 Model graph Torque Vs If T in N-M T If If in Amps Tabulation to find Torque constant [J] Sl no Armature Field Spring balance reading Torque T = 57 current Ia in Amps current If in Amps S1 in Kg S2 in Kg S1~ S2 in Kg Tabulation to find Torque constant [J] Spring balance reading Armature Field Sl current Ia current If S1 in S2 in S1~ S2 no in Amps in Amps Kg Kg in Kg t 9.81* S1 ~ S 2 R 2 in NM Torque T = t 9.81* S1 ~ S 2 R 2 in NM Tabulation to find out the field resistance (Rf) S no Field current (I) Voltage (V) Amps Volts Stator Resistance Rf= V/I Ohms 58 Calculation: Result: Expt. No: 10 Date DESIGN AND IMPLEMENTATION OF COMPENSATORS AIM: To study the compensation of the second order process by using lead – Lag Compensator EQUIPMENT REQUIRED: 1. LEAD – Lag network system kit 2. Capacitors – 0.1μF 3. Decade Resistance Box 4. CRO DESIGN: Lead – Lag network using operational amplifier: An electronic lead –lag network using operational Amplifier is shown in Fig. 4.1. 59 The transfer function for this circuit can be obtained as follows: Let Z1 = R1 || C1 Z2 = R2 || C2 The second op-amp acts as a sign inverter with a variable gain to compensate for the magnitude. The transfer function of the entire system is given by G(j). G( s) R4 R2 (1 R1C1 s) R3 R1 (1 R2 C 2 s) TABULATION: SI NO AMPLITUDE FREQUENCY PHASE R1 (V) (HZ) SHIFT (OHMS) () C1 (F) R2 (OHMS) C2 (F) 60 We have G ( j ) R2 R4 (1 T12 2 ) R1 R3 (1 T22 2 ) Where T1 = R1C1 T2 = R2C2 and Thus the steady state output is Yss (t ) R2 R4 (1 T12 2 ) R1 R3 (1 T ) 2 2 2 Sin (t tan 1 T1 tan 1 T2 ) for an input Esint. From this expression, we find that if T1>T2, then tan 1 T1 tan 1 T2 >0. Thus if T1>T2, then the network is a lead network. If T1 <T2, the network is a lag network. Determination of values for angle compensation: Frequency of sine wave (f)= 20Hz. Phase angle to be compensated =14.50 tan 1 (2fT1 ) tan 1 (2fT2 ) Let T1 0.1sec 14.5 tan 1 (2 * 20 * 0.1) tan 1 (2 * 20 * T2 ) T2 0.023 sec Hence the values of T1 and T2 are chosen from which the values of R1, R2, C1, and C2 can be determined. For Example, T1 = R1C1 = 0.1; If C1 = 0.1μF, R1=1MΩ T2 = 0.023sec If C2 = 0.1 μF, R2 =230KΩ. These values produce a phase lead of 14.5o, which is the desired compensation angle. PROCEDURE: 61 1. Switch ON the power to the instrument. 2. Connect the individual blocks using patch chords bypassing the compensating network and gain as shown in fig. 4.2. 3. Give a sinusoidal input as the set value to the error detector. 4. Measure the amplitude and frequency of the input signal. 5. Measure the amplitude and phase difference of the output signal with respect to the input signal using DSO. 6. Using the technique explained previously, calculate the values of R1, R2, C2, and C1 to compensate for the phase shift of the output signal. 7. Connects the components at the points provided. 8. Now include the compensation block in the forward path before the process using patch chords as shown in fig.4.2. 9. Observe the compensated wave form through DSO. CALCULATION: (frequency = Hz) CALCUALTION : (frequency = Hz) RESULT: Thus the compensator is designed for the given process and the performance of the compensated system is found to work satisfactorily. Frequency : Frequency : Hz Hz R1 = C1 = R2 = C2 = R1 = C1 = R2 = C2 = 62 Expt No: 11 Date STUDY OF D.C MOTOR STARTERS AIM: To study the different kinds of D.C motor starters EQUIPMENT AND APPARATUS REQUIRED : Sl No. 1 2 3 Name of the apparatus Two Point starter Three Point starter Four Point starter Quantity 1 1 1 THEORY : The value of the armature current in a D.C shunt motor is given by Ia = ( V – Eb )/ Ra Where V = applied voltage. Ra = armature resistance. E b = Back .e.m.f . In practice the value of the armature resistance is of the order of 1 ohms and at the instant of starting the value of the back e.m.f is zero volts. Therefore under starting conditions the value of the armature current is very high. This high inrush current at the time of starting may damage the motor. To protect the motor from such dangerous current the D.C motors are always started using starters. The types of D.C motor starters are i) Two point starters ii) Three point starters iii) Four point starters. The functions of the starters are i) It protects the from dangerous high speed. ii) It protects the motor from overloads. i) TWO POINT STARTERS: ( refer fig 1) It is used for starting D.C. series motors which has the problem of over speeding due to the loss of load from its shaft. Here for starting the motor the control arm is moved in clock-wise direction from its OFF position to the ON position against the spring tension. The control arm is 63 held in the ON position by the electromagnet E. The exciting coil of the hold-on electromagnet E is connected in series with the armature circuit. If the motor loses its load, current decreases and hence the strength of the electromagnet also decreases. The control arm returns to the OFF position due to the spring tension, Thus preventing the motor from over speeding. The starter also returns to the OFF position 64 when the supply voltage decreases appreciably. L and F are the two points of the starter which are connected with the motor terminals. 65 ii) THREE POINT STARTER: ( refer fig 2 ) It is used for starting the shunt or compound motor. The coil of the hold on electromagnet E is connected in series with the shunt field coil. In the case of disconnection in the field circuit the control arm will return to its OFF position due to spring tension. This is necessary because the shunt motor will over speed if it loses excitation. The starter also returns to the OFF position in case of low voltage supply or complete failure of the supply. This protection is therefore is called No Volt Release ( NVR). Over load protection: When the motor is over loaded it draws a heavy current. This heavy current also flows through the exciting coil of the over load electromagnet ( OLR). The electromagnet then pulls an iron piece upwar6.ds which short circuits the coils of the NVR coil. The hold on magnet gets de-energized and therefore the starter arm returns to the OFF position, thus protecting the motor against overload. L, A and F are the three terminals of the three point starter. iii) FOUR POINT STARTER: The connection diagram of the four point starter is shown in fig 3. In a four point starter arm touches the starting resistance, the current from the supply is divided into three paths. One through the starting resistance and the armature, one through the field circuit, and one through the NVR coil. A protective resistance is connected in series with the NVR coil. Since in a four point starter the NVR coil is independent of the of the field ckt connection , the d.c motor may over speed if there is a break in the field circuit. A D.C motor can be stopped by opening the main switch. The steps of the starting resistance are so designed that the armature current will remain within the certain limits and will not change the torque developed by the motor to a great extent. 66 STUDY OF INDUCTION MOTOR STARTERS AUTO –TRANSFORMER STARTING 67 An auto transformer starter consists of an auto transformer and a switch as shown in the fig. When the switch S is put on START position, a reduced voltage is applied across the motor terminals. When the motor picks up speed, say to 80 per cent of its mornal speed, the switch is put to RUN position. Then the auto-transformer is cut out of the circuit and full rated voltage gets applied across the motor terminals. (Ref. To text book for fig) The circuit dia in the fig is for a manual auto-transformer starter. This can be made push button operated automatic controlled starter so that the contacts switch over from start to run position as the motor speed picks up to 80% of its speed. Over-load protection relay has not been shown in the figure. The switch S is air-break type for small motors and oil break type for large motors. Auto transformer may have more than one tapping to enable the user select any suitable starting voltage depending upon the conditions. Series resistors or reactors can be used to cause voltage drop in them and thereby allow low voltage to be applied across the motor terminals at starting. These are cut out of the circuit as the motor picks up speed. STAR- DELTA METHOD OF STARTING: The startor phase windings are first connected in star and full voltage is connected across its free terminals. As the motor picks up speed, the windings are disconnected through a switch and they are reconnected in delta across the supply terminals. The current drawn by the motor from the lines is reduced to as compared to the current it would have drawn if connected in delta.The motor windings, first in star and then in delta the line current drawn by the motor at starting is reduced to one third as compared to starting current with the windings delta-connected. In making connections for star-delta starting, care should be taken such that sequence of supply connections to the winding terminals does not change while changing from star connection to delta connection. Otherwise the motor will start rotating in the opposite direction, when connections are changed from star to delta. Star-delta starters are available for manual operation using push button control. An automatic star – delta starter used time delay relays(T.D.R) through which star to delta connections take place automatically with some pre-fixed time delay. The delay time of the T.D.R is fixed keeping in view the starting time of the motor. (Ref. To text book for fig) 68 FULL VOLTAGE OR DIRECT –ON-LINE STARTING When full voltage is connected across the stator terminals of an induction motor, large current is drawn by the windings. This is because, at starting the induction motor 69 70 behaves as a short circuited transformer with its secondary, i.e. the rotor separated from the primary, i.e. the stator by a small air-gap. At starting when the rotor is at standstill, emf is induced in the rotor circuit exactly similar to the emf induced in the secondary winding of a transformer. This induced emf of the rotor will circulate a very large current through its windings. The primary will draw very large current from the supply mains to balance the rotor ampere-turns. To limit the stator and rotor currents at starting to a safe value, it may be necessary to reduce the stator supply voltage to a low value. If induction motors are started direct-on-line such a heavy starting current of short duration may not cause harm to the motor since the construction of induction motors are rugged. Other motors and equipment connected to the supply lines will receive reduced voltage. In industrial installations, however, if a number of large motors are started by this method, the voltage drop will be very high and may be really objectionable for the other types of loads connected to the system. The amount of voltage drop will not only be dependent on the size of the motor but also on factors like the capacity of the power supply system, the size and length of the line leading to the motors etc. Indian Electricity Rule restricts direct on line starting of 3 phase induction motors above 5 hp. RESULT: Thus the construction and working of different starters for starting D.C series, shunt, compound and three phase induction motors are studied. Ex. No : 12 Date: Digital Simulation of Linear Systems 71 Aim: To digitally simulate the time response characteristics of higher-order MIMO linear systems using state – variable formulation Equipments required: PC system with mat lab Theory: Introduction to MATLAB & SIMULINK What is MATLAB? MATLAB® is a high-performance language for technical computing. It integrates computation, visualization, and programming in an easy-to-use environment where problems and solutions are expressed in familiar mathematical notation. Typical uses include Math and computation Algorithm development Data acquisition Modeling, simulation, and prototyping Data analysis, exploration, and visualization Scientific and engineering graphics Application development, including graphical user interface building MATLAB is an interactive system whose basic data element is an array that does not require dimensioning. This allows you to solve many technical computing problems, especially those with matrix and vector formulations, in a fraction of the time it would take to write a program in a scalar no interactive language such as C or FORTRAN. The name MATLAB stands for matrix laboratory. MATLAB was originally written to provide easy access to matrix software developed by the LINPACK and EISPACK projects. Today, MATLAB engines incorporate the LAPACK and BLAS libraries, embedding the state of the art in software for matrix computation. MATLAB has evolved over a period of years with input from many users. In university environments, it is the standard instructional tool for introductory and advanced courses in mathematics, engineering, and science. In industry, MATLAB is the tool of choice for highproductivity research, development, and analysis. MATLAB features a family of add-on application-specific solutions called toolboxes. Very important to most users of MATLAB, toolboxes allow you to learn and apply specialized technology. Toolboxes are comprehensive collections of MATLAB functions (M-files) that extend the MATLAB environment to solve particular classes of problems. Areas in which 72 toolboxes are available include signal processing, control systems, neural networks, fuzzy logic, wavelets, simulation, and many others. Starting MATLAB Instructions for starting MATLAB® depend on your platform. For a list of supported platforms, see the system requirements in the installation documentation, or the Products section of the MathWorks Web site, http://www.mathworks.com Starting MATLAB on Windows Platforms To start MATLAB on a Microsoft Windows platform, select the Start -> Programs -> MATLAB 7.0 -> MATLAB 7.0, or double-click the MATLAB shortcut icon on your Windows desktop. The shortcut was automatically created by the installer. Transfer function of the given 4 systems Transfer function: s-1 ------------s^2 + s + 6.5 Transfer function: s + 7.5 ------------s^2 + s + 6.5 Transfer function: s + 3.553e-015 -------------s^2 + s + 6.5 Transfer function: s^2 + s + 13 ------------s^2 + s + 6.5 Matlab program: Open new m file and type the given program % State Space Analysis of MIMO System %-----X^ = Ax+Bu; y =Cx+Du -------% A=[-1 -1; 6.5 0]; %----State Matrix(nxn)-----% B=[1 1;1 0]; %----Input Mtrix(nxm)------% C=[1 0;0 1]; %----Output Matrix(pxn) ------% D=[0 0;0 1]; %----Transistion Matrix(pxm)---% 73 step(A,B,C,D,1) hold step(A,B,C,D,2) title('Step Response of MIMO System') grid [num1,den1]=ss2tf(A,B,C,D,1) [num2,den2]=ss2tf(A,B,C,D,2) n1=num1(1,:) n2=num1(2,:) n3=num2(1,:) n4=num2(2,:) d1=den1(1,:) d2=den2(1,:) tf1=tf(n1,d1) tf2=tf(n2,d1) tf3=tf(n3,d2) tf4=tf(n4,d2) For impulse response response MIMO system % State Space Analysis of MIMO System %-----X^ = Ax+Bu; y =Cx+Du -------% A=[-1 -1; 6.5 0];%----State Matrix(nxn)-----% B=[1 1;1 0];%----Input Mtrix(nxm)------% C=[1 0;0 1];%----Output Matrix(pxn) ------% D=[0 0;0 1];%----Transistion Matrix(pxm)---% impulse(A,B,C,D,1) hold impulse(A,B,C,D,2) title('Impulse Response of MIMO System') grid [num1,den1]=ss2tf(A,B,C,D,1) [num2,den2]=ss2tf(A,B,C,D,2) n1=num1(1,:) n2=num1(2,:) n3=num2(1,:) n4=num2(2,:) d1=den1(1,:) d2=den2(1,:) tf1=tf(n1,d1) tf2=tf(n2,d1) tf3=tf(n3,d2) tf4=tf(n4,d2) 74 Step Response of MIMO System 3 2.5 Amplitude 2 1.5 1 0.5 0 -0.5 0 2 4 6 8 10 12 Time (sec) Current plot held num1 = 0 1.0000 -1.0000 0 1.0000 7.5000 den1 = 75 1.0000 1.0000 6.5000 num2 = 0 1.0000 0.0000 1.0000 1.0000 13.0000 den2 = 1.0000 1.0000 6.5000 n1 = 0 1.0000 -1.0000 n2 = 0 1.0000 7.5000 n3 = 0 1.0000 0.0000 n4 = 1.0000 1.0000 13.0000 d1 = 1.0000 1.0000 6.5000 d2 = 1.0000 1.0000 6.5000 Transfer function: s-1 ------------s^2 + s + 6.5 Transfer function: s + 7.5 ------------s^2 + s + 6.5 Transfer function: s + 3.553e-015 -------------s^2 + s + 6.5 Transfer function: s^2 + s + 13 ------------s^2 + s + 6.5 Result: 76 Ex. No : 13 Date: Stability Analysis of Linear Systems Aim To analyse the stability of linear systems using Bode, Root locus, Nyquist plots Equipments required: PC system with mat lab Program: STABILITY ANALYSIS Program For Nyquist Plot. %---Given System G(s)=1/(s^2+0.8s+1)-----% %--------Nyquist plot-----------% num=[0 0 1]; den=[1 0.8 1]; nyquist(num,den); axis(v) grid title('Nyquist plot of G(s)=1/(s^2+0.8s+1)') xlabel('Real axis') ylabel('Imag axis') hold on Program for Root Locus %---conditionally stable system--% %---Given System G(s)=k(s^2+2s+4)/[s(s+4)(s+6)(s^2+1.4s+1)-----% clc; close all; 77 clear all; %--------Root Locus----------% numz=[0 0 0 1 2 4]; denp=[1 11.4 39 43.6 24 0]; r=rlocus(numz,denp); plot(r,'o'); axis(v) grid title('Root locus plot of G(s)=k(s^2+2s+4)/[s(s+4)(s+6)(s^2+1.4s+1)]') xlabel('real axis') ylabel('imag axis') hold Program for Bode Plot %---Given System=s^3+2s+3/(s^5+s^4+s^3+s^2+s+1)---% %--------Bode Plot ----------% numg=[1 0 2 3]; deng=[1 1 1 1 1 1 ]; 'G(s)' u=tf(numg,deng); bode(u) grid hold title('Bode plot of G(s)=s^3+2s+3/(s^5+s^4+s^3+s^2+s+1)') [Gm,Pm,Wcg,Wcp] = margin(u) Gm_dB = 20*log10(Gm) Program For Polar Plot format compact set(gcf,'Toolbar','none','Name','Polar Plot', ... 'NumberTitle','off','Position',[10,350,350,300]); theta = 2*pi*linspace(0,1,30); r = 2*(1 + cos(theta)); Polar(theta,r,'r-') set(gca,'Position',[0.1 0.1 0.75 0.75]); title('\bf\itA Polar Plot','Color','k','VerticalAlignment','bottom') textstr(1)={'r = 2(1+cos\theta)'}; textstr(2)={'\theta = 0 -> 2\pi'}; text(5*cos(pi/4),5*sin(pi/4), ... strcat(textstr)) title('Polar plot ') hold Program for Nichols Chart 78 %Plot the Nichols response of the system num = [-4 48 -18 250 600]; den = [1 30 282 525 60]; H = tf(num,den) nichols(H); ngrid Response of various systems Nyquist plot of G( s) 1 ( s 0.8s 1) Root locus plot of G( s) 2 k s 2 2s 4 s( s 4)(s 6)(s 2 1.4s 1) 79 Bode plot of G( s) s 2s 3 ( s s s 3 s 2 s 1) 5 3 4 80 81 Result: Ex. No: 14 Date: STUDY THE EFFECT OF P, PI, PID CONTROLLERS USING MAT LAB Aim: To Study the effect of P, PI, PID controllers using Mat lab. 1 Choice of the Controller type In so far were described proportional, integrative and derivative modes of the controllers and a rational behind their use was explained. However, excerpt for a few tips, an attention was not given to a question when to use different types of controllers. The rest of this section will give some answers on that particular topic. 1.1 On-off Controller On-off controller is the simplest controller and it has some important advantages. It is economical, simple to design and it does not require any parameter tuning. If oscillations will hamper the operation of the system and if controller parameter tuning is to be avoided, on-off controller is a good solution. In addition, if actuators work in only two modes (on and off), then it is almost always only controller that can be used with such actuators. That is a reason why onoff controllers are often used in home appliances (refrigerators, washers etc.) and in process industry when control quality requirements are not high (temperature control in buildings etc.). Additional advantage of on-off controllers is that they in general do not require any maintenance. 1.2 P Controller 82 When P controller is used, large gain is needed to improve steady state error. Stable system do not have a problems when large gain is used. Such systems are systems with one energy storage (1st order capacitive systems). If constant steady state error can be accepted with such processes, than P controller can be used. Small steady state errors can be accepted if sensor will give measured value with error or if importance of measured value is not too great anyway. Example of such system is liquid level control in tanks when exact approximate level of liquid suffice for the proper plant operation. Also, in cascade control sometime it is not important if there is an error inside inner loop, so P controller can a good solution in such cases. Derivative mode is not required if the process itself is fast or if the control system as whole does not have to be fast in response. Processes of 1st order react immediately on the reference signal change, so it is not necessary to predict error (introduce D mode) or compensate for the steady state error (introduce I mode) if it is possible to achieve satisfactory steady state error using only P controller. 1.3 PD controller It is well known that thermal processes with good thermal insulation act almost as integrators. Since insulation is good and thermal losses are small, the most significant art of the energy that is led to the system is used temperature rise. Those processes allow 18 for large gains so that integral mode in the controller is not needed. These processes can be described as different connections of thermal energy storages. Thermal energy is shifted from one storage into another. In general, with such processes there is present a process dynamics with large inertia. Since dynamics is slow, derivative mode is required for control of such processes. Integral mode would only already slow dynamics make more slowly. The other reason for using PPD controllers in such systems is that is possible to measure temperature with low level of noise in the measured signal. PD controller is often used in control of moving objects such are flying and underwater vehicles, ships, rockets etc. One of the reason is in stabilizing effect of PD controller on sudden changes in heading variable y(t). Often a "rate gyro" for velocity measurement is used as sensor of heading change of moving object. 1.3 PI controller PI controllers are the most often type used today in industry. A control without D mode is used when: a) fast response of the system is not required b) large disturbances and noise are present during operation of the process c) there is only one energy storage in process (capacitive or inductive) d) there are large transport delays in the system If there are large transport delays present in the controlled process, error prediction is required. However, D mode cannot be used for prediction because every information is delayed till the moment when a change in controlled variable is recorded. In such cases it is better to predict the output signal using mathematical model of the process in broader sense (process + 83 actuator). The controller structures that can be used are, for example, Otto-Smith predictor (controller), PIP controller or so called Internal Model Controller (IMC). An interesting feature of IMC is that when the model of the process is precise (A = AM and B = BM), then a feedback signal eM = y – yM is equal to disturbance: It follows that a control signal is not influenced by the reference signal and control systems behaves as open loop. A usual problems with stability that arrise when closed loop systems are used are then avoided. Control system with IMC controller will be stable and if IMC and process are stable. With the exact model of process IMC is actually a feedforward controller and can designed as such, but, unlike feedforward controllers, it can compensate for unmeasured disturbances because feedback signal is equal to disturbance, which allows suitable tuning of the reference value of the controller. If model of the process is not exact5 (AM = B), then feedback signal eM will contain not only disturbance d but a modeling error, also. Thus, a feedback will have its usual role, and stability problem can arise. This requires for parameters6 to be tuned again so the stability is not lost. 84 85 1.4 PID controller Derivative mode improves stability of the system and enables increase in gain K and decrease in integral time constant Ti, which increases speed of the controller response. PID controller is used when dealing with higher order capacitive processes (processes with more than one energy storage) when their dynamic is not similar to the dynamics of an integrator (like in many thermal processes). PID controller is often used in industry, but also in the control of mobile objects (course and trajectory following included) when stability and precise reference following are required. Conventional autopilot are for the most part PID type controllers. 1.5 Topology of PID controllers Problem of topology (structure) of controller arises when: There are a number of different PID controller structures. Different manufacturers design controllers in different manner. However, two topologies are the most often case: parallel (non-interactive) Parallel structure is most often in textbooks, so it is often called "ideal" or "textbook type". This non-interactive structure because proportional, integral and derivative mode are independent on each other. Parallel structure is still very rare in the market. The reason for that is mostly historical. First controllers were pneumatic and it was very difficult to build parallel structure using pneumatic components. Due to certain conservatism in process industry most of the controller used there are still in serial structure, although it is relatively simple to realize parallel structure controller using electronics. In other areas, where tradition is not so strong, parallel structure can be found more often. 1.5.1 Parallel PID topology A parallel connection of proportional, derivative and integral element is called parallel or non-interactive structure of PID controller. Parallel structure is shown in Fig. 86 It can be seen that P, I and D channels react on the error signal and that they are unbundled. This is basic structure of PID controller most often found in textbooks. There are other non-interactive structures. RESULT: Thus the effect of P, PI, PID controllers using Mat lab are studied. VIVA questions for the experiments 87 OPEN CIRCUIT CHARACTERISTICS OF SELF EXCITED DC SHUNT GENERATOR VIVA QUESTIONS: 1. Define critical field resistance and critical speed. 2. State the conditions to be satisfied by a DC shunt generator to build-up voltage. 3. What is residual flux and what happens to the generator induces EMF when residual flux is zero? 4. What is the purpose of SPST switch connected in the field circuit of the generator? 5. Why the speed must be maintained constant throughout the experiment? LOAD TEST ON SELF EXCITED DC SHUNT GENERATOR VIVA QUESTIONS: 1. What is a prime mover? 2. Why the speed of generator should be maintained constant during the experiment? 3. Why does the terminal voltage fall as the load on the generator is increased? 4. What is armature reaction and what are its effects on the performance of DC generator? OPEN CIRCUIT CHARACTERISTICS OF A SEPARATELY EXCITED DC SHUNT GENERATOR VIVA QUESTIONS: 1. Define critical field resistance and critical speed. 2. State the conditions to be satisfied by a DC shunt generator to build-up voltage. 3. What is residual flux and what happens to the generator induces EMF when residual flux is zero? 4. What is the purpose of SPST switch connected in the field circuit of the generator? 5. Why the speed must be maintained constant throughout the experiment? 88 LOAD CHARACTERISTICS ON SEPARATELY EXCITED DC SHUNT GENERATOR VIVA QUESTIONS: 1. What is a prime mover? 2. Why the speed of generator should be maintained constant during the experiment? 3. Why does the terminal voltage fall as the load on the generator is increased? 4. What is armature reaction and what are its effects on the performance of DC generator? LOAD TEST ON DC SHUNT MOTOR VIVA QUESTIONS: 1. What is the need for a starter? 2. Name the different types of starters for DC motors. 3. Why a DC shunt motor is called a constant Speed motor? 4. State few applications of DC shunt motor. 5. What is the role of commutator in a DC motor. 6. What is the effect of armature reaction on the performance of DC motor? 7. What happen when the field circuit gets opened when a DC shunt motor is running? 8. How to reverse the direction of rotation of DC shunt motor? SPEED CONTROL OF DC SHUNT MOTOR VIVA QUESTIONS: 1. Which method of speed control is used for controlling the speed of the motor above its rated speed? Give reason. 2. Which method of speed control is used for controlling the speed of the motor below its rated speed? Give reason. 3. Explain the reasons for the shape of the graphs obtained. 4. State any method to control the speed of a D.C series motor? SWINBURNE'S TEST VIVA QUESTIONS: 1. What are the advantages of predetermination techniques? 2. Can the efficiency of a DC series motor be predetermined by Swinburne's test? 3. The efficiency of a generator is always more than the efficiency of motor at all load conditions - Justify. 4. Enumerate the various losses in a DC machine. 89 LOAD TEST ON A SINGLE PHASE TRANSFORMER VIVA QUESTIONS: 1. Define Regulation of a Transformer. 2. What is the effect of load p.f on regulation of Transformer? 3. What is the condition for maximum efficiency? 4. Determine the percentage load at which maximum efficiency occurred for the given single-phase transformer? 5. What is the effect of change in frequency on the efficiency of the transformer? O.C AND S.C TESTS ON A SINGLE PHASE TRANSFORMER VIVA QUESTIONS: 1. Why O.C test is conducted on the L.V side and S.C test on the H.V side? 2. Define regulation in a transformer. 3. Why the regulation graph is not passing through the origin? 4. State the condition for maximum efficiency? 5. What is the regulation of an Ideal transformer? 6. At what fraction of full load does the efficiency of the given transformer is maximum? PREDETERMINATION OF REGULATION BY EMFAND MMF METHOD VIVA QUESTIONS: 1. Define regulation. 2. What is meant by pessimistic method? 3. Which method is called as optimistic method? 4. What are the advantages of EMF and MMF method? 5. Name some other methods used to predetermine the regulation. LOAD TEST ON SQUIRREL CAGE INDUCTION MOTOR VIVA QUESTIONS: 1. What is squirrel cage induction motor? 2. What is Skewing? 3. What is cogging? 4. What is crawling? 5. What is the no load current of an induction motor? 6. Distinguish between rotating transformer and static transformer? 7. Define slip. NO LOAD AND BLOCKED ROTOR TEST ON THREE PHASE INDUCTION MOTOR VIVA QUESTIONS: 1. How will you measure three phase power using two watt meters? 90 2. 3. 4. 5. What is the necessity to have starter for three phase induction motor? How mechanical load is represented in the equivalent circuit of induction motor? Define synchronous speed. Why induction motors cannot run at synchronous speed? STUDY OF D.C MOTOR STARTERS VIVA QUESTIONS: 1. 2. 3. 4. 5. Differentiate two point and three point starter What is the need for starter in electrical technology? Differentiate four point and three point starter What are the types of starter? What are the protective devices used in starters? STUDY OF INDUCTION MOTOR STARTERS VIVA QUESTIONS: 1. Differentiate star – delta and auto transformer starter 2. What is the need for starter in electrical technology? 3. Differentiate auto transformer and DOL starter 4. What are the types of AC starters? 5. What are the protective devices used in starters? DIGITAL SIMULATION OF LINEAR SYSTEMS VIVA QUESTIONS: 1) Define linear system. 2) What is impulse signal? 3) What is MIMO? 4) What is time invariant system? 5) What is step signal? STABILITY ANALYSIS OF LINEAR SYSTEM VIVA QUESTIONS: 1) What is root locus? 2) What is bode plot? 3) What is Nyquist plot? 4) What is phase margin? 5) What is gain margin? DESIGN AND IMPLEMENTATION OF COMPENSATORS VIVA QUESTIONS: 91 1. 2. 3. 4. 5. What is compensation? What is compensator? When lag/lead/lag-lead compensators are employed? What are the types of compensator? Differentiate lag and lead compensators? TRANSFER FUNCTION OF SEPERATELY EXCITED DC SHUNT GENERATOR VIVA QUESTIONS 1. What is the need for transfer function of a system? 2. What are the types of transfer function? 3. Define feedback. 4. Mention few applications of Separately Excited DC generator. 5. What are the basic elements used for modeling mechanical rotational system? TRANSFER FUNCTION OF ARMATURE CONTROLLED DC SHUNT MOTOR VIVA QUESTIONS 1. What are the draw backs of transfer function and advantages of transfer function? 2. What are the types of transfer function? 3. Define transfer function. 4. Mention few applications of Separately Excited DC generator. 5. What are the basic elements used for modeling electrical system? TRANSFER FUNCTION OF FIELD CONTROLLED DC SHUNT MOTOR VIVA QUESTIONS 1. What is the need for transfer function of a system? 2. Mention few applications of DC motor. 3. Differentiate open loop and closed loop system 4. Write transfer function for field control DC motor 5. Define Mechanical time constant 6. Define Electrical time constant. 92